TFC Group SB-Digi+ User Manual

Instruction Manual Digital socket box timer
Grässlin UK Vale Rise Tonbridge/Kent TN9 1TB Tel. (0 17 32) 35 98 88 Fax (0 17 32) 35 44 45 www.tfc-group.co.uk
GB
page
OK
reset
Menu
Prog
Prog.
P0x
prog
P--
prog
del
+1h
Safety precautions, short description, wiring diagram.................................................................3
Installation .......................................................................................................................................................... 3
Technical data ..................................................................................................................................................5
Symbols, keys ...................................................................................................................................................5
Setting the timer ..............................................................................................................................................6
Setting 24h or am/pm clock, time and weekday ............................................................................6
Pre-set programs.............................................................................................................................................8
Selecting pre-set programs P01 to P03................................................................................................ 9
User defined programs ...............................................................................................................................10
Deleting programs ........................................................................................................................................13
Summer/winter time ....................................................................................................................................14
Manual override .............................................................................................................................................14
2
GB
Safety precautions
· The connection and installation of electrical devices may only be carried out by a qualified electrician.
· Interventions in and changes to the device result in the voiding of the warranty claim.
· Observe your national regulations and the respective safety provisions.
· Switch-off commands have priority over switch-on commands.
3
Mains installation
This product must be installed by a quail­fied person in accordance with I.E.E. wiring regulations. The examples are suitable for connecting to a mains input / mains output installation.
Volt-free switching
If there is no link between terminals 3 and 5, it is possible to use the timer to control a load on a separate supply circuit, which can be a different voltage value up to 250 V AC. In this case, connect the mains live and neutral to 5 and 4 respectively, then con­nect the live in / live out of the circuit to be switched, to terminals 2 and 3.
Installation procedure
1. Switch off supply to socket box.
2. Unscrew the two screws located top left and bottom right of the front module cover; remove cover and gently pull module from backplate. Do not put undue stress on, or interfere with fixed blue wires.
3. Fix backplate to socket box.
4. Connect wiring in accordance with wiring diagram. Do not combine solid and flexible conductors in the same terminal. When connecting flexible con­ ductors use the ferrules supplied.
5. Fit cover over module and reassemble to backplate. Ensure fixed blue wires stowed neatly without being trapped.
6. Re-fit and tighten two screws.
7. Switch on mains.
GB
1 2 3 4
L N L N
5 E
M
~
to appliance mains supply
Backplate wiring: Example
54321
Wiring diagram
The link illustrated between terminals 3 and 5 (when required) must be fitted by the installer. The diagram above is appropiate when switching a mains load.
4
Technical Data
OK
reset
1 2 3 4 5 6 7
14
16
18
20
22
24
+ - Menu OK
Res.
+1h
Supply voltage see inprint on device Switching capacity see inprint on device Ambient temperature -10ºC to +55ºC Protection class IP 51 electronic IP 20 terminal box Accuracy +/- 1 sec day at 20ºC Reserve power 3 years from factory at +20ºC Shortest switching time 1 min Memory spaces 20
: Overview of daily switching
program
: Setting of 24h or am/pm
: Summer/winter clock changes
: Weekday display
: Switching status display ON/OFF
: Manual operation / advance ON /
advance OFF
: Automatic operation
+/- : Adjustment keys: By pressing the key longer than 2 sec. you can adjust the timer in steps of 5 units
Res. : Reset Menu : By pressing the menu key
programming is terminated and the system reverts to automatic operation
OK : Confirmation of programming
5GB5