Tjernlund MAC4E User Manual

MAC4E OPERATION
The MAC4E is used in conjunction with the UC1 Universal Control to interlock up to four additional 24 VAC, 115 VAC or millivolt (Dry Contact) controlled appliances. It activates the Venter through its connections to the UC1 and in turn relies on the UC1 Fan Prover safety circuit (P1 & P2) to allow its interlocked appliances to operate. Any pre/post-purge settings on the UC1 will be defaulted to the MAC4E. Two LEDs for each appli­ance interlock block are provided on the MAC4E. LEDs #1, 3, 5, 7 (AMBER) show an appliance call for heat. LEDs #2, 4, 6, 8 (BLUE) show that the burner is approved to fire after the Venter Fan Prover safety circuit (P1 & P2) through the UC1 is completed. The MAC4E also has an LED #9 (RED) which means power is supplied to the MAC4E through the UC1.
MILLIVOLT INSTALLATIONS
MAC4E MOUNTING
Do not mount the MAC4E junction box on a heat source that exceeds 104oF (40oC). Examples of improper mounting surfaces include vent pipe, top of appliance casing or any place where radiant or convective heat would cause the junction box temperature to exceed 104oF.
The MAC4E is intended for indoor installation only.
The MAC4E has a 2 foot whip that contains 1 ground, 2 power and 3 communication leads. Mount MAC4E adjacent to UC1 control.
Using the key hole slots on the back of the MAC4E junction box as a template, mark 4 holes on the mounting surface, drill pilot holes if neces­sary, and secure junction box using provided screws.
MAC4E SAFETY INTERLOCK TEST
PERFORM THE FOLLOWING INTERLOCK TEST AFTER CONNECTING MAC4E(S) TO UC1 AND INTERLOCKING ALL BURNERS
1. Confirm power is supplied to MAC4E control(s) from the UC1. MAC4E Power LED #9 (RED) should be on.
2. Initiate an appliance call for heat. MAC4E LED #1, 3, 5, or 7 (AMBER) should be on indicating an appliance call for heat.
3. If the UC1, P1 & P2 Prover safety circuit is closed, indicating an approved condition, the appliance interlock relay will close making terminal #3 closed to terminal #4. MAC4E LED #2, 4, 6, or 8 (BLUE) show that the burner is approved to fire. Fire all appliances to make sure each burner fires properly.
4. Remove power to the UC1 and any interlocked appliances. The Power LED (RED) on UC1 or any LED’s on UC1 or MAC4E should not be on. Test the safety circuit by removing either lead from Fan Prover switch connected to UC1 P1 and P2 Fan Prover safety circuit. Do not let the opened Lead touch a ground or damage may occur to the control when power is reestablished. Reestablish power to the UC1 and interlocked appliances and initiate a call for heat. After 60 seconds a Prover Start Up fault should arise with UC1 LED #4 (RED) flashing 3 times.
5. Remove appliance call for heat and power to the UC1 and any interlocked appliances. The Power LED (RED) on UC1 or any LED’s on UC1 or MAC4E should not be on. Reconnect Fan Prover switch lead removed in step 4.
6. Reestablish power to UC1 and interlocked appliances and initiate a call for heat from each appliance to confirm proper operation of UC1, MAC4E and appliances.
7. Perform Draft Adjustment and Combustion air safety check as outlined in Venter/Inducer installation manual.
IMPORTANT: DO NOT OPERATE AN APPLIANCE THAT OPERATES WITH THE PROVER SAFETY CIRCUIT DISCONNECTED!
RESETTING FAULT CODE CREATED BY STEP 4 OF SAFETY INTERLOCK TEST
IMPORTANT: Prior to accessing the fault code memory, note the settings of the UC1 dip switches so that they can be returned to their original
Pre / Post-Purge positions. When power is supplied to the UC1 use caution when moving dip switches.
The last fault code can be retrieved at any time by setting all dip switches 1-8 to the up, or “on” position. The last fault code, or lack there of, will be indicated by counting the number of times LED 4 flashes. By moving any of the dip switches back to their original position, the fault code will be cleared. NOTE: The UC1 board must have its 115 VAC power supply present when any of the (1-8) dip switches are moved back to their original position for the fault code to clear.
TJERNLUND PRODUCTS, INC.
1601 Ninth Street • White Bear Lake, MN 55110-6794 PHONE (800) 255-4208 • (651) 426-2993 • FAX (651) 426-9547 Visit our web site • www.tjernlund.com
Copyright © 2005, Tjernlund Products, Inc. All rights reserved. P/N 8504112
Multiple heaters firing at the same time will result in varying volumes of flue gas and varying vent system draft pressures. Make sure all heaters interlocked with the MAC4E operate within the normal draft range specified by the heater manufacturer. All heaters utilizing a fixed speed Venter/Inducer must be equipped with a draft hood, draft diverter, or barometric draft control. Tjernlund ABD-Series Balancing Baffles may be utilized for balancing draft on each heater.
MAC4E
BOARD
VERSION F
REV. B 08/05
C24VDRY3
AMBER
LED7
D115VD24VDRY4
K2
INTERLOCK
RELAY
K3
K1
DRY2
RELAY
BLUE
APPLIANCE 2
LED3
AMBER
LED4
B115V B24V
N
G
G
R
E
E
CONDUIT
24" FLEX
AI
E
T
K
C
W
H
B
L
post-purge settings + safety circuit connections are in the Universal Control.
This device must be connected to a Tjernlund Universal Control. All pre &
Remove power to Universal Control and all connected appliances when
installing or servicing the MAC4E. Failure to do so may result in personal
WARNING:
NOTE:
UNIVERSAL CONTROL
BLUE
LED2
PRE-PURGE SETTINGS
OPEN PROVER OPTION
POST-PURGE SETTINGS
VENTER / INDUCER
1 H.P. MAX @ 115 VAC
MOTOR
N
G
E
E
R
TJERNLUND
INC.
PRODUCTS,
MTR
W
MN
LH
TC
EK
IA
B
K2
APPROVED
50/60 Hz
115 VAC
SUPPLY
R
DO NOT SUPPLY VOLTAGE
TO "A" OR "B".
GREEN
RED
RED
CALL
JUMPER
INTERLOCK
XN
XL
NO
J1
J2
COM
K1
RELAY
DRY
115V
24V
LED5 LED3LED4
Y
R
P/N 1303963B
D
E
AMBER
P2
(9)
(3 - 8)
F
8967
GND
(1 - 2)
14532
CONP1
L
O
G
R
A
E
T
I
V
PROVER
LED1
Burner circuit is energized with contact closure from terminal 3 to terminal 4.
Safety circuit through Universal Control P1 & P2 Fan Prover is verified "Open" upon start up.
Appliance call for heat.
LED STATUS INDICATOR LIGHTS
LED #2 (Blue)
LED #1 (Amber)
AS APPLIANCE INTERLOCK VOLTAGE.
RED JUMPER POSITION MUST BE THE SAME
IMPORTANT:
LED
POWER
RED
24 OR 115 VAC
APPROVED CALL BACK TO HEATER
INTERCEPTED C ALL COMMON OR NEUTRAL
24 OR 115 VAC INTERCEPTED CALL FOR HEAT
5 VDC BOARD-GENERATED POWER
DO NOT SUPPLY POWER!
115 VAC
LEGEND:
TERMINAL 2:
TERMINAL 1:
TERMINAL 4:
LED6
USER-PROVIDED
CALL SWITCH
"DRY"
OR
COMMON /
LINE / HOT
NEUTRAL
INTER-
HEAT
CALL FOR
CEPTED
properly positioned.
selection jumper
Each appliance
Universal Control.
interlocked with the
to each A - B, 1 - 4
its red voltage
MAC4E must have
terminal strip are
Appliance interlocks
the same as on the
MAC4E
injury and/or equipment damage. LED #9 (RED) on the MAC4E should
APPLIANCE 1
INTERLOCK
MAC4E CONTROL
not be on if power has been removed.
RELAY
INTERLOCK
APPLIANCE 3
BLUE
LED5
AMBER
LED6
C115V
OPTIONAL DAISY CHAIN CONNECTIONS
INTERLOCK
RELAY
R
R
APPLIANCE 4
BLUE LED8
F
R
C2
CGND
Y
A
O
L
E
T
V
E
I
D
GREEN
VIOLET
F2 GNDNL
BLK
TO ADDITIONAL MAC4E
K4
POWER
LED9 - RED
DRY1
GRY
RED
BLUE
LED2
A115V A24V
L
N
AMBER
LED1
WHT
CONNECTIONS FROM MAC4E TO UC1 UNIVERSAL CONTROL
1. Connect Black from MAC4E whip to XL on UC1.
2. Connect White from MAC4E whip to XN on UC1.
3. Connect Green from MAC4E whip to ground screw in UC1.
4. Connect Gray from MAC4E whip to GND on UC1.
5. Connect Red from MAC4E whip to F on UC1.
6. Connect Violet from MAC4E whip to C on UC1.
DAISY CHAIN CONNECTIONS FOR MULTIPLE MAC4E’S CONNECTED TOGETHER
IMPORTANT: VENTING MULTIPLE HEATERS WITH A SINGLE FIXED SPEED VENTER /
INDUCER MAY REQUIRE TJERNLUND ABD-SERIES BALANCING BAFFLES. FOR INSTAL-
LATIONS REQUIRING MORE THAN ONE MAC4E INTERLOCK, WE RECOMMEND THAT
OUR TECH SERVICE DEPT. BE CONTACTED AT 1-800-255-4208.
1. Connect White from second MAC4E whip to N on MAC4E connected to UC1.
2. Connect Black from second MAC4E whip to L on MAC4E connected to UC1.
3. Connect Green from second MAC4E whip to ground screw in MAC4E connected to UC1.
4. Connect Red from second MAC4E whip to F2 on MAC4E connected to UC1.
5. Connect Gray from second MAC4E whip to GND on MAC4E connected to UC1.
6. Connect Violet from second MAC4E whip to C2 on MAC4E connected to UC1.
TO 2ND MAC4E WHIP
MAC4E WIRING CONNECTIONS WITH UC1 UNIVERSAL CONTROL
Remove power to UC1 and heating equipment when making connections from the MAC4E to the UC1 or installing, servicing or changing dip switch settings in the UC1.
Failure to do so may result in personal injury and/or equipment damage.
The Power LED (RED) on UC1 or any LED’s on UC1 or MAC4E should not be on.
See UC1 Universal Control wiring section of Venter or UC1 instructions for 24 VAC, 115 VAC or Millivolt (Dry Contact)
appliance interlock diagrams. The MAC4E and UC1 Universal Control appliance interlock steps and diagrams are identical.
IMPORTANT: Venter Fan Prover must be wired to P1 & P2 safety circuit in UC1. Do not
supply power to P1 & P2 or damage will result. The MAC4E contains four appliance
interlock blocks which are identical. Each appliance interlocked with the MAC4E and UC1 must have the Red voltage jumper on the proper 115V, 24V or DRY position based
on appliance interlock voltage.