Toshiba HFC R407C Installation Instructions

Outdoor
Installation Instructions
Air Conditioner – Multi Split Type System
Außengerät
Installationsanleitung
Klimaanlage – Geteilte Multi-Bauweise
Instructions
Climatiseur – Système de Type Multi Split
Buiten
Installatievoorschriften
Airconditioning – Multi-delig Type Systeem
GB
F
D
E
I
NL
Istruzioni per
l’installazione dell’unità esterna
Condizionatore d’aria – Tipo Multi Split
Modular Multi System
Exterior
Instrucciones de Instalación
Aire acondicionado – Sistema de Tipo Multi Split
HFC
R407C
1402241301R01
GB
3
Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Trial Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
Passer à la page 65 pour lire le manuel d’installation en français.
Die deutsche Montageanleitung finden Sie auf Seite 127.
Por favor, vaya a la página 189 para seguir las instrucciones del manual de instalacíon en lengua española.
Il manuale d’installazione italiano è a pagina 251.
Zie bladzijde 313 voor de Nederlandse Installatichandleiding.
F
D
E
I
NL
GB
Introduction
Contents
4
Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Operating Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Metric/Imperial pipe conversion . . . . . . . . . . . . . . . . . . . . .7
GB
Please read these instructions carefully before starting the installation. This equipment should only be installed by suitably trained operatives. In all cases ensure safe working practice: Observe precautions for persons in the vicinity of
the works. Ensure that all local, national and international regulations are satisfied. Check that the electrical specifications of the unit meet the requirements of the site. Carefully unpack the equipment, check for damage or shortages. Please report any damage
immediately.
These units comply with EC Directive: 73/23/EEC (Low Voltage Directive) and 89/336/EEC (Electro Magnetic Compatibility). Accordingly, they are designated for use in commercial and industrial environments.
Avoid installation in the following locations:
Where the water drainage may cause a nuisance or a hazard when frozen. Where there is a danger of flammable gas leakage. Where there are high concentrations of oil. Where the atmosphere contains an excess of salt (as in coastal areas). Special maintenance
is required to maintain product design life. Where the airflow from the outdoor unit may cause annoyance. Where the operating noise of the outdoor unit may cause annoyance. Where the foundation is not strong enough to fully withstand the weight of the outdoor unit. Where strong winds may blow against the air inlet of the outdoor unit.
Precautions for R407C Systems
R407C outdoor units use synthetic oils which are extremely hygroscopic. Therefore ensure that the refrigerant system is NEVER exposed to air or any form of moisture.
Mineral oils are unsuitable for use in these units and may lead to premature system failure. Use only equipment which is suitable for use with R407C. Never use equipment which has
been used with R22. R407C should only be charged from the service cylinder in the liquid phase. It is advisable to
use a gauge manifold set equipped with a liquid sight glass fitted in the centre (entry) port.
5
Introduction
Precautions
GB
6
Introduction
Operating Conditions
1. Allocation standard of Model name
2. Range of combined units
No. of combined units : 1 to 5 units Capacity range : Equivalent to 14HP (0384kW type) to 46HP (1288kW)
3. Restriction for combination units
(1) The Inverter Unit should have the maximum capacity among all units in
that combination.
(2) The 6HP fixed-speed unit is available only with the combination of 14HP
and 22HP. (It cannot be used for any other combination.)
4. Rated conditions
Cooling : Indoor air temperature 27°C DB/19°C WB
Outdoor air temperature 35°C DB/25°C WB
Heating : Indoor air temperature 21°C DB/15.5°C WB
Outdoor air temperature 7°C DB/6° C WB
5. Mode Priority
This Outdoor Unit is set to operate with the Heating mode taking precidence. This precidence can be switched between Heat and Cool mode using the DIP switch 07 on the Outdoor Unit Interface PCB (MCC-1343-01) as follows:
Outdoor Temperature
–5 ~ 43°C Cooling
–15 ~ 21°C Heating
Room Temperature
18 ~ 32°C Cooling 15 ~ 29°C Heating
Room Humidity <80% Cooling
T – Inverter X – Fixed Speed
0280 – 28.0kW (10HP) 0224 – 22.4kW (8HP) 0160 – 16.0kW (6HP)
C – Cooling H – Heating
MM–A0280HT
INDOOR
OUTDOOR
A – Outdoor
Modular Multi
028 – 2.8kW (1HP) 042 – 4.2kW (1.5HP) 056 – 5.6kW (2HP) 080 – 8.0kW (3HP) 112 – 11.2kW (4HP) 140 – 14.0kW (5HP)
MM–TU056
Modular Multi
B – Built-In Duct Type C (CR) – Ceiling Type (IR Remote) K (KR) – High Wall Type (IR Remote) N – Carcase Type S (SR) – Low Wall Type (IR Remote) SB – Built-In Slim Duct Type TU – 2 Way Cassette Type U – 4 Way Cassette Type
ON OFF
ON
OFF
Heat Priority (factory set) Cool Priority
GB
7
Introduction
Components
Metric/Imperial pipe conversion
Inverter unit Fixed-speed unit Appearance
Corresponding HP
8HP 10HP 6HP 8HP 10HP
Model name MM-A0224HT MM-A0280HT MM-A0160HX MM-A0224HX MM-A0280HX
Cooling capacity (kW) 22.4 28.0 16.0 22.4 28.0
Heating capacity (kW) 25.0 31.5 18.0 25.0 31.5
Corresponding HP 8HP 10HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP 32HP 34HP 36HP 38HP 40HP 42HP 44HP 46HP
Combined Model MM-A~HT
0224 0280 0384 0440 0504 0560 0608 0672 0728 0784 0840 0896 0952 1008 1064 1120 1176 1232 1288
Cooling capacity (kW) 22.4 28.0 38.4 44.8 50.4 56.0 60.8 67.2 72.8 78.4 84.0 89.6 95.2 100.8 106.4 112.0 117.6 123.2 128.8
Inverter unit 8HP 10HP 8HP 8HP 10HP 10HP 8HP 8HP 10HP 10HP 10HP 8HP 10HP 10HP 10HP 10HP 10HP 10HP 10HP
6HP 8HP 8HP 10HP 8HP 8HP 8HP 10HP 10HP 8HP 8HP 10HP 10HP 10HP 8HP 10HP 10HP
6HP 8HP 8HP 8HP 10HP 8HP 8HP 8HP 10HP 10HP 8HP 8HP 10HP
——— ————— ———8HP8HP8HP8HP10HP 8HP 8HP 8HP
——— ————— ————————8HP8HP8HP
13 16 16 18 18 20 22 24 26 28 30 32 34 36 38 40 40 40 40
Min. HP Connection 4 5 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Max. HP Connection 10.8 13.5 18.9 21.6 24.3 27 29.7 32.4 35.1 37.8 40.5 43.2 45.9 48.6 51.3 54 56.7 59.4 62.1
Combined outdoor units
No. of connectable indoor units
Fixed­speed unit
1. Outdoor Unit
2. Outdoor Units (Combination of Outdoor Units)
Diameter (mm) 6.4 9.5 12.7 15.9 19.0 22.0 28.6 34.9 41.3 54.1
Nominal Diameter (inch)
1
/4
3
/8
1
/2
5
/8
3
/4
7
/8 1 1/8 1 3/8 1 5/8 2 1/8
Note: 1.0MPaG = 10.2kgf/cm2G
GB
8
Introduction
Components
Type Appearance Model name Capacity code/
Cooling Capacity Heating Capacity
HP (kW) (kW)
MM-U056 2 5.6 6.4 MM-U080 3 8.0 9.6 MM-U112 4 11.2 12.8 MM-U140 5 14.0 15.8
MM-TU028 1 2.8 3.2 MM-TU042 1.5 4.2 4.8 MM-TU056 2 5.6 6.4
MM-SB028 1 2.8 3.2
MM-B056 2 5.6 6.4 MM-B080 3 8.0 9.6 MM-B112 4 11.2 12.8 MM-B140 5 14.0 15.8
MM-C/CR042 1.5 4.2 4.8 MM-C/CR056 2 5.6 6.4 MM-C/CR080 3 8.0 9.6 MM-C/CR112 4 11.2 12.8 MM-C/CR140 5 14.0 15.8
MM-K/KR042 1.5 4.2 4.8 MM-K/KR056 2 5.6 6.4 MM-K/KR080 3 8.0 9.6
MM-N028 1 2.8 3.2 MM-N042 1.5 4.2 4.8 MM-N056 2 5.6 6.4 MM-N080 3 8.0 9.6
MM-S/SR056 2 5.6 6.4 MM-S/SR080 3 8.0 9.6
4 Way Cassette Type ‘U’
2 Way Cassette Type ‘TU’
Built-In Slim Duct Type ‘SB’
Built-In Duct, Type ‘B’
Ceiling Type ‘C’
High Wall Type ‘K’
Carcase Type ‘N’
Low Wall Type ‘S’
3. Indoor Unit
GB
9
Installation
Contents
Outdoor Unit
Transportation of the Outdoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Installation of Outdoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Dimensional Drawings Outdoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . .12
Dimensional Drawings Two Units Connected . . . . . . . . . . . . . . . . . . . .13
Dimensional Drawings Three Units Connected . . . . . . . . . . . . . . . . . . .14
Dimensional Drawings Four Units Connected . . . . . . . . . . . . . . . . . . . .15
Dimensional Drawings Five Units Connected . . . . . . . . . . . . . . . . . . . .16
Multiple Installation on the Rooftop . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Piping
Free Branching System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Connecting Refrigerant Pipes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Permissible Length/Height Separation of Refrigerant Piping . . . . . . . .21
Selection of Refrigerant Piping and Charge Requirement . . . . . . . . . .22
Branch Headers/Branch Joints (Accessories) . . . . . . . . . . . . . . . . . . . . .24
Branch Header/T-shape Branch Joint . . . . . . . . . . . . . . . . . . . . . . . . . .25
Connecting the Branching Kit/Y-shape Branching Joint . . . . . . . . . . . .26
Heat Insulating the Branching Pipes/Branching Header . . . . . . . . . . .27
T-shape Branching Joint – to Connect Outdoor Units . . . . . . . . . . . . . .29
Installation of Gas/Liquid Branching Pipes . . . . . . . . . . . . . . . . . . . . . .30
Airtight Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Leak Position Check/Air Purge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Calculating the Additional Refrigerant Required . . . . . . . . . . . . . . . . .33
Additional Charge Amounts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Wiring
General/Wiring System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Connecting Power Source Cable/Control Cable . . . . . . . . . . . . . . . . . .36
Control Wiring Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
GB
10
Installation
Outdoor Unit
Transportation of the Outdoor Unit
Fork Lift
Front Access – insert the forks into the slots on the fixing legs.
Side Access – see diagram.
Fork lift
Fork lift/ Hand Truck
Transportation Slots
Protection
Fixing Leg
Protection
Rope
Crane
• Check the suitability of the lifting rope (see table).
• Secure lifting rope through transportation slot.
• Protect the unit where rope contact could scratch or deform it.
Model Weight MM-A0280HT 284.0kg MM-A0224HT 282.0kg MM-A0280HX 280.0kg MM-A0224HX 278.0kg MM-A0160HX 204.0kg
Front Access Side Access
GB
Installation
Installation of Outdoor Unit
1. Align the outdoor units at intervals of 20mm or more.
Fix the outdoor units with M12 anchor bolts. (4 positions per unit.)
Anchor bolt with 20mm length is suitable.
• Anchor bolt pitch is as shown in the following figure.
• However, the equivalent pipe length between the nearest outdoor unit and farthest outdoor unit of the refrigerating cycle system should not exceed 20m.
2. When routing the refrigerant piping through the base, the fixing height of the base (two-divided foundations) must be 500m or more.
3. Correct foundation mounts for supporting the Outdoor unit:
Note: The leading outdoor unit to be connected to the main refrigerant piping for the indoor
units must be an inverter unit.
Outdoor Unit
11
M12 anchor bolt, 4 positions per unit
20mm
700mm 310mm 700mm 310mm 700mm
755mm
500mm
20mm
20mm
15 x 20mm slot
Refrigerant Piping
GB
12
Dimensional Drawings
Outdoor Unit
Model Name: MM-A0280HT, MM-A0224HT, MM-A0280HX, MM-A0224HX, MM-A0160HX
Installation
Outdoor Unit
700
990
790
500
1700
1560
700 9088
130
145
140
170
125
64
20
65
35
60
115
173
610 100
700
750
100
630 80
755
80
245
190
755
235
Model
ØA ØB ØC
mm mm mm
MM-A0280HT, MM-A0280HX 28.6 12.7 9.52 MM-A0224HT, MM-A0224HX 22.2 12.7 9.52 MM-A0160HX 22.2 9.52 9.52
4-15 x 20 (Slot)
Fixing bolt pitch
Fixing bolt pitch
(including fixed leg)
Grounding part of bottom plate
Base
Fixing bolt pitch
Base
Fixing bolt pitch
Refrigerant pipe connecting port (Gas side) braze connection (ØA)
Refrigerant pipe connecting port (Liquid side) flare connection (ØB)
Balance pipe connecting port flare connection (ØC)
(Slot pitch)
2-60 x 150 Slot (for transport)
(knock out)
Refrigerant pipe connecting port (Liquid side)
Balance pipe connecting port
Refrigerant pipe connecting port (Gas side)
(knock out)
Details of piping
connections
Base bolt position
Note: All dimensions in (mm)
GB
13
Installation
Dimensional Drawings
Two Units Connected
Model Name: MM-A0384HT, MM-A0440HT, MM-A0504HT, MM-A0560HT
Outdoor Unit
2000
700
990 990
700
750
790
1700
1560
700
90
88
1 2
8-15 x 20 (Slot)
755 Fixing bolt pitch
Fixing bolt pitch
Fixing bolt pitch
(including fixed leg)
20
(Rear side)
300
10
500
(Front side)
20
2020
10
1550
No. Name
Outdoor Unit (Inverter type) Outdoor Unit (Fixed-speed type)
1
2
Note: All dimensions in (mm)
GB
14
Dimensional Drawings
Three Units Connected
Model Name: MM-A0608HT, MM-A0672HT, MM-A0728HT, MM-A0784HT, MM-A0840HT
Installation
Outdoor Unit
700
990 990 990
700 700
750
790
1700
1560
700
90
88
1
2
3
310
310
20
20
12-15 x 20 (Slot)
755 Fixing bolt pitch
(including fixed leg)
Fixing bolt pitch
Fixing bolt pitch
Fixing bolt pitch
(Rear side)
300
10
500
(Front side)
20
20
3030
10
1550
No. Name
Outdoor Unit (Inverter type) Outdoor Unit (Fixed-speed type 1) Outdoor Unit (Fixed-speed type 2)
1
2
3
Note: All dimensions in (mm)
GB
15
Dimensional Drawings
Four Units Connected
Model Name: MM-A0896HT, MM-A0952HT, MM-A1008HT, MM-A1064HT, MM-A1120HT
Installation
Outdoor Unit
20
20 20
16 - 15 x 20 (Slot)
755 Fixing bolt pitch
(including fixed leg)
(Rear side)
300
10
500
(Front side)
4020
1700
1560
700
90
88
700
990
700
990
700
990
700
750
790
1
2
3
4
990
310
310
310
20
20
20
4040
No. Name
Outdoor Unit (Inverter type) Outdoor Unit (Fixed-speed type 1) Outdoor Unit (Fixed-speed type 2) Outdoor Unit (Fixed-speed type 3)
1
2
3
4
Fixing bolt pitch
Fixing bolt pitch Fixing bolt pitch Fixing bolt pitch
1550
10
Note: All dimensions in (mm)
GB
16
Dimensional Drawings
Five Units Connected
Model Name: MM-A1176HT, MM-A1232HT, MM-A1288HT
Installation
Outdoor Unit
5030
1700
1560
700
90
88
700
990
700
990
700
990
700
1
2
3
4
990
700
700
790
5
990
310
310
310
310
20 20 20 20
20 - 15 x 20 (Slot)
755 Fixing bolt pitch
(including fixed leg)
Fixing bolt pitch Fixing bolt pitch Fixing bolt pitch Fixing bolt pitch Fixing bolt pitch
(Rear side)
300
10
500
(Front side)
10
1550
20 20 20 20
5050
No. Name
Outdoor Unit (Inverter type) Outdoor Unit (Fixed-speed type 1) Outdoor Unit (Fixed-speed type 2) Outdoor Unit (Fixed-speed type 3) Outdoor Unit (Fixed-speed type 4)
1
2
3
4
5
Note: All dimensions in (mm)
GB
17
Multiple Installation on the Rooftop
When the Outer Wall is Higher than the Outdoor Unit
If a hole can be made in the wall:
1. Set an aperture ratio so that suction air volume Vs from the hole becomes 1.5m/s or less.
2. Height of discharge duct: HD = H - h.
If a hole cannot be made:
1. Set a base with 500 to 1,000mm height.
2. Height of discharge duct: HD = H - h.
Installation
Outdoor Unit
300
600
20 20 20 2010
(Front side)
Discharge duct
1000
Hole in wall
Vs
HD
h
H
Discharge duct
Base
500 – 1000
Vs
HD
H
300600
20 20 20 2010
(Front side)
h
Note: All dimensions in (mm)
GB
18
Installation
Outdoor Unit
When the Outer Wall is Lower than the Outdoor Unit
1-line installation
2-parallel lines installation
3-parallel lines installation
*When refrigerant piping is routed from the front
of the unit, distance between Outdoor Unit and Connecting piping must be 500mm or more.
300
500
20 20 20 2010
(Front side)
600
*(1000)
300
300
20 20 20 20
800
10
(Front side)
600
*(1000)
300
500 600
20 20 20 2010
(Front side)
(Front side)
800
800
500
500
Connecting Piping
Piping
Note: All dimensions in (mm)
GB
19
Installation
Piping
Free Branching System
The following five branching systems are available to increase the flexibility of refrigerant piping design.
Outdoor units
Branching joint
Indoor units
Line branching system
Remote
controller
Outdoor units
Branching joint
Indoor units
Line branching system after header branching
Header branching system after header branching
Remote
controller
Outdoor units
Branching joint
Indoor units
Header branching system after line branching
Remote
controller
Outdoor units
Branching header
Branching header
Branching header
Indoor units
Header branching system
Remote controller
1
2
3
4
5
GB
20
Installation
Piping
Connecting Refrigerant Pipes
1. To access the refrigerant piping connections and electrical wiring terminals, remove the 7xM5 securing bolts in the front panel. To remove the panel, lift it up and away from its hanging tabs – See diagram.
2. The refrigerant pipes can be routed forwards, downwards or sideways.
3. If the pipes are routed forwards, make sure they exit through the Piping/Wiring Panel – (remove knock out section) and allow at least 500mm between the Outdoor Unit and the main pipe connecting it to the Indoor Unit. This is for servicing access. (Replacing the compressor, for example, requires a space of at least 500mm.)
4. If the pipes are routed downwards, remove the knockout section in the baseplate of the Outdoor Unit. This will enable access. They can then be connected to the left or right, or the rear side. (Leading pipe of the balancing should be within 4m.)
Notes:
1. When brazing, use nitrogen. This prevents internal oxidisation of the pipes.
2. Always use clean new pipe, and ensure it is not contaminated by water or dust.
3. Always use a double spanner on the flare nut – and tighten to the specified torque: (see table).
Connecting pipe Tightening Re-tightening
outer dia. (mm) torque (Nm) torque (Nm)
Ø6.4 11.8 (1.2kgf m) 13.7 (1.4kgf m)
Ø9.5 24.5 (2.5kgf m) 29.4 (3.0kgf m) Ø12.7 49.0 (5.0kgf m) 53.9 (5.5kgf m) Ø15.9 78.4 (8.0kgf m) 98.0 (10.0kgf m) Ø19.0 98.0 (10.0kgf m) 117.7 (12.0kgf m)
WARNING!
During installation – if the refrigerant gas leaks, ventilate the room. After installation – check for gas leakages.
If refrigerant gas comes into contact with fire – noxious gas may result!
Front panel
Piping/Wiring Panel
Within 4m
Pipes routed downwards
Pipes routed forward
500
Ta b
Valve at balance side (oil)
Valve at liquid side
Valve at gas side
Note: All dimensions in (mm)
GB
21
Installation
Piping
Permissible Length/Height Separation of Refrigerant Piping
La
LA LB
Lb Lc
L1
L2
L7
bc dea
ghi jf
L4
L5
L6
L3
Ld
(a)
(d)
(b) (c)
Fixed-speed Unit n
Valve for additional Units
Valve for additional Units
Note: In <Ex.2>, a large amount of refrigerant and oil may
return to the Inverter Unit. Therefore, set the T-shape joint so that oil does not enter directly.
Branching header
Branching piping
Connecting piping of Indoor Unit
Indoor Unit
Length corresponded to farthest piping L125m
Length corresponded to farthest piping after 1st branching L50m
Height difference between Indoor Units H230m
Indoor Unit
1st branching section
Main piping
Main connecting piping between Outdoor Units Length corresponded to farthest piping between Outdoor Units LO≤ 20m
Connecting piping of Outdoor Unit
Fixed­speed Unit 2
Fixed­speed
Unit 1
Inverter
Unit
Fixed-
speed
Unit 2
Fixed­speed Unit 1
Inverter
Unit
Fixed­speed Unit 2
Fixed­speed Unit 1
Inverter
Unit
Outdoor Unit
Height difference between Outdoor Units H34m
Height difference between Outdoor Units H150m
T-shape branching joint
Y-joint
System Restrictions Notes: Combination of Outdoor Units: Inverter Unit +
Fixed-speed Unit (0 to 4 units). Combination of Fixed-speed Units without Inverter Unit is not permissible. The Inverter Unit is the master Outdoor Unit and is directly connected to the indoor distribution pipe. Install the Outdoor Units in order of capacity. (Inverter UnitFixed-speed Unit 1> Fixed-speed Unit 2>Fixed-speed Unit n).
Max. No. of combined outdoor units 5 units Max. capacity of combined outdoor units 128.8kW/46HP Max. No. of connected indoor units 40 units Max. capacity of combined H2≤ 15 135% indoor units H2>15 105%
Allowable value Piping section
Total extension of pipe (Liquid pipe, real length) 250m
LA + LB + La + Lb + Lc + Ld + L1 + L2 + L3 + L4+
L5 + L6 + L7 + a + b + c + d + e + f + g + h + i + j
Farthest piping length L (*)
Real length 100m
LA + LB + Ld + L1 + L3 + L4 + L5 + L6 + j
Piping Equivalent length 125m length Equivalent length of farthest piping from 1st branching Li (*) 50m L3 + L4 + L5 + L6 + j
Equivalent length of farthest piping between outdoor units LO (*) 20m LA + LB + Ld, LA + Lb, LA + LB + Lc Max. equivalent length of outdoor unit connecting piping 10m Ld, La, Lb, Lc
Height between indoor
Upper outdoor unit 50m ——
Height
and outdoor units H1
Lower outdoor unit 30m ——
difference Height between indoor units H2 30m ——
Height between outdoor units H3 4m ——
*(d) is Outdoor Unit farthest from branching and (j) is Indoor Unit farthest from 1st branching.
<Ex. 1> <Ex. 2>
GB
22
Installation
Piping
Selection of Refrigerant Piping and Charge Requirement
3
1
1 1 1
22
4
5 5 5
4
4
4
4
5 5
5 5 5 5 5
2
6
6
6
Fixed­speed Unit n
Fixed­speed Unit 2
Fixed­speed Unit 1
Inverter
Unit
Branching piping
Header Branching Pipe
Outdoor Unit
Outdoor Unit connecting piping
Main connecting piping between Outdoor Units
Main piping
T-shape branching joint
Balance pipe
Y-shape branching joint
Indoor Unit connecting piping
1st branching section
Indoor Unit
Indoor Unit
Indoor Unit connecting pipe
kW HP Model name Gas side Liquid side
16.0 6 MM-A0160HX Ø22.2 Ø9.5
22.4 8 MM-A0224HT, MM-A0224HX Ø22.2 Ø12.7
28.0 10 MM-A0280HT, MM-A0280HX Ø28.6 Ø12.7
Total capacity code of all outdoor units Gas side Liquid side
Below 10 Ø22.2 Ø12.7 10 to Below 14 Ø28.6 Ø12.7 14 to Below 20 Ø34.9 Ø15.9 20 to Below 26 Ø41.3 Ø19.0 26 to Below 32 Ø41.3 Ø22.2
32 or more Ø54.1 Ø22.2
Total capacity code of indoor units
Gas side Liquid side
downstream (*1)
Below 4.0 Ø15.9 Ø9.5
4.0 to Below 6.4 Ø19.0 Ø9.5
6.4 to Below 13.2 Ø22.2 Ø12.7
13.2 to Below 19.2 Ø34.9 Ø15.9
19.2 to Below 25.2 Ø41.3 Ø19.0
25.2 to Below 31.2 Ø41.3 Ø19.0
31.2 or more Ø54.1 Ø22.2
Total capacity code of outdoor
Gas side Liquid side Balance pipe
units
Below 16 Ø28.6 Ø15.9 Ø9.5 16 to Below 20 Ø34.9 Ø15.9 Ø9.5 20 to Below 26 Ø41.3 Ø19.0 Ø9.5 26 to Below 32 Ø41.3 Ø22.2 Ø9.5
32 or more Ø54.1 Ø22.2 Ø9.5
Pipe Size of Outdoor Unit
Connecting Pipe Size Between Outdoor Units
Size of Main Pipe
Size Between Branching Sections
1
2
3
4
Note: All dimensions in (mm)
GB
23
Installation
Piping
Unit Gas side
(*4)
Liquid side
028 type to 056 type Ø12.7 Ø 6.4
080 type Ø15.9 Ø 9.5
112 type to 140 type Ø19.0 Ø 9.5
i.e. MM-SB028 = Gas Ø12.7, Liquid Ø6.4
Liquid pipe size Additional refrigerant amount for liquid pipe 1m (kg)
Ø6.4 0.030
Ø9.5 0.065 Ø12.7 0.115 Ø15.9 0.190 Ø19.0 0.290 Ø22.2 0.420
Piping of Indoor Unit
Additional Refrigerant Amount
(*1) Code is determined according to the capacity code of the Indoor Units connected. For
details, refer to the Introduction section in this manual.
(*2) If the total capacity code value of Indoor Units exceeds that of Outdoor Units, apply the
capacity code of Outdoor Units.
(*3) When using a branch header, Indoor Units with a maximum of 6.0 capacity code in total
can be connected to each branch.
(*4) If the length of the gas pipe exceeds 30m from the 1st branching to an Indoor Unit,
increase the Gas pipe section by 1 size, i.e. MM-U140 = Gas Ø22.2, Liquid Ø9.5.
5
6
7
Note: All dimensions in (mm)
Model name Usage Appearance
RBM-Y018 Indoor unit capacity code (*1): Total below 6.4 Y-shape RBM-Y037 Indoor unit capacity code (*1): Total 6.4 or more and below 13.2 (*2) branching joint RBM-Y071 Indoor unit capacity code (*1): Total 13.2 or more and below 25.2 (*2)
RBM-Y129 Indoor unit capacity code (*1): Total 25.2 or more (*2)
4-branching header (*3)
RBM-H4037 Indoor unit capacity code (*1): Total below 13.2
Max. 4
RBM-H4071 Indoor unit capacity code (*1): Total 13.2 or more and below 25.2
branches
8-branching header (*3) RBM-H8037 Indoor unit capacity code (*1): Total below 13.2
Max. 8
RBM-H8071 Indoor unit capacity code (*1): Total 13.2 or more and below 25.2
branches
1 set of 3 types of T-shape joint pipes as described below: The required quantity is arranged and they are combined at the site.
T-shape branching joint (For connection of RBM-T129 outdoor unit)
Connecting pipe Corresponding dia. (mm) Qty
Balancing pipe Ø9.52 1
Piping at liquid side Ø12.7 to Ø22.2 1
Piping at gas side Ø22.2 to Ø54.1 1
Branching joints/headers
GB
24
Installation
Piping
Branch Headers/Branch Joints (Accessories)
Note:
This additional connecting pipe is used if the gas pipe size is Ø41.3 or less. When brazing, the minimum insertion margin is 15mm.
Y-shape Branch Joint
Note: All dimensions in (mm)
[Gas side]
[Liquid side]
[Liquid side]
[Gas side]
Heat insulator
Heat insulator
RBM-Y018
RBM-Y037
Heat insulator
Heat insulator
Ø9.5
Ø9.5
Ø6.4
Ø6.4
Ø9.5
Ø19.0
Ø19.0
Ø28.6
571
Ø22.2
Ø22.2
Ø28.6
Ø9.5
Ø12.7
Ø15.9
Ø15.9
Ø12.7
Ø12.7
Ø12.7
Ø12.7
Ø9.5
Ø9.5
Ø9.5
Ø6.4
Ø6.4
420
Ø15.9
Ø19.0
Ø19.0
Ø15.9
Ø19.0
Ø9.5
Ø22.2
528
Ø15.9
Ø15.9
Ø12.7
Ø9.5
Ø22.2
Ø31.8
100
80
Ø12.7
Ø12.7
Ø12.7
44
Ø15.9
80
120
420
Heat insulator
Heat insulator
[Gas side]
[Gas side]
[Liquid side]
[Liquid side]
RBM-Y071
RBM-Y129
Ø12.7
Ø9.5
Ø6.4
85
Ø15.9
Ø19.0
518
Heat insulator
523
Ø19.0
Ø22.2 Ø22.2
Ø41.3
Ø41.3
Ø34.9
Ø34.9
Ø41.3
Ø22.2
Ø19.0
Ø15.9
Ø19.0
Ø19.0
Ø6.4
Ø9.5
Ø15.9
Ø15.9
Ø15.9
122.5
85
Ø12.7
Ø12.7
Ø12.7 Ø9.5
A
444
423
638
Ø54.1
(outer dia.)
Ø54.1
Ø54.1
Ø41.3
Ø54.1
212
Ø41.3
(outer dia.)
Ø19.0
Ø19.0
Ø22.2
237
Ø34.9
160
Ø41.3
Ø15.9
Ø15.9
Ø12.7
Ø12.7
Ø34.9
Ø22.2
Ø54.1
(outer dia.)
253.5
126160
Ø34.9
(outer dia.)
Ø41.3
Ø41.3
Ø19.0
194
Ø34.9
Ø22.2
GB
25
Installation
Piping
Branch Header
Note: Pipe dia. shown indicates dia. of pipe to be connected.
T-shape Branch Joint
Note: All dimensions in (mm)
RBM-H8037
[Gas side]
[Liquid side]
Heat insulator
RBM-H4037
[Gas side]
[Liquid side]
Heat insulator
Heat insulator
Heat insulator
515
Ø15.9
Ø12.7
Ø12.7
Ø15.9
Ø15.9
Ø19.0
Ø19.0
80 80 80
80 80 80
204
109
522
75
Ø19.0
Ø9.5
Ø6.4
Ø9.5
Ø9.5
Ø22.2
Ø28.6
Ø9.5
Ø9.5
Ø9.5
Ø6.4
80 80 80 80 80 80 80
80808080808080
75
109
204
842
795
Ø12.7
Ø12.7
Ø19.0
Ø19.0
Ø19.0 Ø2.22
Ø28.6
Ø15.9
Ø15.9
RBM-H4071
RBM-H8071
[Gas side]
[Gas side]
[Liquid side]
[Liquid side]
Heat insulator
Heat insulator
Heat insulator
Heat insulator
80 80 80
8080 80
209
109
449
522
Ø9.5
Ø9.5
Ø9.5
Ø6.4
Ø19.0
Ø19.0
Ø34.9
Ø41.3
Ø15.9
Ø15.9
Ø12.7
Ø12.7
75
Ø9.5
Ø9.5
Ø34.9
Ø9.5
Ø6.4 80 8080808080 80
80 80 80 80 80 80 80
75
209
109
842
769
Ø12.7
Ø12.7
Ø41.3
Ø15.9
Ø19.0
Ø19.0
Ø15.9
RBM-T129
[Gas side]
[Liquid side]
[Balance side]
Outside diameter
Outside diameter
2 pieces included
3 pieces included
3 pieces included
2 pieces included
Outside diameter
Ø54.1
Ø54.1
Ø54.1
Ø54.1
Ø22.2
Ø22.2
Ø22.2
Ø22.2
Ø9.52
Ø9.52
Ø9.52
Ø22.2
Ø19.0
Ø34.9
Ø34.9
Ø41.3
Ø28.6
Ø22.2
Ø12.7
Ø9.53
Ø15.9
Ø15.9
GB
26
Piping
Installation
Connecting the Branching Kit
Y-shape Branching Joint
Y-shape Branching Joint for gas and liquid distribution
When the selected pipe size differs from the size of the y-shape branching joint pipe, cut the centre of the connecting section with a pipe cutter, as shown below.
• Use the attached auxiliary pipe to adjust the pipe dia. of the Y-shape branching joint at gas or liquid side (RBM-Y071, RBM-Y129). Cut the branched pipe and auxiliary pipe to the specified size, and then braze.
Piping at site
Piping at site
To Outdoor Unit
Y-shape branching joint for gas side/liquid distribution
To other Branching Pipe or Indoor Unit
Inlet
Outlet (1)
Outlet (2)
Ø34.9
Ø41.3
Ø41.3
Ø34.9
Ø22.2
Ø19.0
Auxiliary pipe at gas side
Ø12.7
Ø15.9
Ø19.0
Ø34.9
Ø22.2
Y-shape Joint for gas and liquid distribution
• Install Y-shape branching joint so that it branches horizontally or vertically.
• Be sure to fit the insulation to the Y-shape branching joint supplied in the kit.
• Cutting position
Cut the pipe at the centre of each connecting section, and remove burr.
A
(Horizontal line)
(Horizontal line)
(A view)
(B view)
Within ± 30°
Within ± 30°
B
or
Cut at the centre
Note: All dimensions in (mm)
GB
27
Installation
Piping
Branching Header
When the selected pipe size prepared at site differs from the size of the branching header pipe, cut the centre of the connecting section with a pipe cutter as shown.
If the number of Indoor Units to be connected is less than the number of connections on the Branching Header, braze a pipe cap to the unused connectors.
Heat Insulating the Branching Pipes
Ensure the pipe insulation covers the piping up to the brazed accessory joints, as this will eliminate ingress of water – tape the pipe insulation to a thickness of 10mm or more, as shown.
RBM-Y129 (Gas side) (Prepared at site) RBM-Y071 (Gas side, Liquid side), RBM-Y129 (Liquid side)
Use insulator with a heat resistance of 120° C or over for gas pipes. To insulate the Branching Pipes, use a T-Shaped Joint cover with a thickness of 10mm or over – or a machined insulation portion, as shown.
• After the heat insulating, tape to seal.
Seal the joint with urethane foaming agent, etc.
Pipe heat insulator
Cut by approx. 60°
Cut by approx. 90°
Seal with vinyl tape
Heat insulating pipe for piping
Heat insulating pipe for piping
Bring them face to face
Pipe heat insulator prepared at site
Heat insulator (prepared at site), 10mm or over
150
Branching Pipe
Heat insulator included accessory
Pipe heat
insulator
prepared at site
Place them edge to edge
Place them edge to edge
Place them edge to edge
Taping (prepared at site)
Heat insulator (prepared at site)
Heat insulator (prepared at site)
Prepared at site
Prepared at site
Prepared at site
To Indoor Unit
Gas branching header
Liquid branching header
To Indoor Unit
Prepared at site
To Outdoor Unit
To Outdoor Unit
Liquid side
Gas side
Gas side
Liquid side
B
B
Pipe cap
Pipe cap
Inlet
Inlet
GB
28
Installation
Piping
• Install the branching header so that it branches horizontally. DO NOT install vertically.
• Be sure to insulate the branching header with the insulation provided.
• When routing the branching header at the liquid side from the opposite side, cut both ends and use a pipe cap (not supplied), as shown.
• Support of branching header
Set a hanging metal support (prepared at site) for the branching header, after fitting heat insulation.
• Cutting position
Cut the centre of each connecting section, and remove burr.
Use a mini-cutter to cut branching headers up to Ø22.2.
(Horizontal line)
(Horizontal line)
Gas side
Liquid side
(B view)
Gas side
(B view)
Liquid side
To B
B
Cut
A
Cut
C
Cut
To C
Pipe cap
Cut at the centre
Notes:
1. Make sure there’s a straight run of pipe at least 300mm long at the inlet side of Y-shaped Branching Joints and Branching Headers.
2. Install Y-shaped Branching Joint so they branch horizontally or vertically. In horizontal installations, set within ± 30°.
3. Install Branching Headers so they branch horizontally.
4. Do not use T-shaped Branching Joints for Branching Sections.
5. When using Y-Branches or Header Branches to prevent incorrect piping, attach a line number or name to each pipe.
Note: All dimensions in (mm)
GB
29
Installation
Piping
T-shape Branching Joint – to Connect Outdoor Units
Branching Pipes at Gas Side/Liquid Side
Pipe prepared at site
Pipe arranged at site
Pipe arranged at site
Connecting pipe at gas/liquid side
Connecting pipe at gas/liquid side
Branching Pipe at gas/liquid side
To other Branching Pipe or Outdoor Unit
To other Branching Pipe or Branching Section of main pipe
To Outdoor Unit
Connecting pipe at gas/liquid side
To Outdoor Unit
To other Branching Pipe or Outdoor Unit
To other Branching Pipe or Branching Section of main pipe
Cut the centre
• Use the included connecting pipes for
gas/liquid sides to match to the appropriate pipe size. (The diagram shows a connecting example.)
• Cutting position of connecting pipe
When the selected pipe size prepared at site differs from the size of the Branching Pipe, cut the centre of the connecting section with a pipe cutter.
GB
30
Installation
Piping
Installation of Gas/Liquid Branching Pipes
When combining two units, connect directly.
Balancing Branch Pipes (Oil)
Heat Insulation
Insulate liquid side, gas side and Balancing Pipes separately. Use insulator with a resistance of 120°C + for gas pipes. To insulate the Branching Pipes, use a T-Shaped Joint cover with a thickness of 10mm or over – or the machined one included. (Insulation for branching is not included.) To prevent condensation or dripping – seal the Branching Pipe securely, with no gaps.
Inverter
Outdoor Unit
Fixed-speed
Outdoor Unit
Inverter
Outdoor Unit
Fixed-speed
Outdoor Unit
INCORRECT
ROUTING
To Outdoor
Unit
Branching Pipe for Balancing Pipe (included)
Pipe prepared at site
Pipe prepared at site
Pipe prepared at site
To other Branching Pipe or Outdoor Unit
To other Branching Pipe or Outdoor Unit
Inverter
Outdoor Unit
Connect
Balancing
Pipe directly
Fixed-speed
Outdoor Unit
Seal with vinyl tape
Heat insulator
External dia. of Branching Pipe
Seal the joint with urethane foaming agent, etc.
Heat insulating pipe for piping
Heat insulating pipe for piping
Drill a hole with dia. larger than external dia. of heat insulating pipe for piping
Loading...
+ 346 hidden pages