INSTALLATION INSTRUCTIONS
2 PORT ZONE VALVE VAL222MV VAL228MV
VAL222MV and VAL228MV are 2 port spring return zone valves with 22mm and 28mm compression
fittings and an auxiliary switch. This is for general purpose flow control applications or central heating
systems. When correctly wired with an appropriate room thermostat, cylinder thermostat and
programmer the valve will control the water flow from the boiler to hot water and from boiler to central
heating.
SPECIFICATIONS
• Supply voltage 240V. AC 50Hz
• Power consumption: 6W
• Operating temperature range: +5 to +88
• Cable length one metre
• Max. differential pressure for 22mm = 1Bar
• Max. static pressure 10.0 Bar
• Max. fluid temperature 100
• Max. ambient temperature 52
0
C
0
C
0
C
88
55
A B
ALL DIMENSIONS IN MM
60
55
INSTALLATION
Before fitting the valve, read through the plumbing
and wiring instructions. When replacing the valve
actuator only, set the Auto/Manual lever to the
“Manual Open” position before removal. On the
replacement actuator set the Auto/Manual lever to
“Manual Open” position before fitting.
WIRING
All wiring should be carried out to IEE Regulations
Brown - live
Orange - end switch out
Grey - end switch in
Blue - neutral
Green & Yellow - earth
PLUMBING
When connecting to pipe work do not use the
actuator for leverage. Valves should be held by
wrench flats on body. Place the AUTO/MAN lever in
the MAN position when filling, venting or draining
the system
TAKE CARE NOT TO OVERTIGHTEN
WARNING
All controls must be earthed. All valves should have a
means of disconnection from electrical mains supply
which incorporates a contact separation of at least 3mm
in all Poles.
All wiring must be carried out by a competent
electrician.
93
Typical circuit using two zone Valves (VAL222MV)
Programmer, Room Thermostat and Cylinder Thermostat
PROGRAMMER HEATNG H, WATER
L
N
240V AC 50 Hz
Supply fused
at 3A
BROWN
GREY
BLUE
ORANGE
Valve
GRN/YLO
L N
CALL
ON
OFF
COM
SAT
OFF
ON
CALL = THERMOST AT DEMAND
SAT = THERMOSTAT NO DEMAND
COM = COMMON
PERMANENT LIVE
NEUTRAL
COM
CALL
SAT
BROWN
GREY
BLUE
ORANGE
GRN/YLO
Cylinder
Thermostat
Valve
P B
NEUTRAL (P=PUMP) NEUTRAL (B=BOILER)
0
45
0
45
TFC GROUP LTD
Tower House, Vale Rise, Tonbridge, Kent, TN9 1TB, Telephone: 01732 359888 Fax: 01732 354445

INSTALLATION INSTRUCTIONS
MID-POSITION VALVE VAL322MP VAL328MP
VAL322MP and VAL328MP are 3 port spring return mid-position valves with 22mm and 28mm
compression fittings and switched output. These are for use on fully pumped systems which
when correctly wired with an appropriate room thermostat, cylinder thermostat and programmer
will control the water flow from the boiler to either to hot water only, heating only, or to both
simultaneously.
H,WATER
OFF
ON
GREY
60
55
Pumped flow from boiler
Domestic hot water circuit
INCLUDE IF PROGRAMMER HAS A
HEATING ONLY SELECTION
COM
CALL SAT
CYLINDER
THERMOSTAT
TO BOILER & PUMP
SPECIFICATIONS
• Supply voltage 240V. AC 50Hz
• Power consumption: 6W
• Operating temperature range: +5 to +88
0
C
• Cable length one metre
• Max. differential pressure for 22mm = 1Bar
• Max. static pressure 10.0 Bar
• Max. ambient temperature 52
0
C
INSTALLATION
Before fitting the valve, read through the plumbing
and wiring instructions. When replacing the valve
actuator only, set the Auto/Manual lever to the
“Manual Open” position before removal. On the
replacement actuator set the Auto/Manual lever to
“Manual Open” position before fitting.
WIRING
All wiring should be carried out to IEE Regulations
White -
Room Thermostat Call / Heating on
Grey - Cylinder Thermostat Sat / Hot water off
Orange - Cylinder Thermostat Call / Boiler and Pump
Blue - Neutral
Green & Yellow -
Earth
PLUMBING
When connecting to pipe work do not use the
actuator for leverage. Valves should be held by
wrench flats on body. Place the AUTO/MAN lever
in the MAN position when filling, venting or draining
the system.
TAKE CARE NOT TO OVERTIGHTEN
88
55
122
A
B
All dimensions in MM
AB
Port AB =
43.5
Port A = Heating circuit
HEATING
OFF
COM
SAT
WHITE
ORANGE
Port B =
93
Typical circuit showing Programmer, Room and Cylinder Thermostats as control elements
PROGRAMMER
240V AC 50Hz
Supply fused
At 3A
Mid - position Valve
L N ON
CALL
ROOM
THERMOSTAT
BLUE
GRN / YLO
VALVE
MOUNTING OPTIONS
Valves may be mounted vertically, or horizontally within
the limits shown in the diagram.
0
45
0
45
WARNING
All controls must be earthed. All valves should have a
means of disconnection from electrical mains supply
which incorporates a contact separation of at least 3mm
in all Poles.
All wiring must be carried out by a competent
Electrician.