TJERNLUND IN-LINE DRAFT INDUCER REFERENCE GUIDE 8500590 REV. B 0403, DJ-3, D-3, I, IL Reference Manual

...
Improve Heating Efficiency
In-Line Draft Inducers assure positive draft when restricted boilers and furnaces, poor chimneys or negative pressures in build­ings prevent proper exhaust of combus­tion gases. The Venturi action starts air moving up the stack instantly and keeps it moving smoothly. In-Line inducers are built for long-lasting, trouble-free service and available in sizes and capacities to meet virtually all heating system require­ments. The Vari-Draft control permits adjustment to individual job require­ments. Vents/Chimneys utilizing In-Line Draft Inducers must be vertically terminat­ed above the roof line.
www.tjernlund.com •
800.255.4208
Residential Commercial Industrial
Reference Guide
by
Tjernlund
In-Line
Draft
Inducers
Use On Vertically Terminated Vent Systems Only
Typical Applications:
• Boilers/Furnaces
• Water Heaters
• Modular Boiler Systems
• Multiple Appliances
• Bakery Ovens
• Factory Processes
Solves Venting Problems:
Undersized Chimneys
Negative Pressures
Long Horizontal Vent Connectors
Down Drafts
Cold Equipment Starts
Restrictive Heat Exchangers/Combustion
Chambers
Everything Needed to Conform
Easy Installation
www.tjernlund.com
800.255.4208
A Size For Every Application
Models
DJ-3, D-3
Models I, IL, XL
Model
HD
1. Cut Slot in Pipe
2. Insert Inducer
3. Install Bands*
Select a position between draft hood, diverter or barometric damper and chimney, locating the Inducer as close to the chimney as possible. Inducer should be mounted 2-3 pipe diameters away from a directional change, i.e. elbows and tees, so turbulence is not created.
Mount the Draft Inducer on vertical, horizontal or inclined vent pipe. If used on a horizontal vent pipe, mount Inducer on bottom of pipe, not on top, to avoid creating a heat trap in the Inducer.
The motor shaft must be level and horizontal to avoid excessive wear on bearing.
Three Basic Steps...
Typical In-Line Inducer and safety interlock using UC1 Control and PS1505 Fan Prover
Tjernlund offers six In-Line Draft Inducers to fit vent pipe sizes from 3" to 24".
UC1 Control
PS1505 Fan Prover
* Models DJ-3 & D-3 fasten with screws.
If change in vent pipe size is required, use a tapered increaser or reducer.
In-Line Inducers should be installed on a section of single wall vent pipe in order to assure proper performance.
Do not use In-Line Draft Inducers on condensing heating equipment.
We recommend the use of a carbon monoxide detector in all mechanical rooms.
Fan Prover Safety Interlock
Model PS1505
To satisfy national mechanical codes for oil and gas installations, Draft Inducers must be properly interlocked with burner circuits. The PS1505 Fan Proving Switch monitors pressure within the Inducer housing to verify Inducer operation. Used in conjunction with the UC1 Universal Control, it assures compliance with codes and simplifies electrical interlock with all 24 /115 VAC burner circuits. The PS1505 is not compatible with millivolt gas valves.
with National Mechanical Codes
Chimney
Quality engineered and manufactured to maintain a consistent draft on a wide range of oil and gas fired heating equipment. May be used with chimney vented or power vented heating equip­ment. For fan assisted gas, oil or solid fuel applications with vent diameters from 4"–10", choose the DC4 thru DC10.
For LP and natural gas appli­cations with vent diameters from 4"–10", choose the DC4G thru DC10G.
Used with any UC1 con­trolled Inducer to inter­lock additional 24/115 VAC heaters. Powered by and communicates with the UC1 through a factory wired whip. For one additional 24/115 VAC heater add the MAC1E. To interlock up to four more additional 24/115 VAC heaters, add the MAC4E. MAC4Es can be
daisy chained together for greater than 5 heaters.
Important:
Total combined BTU/hr. input of all heaters and total equivalent pipe lengths must be within Inducers capacity.
For use with UC1 Universal Control, MAC1E or MAC4E auxiliary controls. The WHKE gas pressure switch actuates the Inducer through the A - B dry contacts. The Linear Limit switch disables the heater in the event of a venting malfunction. Includes JA1 thermocouple junction adapter. To interlock millivolt water heater(s) only with a
UC1 controlled Inducer add a WHKE for each millivolt heater. To interlock a millivolt water heater and one 24/115 VAC furnace or boiler with a UC1 controlled Inducer, add a WHKE and a MAC1E.
Solid state control interlocks with virtually any burner control circuit. Features include: adjustable pre and post purge, LED status/diagnostic indicators, prover switch delay to avoid burner start up and wind induced short cycling. Interlocks with any 24/115 VAC burner control circuit and also includes dry contact actuation option. Selectable voltage eliminates false activation by burner control check circuits.
Universal Control
Model UC1
Millivolt Safety Interlock Kit
Model WHKE
Barometric Draft Controls
Models DC4, DC5, DC6, DC7, DC8, DC9, DC10
DC4G, DC6G, DC7G, DC8G, DC9G, DC10G
Multiple Appliance Controls
Models MAC1E, MAC4E
www.tjernlund.com
800.255.4208
For additional information request brochure #8500004
For additional information request brochure #8500490
Accessories
The UC1 is a standardized control for Tjernlund Inducers/Venters. It offers many installation, operational and safety benefits.
Model Dimensions
Model
DJ-3
D-3
I
IL
XL
HD
H
7 1/2 9 1/8
14 1/2
17 18 7/8 27 1/2
W
8 1/2
9 1/2 13 1/2 14 3/4 18 1/2 16 3/4
D
5 7/8
7
8 3/4
10
10 1/2
25
X
2 5/8 3 1/8
4 4 1/8 5 1/8
6
Unit
Dimensions (In.)
Slot
Y
7 5/8 8 5/8
12 3/4
15 16 3/4 24 1/2
Ship
Weight
8 Lbs 10 Lbs 31 Lbs 34 Lbs 53 Lbs
176 Lbs
“H” — Overall Height “D” — Overall Depth “W”— Overall Width “X” — Pipe Slot Width “Y” — Pipe Slot Height
TJERNLUND PRODUCTS, INC.
1601 Ninth Street White Bear Lake, MN 55110-6794 Phone: 651.426.2993 800.255.4208 Fax: 651.426.9547 Visit our web site: www.tjernlund.com
Copyright © 2003 Tjernlund Products, Inc. P/N 8500590 Rev B 4/03
1. Inputs shown are believed to be maximum capacities for inducers when mounted on pipe sizes shown for ordinary jobs where a moderate amount of mechanical induced draft is required.
2. Consideration is given to typically higher static pressure requirements for larger installations, for the type of fuel burned and for the type of draft control installed.
3. Some ratings may only be valid for extremely short vent lengths due to excessive pressure loss; i.e. the Model IL gas firing with draft hood in 10" pipe at 2,080,000 BTU/hr.
4. Where pressure require­ments are unknown or believed to be unusually severe, ask for complete performance curves or consult factory.
5.
Draft Inducers should be installed in single wall vent pipe in order to assure proper performance.
Model Selection Table and Electrical Data
Model
DJ-3
D-3
I
IL
XL
HD
Pipe Size
In.
3 4 5 6 5 6 7 8 8
9 10 12
9 10 12 14 16 18 16 18 20 24 20 24
69,000 105,000 111,000 100,000 270,000 356,000 360,000 320,000 900,000
1,110,000 1,250,000 1,030,000 1,460,000 2,080,000 1,920,000 1,840,000
900,000 650,000
4,000,000 3,900,000 2,800,000 1,500,000 5,300,000 3,500,000
Gas Firing with Draft
Hood
270
0
F
Flue Gas
S.P. .034 .042 .043 .041 .063 .073 .075 .068 .125 .135 .140 .128 .145 .170 .160 .159 .120 .099 .250 .240 .195 .150 .290 .220
CFM
48 72 72
68 190 246 259 217 590 765 850 710
1010 1370 1325 1270
620 450
2760 2650 1935 1035 3690 2415
72,000 109,000 104,000
34,000 330,000 377,000 330,000 222,000
1,200,000 1,330,000 1,260,000
710,000
1,970,000 2,460,000 2,230,000 1,470,000
650,000 440,000
4,000,000 3,250,000 2,100,000 1,100,000 5,200,000 3,750,000
Gas Firing
with Barometric
Draft Control
390
0
F
Flue Gas
S.P. .047 .053 .052 .042 .085 .090 .085 .075 .143 .150 .145 .115 .175 .185 .182 .158 .113 .095 .260 .240 .175 .125 .270 .220
CFM
36 55 52
17 166 190 166 110 603 653 615 357 989
1240 1120
740 340 220
2010 1660 1079
527
2440 1660
58,000 92,000 74,000
25,000 295,000 300,000 230,000 123,000
1,100,000 1,100,000
840,000 400,000
1,700,000 1,900,000 1,500,000
825,000 350,000 200,000
3,300,000 2,100,000 1,200,000
503,000
3,600,000 2,900,000
Oil Firing
with Barometric
Draft Control
530
0
F
Flue Gas
S.P. .048 .057 .052 .035 .092 .093 .080 .065 .147 .148 .136 .100 .180 .180 .170 .135 .095 .075 .230 .190 .150 .110 .240 .218
CFM
33 48 39
13 163 169 118
65 566 566 440 211 900
1010
789 453 184 106
1763 1103
626 266
1870 1550
Therm
Volts HZ RPM Watts Amps Prot.
115 60 1550 35 .43 Imp.
Prot.
115 60 1550 74 .96 Yes
115 60 1725 1/4 HP 5.4 Yes
115 60 1725 1/4 HP 5.4 Yes 115 60 1725 1/3 HP 6.0 Yes
115 12.6 208 60 1725 1 HP 6.2 Yes 230 6.3
208 6.3 230 60 1725 2 HP 6.4 No 460 3.2
Heater
BTU
Input
Heater
BTU
Input
Heater
BTU
Input
Electrical Specifications
IMPORTANT: Vents/Chimneys utilizing In-Line Draft Inducers must be vertically terminated above the roof line. Do not use for side wall venting. Consult factory for proper side wall vent system options.
Tjernlund Products also offers:
Auto-Draft variable & fixed speed Inducers for roof top or side wall venting. Reduce vent diameters by up to 50% and overcome convolut­ed vent layouts. Fan speed is automatically regulated based on a user set manifold/vent pressure, resulting in perfect draft and true energy savings. Virtually unlimited capacities.
Combustion Air In-Forcers provide dedicated combustion air for safer, more efficient equipment operation. Eliminates burner control lockouts & oil odors associated with backdrafting. Ideal for "confined space" and electric to oil or gas conversions. Residential and commercial fixed & variable speed capacities up to 6000 CFM available.
Auto-Draft®Inducer
Combustion Air In-Forcer
Note: Tjernlund Products Inc. reserves the right to make changes to specifica­tions without notice.