Tjernlund MAC1E User Manual

MAC1E OPERATION
The MAC1E is used in conjunction with the UC1 Universal Control to interlock one additional 24 VAC, 115 VAC or millivolt (Dry Contact) con­trolled appliance. It activates the Venter through its connections to the UC1, and in turn relies on the UC1 Fan Prover safety circuit (P1 & P2) to allow its interlocked appliance to operate. Any pre/post-purge settings on the UC1 will be defaulted to the MAC1E. Two LEDs are provided on the MAC1E. LED #1 (Amber) shows an appliance call for heat. LED #2 (Green) shows that the burner is approved to fire after the Venter Fan Prover safety circuit through the UC1 is completed.
MILLIVOLT INSTALLATIONS
Each millivolt appliance interlocked with the MAC1E must have its own WHKE kit installed. The WHKE Gas Pressure Switch actuates the Venter through the A - B Dry contacts. The Linear Limit switch disables the heater in the event of a venting malfunction. IMPORTANT: Each millivolt appliance interlocked with the MAC1E must have its own Linear Limit spill switch.
MAC1E MOUNTING
Do not mount the MAC1E junction box on a heat source that exceeds 104oF (40oC). Examples of improper mounting surfaces include vent pipe, top of appliance casing or any place where radiant or convective heat would cause the junction box temperature to exceed 104oF.
The MAC1E is intended for indoor installation only.
The MAC1E has a 2 foot whip that contains 1 ground, 2 power and 3 communication leads. Mount MAC1E adjacent to UC1 control.
Using the key hole slots on the back of the MAC1E junction box as a template, mark 4 holes on the mounting surface, drill pilot holes if neces­sary, and secure junction box using provided screws.
MAC1E SAFETY INTERLOCK TEST
PERFORM THE FOLLOWING INTERLOCK TEST AFTER CONNECTING MAC1E TO UC1 AND INTERLOCKING ALL BURNERS
1. Confirm power is supplied to MAC1E control from the UC1.
2. Initiate an appliance call for heat. MAC1E LED #1 (AMBER) should be on indicating an appliance call for heat.
3. If the UC1, P1 & P2 Prover safety circuit is closed, indicating an approved condition, the appliance interlock relay will close making terminal #3 closed to terminal #4. MAC1E LED #2 (GREEN) shows that the burner is approved to fire. Fire all appliances to make sure each burner fires properly.
4. Remove power to the UC1 and any interlocked appliances. The Power LED #5 (RED) on UC1 or any LED’s on UC1 or MAC1E should not be on. Test the safety circuit by removing either lead from Fan Prover switch connected to UC1 P1 and P2 Fan Prover safety circuit. Do not let the opened LEAD touch a ground or damage may occur to the control when power is reestablished. Reestablish power to the UC1 and interlocked appliances and initiate a call for heat. After 60 seconds a Prover Start Up fault should arise with UC1 LED #4 flashing 3 times.
5. Remove appliance call for heat and power to the UC1 and any interlocked appliances. The Power LED #5 (RED) on UC1 or any LED’s on UC1 or MAC1E should not be on. Reconnect Fan Prover switch lead removed in step 4.
6. Reestablish power to UC1 and interlocked appliances and initiate a call for heat from each appliance to confirm proper operation of UC1, MAC1E and appliances.
7. Perform Draft Adjustment and Combustion air safety check as outlined in Venter/Inducer installation manual.
IMPORTANT: DO NOT OPERATE AN APPLIANCE THAT OPERATES WITH THE PROVER SAFETY CIRCUIT DISCONNECTED!
RESETTING FAULT CODE CREATED BY STEP 4 OF SAFETY INTERLOCK TEST
IMPORTANT: Prior to accessing the fault code memory, note the settings of the UC1 dip switches so that they can be returned to their original
Pre / Post-Purge positions. When power is supplied to the UC1 use caution when moving dip switches.
The last fault code can be retrieved at any time by setting all dip switches 1-8 to the up, or “on” position. The last fault code, or lack there of, will be indicated by counting the number of times LED 4 flashes. By moving any of the dip switches back to their original position, the fault code will be cleared. NOTE: The UC1 board must have its 115 VAC power supply present when any of the (1-8) dip switches are moved back to their original position for the fault code to clear.
NS WIT
TJERNLUND PRODUCTS, INC.
1601 Ninth Street • White Bear Lake, MN 55110-6794 PHONE (800) 255-4208 • (651) 426-2993 • FAX (651) 426-9547 Visit our web site • www.tjernlund.com
Copyright © 2004, Tjernlund Products, Inc. All rights reserved. P/N 8504110 REV A 1204
Multiple heaters firing at the same time will result in varying volumes of flue gas and varying vent system draft pressures. Make sure all heaters interlocked with the MAC1E operate within the normal draft range specified by the heater manufacturer. All heaters utilizing a fixed speed Venter/Inducer must be equipped with a draft hood, draft diverter, or barometric draft control. Tjernlund ABD-Series Balancing Baffles may be utilized for balancing draft on each heater.
MAC1E WIRING CONNECTIONS WITH UC1 UNIVERSAL CONTROL
Remove power to UC1 and heating equipment when making connections from the MAC1E to the UC1 or installing, servicing or changing dip switch settings in the UC1. Failure to do so may result in personal injury and/or equipment damage. LED #5 (RED) or any LED on the UC1 should not be on if 115 VAC supply power is removed from the control.
See UC1 Universal Control wiring section of Venter or UC1 instructions for 24 VAC, 115 VAC or Millivolt (Dry Contact) appliance inter­lock diagrams. The MAC1E and UC1 Universal Control appliance interlock steps and diagrams are identical.
MAC1E SAFETY INTER-
LOCK TEST
IMPORTANT:
RED JUMPER POSITION VOLTAGE MUST BE THE SAME AS APPLIANCE INTERLOCKED WITH UC1.
CALL
RELAY
INTERLOCK
PRODUCTS,
INC.
R
TJERNLUND
MTRMN
24 VAC
D/N 8056003
DO NOT SUPPLY POWER!
5 VDC BOARD-GENERATED POWE R
115V
J2
24V
DRY
LEGEND: 115 VAC
5
POST-PURGE SETTINGS
OPEN PROVER OPTION
(9)
(3 - 8)
9
786
FGND
ON
PRE-PURGE SETTINGS
(1 - 2)
24 3
1
CP1P2
J1
XL
XN
115 OR 24 VAC FROM CALL JUMPER OR USER-PROVIDED VOLTAGE FROM TERMINAL 3 TO 4 WITH CALL JUMPER REMOVED
K2
K1
JUMPER
NEUT.
INC.
PRODUCTS,
TJERNLUND
APPROVED
R
USER-PROVIDED
COM.
HOT
24 VAC
OR
CALL SWITCH
OR
LINE
115 VAC
"DRY"
XN
XL
K1
JUMPER
J2
J1
115V
DRY
CALL
24V
FGNDC
RED JUMPER POSITION VOLTAGE MUST BE THE SAME AS APPLIANCE INTERLOCKED WITH MAC1E.
DO NOT SUPPLY VOLTAGE
TO "A" OR "B".
IMPORTANT:
W H
I T
E
A
E
E D
R
Y
T
G R
O L
I
V
MAC1E CONTROL UNIVERSAL CONTROL
E
A C K
I
T
WHB
L
INTERLOCK
RELAY
A
K
C
B L
APPLIANCE CALL
APPLIANCE "GO"
PROVER
V
I
E
O L
A Y
R
G
D
E
R
T
CONDUIT
24" FLEX
N
E E
R
G
R
N
E
E
G
GREEN
AMBER
LED1LE D2 LED1LED5 LED4 LED2LED3
RED
RED
GREEN
GREEN
AMBER
Connect Black from MAC1E whip to XL on UC1. Connect White from MAC1E whip to XN on UC1. Connect Violet from MAC1E whip to C on UC1 Connect Gray from MAC1E whip to GND on UC1. Connect Red from MAC1E whip to F on UC1. Connect Green from MAC1E whip to ground in UC1.
IMPORTANT: Venter Fan Prover must be wired to P1 and P2 safety circuit in UC1.
RED appliance interlock voltage jumper in MAC1E and UC1 must be positioned based on the control voltage of the appliance interlocked with each control.