Thermador MEMCW301ES01, ME302ES01 Installation Guide

INSTALLATION MANUAL
Built-in Ovens
Use and Care Manual 3
Manual de uso y cuidado 16 Guide d'utilisation et d'entretien 29
Models: M271
M301 ME271
ME301 ME272
ME302 MED272
MED302 MEW301
MEM271 MEM301
MEMC301 MEMW271
MEMW301 MEMCW301
PO301 POD301
PO302 POD302
PODC302 POM301
POMW301
This Thermador Appliance is made by
BSH Home Appliances Corporation
5551 McFadden Ave.
Huntington Beach,CA 92649
Questions?
1-800-735-4328
www.thermador.com
We look forward to hearing from you!
Safety
Important Safety Instructions
READ AND SAVE THESE INSTRUCTIONS
Appliance Handling Safety
Safety Codes and Standards
WARNING: If the information in this manual is not followed exactly, fire or shock may result causing property damage or personal injury.
WARNING: Do not repair or replace any part of the appliance unless specifically recommended in the manuals. Improper installation, service or maintenance can cause injury or property damage. Refer to this manual for guidance. All other ser- vicing should be done by a qualified technician.
Do not lift appliance by door handle. Remove the door for easier handling and in- stallation. See instructions in Use and Care Manual.
Unit is heavy and requires at least two people or proper equipment to move. Hidden surfaces may have sharp edges. Use caution when reaching behind or un-
der appliance.
This appliance complies with one or more of the following Standards:
UL 858, The Standard for the Safety of Household Electric Ranges UL 923, The Standard for the Safety of Microwave Cooking Appliances UL 507, The Standard for the Safety of Electric Fans
ANSI Z21.1, The American National Standard for Household Cooking Gas Ap- pliances
CAN/CSA-C22.2 No. 113-M1984 Fans and Ventilators CAN/CSA-C22.2 No. 61-M89 Household Cooking Ranges
It is the responsibility of the owner and the installer to determine if additional re- quirements and/or standards apply to specific installations.
Electric Safety
Before you plug in an electrical cord, be sure all controls are in the OFF position. If required by the National Electrical Code (or Canadian Electrical Code), this ap-
pliance must be installed on a separate branch circuit. Installer- show the owner the location of the circuit breaker or fuse. Mark it for easy
reference. Important - Save these instructions for the local electrical inspector's use.
Before installing, turn power OFF at the service panel. Lock service panel to pre- vent power from being turned ON accidentally.
Refer to data plate for more information. See "Product Data Plate" under "Service" for data plate location.
Be sure your appliance is properly installed and grounded by a qualified technician. Installation, electrical connections and grounding must comply with all applicable
codes.
,_ Important Safety Instructions
READ AND SAVE THESE INSTRUCTIONS
Related Equipment Safety
Remove all tape and packaging before using the appliance. Destroy the packaging after unpacking the appliance. Never allow children to play with packaging materi-
al. Never modify or alter the construction of the appliance. For example, do not re-
move leveling legs, panels, wire covers or anti-tip brackets/screws.
Transport
To avoid damage to the oven vent, use the transport method shown in the picture below.
Installation
Before you Begin
Tools and Parts Needed
Parts Included
27" Appliances
General Information
Power Requirements
Dimensions for 27" Wall-Mounted Units
263/4"
2413/16" (718mm)
(630mm)
291/16"
(738mm)
27"
(686mm)
L.
237/8" (606mm)
22" (559mm)
Phillips head screwdriver Measuring tape Drill with bit (1/8")
Phillips head screws (6)
The outlet must be properly grounded in accordance with all applicable codes.
251/2"
m)
24"
(610mm)
min. 43/4"(121mm)
max. 313/8"
Single Oven 27"
It is good practice, when oven is in-
stalled at the end of a cabinet run, ad- jacent to a perpendicular wall or cabinet door, to allow at least 1/4"
space between the side of the oven and the wall/door.
For oven support, install 2x4's extend-
ing front to back flush with the bottom and the side of the opening. The sup-
porting base must be well secured to the floor/cabinet and level.
Note: The conduit box must be in-
stalled either above or below the unit. If the conduit box is installed below the
unit, a 2" diameter hole or space is re- quired between the back wall and the
right rear of the 2x4 supports. The cabinet base must be flat and
capable of supporting a weight of at
least 210 Ibs (95 kg).
513/4"
(1314mm)
263/4"
(680mm)
2413/16"
(630mm)
493/4"
(1264mm)
237/8" (606mm)
511/8"
(
r
93/4"
(248mm)
Double Oven 27"
It is good practice, when oven is in- stalled at the end of a cabinet run, ad-
jacent to a perpendicular wall or
cabinet door, to allow at least 1/4" space between the side of the oven
and the wall/door. For oven support, install 2x4's extend-
ing front to back flush with the bottom and the side of the opening. The sup- porting base must be well secured to
the floor/cabinet and level. Note: The conduit box must be located
above the unit to facilitate connecting and servicing.
The cabinet base must be flat and capable of supporting a weight of at
least 355 Ibs (161 kg).
50"
1270mm)
22" (559mm)
263/4"
_-_ (680mm) 2413116"
/"_ (630mm)
483/8"
(1229mm)
24"
(610mm)_
491/2"
(1257mm)
191/2"
(500mm)
25i/2"
Combo Oven with Microwave 27"
It is good practice, when oven is in-
stalled at the end of a cabinet run, ad-
jacent to a perpendicular wall or
cabinet door, to allow at least 1/4" space between the side of the oven
and the wall/door. For oven support, install 2x4's extend-
ing front to back flush with the bottom and the side of the opening. The sup- porting base must be well secured to
the floor/cabinet and level. Note: The conduit box must be located
above the unit to facilitate connecting and servicing.
The cabinet base must be flat and capable of supporting a weight of at
least 330 Ibs (150 kg).
237/8" (606mm)
22" (559mm)
613/8"
(1559mm
2413/16"
(630mm)
595/8"
(1514mm)
24"
603/4"
(1543mm)
93/4"
(248mm)
251/2"
Combo Oven with Microwave and Warming Drawer 27"
It is good practice, when oven is in- stalled at the end of a cabinet run, ad-
jacent to a perpendicular wall or
cabinet door, to allow at least 1/4" space between the side of the oven
and the wall/door. For oven support, install 2x4's extend-
ing front to back flush with the bottom and the side of the opening. The sup- porting base must be well secured to
the floor/cabinet and level. Note: The conduit box must be located
above the unit to facilitate connecting and servicing.
The cabinet base must be flat and capable of supporting a weight of at least 370 Ibs (168 kg).
j_ 237/8"(606mm)
(559mm)
27"Under-the-counterunits
263/4"
T_
291/16"
(738mm)
22" (559mm)
281/4"
(718mm)
2413/16"
(686mm)
237/8" (606mm)
24"
(610mm)
251/2"
27"
11
(102mm)
161/2"
(419mm)
36"
(915mm)
A single oven installed under the counter allows for the installationof
most Thermador Gas or Electric non-Cook'n'Vent® Model Cook-
tops. Downdraft units cannot be in- stalled in this configuration;
Thermador overhead ventilation is recommended.
Some TMH cooktops require addi- tional clearances to combustible
walls. A Thermador cooktop should be in-
stalled on the same center line as the under-the-counter single oven.
Follow the installation instructions provided with cooktop for installa-
tion of cooktops. 3 3/4" (95 mm) minimum is required from the top of the countertop to the top of the cut- out opening for under-counter in- stallation with Thermador cooktops. If the type of cabinet or countertop thickness does not provide for this minimum space, the cabinet base may have to be lowered, into the toe space, to provide the necessary space above the oven. However, a
4" minimum distance between the floor and the oven bottom must re- main.
30" Appliances
Dimensions for 30" Wall-Mounted Units
291/16"
(738mm)
237/8"(606mm)
_,_22" (559mm)
27"
(686mm)
24"
(610mm)
281/2"
Single Oven 30"
It is good practice, when oven is in-
stalled at the end of a cabinet run, ad- jacent to a perpendicular wall or cabinet door, to allow at least 1/4"
space between the side of the oven and the wall/door.
For oven support, install 2x4's extend-
ing front to back flush with the bottom and the side of the opening. The sup-
porting base must be well secured to the floor/cabinet and level.
Note: The conduit box must be in-
stalled either above or below the unit. If the conduit box is installed below the
unit, a 2" diameter hole or space is re- quired between the back wall and the
right rear of the 2x4 supports. The cabinet base must be flat and
capable of supporting aweight of at
least 190 Ibs (86 kg).
513/4"
(1314mm)
293/4"
(755mm)
2713/16"
(706mm)
493/4"
(1264mm)
237/8"(606mm)
24"
(610mm)_
511/8"
(
93/4"
(248mm)
r-_ (724mm_)
F
281/2"
Double Oven 30"
It is good practice, when oven is in- stalled at the end of a cabinet run, ad-
jacent to a perpendicular wall or
cabinet door, to allow at least 1/4" space between the side of the oven
and the wall/door. For oven support, install 2x4's extend-
ing front to back flush with the bottom and the side of the opening. The sup- porting base must be well secured to
the floor/cabinet and level. Note: The conduit box must be located
above the unit to facilitate connecting and servicing.
The cabinet base must be flat and capable of supporting aweight of at
least 330 Ibs (150 kg).
50"
(1270mm)
22" (559mm)
293/4"
_ (755mm)
2713/16"
(706ram)
(1229mm)
483/8"
491/2"
(
p
191/2"
(500mm)
281/2"
Combo Oven with Microwave 30"
It is good practice, when oven is in- stalled at the end of a cabinet run, ad-
jacent to a perpendicular wall or
cabinet door, to allow at least 1/4" space between the side of the oven
and the wall/door. For oven support, install 2x4's extend-
ing front to back flush with the bottom and the side of the opening. The sup- porting base must be well secured to
the floor/cabinet and level. Note: The conduit box must be located
above the unit to facilitate connecting and servicing.
The cabinet base must be flat and capable of supporting aweight of at
least 290 Ibs (132 kg).
237/8" (606mm)
22" (559mm)
613/8"
(1559mm
293/4"
(755mm)
2713/16"
(706mm)
595/8"
(1514mm)
24"
603/4"
(1543mm
93/4"
(248mm)
28112"
iiiiiiiiiiiiiiiiiiiiii
Combo Oven with Microwave and Warming Drawer 30"
It is good practice, when oven is in-
stalled at the end of a cabinet run, ad-
jacent to a perpendicular wall or
cabinet door, to allow at least 1/4" space between the side of the oven
and the wall/door.
For oven support, install 2x4's extend- ing front to back flush with the bottom and the side of the opening. The sup- porting base must be well secured to
the floor/cabinet and level. Note: The conduit box must be located
above the unit to facilitate connecting and servicing.
The cabinet base must be flat and capable of supporting a weight of at
least 310 Ibs (141 kg).
F
407/16"
293/4"
(755mm)
_ 237/8" (606mm)
24"
(610mm)_
2713/16" 40"
=m) (1018mm)
381/8"
(968mm)
(248mm)
93/4"
28112"
Combo Oven with Warming Drawer 30"
It is good practice, when oven is in- stalled at the end of a cabinet run, ad-
jacent to a perpendicular wall or
cabinet door, to allow at least 1/4" space between the side of the oven
and the wall/door. For oven support, install 2x4's extend-
ing front to back flush with the bottom and the side of the opening. The sup-
porting base must be well secured to the floor/cabinet and level.
Note: The conduit box must be located above the unit to facilitate connecting
and servicing. The cabinet base must be flat and
capable of supporting aweight of at least 290 Ibs (132 kg).
.._ 237/8" (606mm)
30" Under-the-counter-Units
293/4"
291/16"
(738mm)
22" (559mm)
281/4"
(718mm)
2713/16"
(7O6mm)
(686mm)
237/8" (606mm)
24"
(610mm)
281/2"
27"
(419mm)
all
(102mm)
161/2"
36"
(915mm)
A single oven installed under the counter allows for the installation
of most Thermador Gas or Electric non-Cook'n'Vent® Model Cook-
tops. Downdraft units cannot be installed in this configuration;
Thermador overhead ventilation is recommended.
Some TMH cooktops require addi- tional clearances to combustible
walls. A Thermador cooktop should be
installed on the same center line as the under-the-counter single
oven. Follow the installation in- structions provided with cooktop
for installation of cooktops. 3 3/4" inches (95mm) minimum is re- quired from the top of the counter- top to the top of the cutout opening
for under-counter installation with Thermador cooktops. If the type of
cabinet or countertop thickness does not provide for this minimum space, the cabinet base may have to be lowered, into the toe space, to provide the necessary space
above the oven. However, a 4" minimum distance between the
floor and the oven bottom must re- main.
Electrical Installation
All model ovens on the front cover are dual rated, designed to be connected to ei- ther 208/240V AC, 60 Hz, 4 wire, single-phase power supply.
Model Circuit Required
208V, 60 Hz 240V, 60 Hz
M271, M301 25 AMP 30 AMP ME301, MEW301 30 AMP 30 AMP
ME271, PO301, POD301, DE301, DEC301
ME302, MED302 ME272, MED272,
PO302, POD302, PODC302, DE302, MEM271, MEM301, POM301, MEMC301, MEMCW301, MEMW271, MEMW301,
POMW301
The electrical supply should be a 4-wire single-phase AC. Install a suitable conduit box (not furnished).
Important: Local Codes may vary, installation, electrical connections and ground- ing must comply with all applicable local codes.
If local codes permit grounding through the electrical supply neutral, connect both the white neutral wire and the bare ground wire from the oven to the white neutral electrical supply wire.
Electrical Connection
1. Connect the red oven wire to the red electrical supply wire (hot wire).
2. Connect the black oven wire to the black electrical supply wire (hot wire).
3. Connect the white neutral oven wire to the white neutral (not bare ground) electrical supply wire.
4. Connect the bare ground oven wire to the bare ground electrical supply wire.
The conduit cable, where connected at the oven, swivels. Rotate conduit cable up- ward (or downward) and direct through hole prepared in cabinet to attach to J-Box.
To facilitate maintain serviceability, the flex conduit must not be shortened and should be routed to permit temporary removal of the oven.
40 or 50 Amp circuit. Refer to local electrical codes for de-rating requirements.
Loading...
+ 29 hidden pages