TJERNLUND IN-LINE DRAFT INDUCER REFERENCE GUIDE 8500590 REV. B 0403, DJ-3, D-3, I, IL Reference Manual

...
Improve Heating Efficiency
In-Line Draft Inducers assure positive draft when restricted boilers and furnaces, poor chimneys or negative pressures in build­ings prevent proper exhaust of combus­tion gases. The Venturi action starts air moving up the stack instantly and keeps it moving smoothly. In-Line inducers are built for long-lasting, trouble-free service and available in sizes and capacities to meet virtually all heating system require­ments. The Vari-Draft control permits adjustment to individual job require­ments. Vents/Chimneys utilizing In-Line Draft Inducers must be vertically terminat­ed above the roof line.
www.tjernlund.com •
800.255.4208
Residential Commercial Industrial
Reference Guide
by
Tjernlund
In-Line
Draft
Inducers
Use On Vertically Terminated Vent Systems Only
Typical Applications:
• Boilers/Furnaces
• Water Heaters
• Modular Boiler Systems
• Multiple Appliances
• Bakery Ovens
• Factory Processes
Solves Venting Problems:
Undersized Chimneys
Negative Pressures
Long Horizontal Vent Connectors
Down Drafts
Cold Equipment Starts
Restrictive Heat Exchangers/Combustion
Chambers
Everything Needed to Conform
Easy Installation
www.tjernlund.com
800.255.4208
A Size For Every Application
Models
DJ-3, D-3
Models I, IL, XL
Model
HD
1. Cut Slot in Pipe
2. Insert Inducer
3. Install Bands*
Select a position between draft hood, diverter or barometric damper and chimney, locating the Inducer as close to the chimney as possible. Inducer should be mounted 2-3 pipe diameters away from a directional change, i.e. elbows and tees, so turbulence is not created.
Mount the Draft Inducer on vertical, horizontal or inclined vent pipe. If used on a horizontal vent pipe, mount Inducer on bottom of pipe, not on top, to avoid creating a heat trap in the Inducer.
The motor shaft must be level and horizontal to avoid excessive wear on bearing.
Three Basic Steps...
Typical In-Line Inducer and safety interlock using UC1 Control and PS1505 Fan Prover
Tjernlund offers six In-Line Draft Inducers to fit vent pipe sizes from 3" to 24".
UC1 Control
PS1505 Fan Prover
* Models DJ-3 & D-3 fasten with screws.
If change in vent pipe size is required, use a tapered increaser or reducer.
In-Line Inducers should be installed on a section of single wall vent pipe in order to assure proper performance.
Do not use In-Line Draft Inducers on condensing heating equipment.
We recommend the use of a carbon monoxide detector in all mechanical rooms.
Fan Prover Safety Interlock
Model PS1505
To satisfy national mechanical codes for oil and gas installations, Draft Inducers must be properly interlocked with burner circuits. The PS1505 Fan Proving Switch monitors pressure within the Inducer housing to verify Inducer operation. Used in conjunction with the UC1 Universal Control, it assures compliance with codes and simplifies electrical interlock with all 24 /115 VAC burner circuits. The PS1505 is not compatible with millivolt gas valves.
with National Mechanical Codes
Chimney