Service, Parts & Accessories. . . . . . . . . . . . back page
This THERMADOR® appliance is made by
BSH Home Appliances Corporation
1901 Main Street, Suite 600
Irvine, CA 92614
Questions?
1-800-735-4328
www.thermador.com
We look forward to hearing from you!
Safety
Important Safety Instructions
READ AND SAVE THESE INSTRUCTIONS
IMPORTANT: Save these Instructions for the local
electrical inspector’s use.
INSTALLER: Please leave these Instructions with this unit
for the owner. Show the owner the location of the circuit
breaker or fuse. Mark it for easy reference.
OWNER: Please retain these instructions for future
reference.
WARNING:
If the information in this manual is not followed exactly,
fire or shock may result causing property damage or
personal injury.
WARNING:
Do not repair or replace any part of the appliance unless
specifically recommended in the manuals. Improper
installation, service or maintenance can cause injury or
property damage. Refer to this manual for guidance. All
other servicing should be done by a qualified technician.
Electric Safety
WARNING:
WARNING:
Turn off power circuit at service panel and lock out panel
before wiring this appliance. Requirement: 120 VAC, 60
Hz 15 A. Allow the appliance to cool after the power has
been turned off before servicing the appliance.
WARNING:
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK,
OR INJURY TO PERSONS, OBSERVE THE
FOLLOWING:
•Use this unit only in the manner intended by the
manufacturer. If you have questions, contact the
manufacturer at the address or telephone number
listed on the back page.
•Before servicing or cleaning unit, switch power off at
service panel and lock the service disconnecting
means to prevent power from being switched on
accidentally. When the service disconnecting means
cannot be locked, securely fasten a prominent
warning device, such as a tag, to the service panel.
IMPROPER GROUNDING CAN RESULT IN
A RISK OF ELECTRIC SHOCK.
Consult a qualified electrician if the
grounding instructions are not completely
understood, or if doubt exists as to whether
the appliance is properly grounded. If the
power cord is too short, have a qualified
electrician install an outlet near the
appliance.
CORD.
DO NOT USE AN EXTENSION
WARNING:
Electrical Shock Hazard
•Do not remove ground prong.
•Do not use an adapter.
•Do not use an extension cord.
•Improper grounding can result in a risk
of electric shock.
•Failure to follow these instructions can
result in death, fire, or electrical shock.
English 1
Important Safety Instructions
READ AND SAVE THESE INSTRUCTIONS
Grounding Instructions:
This appliance must be grounded. In the event of an
electrical short circuit, grounding reduces the risk of electric
shock by providing an escape wire for the electric current.
Be sure your appliance is properly installed and grounded
by a qualified technician. Installation, electrical connections
and grounding must comply with all applicable codes.
If required by the National Electrical Code (or Canadian
Electrical Code), this appliance must be installed on a
separate branch circuit.
To reduce the risk of fire or electric shock, do not use this
appliance with any solid-state speed control devices.
Appliance Handling Safety
CAUTION:
Unit is heavy and requires at least two
people or proper equipment to move and
install.
Safety Codes and Standards
This appliance complies with one or more of the following
Standards:
•UL 858, The Standard for the Safety of Household
Electric Ranges
•UL 923, The Standard for the Safety of Microwave
Cooking Appliances
•UL 507, The Standard for the Safety of Electric Fans
•UL 1026, The Standard for the Safety of Electric
Household Cooking and Food Serving Appliances
•ANSI Z21.1, The American National Standard for
Household Cooking Gas Appliances
•CSA C22.2 No. 64, Household Cooking and LiquidHeating Appliances
•CSA C22.2 No. 113, Fans and Ventilators
•CSA C22.2 No. 61, Household Cooking Ranges
It is the responsibility of the owner and the installer to
determine if additional requirements and/or standards
apply to specific installations.
Ventilation Safety
Hidden surfaces may have sharp edges.
Use caution when handling the appliance.
Failure to do so may result in property
damage or personal injury.
Related Equipment Safety
Never modify or alter the construction of the appliance. For
example, do not remove panels, wire covers or brackets/
screws.
CAUTION:
For general ventilating use only. Do not use to exhaust
hazardous or explosive materials and vapors. To reduce
the risk of fire, use only metal ductwork.
When cutting or drilling into wall or ceiling, be careful not to
damage electrical wiring and other hidden utilities.
Use a quali¿ed and trained installer.
WARNING:
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK,
OR INJURY TO PERSONS, OBSERVE THE
FOLLOWING:
•Installation work and electrical wiring must be done
by qualified person(s) in accordance with all
applicable codes and standards, including fire-rated
construction.
•Sufficient air is needed for proper combustion and
exhausting of gases through the flue (chimney) of
fuel burning equipment to prevent back drafting.
Follow the heating equipment manufacturer's
guideline and safety standards such as those
published by the National Fire Protection
Association (NFPA), and the American Society for
Heating, Refrigeration and Air Conditioning
Engineers (ASHRAE), and the local code
authorities.
•Use only metal ductwork.
•Ducted fans must always be vented to the outdoors.
Do not vent exhaust air into spaces within walls,
ceilings, attics, crawl spaces or garages.
•When cutting or drilling into wall or ceiling, do not
damage electrical wiring and other hidden utilities.
English 2
Advance Planning
Before You Begin
CAUTION:
Parts Included
1 – 1000 CFM integral blower
(VCIBxxJP models only)
1 – Metal transition with backdraft
damper
2, 3, or 4 – Stainless steel baffle
filters (depending on model size)
2 – Filter spacers
2 or 3 – Grease trays (depending on
model size)
Before installing, turn power OFF at the service panel.
Lock service panel to prevent power from being turned
ON accidentally.
Tools and Parts Needed
Blower motor (VCINxxJP models only, see Table 5)
Ductwork as necessary (style varies, see Table 4)
Additional sheet metal screws (as necessary for
ductwork installation)
1” (25.4 mm) Strain relief
Aluminum tape (DO NOT use duct tape)
1/2” (13 mm) Conduit if required (follow local codes)
Framing material (as necessary for framework)
Circular saw or jigsaw
Tape measure
Phillips head screwdriver
Protective work gloves
1 – Liner (
4 – Side trims (VC
2 or 4 – Halogen lights (installed)
1 – Remote blower adaptor
1 – Fastener assortment
Use & Care Guide, Installation Manual, and Registration
Card
VCIBxxJP models only)
INxxJP models
only)
Available Accessories
LINER236 – 36” Custom Hood Liner (VCIN models
only)
LINER248 – 48” Custom Hood Liner (VCIN models
only)
LINER254 – 54” Custom Hood Liner (VCIN models
only)
VCI2REMKS – Remote Control
Remove all tape and packaging before using the
appliance. Please, recycle the packaging
material, as all THERMADOR® appliance
packaging material is recyclable. Never allow
children to play with packaging material.
English 3
General Information
This manual provides the proper installation instructions for two styles of THERMADOR PROFESSIONAL® custom insert
hoods:
VCINxxJP Overall Dimensions
VCINxxJP — 22” (559 mm) in depth and with widths of 33¾” (857 mm), 45¾” (1,162 mm) or 51¾” (1,315 mm). This
model series features brushed stainless-steel filters and halogen lights.
36” 48” 54”
5
"
/
1
8
(42mm)
5
"
4
/
16
(110 mm)
Top View
21¾”
(553 mm)
22”
(559 mm)
A
B
C
33¾”
(857 mm)
ǩ”
16
(410 mm)
Ǫ”
32
(822 mm)
45¾”
(1,162 mm)
22ǩ”
(562 mm)
40Ǫ”
(1,127 mm)
51¾”
(1,315 mm)
25ǩ”
(640 mm)
50Ǫ”
(1,280 mm)
13
12
/
16
(325 mm)
A
Rear View
C
B
”
11/16”
(17 mm)
Table 1: VCIN Custom Insert Overall Dimensions
English 4
VCIBxxJP Overall Dimensions
VCIBxxJP — 24” (610 mm) in depth and with widths of 41½” (1,054 mm), 52½” (1,334 mm) or 58½” (1,486 mm). This
model series features brushed stainless-steel filters, halogen lights, hood liner, and a 1000CFM integral blower.
36 po48 po54 po
5
"
/
1
8
(42mm)
5
4
/
16
(110 mm)
Top View
A
21¾”
"
(553 mm)
24¾”
B
(629 mm)
C
A
Rear View
C
B
40½”
(1,029 mm)
3
16
/
”
16
(411 mm)
32Ǫ”
(822 mm)
52½”
(1,334 mm)
3
22
/
”
16
(564 mm)
44Ǫ”
(1,127 mm)
58½”
(1,486 mm)
3
25
/
”
16
(640 mm)
50Ǫ”
(1,280 mm)
5
14
/
16
”
(363 mm)
Table 2: VCIB Custom Insert Overall Dimensions
English 5
Installation Preparation
The custom insert unit is designed for installation inside a
custom-built hood assembly. It is for ducting to the outside.
It cannot be used in conjunction with a recirculation unit.
Hood installation height above a cooktop, rangetop or
range can vary. To obtain the necessary installation height
above a cooktop, rangetop or range, consult the
appliance's installation manual.
30” – 40”
(762 – 1,016 mm)
to Countertop
Figure 1: Typical Hood Installation
NOTICE:
The hood could incur some damage from heat if a
THERMADOR PROFESSIONAL
rangetop is operated with multiple burners at high settings
under a hood that is installed at minimum clearances.
®
series range or
Hood Width
The hood width should be no less than the width of the
cooking surface. For proper performance, the housing must
cover the entire cooking surface.
Where space is not restricted, a wider hood can be used to
increase capture area.
Distance From Cooking Surface
The installation height ranges from a minimum height of 30”
(762 mm) to a maximum height of 40” (1,016 mm);
however, it is necessary to follow the cooking appliance
manufacturer’s installation instructions for proper hood
height.
Unit Weight
When calculating the load for the housing support system,
be sure to consider the weight of the ventilation unit.
ModelWeight
VCIN36JP
VCIN48JP
VCIN54JP
VCIB36JP
VCIB48JP
VCIB54JP
IMPORTANT:
The supplied weights address only the ventilation unit
and blower. Installer must account for weight of any
materials of construction when calculating the total dead
weight load of installation, including but not limited to:
wall, tile, mortar, plaster, brick, finishes, partitions, and
other similarly incorporated architectural and structural
items. It is the responsibility of the owner and the
installer to determine if additional requirements and/or
standards apply to specific installations.
60 lb (27.22 kg)
73 lb (33.11 kg)
82 lb (37.20 kg)
96 lb (43.54 kg)
111 lb (50.35 kg)
122 lb (55.34 kg)
Table 3: Unit Weight with Blowers
English 6
Ductwork Preparation
Ducting Recommendations
Proper performance is dependent upon proper ducting.
Local building codes may require the use of make-up air
systems when using ducted ventilation systems greater
than speci¿ed cubic feet per minute (CFM) of air
movement. The speci¿ed CFM varies from locale to locale.
It is the responsibility of the owner and the installer to
determine if additional requirements and/or standards
apply to specific installations.
DO NOT USE FLEXIBLE DUCT; it creates back pressure/
air turbulence and reduces performance. Always use metal
ductwork with a minimum diameter of 6” (150 mm).
Always install a metal vent cover where the ductwork exits
the house.
COLD WEATHER installations should have an additional
backdraft damper installed to minimize backward cold air
flow and a nonmetallic thermal break to minimize
conduction of outside temperatures as part of the ductwork.
The damper should be on the cold air side of the thermal
break. The break should be as close as possible to where
the ducting enters the heated portion of the house.
MAKE-UP AIR: Local building codes may require the use
of make-up air systems when using ducted ventilation
systems greater than specified CFM of air movement. The
specified CFM varies from locale to locale. It is the
responsibility of the owner and the installer to determine if
additional requirements and/or standards apply to specific
installations.
For safety reasons, ducting should vent directly outdoors
(not into an attic, underneath the house, into the garage or
into any enclosed space). The unit cannot be used in
conjunction with a recirculation unit.
If using a 10" (254 mm) duct, THERMADOR
not exceeding 150 ft (46 m) of duct.
Keep duct runs as short and straight as possible. Elbows
and transitions fittings reduce air flow efficiency. Back to
back elbows and “S” turns give very poor delivery and are
not recommended.
A short straight length of duct at the inlet of a remote
blower gives the best delivery.
Hoods are supplied with a 10" (254 mm) round transition. A
locally supplied transition is required for other sizes.
Transitions, elbows and wall or roof caps are all factors that
will add more static pressure, therefore increasing your
equivalent duct run. For example, assume you have 30 ft
(9.2 m) of straight 10" (254 mm) duct with two 90° elbows
and an outside wall cap. To calculate the equivalent
straight duct run pressure, you would add 12 ft (12.7 m) for
each elbow, and 5 ft (1.5 m) for the outside wall cap,
increasing your equivalent total run from 30 to 59 ft (9.1 to
17.9 m).
Use Table 4 on page 8 to compute permissible lengths for
duct runs to outdoors.
NOTE:
Do not exceed maximum permissible equivalent lengths.
®
recommends
English 7
EQUIVALENT DUCT LENGTHS FOR COMMONLY USED TRANSITIONS
Duct Piece
Smooth
Straight
3¼" x 10"
Straight
3¼" x 14"
Straight
90° Elbow
Round
45° Elbow
Round
3¼" x 10"
90° Elbow
Round
Size of Duct
Piece (in)
61.2
70.95
80.7
100.6
N/A1
N/A0.7
612
78
86
65
74
83
N/A5
Equivalent
Length (ft)
Duct Piece
3¼" x 10"
to Round
90° Elbow
3¼" x 10"
Center Reverse
Elbow Left
3¼" x 10"
Center Reverse
Elbow Right
3¼" x 10" Left
Reverse Elbow
3¼" x 10"
Right Reverse
Elbow
Round
Wall Cap
Round
Roof Cap
Size of Duct
Piece (in)
610
75
N/A15
N/A25
N/A15
N/A25
62
72
82
102
62
72
Equivalent
Length (ft)
3¼” x 10"
45° Elbow
Round
3¼" x 10"
Flat Elbow
Round to
3¼" x 10"
3¼" x 10"
to Round
Round to
3¼" x 10"
90° Elbow
N/A15
N/A20
61
71
65
73
610
78
82
2' Long
3¼" x 10"
Flex
3¼" x 10"
to Round
7" Inline
Backdraft
Damper
3¼" x 10"
Roof Jack
and Shutter
NOTE: These commonly used installation parts can be purchased
at a local hardware store. THERMADOR® does not manufacture all
these parts.
N/A20
101
7
N/A
Table 4: Duct Lengths
English 8
Assembly of the Transition
10” (254 mm)
Duct
1” (25.4 mm)
screw x2
10¼”
(260 mm)
13
12
”
/
16
(325 mm)
3
(84 mm)
5/
"
4
16
(502 mm)
5
”
/
16
11¼”
(286 mm)
17½” (445 mm)
Figure 2: Transition Dimensions
21¾”
(552 mm)
17½”
(444 mm)
Figure 3: Transition Cutout
Figure 4: Transition Centerline
1. A minimum height clearance of 10¼” (260 mm) is
needed above the hood for transition mounting.
2. Remove transition from inside of hood. Discard
brackets attaching transition to the inside of hood.
3. Align mounting holes at base of transition with the
mounting holes of the 1/2” (13 mm) flange located at
the top or rear of the hood.
4. Fasten transition to hood using two (2) 1” (25.4 mm)
sheet metal screws included with hood.
5. Seal connection between transition and hood with
aluminum tape. DO NOT use duct tape.
6. Remove tape holding damper closed.
English 9
Electrical Requirements
Choosing the Correct
The unit requires a 120V AC, 60Hz. 15A branch circuit.
The hood should only be connected to a grounded socket
that has been installed according to relevant regulations. If
possible, place the grounded socket directly behind the
chimney paneling. Attach the grounded socket as close to
the appliance as possible and in an accessible location.
•The grounded socket should be connected to its own
circuit.
•If the grounded socket is no longer accessible following
installation of the hood, make sure that an electrical
switch is permanently installed for turning off the
appliance.
When connected to a GFCI-protected supply,
THERMADOR PROFESSIONAL
suitable for use in damp locations that are protected from
outside weather conditions and not subject to saturation
with water and other liquids, but can be subject to
moderate degrees of moisture (such as an outdoor covered
patio or lanai area). Refer to local codes, NEC/CEC, and or
the Authority Having Jurisdiction (AHJ) for additional
information.
Check your local building codes for proper method of
installation. In the U.S., if there are no applicable local
codes, this unit should be installed in accordance with the
National Electric Code ANSI/NFPA No. 70, Current Issue.
In Canada, installation must be in accordance with the CAN
1- B149.1 and .2 - Installation Codes for Gas Burning
Appliances and/or local codes.
The appliance must be grounded. In the event of an
electrical short circuit, grounding reduces the risk of electric
shock by providing a wire that allows the electric current to
escape. This appliance has a cord with a ground wire and
grounded plug. The plug must be plugged into an outlet
that is properly installed and grounded.
®
custom insert hoods are
Blower
A variety of interior and exterior blower options (Remote,
Inline or Integral) are available for THERMADOR
PROFESSIONAL® custom insert series hoods. If the unit
you have selected does not have a blower included, one
must be purchased separately.
Use only THERMADOR
ventilation hoods. See Table 5: Blower & Circuit Breaker Ratings on page 11, for recommended blowers. Contact
Customer Service for additional options (see the back page
for contact information).
Blower selection will vary based on the volume of air that
needs to be moved and the length and location of the duct
run. For long duct runs with multiple turns and bends,
consider using a more powerful blower. For the most
efficient air-Àow exhaust, use a straight run or as few
elbows as possible (refer to “Ductwork Preparation” on page 7).
For indoor grill installations, THERMADOR recommends a
minimum of 36" (914 mm) clearance to the bottom of the
ventilation unit and Remote or Inline blowers only.
Integral Blowers
These blowers are integrated into the hood at the time of
installation (included with the VCIB model units).
Remote Blowers
Depending on preference and ducting situation, these
blowers can be mounted on the roof or exterior wall of the
home. An exterior installation may be more appealing to
reduce noise in the kitchen.
Inline Blowers
®
blowers with THERMADOR
WARNING:
The appliance must be grounded.
Electrical Data:
Data, including the model and serial number, is located on
the product data rating plate inside the appliance, visible
after removal of the filter frame (see Figure 40 on page 29).
English 10
To minimize noise in the kitchen, these blowers are
mounted along the duct line anywhere between the kitchen
and the exterior wall. If there is easy access to duct line (in
an attic, for example), this may be an appealing option.
Integral Blower models VTN630C and VTN1030C are
integrated into the hood at the time of installation (
models). For complete installation instructions see the
instructions supplied with the blower unit.
1. Remove junction box channel covering the wires (see Figure 5 on page 11).
2. Remove circular knockouts (Figure 5 on page 11).
3. Connect the blower’s Molex plug connector to the
connector present inside the hood, as shown in
Figure 7.
4. Install 1” (25.4 mm) conduit connector in junction box.
5. Run black, white, and green wires (#12 AWG) in 1”
(25.4 mm) conduit from the power supply to the
junction box.
6. Connect the power supply wires to the hood wires in
the following order: black to black, white to white, and
green wire to green ground screw on chassis. Use
spring type wire nuts supplied.
•Lost or missing wire nuts should only be replaced
with spring type wire nuts rated for a minimum of
two (2) #18 gauge wires and maximum of four (4)
#14 gauge wires, UL & CSA rated to 600V and
302°F (150°C.)
7. Close the junction box cover.
VCIN
From Control Panel
Figure 7: Wiring the Hood with an Integral Blower
English 12
Wiring the Hood with a
Remote Blower
5/
13
"
8
(346 mm)
1/
2
"
8
7/
1
"
8
(48 mm)
6
(165 mm)
7/
12
"
8
(327 mm)
(54 mm)
1/
"
2
(54 mm)
1/
2
"
8
Figure 8: VTR1330E Remote Blower
1/
12
"
8
(308 mm)
7/
dia. 9
(251 mm)
10"
(254 mm)
7/
19
(505 mm)
"
8
(527 mm)
"
8
20
3/
Custom insert models can be installed with remote blowers
(
VCIN models). For complete installation instructions see
the instructions supplied with the blower unit.
1. Remove junction box channel covering the wires (see Figure 5 on page 11).
2. Remove circular knockouts (Figure 5 on page 11).
3. Install 1” (25.4 mm) conduit connectors.
4. Run black, white, and green wires (#12 AWG) in 1”
(25.4 mm) conduit from the power supply to the
junction box.
5. Connect the power supply wires to the hood wires in
the following order: black to black, white to white, and
"
4
green wire to green ground screw on chassis. Use
spring type wire nuts supplied.
•Lost or missing wire nuts should only be replaced
with spring type wire nuts, rated for a minimum of
two (2) #18 gauge wires and maximum of four (4)
#14 gauge wires, UL & CSA rated to 600V and
302°F (150°C).
6. Connect the “pigtail” to the connector inside the
junction box.
7. Run five (5) #14 AWG wires in 1” (25.4 mm) conduit
from the remote blower to the second conduit
connector.
8. Connect the remote blower to the pigtail wires as per
Figure 9. Connect the remote blower green (ground)
wire to the ground screw in the junction box. Refer to
the blower installation instructions for further wiring
details.
9. Close the junction box cover.
Figure 9: Wiring the Hood with a Remote Blower
English 13
Wiring the Hood with an
Inline Blower
"
12
(305 mm)
7/
12
"
8
(327 mm)
7/
" (22 mm)
8
19
(486 mm)
(44 mm)
3/
"
8
14
(365 mm)
1/
8
3/
1
7/
ø9
8
(251 mm)
1/
12
(308 mm)
"
8
"
Figure 10: VTI1010D Inline Blower
"
Both VCIN and VCIB custom insert models can be
installed with inline blowers. For complete installation
instructions see the instructions supplied with the blower
unit.
1. Remove junction box channel covering the wires (see Figure 5 on page 11).
2. Remove circular knockouts (Figure 5 on page 11).
3. Install 1” (25.4 mm) conduit connectors.
4. Run black, white, and green wires (#12 AWG) in 1”
(25.4 mm) conduit from power supply to junction box.
5. Connect the power supply wires to the hood wires in
the following order: black to black, white to white, and
green wire to green ground screw on chassis. Use
spring type wire nuts supplied.
•Lost or missing wire nuts should only be replaced
"
4
6. Connect the “pigtail” to the connector inside the
7. Run five (5) wires (#14 AWG) in 1” (25.4 mm) conduit
8. Connect the inline blower to the pigtail wires as per
9. Close the junction box cover.
with spring type wire nuts, rated for a minimum of
two (2 #18 gauge wires and maximum of four (4)
#14 gauge wires, UL & CSA rated to 600V and
302°F (150°C).
junction box.
from the inline blower to the second conduit connector.
Figure 11. Connect the inline blower green (ground)
wire to the ground screw in the junction box.
English 14
Figure 11: Wiring the Hood with an Inline Blower
Remote Control Installation (optional)
NOTE: When using the Custom Insert with remote the unit
loses the “AUTO” function and the over-temperature heat
sensor described in the Use & Care Guide.
It is recommended that the Remote Control be wired to the
hood after the hood is installed.
1. Access wiring
a) Remove filters, spacers and grease trays.
b) Remove the junction box cover (refer to Figure 5
on page 11).
c) Remove three screws holding stainless steel panel
to canopy.
Remove 3x screws
2. Connecting the harness to the relay board
a) Insert remote harness end into the mounting hole,
as indicated in Figure 14, until it clicks.
Remote
Harness
Harness
Mounting
Hole
Figure 14: Remote Harness Mounting Hole
b) Run harness through core partition hole
(Figure 15).
Figure 12: Remove stainless steel panel
d) Remove core partition (Figure 13).
Figure 13: Remove core partition
Figure 15: Wire Routing through Partition
c) Unplug harness from the remote control to the
relay board (Figure 16).
English 15
d) Plug in harness included in the remote kit
(Figure 16).
Figure 16: Relay Board Hookup
e) Connect the extension harness to the connector
inside the junction box.
Figure 17: Pigtail Remote Connection
3. Prepare wall or similar surface for installation as shown below in Figure 18.
11¾”
1½”
(40 mm)
11
”
/
16
(17 mm)
(298 mm)
3
”
/
16
(5 mm)
11
/
16
(17 mm)
2¾”
(69 mm)
15
”
/
16
(23 mm)
3
”
/
8
(10 mm)
3
”
10
/
3
”
1
/
8
(35 mm)
8
(263 mm)
”
¼”
(6 mm)
1½”
(40 mm)
5
”
/
8
(17 mm)
9
”
/
3
”
1
/
8
16
(15 mm)
(35 mm)
English 16
Figure 18: Wall Cutout (view is shown facing wall)
4. Connect remote control to extension harness with the included 30 ft (914.4 cm) cable.
5. Insert remote control into cutout. Secure from behind with two (2) nuts onto the weld studs.
6. Reinstall hood components from Figure 12 and Figure 13.
Figure 19: Remote Install
English 17
Preparing VCINxxJP Housing Framework
The unit must be mounted to the surrounding housing. See “Installation Preparation” on page 6 for suggestions on
determining hood height.
When calculating the load for the housing support system, be sure to include the weight of the ventilation unit. See Table 3 on page 6 for unit weight by model.
Build housing in accordance with the dimensions noted in Figure 20 thru Figure 24.
ModelA
3
14
/
19
22
13
13
” (360 mm)
16
/
” (503 mm)
16
/
” (579 mm)
16
1
(47mm)
A
7/
"
8
23”
(584mm)
VCIN36JP
VCIN48JP
VCIN54JP
Back of Trim
Back of Hood
1/
"
1
8
(29mm)
3/
"
3
16
(81mm)
3/
"
2
8
(86mm)
7/
"
1
7/
"
8
7
(200mm)
10¼”
(260mm)
8
(48mm)
Diameter
clearance
holes for 1”
(25.4mm)
conduit to
junction box
Figure 20: Transition and Conduit Cutout Dimensions
English 18
Model
AB
VCIN36JP
VCIN48JP
VCIN54JP
15
32
/
”
16
(836 mm)
15
44
/
”
16
(1,141 mm)
15
50
/
”
16
(1,294 mm)
21¼”
(540 mm)
21¼”
(540 mm)
21¼”
(540 mm)
B
A
Figure 21: VCINCutout Dimensions
To be placed on 16”
(407 mm) stud centers
2⅛”
(54 mm)
1½” x 3½” x 12⅛”
(38 x 89 x 308 mm)
1½” x 3½” x 44½”
(38 x 89 x 1,130 mm)
Figure 22: VCIN Back Stud Dimensions
English 19
A
1½” x 3½” x 27
(38 x 89 x 707 mm)
Bǫ” (16 mm)
13
/
”
16
A
B
C
C
Figure 23: VCIN Stud Dimensions
1½” x 3½” x 23Ǫ”
(38 x 89 x 594 mm)
5/
26
16
(668 mm)
3”
(76 mm)
12¼”
(311 mm)
"
Figure 24: VCIN Side View
English 20
VCINxxJP Installation
Procedure
WARNING:
To avoid electrical shock hazard, before installing, switch
power off at the service panel and lock the panel to
prevent the power from being switched on accidentally.
CAUTION:
The hood weighs at least 60 lbs; therefore, it
requires at least two people to lift it safely.
Hidden surfaces may have sharp edges.
Use caution when handling the appliance.
Failure to do so may result in property
damage or personal injury.
5. Install hood trim
a) Hold trim flush to the bottom of the housing.
Secure the trim to the hood with eighteen (18) x ½”
(12.7 mm) screws, as indicated in Figure 25.
½” (12.7 mm)
x18
Figure 25: VCIN Trim Installation
1. Turn power OFF at the service panel. Lock service
panel to prevent power from being turned ON.
2. Prepare ductwork
a) Refer to “Ductwork Preparation” on page 7.
b) Install metal transition with backdraft damper so
that the flap opens up toward the ceiling. If
necessary, install thermal break and additional
backdraft damper (refer to “Assembly of the Transition” on page 9).
3. Build housing framework
a) Refer to “General Information” on page 4 for the
applicable model dimensions.
b) Refer to “Installation Preparation” on page 6 for
clearance specifications.
c) Build housing framework for applicable model
according to dimensions in “Preparing VCINxxJP
Housing Framework” beginning on page 18.
4. Install blower motor
a) Refer to “Choosing the Correct Blower” on
page 10.
b) Refer to “Blower Motor Installation” beginning on
page 11.
6. Install the unit
a) Install the custom insert inside the custom hood.
b) Secure to the rear of the housing framework using
six (6) x 2” (50.8 mm) mounting screws, as
indicated in Figure 26.
2” (50.8 mm)
X6 mounting
screws
Figure 26: VCIN Rear Screws
English 21
c) Secure to the sides of the housing framework using
six (6) x 2” (50.8 mm) mounting screws, 3 per side
as indicated in Figure 27.
2” (50.8 mm)
mounting screws
X3 per side
Figure 27: VCIN Side Screws
7. Connect to ductwork
8. Connect electric
a) Remove the junction box cover (see Figure 5 on
page 11).
b) Remove circular knock-out holes located on back
side of the insert (see Figure 5 on page 11).
c) Connect wiring for applicable blower motor (see
blower instructions beginning on page 11).
d) Ensure all controls are in the OFF position. Plug
electrical cord into grounded outlet.
9. Install hood filters, filter spacers, and grease trays
a) Refer to “Installing Grease Trays, Filter Spacers,
and Filters” on page 28.
10. Test the installation
a) Test the operation of the blower and the lights.
b) Be sure to check for backdraft. With the blower on
high, close the windows and doors to the area to
ensure that fan does not cause back drafting in any
outlet vent for another appliance.
English 22
Preparing VCIBxxJP Housing Framework
The unit must be mounted to the surrounding housing. See “Installation Preparation” on page 6 for suggestions for
determining hood height.
When calculating the load for the housing support system, be sure to include the weight of the ventilation unit. See Table 3 on page 6 for unit weight by model.
Build housing in accordance with the dimensions noted in Figure 28 thru Figure 32.
Model
VCIB36JP
VCIB48JP
VCIB54JP
Back of Hood
A
3
14
/
” (360 mm)
16
13
19
/
” (503 mm)
16
13
22
/
” (579 mm)
16
Back of Liner
(29mm)
3/
"
3
16
(81mm)
1/
"
1
8
23”
(584mm)
3/
"
3
16
(81mm)
A
7/
"
7
8
(200mm)
10¼”
(260mm)
3/
"
2
8
(86mm)
7/
1
8
"
(48mm)
Diameter
clearance
holes for 1”
(25.4mm)
conduit to
junction box
Figure 28: Transition and Conduit Cutout Dimensions
English 23
B
A
Model
VCIB36JP
VCIB48JP
VCIB54JP
To be placed on 16”
(407 mm) stud centers
AB
39¾” (1,010 mm)
51¾” (1,315 mm)
57¾” (1,467 mm)
23
Ǭ” (606 mm)
23Ǭ” (606 mm)
23Ǭ” (606 mm)
Figure 29: VCIB Cutout Dimensions
1½” x 3½” x 16⅛”
(38 x 89 x 410 mm)
1½” x 3½” x 44½”
(38 x 89 x 1,130 mm)
English 24
6⅛”
(165 mm)
Figure 30: VCIB Back Stud Dimensions
A
Bǫ” (16 mm)
1½” x 3½” x 2713/16”
(38 x 89 x 707 mm)
A
B
C
C
Figure 31: VCIB Stud Dimensions
1½” x 3½” x 23Ǫ”
(38 x 89 x 594 mm)
5/
26
"
16
(668mm)
3”
(76mm)
3/
"
16
8
(416mm)
Figure 32: VCIB Side View
English 25
VCIBxxJP Installation
Procedure
WARNING:
To avoid electrical shock hazard, before installing, switch
power off at the service panel and lock the panel to
prevent the power from being switched on accidentally.
CAUTION:
The hood weighs at least 60 lbs; therefore, it
requires at least two people to lift it safely.
Hidden surfaces may have sharp edges.
Use caution when handling the appliance.
Failure to do so may result in property
damage or personal injury.
5. Hood liner installation
a) Slide the liner onto the hood (Figure 34).
b) Hold liner flush to the bottom of the housing.
Secure the liner to the hood with eighteen (18) x ½”
(12.7 mm) screws, as indicated in Figure 35 and
Figure 36.
Figure 33: VCIB Liner
1. Turn power OFF at the service panel. Lock service
panel to prevent power from being turned ON.
2. Prepare ductwork
a) See “Ductwork Preparation” on page 7.
b) Install metal transition with backdraft damper so
that the flap opens up toward the ceiling. If
necessary, install thermal break and additional
backdraft damper (refer to “Assembly of the Transition” on page 9).
3. Build housing framework
a) Refer to “General Information” on page 4 for the
applicable model dimensions.
b) Refer to “Installation Preparation” on page 6 for
clearance specifications.
c) Build housing framework for applicable model
according to dimensions in “Preparing VCIBxxJP
Housing Framework” beginning on page 23.
4. Install blower motor
a) Refer to “Blower Motor Installation” beginning on
page 11.
Figure 34: VCIB Liner Installation
½" (12,7 mm)
x3 cada lado
English 26
Figure 35: VCIB Secure Liner Sides
½” (12.7 mm)
X6 each front
& back side
Figure 36: VCIB Secure Liner Front & Back
6. Install the Unit
a) Install the custom insert inside the custom hood.
b) Secure to the rear of the frame using six (6) 2”
(50.8 mm) mounting screws provided (Figure 37).
2” (50.8 mm)
X6 mounting
screws
7. Connect to Ductwork
8. Connect Electric
a) Remove the junction box cover (see Figure 5 on
page 11).
b) Remove circular knock-out holes located on back
side of the insert (see Figure 5 on page 11).
c) Connect wiring for blower motor (see blower
instructions beginning on page 11).
d) Ensure all controls are in the OFF position. Plug
electrical cord into grounded outlet.
9. Install Hood Filters and Grease Trays
a) Refer to “Installing Grease Trays, Filter Spacers,
and Filters” on page 28.
10. Test the installation.
a) Test the operation of the blower and the lights.
b) Be sure to check for backdraft. With the blower on
high, close the windows and doors to the area to
ensure that fan does not cause back drafting in any
outlet vent for another appliance.
Figure 37: VCIB Rear Screws
c) Secure to the sides of the frame using six (6) 2”
(50.8 mm) mounting screws provided (Figure 38).
2” (50.8 mm)
mounting screws
X3 per side
Figure 38: VCIB Side Screws
English 27
Loading...
+ 67 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.