Please read this Installation Manual carefully before installing the Air to Water Heat Pump.
• This Manual describes the installation method of the outdoor unit.
• For installation of the hydro unit, follow the Installation Manual attached to the hydro unit.
Outdoor Unit Installation Manual
ADOPTION OF NEW REFRIGERANT
This Air to Water Heat Pump is a new type which adopts a new refrigerant HFC (R410A) instead of the
conventional refrigerant R22 in order to prevent destruction of the ozone layer.
• Piping kit used for the conventional refrigerant cannot be used.
• Use copper pipe with 0.8 mm or more thickness for Ø9.5 mm.
Use copper pipe with 1.0 mm or more thickness for Ø15.9 mm.
• Flare nut and flare works are also different from those of the conventional refrigerant.
Take out the flare nut attached to the Air to Water Heat Pump, and use it.
–3–
EN
2-EN
Air to Water Heat Pump
Outdoor Unit Installation Manual
2PRECAUTIONS FOR SAFETY
• Ensure that all Local, National and International regulations are satisfied.
• Read this “PRECAUTIONS FOR SAFETY” carefully before Installation.
• The precautions described below include the important items regarding safety.
Observe them without fail.
• After the installation work, perform a trial operation to check for any problem.
Follow the Owner’s Manual to explain how to use and maintain the unit to the customer.
• Turn off the main power supply switch (or breaker) before the unit maintenance.
• Ask the customer to keep the Installation Manual together with the Owner’s Manual.
WARNING
•
Ask an authorized dealer or qualified installation professional to install/maintain the Air to Water Heat Pump.
Inappropriate installation may result in water leakage, electric shock or fire.
• Be sure to connect earth wire. (grounding work)
Incomplete grounding cause an electric shock.
Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone wires.
• Turn off the main power supply switch or breaker before attempting any electrical work.
Make sure all power switches are off. Failure to do so may cause electric shock.
Use an exclusive power circuit for the Air to Water Heat Pump. Use the rated voltage.
• Connect the connecting wire correctly.
If the connecting wire is connected in a wrong way, electric parts may be damaged.
• When moving the Air to Water Heat Pump for the installation into another place, be very careful not to enter
any gaseous matter other than the specified refrigerant into the refrigeration cycle.
If air or any other gas is mixed in the refrigerant, the gas pressure in the refrigeration cycle becomes abnormally high
and it may resultingly causes pipe burst and injuries on persons.
• Do not modify this unit by removing any of the safety guards or by by-passing any of the safety interlock
switches.
• After unpacking the unit, examine it carefully if there are possible damage.
• Do not install in a place that might increase the vibration of the unit.
• To avoid personal injury (with sharp edges), be careful when handling parts.
• Perform installation work properly according to the Installation Manual.
Inappropriate installation may result in water leakage, electric shock or fire.
• When the Air to Water Heat Pump hydro unit is installed in a small room, provide appropriate measures to
ensure that the concentration of refrigerant leakage occur in the room does not exceed the critical level.
• Tighten the flare nut with a torque wrench in the specified manner.
Excessive tightening of the flare nut may cause a crack in the flare nut after a long period, which may result in
refrigerant leakage.
• Wear heavy gloves during the installation work to avoid injury.
• Install the Air to Water Heat Pump securely in a location where the base can sustain the weight adequately.
• Perform the specified installation work to guard against an earthquake.
If the Air to Water Heat Pump is not installed appropriately, accidents may occur due to the falling unit.
• If refrigerant gas has leaked during the installation work, ventilate the room immediately.
If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.
• After the installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas might
generate.
• Electrical work must be performed by a qualified electrician in accordance with the Installation Manual. Make
sure the Air to Water Heat Pump uses an exclusive power supply.
An insufficient power supply capacity or inappropriate installation may cause fire.
• Use the specified wires for wiring connect the terminals securely fix.
To prevent external forces applied to the terminals from affecting the terminals.
3-EN
–4–
Air to Water Heat Pump
Outdoor Unit Installation Manual
WARNING
• When the Air to Water Heat Pump cannot cool or heat water well, contact the dealer from whom you
purchased the Air to Water Heat Pump as refrigerant leakage is considered as the cause.
In the case of repair that requires refill of refrigerant, ask service personnel about details of the repair.
The refrigerant used in the Air to Water Heat Pump is harmless.
Generally, the refrigerant does not leak. However, if the refrigerant leaks in a room and a heater or stove burner in
the room catches fire, it may generate toxic gas.
When you ask service personnel for repairing refrigerant leakage, confirm that the leakage portion has been
completely repaired.
• Conform to the regulations of the local electric company when wiring the power supply.
Inappropriate grounding may cause electric shock.
• Do not install the Air to Water Heat Pump in a location subject to a risk of exposure to a combustible gas.
If a combustible gas leaks, and stays around the unit, a fire may occur.
• Install the refrigerant pipe securely during the installation work before operating the Air to Water Heat Pump.
If the compressor is operated with the valve open and without the refrigerant pipe, the compressor sucks air and the
refrigeration cycle is overpressurized, which may cause a burst or injury.
• For the refrigerant recovery work (collection of refrigerant from the pipe to the compressor), stop the
compressor before disconnecting the refrigerant pipe.
If the refrigerant pipe is disconnected while the compressor is working with the valve open, the compressor sucks air
and the refrigeration cycle is overpressurized, which may cause a burst or injury.
CAUTION
New Refrigerant Air to Water Heat Pump Installation
• THIS AIR TO WATER HEAT PUMP ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT
DESTROY OZONE LAYER.
• The characteristics of R410A refrigerant are ; easy to absorb water, oxidizing membrane or oil, and its pressure is
approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also
been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating oil does
not enter the refrigerating cycle.
• To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of
the main unit and installation tools are changed from those for the conventional refrigerant.
• Accordingly the exclusive tools are required for the new refrigerant (R410A).
• For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not
enter.
To Disconnect the Appliance from Main Power Supply
• This appliance must be connected to the main power supply by means of a switch with a contact separation of at
least 3 mm.
• The installation fuse 25 A (All type fuse can be used) must be used for the power supply line of this unit.
3INSTALLATION OF NEW REFRIGERANT
AIR TO WATER HEAT PUMP
EN
• The R410A refrigerant is more susceptible to impurities such as water, oxide membrane, oils, and fats. With the
adoption of the new refrigerant, refrigerating oil has also been changed.
Be careful so that water, dust, conventional refrigerant, and/or conventional refrigerating oil do not enter the
refrigerating cycle of the new refrigerant Air to Water Heat Pump.
• To prevent different refrigerant or refrigerating oil being mixed, the sizes of the charging port of the unit and the
installation tool connecting sections are different from the conventional refrigerant. Accordingly the following
exclusive tools are required for the new refrigerant R410A.
–5–
4-EN
Air to Water Heat Pump
Outdoor Unit Installation Manual
Required Tools/Equipment and Precautions for Use
Prepare the tools and equipment listed in the following table before starting installation work.
Newly prepared tools and equipment must be used exclusively.
Legend
: Prepared newly (Use for R410A only. Do not use for refrigerant R22 or R407C etc..)
: Conventional tools/equipment are available
Tools/equipmentUseHow to use tools/equipment
Gauge manifoldVacuuming/charging
Charging hosePrepared newly for R410A only
Charging cylinderCan not be usedUnusable (Use the refrigerant charging measure instead.)
Gas leak detectorGas leak checkPrepared newly
Vacuum pump with backflow
prevention function
Vacuum pump with backflow
prevention function
Flare toolFlare machining of pipesUsable if dimensions are adjusted.
BenderBending pipesR22 (Conventional tools)
Refrigerant recovery equipmentRefrigerant recoveryFor R410A only
Torque wrenchTightening flare nutsExclusive for Ø12.7 mm and Ø15.9 mm
Pipe cutterCutting pipesR22 (Conventional tools)
Discriminated by the refrigerant name on the cylinder.
Refrigerant Piping
New refrigerant (R410A)
When using the conventional piping kit
• When using the conventional piping kit that has no indication of applicable refrigerant types, be sure to use it with
a wall thickness of 0.8 mm for Ø6.4 mm, Ø9.5 mm, and Ø12.7 mm, and with a wall thickness of 1.0 mm for Ø15.9
mm. Never use the conventional piping kit with a wall thickness less than these thicknesses due to insufficient
pressure capacity.
When using general copper pipes
• Use general copper pipes with a wall thickness of 0.8 mm for Ø6.4 mm, Ø9.5 mm, and Ø12.7 mm, and with a
wall thickness of 1.0 mm for Ø15.9 mm.
Never use any copper pipes with a wall thickness less than these thicknesses.
Flare nuts and flare machining
• The flare nuts and flare machining are different from those for the conventional refrigerant.
Use the flare nuts supplied with the Air to Water Heat Pump or those for R410A.
• Before performing flare machining, carefully read “REFRIGERANT PIPING”
5-EN
–6–
Air to Water Heat Pump
Outdoor Unit Installation Manual
4SELECTION OF INSTALLATION
Before installation
Be careful to the following items before installation.
Length of refrigerant pipe
Length of refrigerant
pipe connected to hydro/
outdoor unit
3 m to 30 m
* Do not connect a refrigerant pipe shorter than 3m.
This may cause a malfunction of the compressor or
other devices.
Addition of refrigerant is
unnecessary at the local site.
Item
Airtight test
1. Before starting an airtight test, further tighten the
spindle valves on the gas side and liquid side.
2. Pressurize the pipe with nitrogen gas charged from
the service port to the design pressure (4.15 Mpa) to
conduct the airtight test.
3. After the airtight test is completed, evacuate the
nitrogen gas.
Air purge
• For air purge, use a vacuum pump.
• Do not use refrigerant charged in the outdoor unit for
air purge. (The refrigerant for air purge is not
contained in the outdoor unit.)
Electrical wiring
Be sure to fix the power wires and hydro/outdoor
connecting wires with clamps so that they do not
contact with the cabinet, etc.
Earthing
WARNING
Make sure that proper earthing is provided.
Improper earthing may cause electric shock. For how
to check earthing, contact the dealer who installed the
Air to Water Heat Pump or a professional installation
company.
• Proper earthing can prevent charging of electricity on
the outdoor unit surface due to high frequency of the
frequency converter (inverter) in the outdoor unit, as
well as prevent electric shock. If the outdoor unit is
not properly earthed, you may feel electric shock.
• Be sure to connect earth wire. (grounding work)
Incomplete grounding cause an electric shock.
Do not connect ground wires to gas pipes, water
pipes, lightning rods or ground wires for telephone
wires.
Test Run
• Start test run when the water piping work is
completed and the system is filled with the proper
amount of water.
• Turn on the leakage breaker at least 12 hours before
starting a test run to protect the compressor during
startup.
CAUTION
Incorrect work may result in a malfunction or
complaints of customers.
–7–
EN
6-EN
Air to Water Heat Pump
Outdoor Unit Installation Manual
Installation Place
WARNING
Install the outdoor unit properly at a place that is
durable enough to the weight of the outdoor unit.
Insufficient durability may cause the outdoor unit to fall,
which may result in injury.
CAUTION
Do not install the outdoor unit at a place subject to
combustible gas leak.
Accumulation of combustible gas around the outdoor
unit may cause a fire.
Install the outdoor unit at a place that meets the
following conditions after customer’s consent is
obtained.
• A well-ventilated place free from obstacles near the
air inlets and air outlet
• A place that is not exposed to rain or direct sunlight
• A place that does not increase the operating noise or
vibration of the outdoor unit
• A place that does not cause any drainage problem
with discharged water
CAUTION
1. Install the outdoor unit at a place where
discharge air is not blocked.
2. When an outdoor unit is installed in a place that
is always exposed to a strong wind like a coast
or on a high storey of a building, secure a
normal fan operation by using a duct or a wind
shield.
3. When installing the outdoor unit in a place that
is constantly exposed to a strong wind such as
the upper stairs or rooftop of a building, apply
the windproof measures referring to the
following examples.
1) Install the unit so that its discharge port faces
to the wall of the building.
Keep a distance 500 mm or more between the
unit and the wall surface.
500
Do not install the outdoor unit at the following
places.
• A place full of saline atmosphere (coastal area) or
sulfide gas (hot-spring area)
(Special maintenance is required.)
• A place subject to oil, vapor, oily smoke, or corrosive
gas
• A place where organic solvent is used
• A place where high-frequency equipment (including
inverter equipment, private power generator,
medical equipment, and communication equipment)
is used
(Installation in this place may cause malfunction of
the Air to Water Heat Pump, abnormal control or
problems due to noise to such equipment.)
• A place where the discharged air of the outdoor unit
blows against the window of the neighboring house
• A place where the operating noise of the outdoor unit
is transmitted
• When the outdoor unit is installed in an elevated
position, be sure to secure its feet.
• A place where the drain water does not make any
problem.
2) Supposing the wind direction during the
operation season of the Air to Water Heat
Pump, install the unit so that the discharge port
is set at right angle to the wind direction.
Strong
Strong
wind
• When using an Air to Water Heat Pump under low
outside temperature condition (Outside temp.:-5 °C or
lower) with COOL mode, prepare a duct or wind shield
so that it is not affected by the wind.
<Example>
Wind shield
wind
Wind shield
Wind shield
7-EN
–8–
Air to Water Heat Pump
Outdoor Unit Installation Manual
Necessary Space for Installation(Unit:mm)
Obstacle at rear side
▼ Upper side is free
1. Single unit installation
150
2. Obstacles at both right and left sides
200
or more
150
or more
3. Serial installation of two or more units
The height of the
obstacle should be
lower than the height
of the outdoor unit.
300
or more
or more
Obstacle at front side
▼ Upper side is free
1. Single unit installation
2. Serial installation of two or more units
▼ Obstacle also at the upper side
1000
or more
1000
or more
500
or more
1000
or more
150
or more
The height of the obstacle should be lower
than the height of the outdoor unit.
300
or more
300
or more
▼ Obstacle also at the upper side
150
or more
500
or more
300
or more
200 or more
Obstacles at both front and rear sides
Open the upper side and both right and left sides.
The height of obstacle at both front and rear side,
should be lower than the height of the outdoor unit.
▼ Standard installation
1. Single unit installation
150
or more
EN
1000
or more
–9–
8-EN
Air to Water Heat Pump
Outdoor Unit Installation Manual
2. Serial installation of two or more units
300
or more
300
or more
Serial installation at front and rear sides
Open the upper side and both right and left sides.
The height of obstacle at both front and rear sides
should be lower than the height of the outdoor unit.
▼ Standard installation
1000
or more
300
or more
1500
or more
2000
or more
or more
Installation of Outdoor Unit
200
1000
200
• As shown in the figure below, install the foundation
and vibration-proof rubbers to directly support the
bottom surface of the fixing leg that is in contact with
or more
the bottom plate of the outdoor unit.
* When installing the foundation for an outdoor unit
with downward piping, consider the piping work.
GOOD
or more
Fixing leg
Foundation
Absorb vibration
with vibration-
proof rubbers
GOOD
Bottom plate
of outdoor unit
Foundation
Support the bottom surface of
the fixing leg in contact with
the bottom plate of the outdoor
unit.
If only the end of the
fixing leg is
supported, it may be
deformed.
NO GOOD
Do not support
the outdoor unit
only with the
fixing leg.
• Before installation, check strength and horizontality
of the base so that abnormal sound does not
generate.
• According to the following base diagram, fix the base
firmly with the anchor bolts.
(Anchor bolt, nut: M10 x 4 pairs)
150
400
365
Drain
nipple mounting hole
Drain hole
Drain hole
525
600
45
150
Foundation
Set the out margin of the anchor bolt to 15 mm or less.
15 or less
9-EN
–10–
Air to Water Heat Pump
• In case of draining through the drain hose, attach the
following drain nipple and the waterproof rubber cap,
and use the drain hose (Inner diam.: 16 mm) sold on
the market. And also seal the screws securely with
silicone material, etc. so that water does not drop
down. Some conditions may cause dewing or
dripping of water.
• When collectively draining discharged water
completely, a drain pan must be made locally.
Outdoor Unit Installation Manual
Drain nipple
Waterproof rubber cap
(5pcs.)
Drain nipple
Waterproof rubber cap
For Reference
If a heating operation would be continuously performed
for a long time under the condition that the outdoor
temperature is 0 °C or lower, draining of defrosted
water may be difficult due to freezing of the bottom
plate, resulting in a trouble of the cabinet or fan.
It is recommended to procure an anti-freeze heater
locally for a safety installation of the Air to Water Heat
Pump.
For details, contact the dealer.
–11–
EN
10-EN
Air to Water Heat Pump
5REFRIGERANT PIPING
Outdoor Unit Installation Manual
Knockout of Pipe Cover
Rear direction
Pipe cover
Side direction
Front direction
Down direction
Knockout procedure
• The hydro/outdoor connecting pipes can be
connected to 4 directions.
Take off the knockout part of the pipe cover in which
pipes or wires pass through the base plate.
• Detach the piping cover and give an impact on the
knockout section a few times with the shank of a
screwdriver. A knockout hole can easily be punched.
Supplied protective bush
Supplied passage hole guard
material
* Attach the guard material
securely so that it does not
come loose.
Optional Installation Parts
(Local Procure)
Parts nameQ’ty
Refrigerant piping
A
Liquid side : Ø9.5 mm
Gas side : Ø15.9 mm
Pipe insulating material
B
(polyethylene foam, 10 mm thick)
C Putty, PVC tapesEach one
Each one
1
• After punching the knockout hole, remove burrs of
the hole and then install the supplied protective bush
and guard material for passage part to protect wires
and pipes.
Be sure to attach the pipe covers after pipes have
been connected. Cut the slits under the pipe covers
to facilitate the installation.
After connecting the pipes, be sure to mount the pipe
cover. The pipe cover is easily mounted by cutting off
the slit at the lower part of the pipe cover.
* Be sure to wear heavy work gloves while working.
Refrigerant Piping
Connection
CAUTION
TAKE NOTICE THESE IMPORTANT
4 POINTS BELOW FOR PIPING WORK
1. Keep dust and moisture away from inside the
connecting pipes.
2. Tightly connect the connection between pipes
and the unit.
3. Evacuate the air in the connecting pipes using
VACUUM PUMP.
4. Check gas leak at connected points.
▼ Piping connection
Liquid sideGas side
Outer
diameter
Ø9.5 mm0.8 mmØ15.9 mm1.0 mm
Thickness
Outer
diameter
Thickness
11-EN
–12–
Air to Water Heat Pump
Outdoor Unit Installation Manual
Flaring
1. Cut the pipe with a pipe cutter.
Be sure to remove burrs that may cause gas
leak.
2. Insert a flare nut into the pipe, and then flare the
pipe.
Use the flare nuts supplied with the Air to Water
Heat Pump or those for R410A.
Insert a flare nut into the pipe, and flare the pipe.
As the flaring sizes of R410A differ from those of
refrigerant R22, the flare tools newly manufactured
for R410A are recommended.
However, the conventional tools
can be used by adjusting
projection margin of the copper
pipe.
▼ Projection margin in flaring : B (Unit : mm)
Rigid (Clutch type)
Outer diam. of
copper pipe
15.9
R410A tool used
R410A
0 to 0.5
▼ Flare nut width: H and flare matching size: A.
Flare nut width: H
Copper pipe
outer diam.
H
For R410A1722262936
Ø6.4Ø9.5Ø12.7 Ø15.9 Ø19.0
Conventional
tool used
1.0 to 1.59.5
(mm)
Tightening of Connecting
Part
1. Align the centers of the connecting pipes and fully
tighten the flare nut with fingers. Then fix the nut with
a spanner as shown in the figure and tighten it with
a torque wrench.
2. As shown in the figure, be sure to use two spanners
to loosen or tighten the flare nut of the valve on the
gas side. If you use a single spanner, the flare nut
cannot be tightened to the required tightening
torque.
B
On the other hand, use a single spanner to loosen or
tighten the flare nut of the valve on the liquid side.
Outer diam. of copper pipeTightening torque
9.5 mm (diam.)33 to 42 (3.3 to 4.2 kgf•m)
15.9 mm (diam.)68 to 82 (6.8 to 8.2 kgf•m)
Half union or packed valveFlare nut
Externally
threaded side
Fix with spanner.Tighten with torque wrench.
Cover
Cap
(Unit: N•m)
Internally
threaded side
Flare machining size: A
A
Copper pipe
outer diam.
For R410A9.113.216.619.724.0
Ø6.4Ø9.5Ø12.7 Ø15.9 Ø19.0
A +0, -0.4(mm)
Do not apply the refrigerator oil to the flare surface.
* In case of flaring for R410A with the
A
conventional flare tool, pull it out approx.
0.5 mm more than that for R22 to adjust
to the specified flare size.
The copper pipe gauge is useful for
adjusting projection margin size.
Piping valve
Loosened
Tightened
Flare nut
Valve at gas side
EN
–13–
12-EN
Air to Water Heat Pump
Outdoor Unit Installation Manual
CAUTION
1. Do not put the spanner on the cap or cover.
The valve may be broken.
2. If applying excessive torque, the nut may be
broken according to some installation
conditions.
• After the installation work, be sure to check gas leak
of connecting part of the pipes with nitrogen.
NO GOOD
Cover
Cap
Refrigerant Pipe Length
Refrigeration pipe
H: max. ±30 m (above/below)
L: max. 30 m, min. 3 m
Hydro Unit
Outdoor unit
L
H
30 m chargeless
• Pressure of R410A is higher than that of R22
(Approx. 1.6 times).
Therefore, using a torque wrench, tighten the flare
pipe connecting sections which connect the hydro/
outdoor units at the specified tightening torque.
Incomplete connections may cause not only a gas
leak, but also a trouble of the refrigeration cycle.
Do not apply refrigerating machine oil to the
flared surface.
13-EN
–14–
Air to Water Heat Pump
Outdoor Unit Installation Manual
6AIR PURGING
Airtight test
Before starting an airtight test, further tighten the spindle valves on the gas side and liquid side.
Pressurize the pipe with nitrogen gas charged from the service port to the design pressure (4.15 Mpa) to conduct
the airtight test.
After the airtight test is completed, evacuate the nitrogen gas.
Air Purge
With respect to the preservation of terrestrial environment, adopt “Vacuum pump” for air purge
(Evacuate air in the connecting pipes) when installing the unit.
• Do not discharge the refrigerant gas to the atmosphere to preserve the terrestrial environment.
• Use a vacuum pump to discharge the air (nitrogen, etc.) remained in the set. If the air remains,
the capacity may decrease.
For the vacuum pump, be sure to use one with backflow preventer so that the oil in the pump
does not backflow into the pipe of the Air to Water Heat Pump when the pump stops.
(If oil in the vacuum pump is put in an Air to Water Heat Pump including R410A, it may cause trouble on the
refrigeration cycle.)
Vacuum pump
As shown in the figure, connect the charge hose after the manifold
valve are closed completely.
È
Attach the connecting port of the charge hose with a projection to
push the valve core (setting pin) to the charge port of the set.
È
Open handle Low fully.
È
Turn ON the vacuum pump (*1)
È
Loosen the flare nut of the packed valve (Gas side) a little to check
the air passes through. (*2)
È
Tighten the flare nut again.
È
Execute vacuuming until the compound pressure gauge indicates –
101kPa (–76cmHg). (*1)
È
Close handle Low completely.
È
Turn OFF the vacuum pump.
È
Leave the vacuum pump as it is for 1 or 2 minutes, and check the
indicator of the compound pressure gauge does not return.
È
Open fully the valve stem or the valve handle. (First, at liquid side,
then gas side)
È
(continued)
Disconnect the charge hose from the charge port.
Tighten valve and caps of the charge port surely.
È
È
*1Use the vacuum pump, vacuum pump adapter, and
gauge manifold correctly referring to the manuals
supplied with each tool before using them.
Check that the vacuum pump oil is filled up to the
specified line of the oil gauge.
2
*
When air is not charged, check again whether the
connecting port of the discharge hose, which has a
projection to push the valve core, is firmly connected
to the charge port.
Compound pressure gauge
–101 kPa
(–76 cmHg)
Handle Lo
Charge hose
(For R410A only)
Charge port
(Valve core
(Setting pin))
Packed valve
at gas side
Pressure gauge
Gauge manifold
valve
Handle Hi
(Keep fully
closed)
Charge hose
(For R410A only)
Vacuum pump
adapter for
counter-flow
prevention
(For R410A only)
Vacuum
pump
EN
–15–
14-EN
Air to Water Heat Pump
Outdoor Unit Installation Manual
How to open the valve
Confirm the structure surely and then open or close the
valve.
▼ Liquid side
Open the valve with a 4-mm hexagon wrench.
▼ Gas side
Valve unit
Using a minus
screwdriver, turn it
counterclockwise by
90° until it hits the
stopper. (Full open)
Charge port
Flare nut
Replenishing refrigerant
This model is a 30 m chargeless type that does not
need to replenish refrigerant for refrigerant pipes up to
30 m.
Refrigerant replenishing procedure
1. After the vacuuming of the refrigerant pipe is
completed, close the valves and then charge
refrigerant while the Air to Water Heat Pump is not
working.
2. When the refrigerant cannot be charged to the
specified amount, charge the required amount of
refrigerant from the charge port of the valve on the
gas side during cooling.
Requirement for replenishing refrigerant
Replenish liquid refrigerant.
When gaseous refrigerant is replenished, the
refrigerant composition varies, which disables normal
operation.
Handle position
Closed completelyOpened fully
Stopper pin
Main stopper
Movable part of valve (Stem)
• While the valve is fully opened, after the screwdriver
has reached the stopper, do not apply torque
exceeding 5N•m. Applying excessive torque may
damage the valve.
Valve handling precautions
• Open the valve stem until it strikes the stopper.
It is unnecessary to apply further force.
• Securely tighten the cap with a torque wrench.
• Cap tightening torque
Valve size
Charge port14 to 18 N•m (1.4 to 1.8 kgf•m)
Ø9.5 mm33 to 42 N•m (3.3 to 4.2 kgf•m)
Ø15.9 mm20 to 25 N•m (2.0 to 2.5 kgf•m)
Additional amount of refrigerant
The refrigerant need not be reduced for a 30 meter (or
less) refrigerant pipe.
15-EN
–16–
Air to Water Heat Pump
7ELECTRICAL WORK
Outdoor Unit Installation Manual
WARNING
1. Using the specified wires, ensure to connect the
wires, and fix wires securely so that the external
tension to the wires do not affect the connecting
part of the terminals.
Incomplete connection or fixation may cause a fire,
etc.
2. Be sure to connect earth wire. (grounding work)
Incomplete grounding cause an electric shock.
Do not connect ground wires to gas pipes, water
pipes, lightning rods or ground wires for telephone
wires.
3. Appliance shall be installed in accordance with
national wiring regulations.
Capacity shortage of power circuit or incomplete
installation may cause an electric shock or a fire.
CAUTION
• Wrong wiring may cause a burn-out to some electrical
parts.
• Be sure to use the cord clamps attached to the
product.
• Do not damage or scratch the conductive core and
inner insulator of power and inter-connecting wires
when peeling them.
• Use the power and Inter-connecting wires with
specified thickness, specified type and protective
devices required.
Furthermore, be sure to secure these wires with the
pipe valve fixing plate and cord clamps stored in the
electric parts box.
Electric parts box
Pipe valve
fixing plate
Cord
clamp
Pipe hole
Panel
Wiring between Hydro Unit
and Outdoor Unit
The dashed lines show on-site wiring.
11
Input power
230 V
50 Hz
Leakage
breaker
30 mA
L
N
Outdoor Unit
22
TB01
33
Hydro Unit
• Remove the panel, and you can see electric parts on
the front side.
• A metal pipe can be installed through the hole for
wiring. If the hole size does not fit the wiring pipe to
be used, drill the hole again to an appropriate size.
• Be sure to clamp the power wires and hydro/outdoor
connecting wires with banding band along the
connecting pipe so that the wires do not touch the
compressor or discharge pipe. (The compressor and
the discharge pipe become hot.)
• Connect the hydro/outdoor connecting wires to the
identical terminal numbers on the terminal block of
each unit.
Incorrect connection may cause a failure.
For the Air to Water Heat Pump, connect a power wire
as mentioned below.
Model HWS-802H-E1102H-E1402H-E
Power supply230 V~, 50 Hz
Maximum
running
current
Installation
fuse rating
Power wire
Hydro/outdoor
connecting
wires
20.8 A22.8 A
(2.5 mm
(1.5 mm
25 A
2
or more)
2
or more)
(all types can be used)
H07 RN-F or 60245 IEC 66
H07 RN-F or 60245 IEC 66
EN
–17–
16-EN
Air to Water Heat Pump
Outdoor Unit Installation Manual
How to wire
1. Connect the connecting wire to the terminal as
identified with their respective numbers on the
terminal block of hydro and outdoor unit.
H07 RN-F or 60245 IEC 66 (1.5 mm
2. When connecting the connecting wire to the outdoor
unit terminal, prevent water coming in the outdoor
unit.
3. Insulate the unsheathed cords (conductors) with
electrical insulation tape. Process them so that they
do not touch any electrical or metal parts.
4. For inter connecting wire, do not use a wire jointed
to another on the way.
Use wires long enough to cover the entire length.
To Hydro unit
terminal block
123
Earth screw
Earth screw
2
or more)
Power supply
terminal block
LN
CAUTION
• The installation fuse must be used for the power
supply line of this outdoor unit.
• Incorrect/incomplete wiring might cause an electrical
fire or smoke.
• Prepare the exclusive power supply for the Air to
Water Heat Pump.
• This product can be connected to the mains.
Connection to the fixed wiring :
A switch which disconnects all poles and has a
contact separation of at least 3 mm must be
incorporated in the fixed wiring.
Connecting wire
Pipe valve fixing
plate
Power supply
wire
Stripping length power cord and connecting
wire
10
LN
10
50
40
Earth lineEarth line
Power supply
wire
50
10
123
10
30
(mm)
Connecting wire
17-EN
–18–
Air to Water Heat Pump
Outdoor Unit Installation Manual
8EARTHING
WARNING
• Be sure to connect earth wire. (grounding work)
Incomplete grounding cause an electric shock.
Connect the earth line properly following applicable technical standards.
Connecting an earth line is essential to prevent electric shock and to reduce noise and electricity charge on the
outdoor unit surface due to high frequency generated by the frequency converter (inverter) in the outdoor unit.
If you touch the charged outdoor unit without earth line, you may feel electric shock.
9FINISHING
After the refrigerant pipe and the inter-unit wires have been connected, cover them with finishing tape and clamp
them to the wall with off-the-shelf support brackets or equivalent.
Keep the power wires and hydro/outdoor connecting wires off the valve on the gas side or pipes that have no heat
insulator.
10TEST RUN
• The test run, on the outdoor unit, can only be completed when the complete Air to Water Heat Pump system has
been installed. (Hydro unit, heating system or/and the others)
• Please refer to the hydro unit installation manual for the details of the test run procedure.
11ANNUAL MAINTENANCE
• For Air to Water system which is operated regularly, cleaning and maintenance of the hydro/outdoor units are
strongly recommended.
As a general rule, if an hydro unit is operated for about 8 hours daily, the hydro/outdoor units will need to be
cleaned at least once every 3-month. This cleaning and maintenance shall be carried out by a qualified person.
Failure to clean the hydro/outdoor units regularly will result in poor performance, icing, water leaking and even
compressor failure.
EN
–19–
18-EN
Air to Water Heat Pump
Outdoor Unit Installation Manual
12
FUNCTIONS TO BE IMPLEMENTED LOCALLY
Recovering Refrigerant
• Use the refrigerant recovery switch SW801 on the P.C. board of the outdoor unit to recover refrigerant when the
hydro unit or outdoor unit is moved.
Procedure
1. Drain off the water in the hydro unit.
2. Turn on the power of the Air to Water Heat Pump.
3. Set SW804 on the P.C. board of the outdoor unit to all OFF, and then press SW801 for one second or more.
The Air to Water Heat Pump enters the forced cooling mode for up to 10 minutes. Operation or handling the
valve to recover refrigerant during this time period.
4. Upon completion of refrigerant recovery, close the valve and press SW801 for at least one second to stop
operation.
5. Turn off the power.
Refrigerant
recovery
switch
SW801
Optional
connector
CN610
P.C. board
Special
operation
select switch
SW804
DANGER
Take care for an electric shock because the P.C.board is electrified.
1234
ON
1234
ON
19-EN
–20–
Air to Water Heat Pump
Outdoor Unit Installation Manual
13TROUBLESHOOTING
You can perform fault diagnosis of the outdoor unit with the LEDs on the P.C. board of the outdoor unit in addition
to check codes displayed on the wired remote controller of the hydro unit.
Use the LEDs and check codes for various checks. Details of check codes displayed on the wired remote controller
of the hydro unit are described in the Installation Manual of the hydro unit.
Check of the current abnormal status
1. Check that DIP switch SW803 is set to all OFF.
2. Jot down the states of LED800 to LED804. (Display
mode 1)
3. Press SW800 for at least one second. The LED
status changes to display mode 2.
4. Check the code whose display mode 1 equals the
jotted LED status and display mode 2 equals the
current flashing status of LED800 to LED804 from
the following table to identify the cause.
No.Cause
1Normal
2Discharge (TD) sensor error
3Heat exchanger (TE) sensor error
4Heat exchanger (TL) sensor error
5Outside air temperature (TO) sensor error
6Suction (TS) sensor error
7Heat sink (TH) sensor error
8Outdoor temperature sensor (TE/TS) connection error
9Outdoor EEPROM error
10 Compressor lock
11 Compressor lock
12 Current detect circuit error
13 Thermostat for compressor activated
Model data not set
14
(on the service P.C. board)
15 MCU-MCU communication error
16
Discharge temperature error
Abnormal power
17
(open phase detected or abnormal voltage)
18 Heat sink overheat
19 Gas leak detected
20 4-way valve reverse error
21 High pressure release operation
22 Outdoor fan motor error
23 Compressor driver short-circuit protection
24 Position detect circuit error in one-line display
Check of the abnormal status in the past although the
abnormal status is not occurred now.
1. Set bit 1 of DIP switch SW803 to ON.
2. Jot down the states of LED800 to LED804. (Display
mode 1)
3. Press SW800 for at least one second. The LED
status changes to display mode 2.
4. Find an error whose display mode 1 equals the jotted
LED status and display mode 2 equals the current
flashing status of LED800 to LED804 from the
following table to identify the error.
• An outside air temperature (TO) sensor error can
be checked only while an error occurs.
Display mode 1 Display mode 2
D800D801D802D803D804D800D801D802D803D804
●●●●●●●●●●
{{●●{●●●●
{{●●{●●●
{{●●{●●
{{●●{●●●●
{{●●{●●●
{{●●{●●
{{●●{●
{{●●{
●●{●{●●●●
●●{●{●●●●
●●{●{●●●
●●{●{●●●●
●{{●{●●●
●{{●{●
{{{●{●●●
EN
{{{●{●●●
{{{●{●●
{{{●{●
{{{●{●●
{{{●{●●●
{{{●{●●
{{{●{●●
{{{●{●
(●:OFF {:ON :Flashing)
–21–
20-EN
Air to Water Heat Pump
Outdoor Unit Installation Manual
* The LEDs and DIP switches are located at the lower left of the P.C. board of the outdoor unit.
SW801
SW800
Enlarged view
of LEDs
ON
SW804
1234
D800
D801
D802
D803
D804
D805
LED
SW803
1234
ON
D800
D801
D802
D803
D804
D805
SW802
1234
ON
14APPENDIX
Curing of pipes
When removing and opening the hydro unit or outdoor unit for a long time, cure the pipes as follows:
• Otherwise rust may generate when moisture or foreign matter due to dewing enters in the pipes.
• The rust cannot be removed by cleaning, and a new piping work is necessary.
Place positionTermCuring manner
Outdoors
Hydro unitsEvery time
1 month or morePinching
Less than 1 month
Pinching or taping
21-EN
–22–
Air to Water Heat Pump
Outdoor Unit Installation Manual
IMPORTANT INFORMATION AND WARNING:
READ BEFORE INSTALLING THE UNIT. KEEP IN A SAFE PLACE THE INFORMATION IN THIS BOOKLET IS NEEDED
FOR END OF LIFE, DISPOSAL OR REUSE OF THE UNIT
• We are very sensitive to environment and welcomes the 2002/96/EC Directive WEEE (Waste Electrical and Electronic Equipment).
• This product is compliant with EU directive 2002/96/EC. It must be collected separately after its use is completed, and cannot be disposed
as unsorted municipal waste.
• The objectived of EU directive 2002/96/EC are to tackle the fast increasing waste stream of electrical and electronic equipment, increase
recycling of electric & electronic equipment ("EEE"), and to limit the total quantity of waste EEE ("WEEE") going to final disposal.
• The crossed out wheeled bin symbol that is affixed to the product means that this product falls under the Directive.
• The user is responsible for returning the product to the appropriate collection facility, as specified by your municipality or the distributor.
In case of installation of a new product, it may be possible to have the distributor pick up old WEEE directly.
• The producer, importer and distributor of are responsible for collection and treatment of waste, either directly or through a collective system.
The list of our distributor in each country is shown in the attached table.
• In case of violation of the Directive, sanctions are set in each country.
• We are in general following the "CECED interpretation", and consider the WEEE applicable to Portable units, Dehumidifiers, WRACs
(Window Room Air to Water Heat Pumps), Split Systems up to 12 kW, plug in refrigerators and freezers.
• Nevertheless, there may be difference among member state laws. In case country law exclude some products from WEEE scope, country
law must be followed, and WEEE obligations do not have to be followed for products that fall out of country low scope.
• This directive does not apply to products sold outside European Community. In case the product is sold out of Eu, WEEE obligations do
not have to be followed, while compliance with local regulation must be ensured.
• For additional information, please contact the municipal facility, the shop/dealer/installer that have sold the product, or the producer.
➊ Country
➋ Name of Company responsible for WEEE.
➊➋
AIRCOND, Klimaanlagen
Austria
Belgium
Cyprus
Denmark
Estonia
Finland
France
Germany
Greece
Handelsgesellshcaft m.b.H
Petesgasse 45, A-8010
Graz Austria
AIRCOND, Klimaanlagen
Handelsgesellshcaft m.b.H
Petersgasse 45, A-8010
Graz Austria
EN
The manufacturer reserves the right to change any product specifications without notice.
–23–
22-EN
Air to Water Heat Pump
Avant d’installer la pompe à chaleur air/eau, lisez attentivement ce Manuel d’installation.
• Ce manuel décrit la méthode d’installation de l’unité extérieure.
• Pour l’installation de l’unité hydroélectrique, reportez-vous au Manuel d’installation fourni avec l’unité
hydroélectrique.
Outdoor Unit Installation Manual
ADOPTION DU NOUVEAU REFRIGERANT
Cette pompe à chaleur air/eau est un nouveau type qui adopte un nouveau réfrigérant HFC (R410A) au lieu
du réfrigérant traditionnel R22 en vue d’éviter la destruction de la couche d’ozone.
1Ce manuel(Remettez celui-ci directement au client.)
Bouchon en caoutchouc
étanche
Manchon de protection1Pour la protection des câbles (protection des tuyaux)
Matériau de protection
pour passages
5
1Pour la protection des passages (protection des tuyaux)
Tuyaux de réfrigérant
• Le kit de tuyaux utilisé pour le réfrigérant traditionnel ne peut être utilisé.
• Utilisez un tuyau en cuivre de 0,8 mm ou plus d’épaisseur pour Ø9,5 mm.
Utilisez un tuyau en cuivre de 1,0 mm ou plus d’épaisseur pour Ø15,9 mm.
• Les écrous évasés et l’évasement diffèrent également de ceux des tuyaux du réfrigérant traditionnel.
Retirez l’écrou évasé fourni avec la pompe à chaleur air/eau et utilisez-le.
–25–
FR
2-FR
Air to Water Heat Pump
Outdoor Unit Installation Manual
2MESURES DE SECURITE
• Assurez-vous de respecter toutes les règles locales, nationales et internationales.
• Lisez attentivement ces « MESURES DE SECURITE » avant l’installation.
• Les mesures décrites ci-après comprennent des points importants concernant la sécurité.
Observez-les scrupuleusement.
• Après l’installation, faites un essai de fonctionnement pour vous assurer de l’absence de problèmes.
Reportez-vous au Manuel du propriétaire pour expliquer au client comment utiliser l’unité et effectuer son
entretien.
• Mettez l’interrupteur général (ou le disjoncteur) hors tension avant d’effectuer l’entretien de l’unité.
• Demandez au client de conserver le Manuel d’installation avec le Manuel du propriétaire.
AVERTISSEMENT
•
Demandez à un revendeur autorisé ou à un installateur professionnel d’installer la pompe à chaleur air/eau ou
d’effectuer son entretien.
Une installation inadéquate peut se solder par une fuite d’eau, une électrocution ou un incendie.
• Veillez à raccorder les fils de terre. (mise à la terre)
Une mise à la terre incomplète provoque une électrocution.
Ne raccordez pas les fils de terre aux tuyaux de gaz, aux tuyaux d’eau, aux paratonnerres ou aux fils de terre des
câbles téléphoniques.
• Mettez l’interrupteur général ou le disjoncteur hors tension avant d’entreprendre l’installation électrique.
Assurez-vous que tous les interrupteurs sont hors tension. La non-observation de cet avertissement peut se solder
par une électrocution.
Utilisez un circuit d’alimentation exclusif pour la pompe à chaleur air/eau. Utilisez la tension nominale.
• Branchez correctement le câble de raccordement.
Si le câble de raccordement est mal branché, les composants électriques peuvent s’endommager.
• Lorsque vous déplacez la pompe à chaleur air/eau pour l’installer ailleurs, faites très attention à ce qu’aucun
corps gazeux autre que le réfrigérant spécifié ne pénètre dans le circuit de réfrigération.
Si l’air ou tout autre gaz se mélange au réfrigérant, la pression gazeuse du circuit de réfrigération augmentera
anormalement et pourra faire éclater les tuyaux et blesser quelqu’un.
• Ne modifiez pas cette unité en démontant ses carters de protection ou en by-passant ses verrous de sûreté.
• Après avoir déballé l’unité, examinez-la attentivement pour vous assurer qu’elle n’est pas endommagée.
• Ne l’installez pas dans un endroit susceptible d’augmenter ses vibrations.
• Afin d’éviter de vous blesser (avec des bords tranchants), faites attention lorsque vous manipulez les pièces.
• Effectuez l’installation conformément au Manuel d’installation.
Une installation inadéquate peut se solder par une fuite d’eau, une électrocution ou un incendie.
• Si l’unité hydroélectrique de la pompe à chaleur air/eau est installée dans une petite pièce, prenez les
mesures appropriées pour garantir que la concentration de fuite de réfrigérant dans la pièce ne dépasse pas
le niveau critique.
• Serrez l’écrou évasé avec une clé dynamométrique de la manière spécifiée.
Un serrage excessif de l’écrou évasé peut se solder par une rupture de l’écrou évasé après une longue période, ce
qui peut entraîner une fuite de réfrigérant.
• Portez des gants épais pendant l’installation pour éviter de vous blesser.
• Installez solidement la pompe à chaleur air/eau dans un endroit qui supporte son poids de manière adéquate.
• Effectuez l’installation spécifiée pour protéger le climatiseur contre un tremblement de terre.
Si la pompe à chaleur air/eau n’est pas installée de manière appropriée, elle peut tomber et provoquer des accidents.
• Si le gaz réfrigérant a fui durant l’installation, aérez immédiatement la pièce.
Si le gaz réfrigérant qui a fui entre en contact avec le feu, un gaz nocif peut se dégager.
• Après l’installation, assurez-vous que le gaz réfrigérant ne fuit pas.
Si le gaz réfrigérant fuit dans la pièce et s’écoule près d’un appareil ignigène, comme une cuisinière, un gaz nocif
peut se dégager.
• L’installation électrique doit être effectuée par un électricien professionnel conformément au Manuel
d’installation. Assurez-vous que la pompe à chaleur air/eau utilise une alimentation exclusive.
Une alimentation de puissance insuffisante ou une installation inappropriée peuvent provoquer un incendie.
• Utilisez les câbles spécifiés et raccordez-les bien aux bornes.
Evitez qu’une pression externe ne s’exerce sur les bornes et ne les affecte.
3-FR
–26–
Air to Water Heat Pump
Outdoor Unit Installation Manual
AVERTISSEMENT
• Lorsque la pompe à chaleur air/eau ne peut pas refroidir ou chauffer convenablement une pièce, contactez
le revendeur qui vous l’a vendue si une fuite de réfrigérant est susceptible d’être la cause.
En cas de réparation requérant le remplissage de réfrigérant, demandez les détails de la réparation au
personnel chargé de l’entretien.
Le réfrigérant utilisé dans la pompe à chaleur air/eau est inoffensif.
Généralement, le réfrigérant ne fuit pas. Cependant, si le réfrigérant fuit dans une pièce et qu’un chauffage ou une
cuisinière prend feu, un gaz toxique peut se dégager.
Si vous demandez au personnel chargé de l’entretien de réparer la fuite de réfrigérant, vérifiez que la partie qui fuyait
a été complètement réparée.
• Observez les règles de la compagnie d’électricité locale lorsque vous raccordez les câbles d’alimentation.
Une mise à la terre inappropriée peut provoquer une électrocution.
• N’installez pas la pompe à chaleur air/eau dans un endroit susceptible d’être exposé à des gaz inflammables.
Si un gaz inflammable fuit et stagne autour de l’unité, il peut provoquer un incendie.
• Installez solidement le tuyau de réfrigérant pendant l’installation avant d’utiliser la pompe à chaleur air/eau.
Si le compresseur fonctionne avec la soupape ouverte et sans le tuyau de réfrigérant, le compresseur aspire l’air et
le circuit de réfrigération est surpressurisé, ce qui peut faire éclater l’unité et blesser quelqu’un.
• Pour la récupération du réfrigérant (collecte du réfrigérant du tuyau vers le compresseur), arrêtez le
compresseur avant de débrancher le tuyau de réfrigérant.
Si le tuyau de réfrigérant est débranché alors que le compresseur fonctionne avec la soupape ouverte, le
compresseur aspire l’air et le circuit de réfrigération est surpressurisé, ce qui peut faire éclater l’unité et blesser
quelqu’un.
ATTENTION
Installation du nouveau réfrigérant dans la pompe à chaleur air/eau
• CETTE POMPE A CHALEUR AIR/EAU UTILISE LE NOUVEAU REFRIGERANT HFC (R410A) QUI NE DETRUIT
PAS LA COUCHE D’OZONE.
• Le réfrigérant R410A se distingue par son absorption aisée de l’eau, de la membrane oxydante ou de l’huile ainsi
que par sa pression, qui est d’environ 1,6 fois celle du réfrigérant R22. Outre l’utilisation du nouveau réfrigérant,
l’huile réfrigérante a elle aussi été remplacée. Par conséquent, durant l’installation, assurez-vous que l’eau, la
poussière, le réfrigérant précédent ou l’huile réfrigérante n’entrent pas dans le circuit de réfrigération.
• Pour éviter de remplir du réfrigérant et de l’huile réfrigérante inappropriés, la taille des sections de raccordement de
l’orifice de remplissage de l’unité principale et les outils d’installation sont différents de ceux qui sont utilisés pour le
réfrigérant traditionnel.
• En conséquence, les outils exclusifs sont requis pour le nouveau réfrigérant (R410A).
• Quant aux tuyaux de raccordement, utilisez des tuyaux neufs et propres conçus pour le R410A et veillez à ce que
l’eau ou la poussière n’y entrent pas.
Pour déconnecter l’appareil du secteur
• Cet appareil doit être connecté au secteur via un interrupteur ayant une séparation de contact d’au moins 3 mm.
• Vous devez utiliser le fusible d’installation 25 A (vous pouvez utiliser n’importe quel type de fusible) sur la ligne
d’alimentation de cette unité.
3
INSTALLATION DU NOUVEAU REFRIGERANT
DANS LA POMPE A CHALEUR AIR/EAU
• Le réfrigérant R410A est plus sensible aux impuretés telles que l’eau, la membrane oxydante, les huiles et les
graisses. Outre l’adoption du nouveau réfrigérant, l’huile réfrigérante a elle aussi été remplacée.
Veillez à ce que l’eau, la poussière, le réfrigérant traditionnel et/ou l’huile réfrigérante traditionnelle ne pénètrent
pas dans le circuit de réfrigération de la pompe à chaleur air/eau utilisant le nouveau réfrigérant.
• Pour éviter le mélange de différents réfrigérants ou huiles réfrigérantes, la taille des sections de raccordement
de l’orifice de remplissage de l’unité et l’outil d’installation sont différents de ceux utilisés pour le réfrigérant
traditionnel. En conséquence, les outils exclusifs suivants sont requis pour le nouveau réfrigérant (R410A).
–27–
FR
4-FR
Loading...
+ 63 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.