1. Connections
Note:
3-line connection for new systems not permissible!
3-line connection 4-line connection
LN1
2

2
GB
2. Putting into operation/use
2.1 Setting the operation time/operating state
The operating time is displayed during setting.
Key + 05; 1 … 995minutes
Key – 995; 99 … 05minutes
Hand switch, light continuously ON
Key
Function: Continuous/ON Display:
Function: Set time Display: when the unit is activated
when the unit is not activated
2.2 Operation for the user
Key in stairwell
Press 1x, approx. 1 sec.
= for the operation time
Press 1x, approx. 3 sec.
= for one hour
If the key is pressed again for approx. 1 sec. during this period, you switch off the lighting immediately.
Only for units with OFF prewarning.
Approx. 20 seconds before the end of the set time, the lighting is switched off for a very.
brief time. The user can switch ON the lighting again with any key in the stairwell.
The lighting is again activated for the set operating time.
–
+

3
GB
2. Putting into operation/use
2.3 Diagnosis
a) Key check
If one of the keys in the stairwell is pressed, appears in the display.
If this symbol is continuously displayed, one or more keys may be blocked or even
defective.
b) Lamp ON period/operating hours (displayed value x 100)
Begin: Press keys + and – simultane
Example: 0
5
= 50 hours
1 = 100 hours
15= 150 hours etc.
End: Press + or – once current switching state
The number of operating hours is an indication of whether and
when it seems appropriate to change the lamps.
c) Lighting ON
If one of the keys in the stairwell or the hand switch on the unit has been pressed,
the symbol in the display must be visible. If the lighting in the stairwell is still OFF,
there may be an installation fault or all lights are faulty.
–
+

4
GB
3. Technical Data
Dimensions H x W x D mm 45 x 17,5 x 60
Distributor section mm 46 x 18,5
Connection see unit imprint
Switching capacity AC
– ohmic load (VDE, IEC) cos phi 1 16 A/230 V
– inductive load cos phi 0,6 10 A/230 V
– incandescent lamp load 2300 W
– fluorescent lamp in DUO circuit 20 x 2 x 58 W
– fluorescent lamp, parallel-compensated 20 x 58 W
– fluorescent lamp, series-compensated 40 x 58 W
– electronic ballast 5 x 20 W
– conventional ballast 1500 W
Switching contact N/O contact
Ambient temperature –10° C … +55° C
Protection class/type II/IP 20
Adjustment range 0.5 … 99.5 minutes
Glow lamp load max. 50 x 1 mA
ON period 100% on-load factor
Hand switch yes
Resettable immediately
Attachment captive +/– screws
Connection type 3/4 wire connection
Diagnosis functions yes
Caretaker function = 1 hour press approx. 3 seconds
Options/prewarning yes