Always follow TI’s set-up and application instructions, including use of all interface components within their
recommended electrical rated voltage and power limits. Always use electrical safety precautions to help
ensure your personal safety and the safety of those working around you. Contact TI’s Product Information
Center http://support/ti./com for further information.
Save all warnings and instructions for future reference.
Failure to follow warnings and instructions may result in personal injury, property damage, or
death due to electrical shock and/or burn hazards.
The term TI HV EVM refers to an electronic device typically provided as an open framed, unenclosed
printed circuit board assembly. It is intended strictly for use in development laboratory environments,
solely for qualified professional users having training, expertise, and knowledge of electrical safety risks in
development and application of high-voltage electrical circuits. Any other use and/or application are strictly
prohibited by Texas Instruments. If you are not suitably qualified, you should immediately stop from further
use of the HV EVM.
1. Work Area Safety:
(a) Keep work area clean and orderly.
(b) Qualified observer(s) must be present anytime circuits are energized.
(c) Effective barriers and signage must be present in the area where the TI HV EVM and its interface
electronics are energized, indicating operation of accessible high voltages may be present, for the
purpose of protecting inadvertent access.
(d) All interface circuits, power supplies, evaluation modules, instruments, meters, scopes and other
related apparatus used in a development environment exceeding 50 V
electrically located within a protected Emergency Power Off (EPO) protected power strip.
(e) Use a stable and non-conductive work surface.
(f) Use adequately insulated clamps and wires to attach measurement probes and instruments. No
freehand testing whenever possible.
2. Electrical Safety:
(a) De-energize the TI HV EVM and all its inputs, outputs, and electrical loads before performing any
electrical or other diagnostic measurements. Revalidate that TI HV EVM power has been safely deenergized.
(b) With the EVM confirmed de-energized, proceed with required electrical circuit configurations, wiring,
measurement equipment hook-ups and other application needs, while still assuming the EVM circuit
and measuring instruments are electrically live.
(c) Once EVM readiness is complete, energize the EVM as intended.
/75 VDC must be
RMS
WARNING: while the EVM is energized, never touch the EVM or its electrical circuits as they
could be at high voltages capable of causing electrical shock hazard.
3. Personal Safety:
(a) Wear personal protective equipment e.g. latex gloves and/or safety glasses with side shields or
protect EVM in an adequate lucent plastic box with interlocks from accidental touch.
4. Limitation for Safe Use:
(a) EVMs are not to be used as all or part of a production unit.
Fusion Digital Power is a trademark of Texas Instruments.
This evaluation model (EVM), the UCD3138PSFBEVM-027, is used to evaluate the UCD3138 64-pin
digital control IC in an off-line power-converter application and then to aid in its design. The EVM is a
standalone phase-shifted full-bridge DC-DC power converter. The EVM is used together with a control
card, the UCD3138CC64EVM-030, which is an EVM placed on the UCD3138RGC.
The UCD3138PSFBEVM-027, together with the UCD3138CC64EVM-030, evaluates a phase-shifted fullbridge DC-DC converter. Each EVM is delivered without requiring additional work, from either hardware or
firmware. This EVM combination allows for some of the design parameters to be retuned using Texas
Instruments' graphical user interface (GUI) based tool, Fusion Digital Power™ Designer. Loading custom
firmware with user-designed definition and development is also possible.
Three EVMs are included in the kit: the UCD3138PSFBEVM-027, UCD3138CC64EVM-030, and USB-TOGPIO.
This user’s guide provides basic evaluation instruction with a focus on system operation in a standalone
phase-shifted full-bridge DC-DC power converter.
User's Guide
SLUUAK4–August 2013
Using the UCD3138PSFBEVM-027
WARNING
High voltages are present on this evaluation module during
operation and for a a time period after power off. This module
should only be tested by skilled personnel in a controlled
laboratory environment.
An isolated DC voltage source meeting IEC61010 reinforced
insulation standards is recommended for evaluating this EVM.
High temperature exceeding 60°C may be found during EVM
operation and for a time period after power off.
The purpose of this EVM is to facilitate the evaluation of digital
control in a phase-shifted full-bridge DC-DC converter using the
UCD3138, and cannot be tested and treated as a final product.
Extreme caution should be taken to eliminate the possibility of
electric shock and heat burn. Please refer to the page EvaluationModule Electrical Safety Guideline after the cover page for your
safety concerns and precautions.
Read and understand this user’s guide thoroughly before starting
any physical evaluation.
The UCD3138PSFBEVM-027, along with the UCD3138CC64EVM-030, demonstrates a phase-shifted fullbridge DC-DC power converter with digital control using the UCD3138 device. The UCD3138 device is
located on the UCD3138CC64EVM-030 board. The UCD3138CC64EVM-030 is a daughter-card with
preloaded firmware providing the required control functions for an phase-shifted full-bridge converter.
Please contact TI for details on the firmware. The UCD3138PSFBEVM-027 accepts a DC input from 370
to 400 VDC, and outputs a typical 12 VDC with full-load output power at 360 W, or full output current of 30
A.
NOTE: This EVM does not have an input fuse. It relies on the input current limit from the input
voltage source that is used.
2.1Typical Applications
•Offline DC-DC power conversions
•Servers
•Telecommunication systems
2.2Features
•Digitally-controlled phase-shifted full-bridge DC-DC power conversion
•DC input from 370 to 400 VDC
•12-VDC regulated output from no load to full load
•Full-load power at 360 W, or full-load current at 30 A
•High efficiency
•Constant soft-start time
•Overvoltage, overcurrent, and brownout protection
•Test points to facilitate device and topology evaluation
Device ID (Version)UCD3100ISO1 | 0.0.01.0001|130315
FilenameUCD3138PSFBPWR027_03152013.x0
(1)
The load current and load power are commanded using the designer GUI. See Section 12 for more information on CPCC
operation. See Section 13 for more information on GUI application.
DC voltage source: This source is capable of 350 to 400 VDC. The source is adjustable, with a minimum
power rating of 400 W, or current rating no less than 1.5 A, and has a current limit function. The DC
voltage source used should meet IEC61010 safety requirements.
DC multi-meter: The multi-meter has two units, one is capable of a 0 to 400 VDC input range and
preferred four-digit display. The other unit is capable of a 0 to 15 VDC input range and a preferred fourdigit display.
Output load: This DC load is capable of receiving 0 to 15 VDC, 0 to 30 A, and 0 to 360-W or greater, with
display such as load current and load power.
Current meter: If the load does not have a display, this DC current-meter is optional. This unit is capable
of 0 to 30 A. A low-ohmic shunt and DMM are recommended.
Oscilloscope: The oscilloscope is capable of 500-MHz full bandwidth, digital or analog. If choosing a
digital oscilloscope, TI recommends 5 Gs/s or better.
Fan: A fan with 400-LFM forced-air cooling is required.
Recommended wire gauge: The recommended gauge must be capable of 30 A, or better than No. 14
AWG, with the total wire length less than 8 ft (4-ft input and 4-ft return).
5.2Recommended Test Setup
www.ti.com
10
Figure 5. UCD3138PSFBEVM-027 Recommended Test Setup
TP31Not used
TP323.3V3.3 V
TP33SW1Switch node
TP34PWRGNDPrimary 12-V bias return
TP35SW2Switch Node
TP36CASSPrimary commutation-assist junction
TP37ISECIOUT sensing output (EADC1 Input)
TP38Not used
TP39Not used
TP40Not used
TP41S1S1 status
7Terminals
TerminalNameDescription
Table 3. List of Terminals
J1Input_PInput voltage positive terminal
J2Remote SenseRemote sense and I_SHARE
J312VO+12-V output
J4–12VO12-V output return
J5BiasVAUX_S and 3.3V_EXT
J6UART1Standard UART connection, RS232, 9-pin
J7UART0UART0 and ACFAIL_IN (communication with PFC)
J8VO_RIPPLEBNC VO_Ripple
J9JumperJumper (reserved to an input-fuse substitution)
J10JumperUsed when T5 not populated
J11Input_NInput voltage return terminal
1. See Figure 4 for basic setup to measure power-conversion efficiency. The required equipment for this
measurement is listed in Figure 5.
2. Check the boards visually before making electrical connections to ensure that no shipping damage
occurred.
3. Use the UCD3138PSFBEVM-027 and UCD3138CC64EVM-030 for this measurement which are
included this EVM package along with the USB-TO-GPIO.
4. Install the UCD3138CC64EVM-030 board onto the UCD3138PSFBEVM-027 first. Take care with the
alignment and orientation of the two boards to avoid damage.
•See Figure 6 for the UCD3138PFCEVM-030 board orientation.
5. Connect the DC-voltage source to J1 (+) and J11 (–). The DC-voltage source should be isolated and
meet IEC61010 requirements.
•Set up the DC-output voltage in the range specified in Table 1, between 370 VDC and 400V DC;
set the DC-source current limit at 1.2 A.
Test Procedure
WARNING
CAUTION
CAUTION
NOTE: A fuse is not installed on the board and, therefore, the board relies on the current limit of the
external voltage source for circuit protection.
6. Connect an electronic load with either a constant-current mode or constant-resistance mode. The load
range is from 0 to 30 A.
7. Ensure a jumper is installed on J6 of the UCD3138CC64EVM-030
8. Use the switch S1 to turn on the board output after the input voltage is applied to the board. Before
applying input voltage, ensure that the switch, S1, is in the OFF position.
9. Use a current meter or low-ohmic shunt and DMM between the load and the board for current
measurements if the load does not have a current or a power display.
10. Connect a volt-meter across the output connector and set the volt-meter scale at 0 to 15 V (DC).
11. Turn on the DC-voltage source output. Flip S1 to ON and vary the load.
12. Record output voltage and current measurements.
Figure 15. Control-Loop Bode Plots at 385 VDC Across Load Range
www.ti.com
10EVM Assembly Drawing and PCB layout
Figure 16, Figure 17, Figure 18, Figure 19, Figure 20 and Figure 21 show the design of the
UCD3138PSFBEVM-027 printed circuit board (PCB). The PCB dimensions are L × W = 8 × 6 in, the PCB
material is FR4, or compatible, four layers with 2-oz copper on each layer.
The UCD3138 pins are defined according to Figure 23. The definitions shown in Figure 23 are for the pins
used in the EVM to control a phase-shifted full-bridge converter. See Figure 21 for how the signals on
these pin signals are used.
Description of the Digital Phase-Shifted Full-Bridge Converter
SLUUAK4–August 2013Using the UCD3138PSFBEVM-027
Submit Documentation Feedback
Figure 23. UCD3138 Pin Definition in Phase-Shifted Full-Bridge Control
Description of the Digital Phase-Shifted Full-Bridge Converter
12.3 EVM Hardware — Introduction
This section describes the EVM hardware functions.
12.3.1Power Stage
This EVM implements topology for a phase-shifted full-bridge DC-DC converter. The key waveforms
generated by the UCD3138 to control the phased-shifted power stage are shown in Figure 24. See
Section 4 for the complete schematics. On the primary side, QT1, QB1, QT2, and QB2 are the power
switches, L2 is a resonant inductor (often called shim inductor), and T1 is the main transformer. D9 and
D10 are clamping diodes. T2 is a current transformer for sensing primary-side current and is located on
the high side. T5 is not used and is shorted by jumper J10.
The secondary side is configured as a central-tap synchronous rectifier comprised of an output choke
(L1), output capacitor (C4 and C62), and synchronous MOSFETS (QSYN1, QSYN2, QSYN3 and
QSYN4). Q6 and Q10 are oring FETS for hot swap. T3 and T4 are gate transformers to drive primary-side
power MOSFETs and provide isolation boundary. Two gate drivers (U4 and U5) are used for driving the
gate transformers. Two low-side drivers, U3 and U8, are used for driving the secondary-side synchronous
MOSFETs.
www.ti.com
26
Figure 24. Driving Scheme of Phase-Shifted Full-Bridge Control
The following lists the DPWM configuration for the phase-shift full bridge converter:
DPWM3A to VGS_QB1DPWM3B to VGS_QT1
DPWM2A to VGS_QT2DPWM2B to VGS_QB2
DPWM1B to VGS_QSYN2 and QGS_QSYN4DPWM0B to VGS_QSYN1 and QGS_QSYN3
When both QB1 and QT2 turn on, the input voltage Vbus is applied to the power transformer and energy
is transferred to the output. During this period, QSYN1 and QSYN3 are turned off and power is transferred
through L1 to the output. The return current flows through QSYN2 and QSYN4, which are turned on, and
then the current flows back to the secondary side of the main transformer. When QB2 and QT1 are both
on, the bus voltage is applied to the power transformer in the opposite direction. In this case, QSYN2 and
QSYN4 are turned off and power is transferred through L1 to the output. The return current flows through
QSYN1 and QSYN3, which are turned on, and then flows back to the main transformer. When all four
switches on the primary side are turned off, the secondary side works in a freewheeling mode, meaning all
sync FETs are turned on and the inductor current flows through the switches. See Section 15 for a list of
references containing additional details about the phase-shift full-bridge converter.
Because the digital controller generating the six DPWMs in on the secondary side and four of the power
switches are on the primary side, the converter requires an isolation component to cross the boundary.
Pulse transformers, T3 and T4, transmit the gate signal and drive the primary-side power MOSFETs.
These transformers are used because they are simple and low cost although they typically require more
space than digital isolators. Two drives, U5 and U6, drive the gate-drive transformers from the secondary
side. The leakage inductance of the gate transformer oscillates with other capacitors in the gate-drive
circuit during dead time. If the leakage inductance oscillates with other capacitors, a glitch can occur. A
negative voltage is provided by the components D20 and C36 for QT1. Other switches use the same
circuit that generates negative current. The secondary-side switches do not require isolation. Two ICs, U3
and U8, directly drive these switches.
The dead time between all switches is important to achieve zero-voltage switching based on different
operation conditions such as load current and input voltage.
For peak-current-mode control, slope compensation is important to stabilize the loop and avoid the nonperiodic ripple of the output voltage. The slope is generated either internally or externally. If the slope
compensation is generated externally, DPWM0A and DPWM1A are used. In this case, install the jumpers
between Pin1 to Pin2 and between Pin5 and Pin6 for proper operation. Install Q1, Q2, Q4, and Q8 to
generate the slope.
External slope-compensation circuits require many external components. In default, internal slope
compensation is used. The controller generates the slope and adds the slope on the filter output of the
voltage loop. EAP2 requires a pullup resistor to provide over 100-mV DC offset voltage, which is important
to stabilize the loop at the small duty.
Description of the Digital Phase-Shifted Full-Bridge Converter
12.3.2Bias Power Supply
The bias supply is a flyback converter using the UCC28600 controller from TI. The bias is an independent
daughter-card, the PWR050. The design files (SLUR924) are located in the UCD3138PSFBEVM-027
product folder on www.ti.com. Figure 25 shows the schematic of the PWR050.
There is one 12-V output (PN3-PN4) on the primary side and one 12-V output (PN5-PN7) on the
secondary side. The feedback signal is taken from the secondary 12-V output. The controller requires +3.3
V, which is derived from the secondary 12-V output through a LDO regulator (U2).
Description of the Digital Phase-Shifted Full-Bridge Converter
12.3.3Sensing Input Voltage on Secondary-Side
In Figure 25 there is sample-and-hold circuit on the secondary side of the PWR050, which senses the
primary-side voltage. When the Q2 switch turns on, D5 turns on. The voltage on the winding (6, 7) of the
bias transformer T1 charges capacitor C9 to a voltage equal to VIN / N after the divider of R16 and R14,
where N is the turns ratio of T1. When Q2 turns off, D5 turns off, and the voltage on C9 is held until the
next switching period. The voltage on C9 is proportional to the input voltage. U4 is used to scale the
sampled voltage to the application.
Figure 26 and Figure 27 show how the load current is sensed and fed back to the UCD3138. A 1-mΩ
sense-resistance value (R53 // R104 // R105) senses the load current. A differential amplifier circuit
amplifies and filters this signal. The result is supplied to EADC1 and AD13. The sensed current is also
used in constant-current and constant-power (CPCC) operation. The AD13 monitors the current. The
AD13 also has a mechanism for a fast latch-off over current and the means to implement either masterand-slave or average-mode current sharing.
Description of the Digital Phase-Shifted Full-Bridge Converter
Description of the Digital Phase-Shifted Full-Bridge Converter
12.3.5Serial Port Interface
The schematic of the interface for the serial port (UART) is shown in Figure 28. The UART provides realtime debug and subsequently reduces code-development time. This serial port also monitors for fastchanging internal variables.
www.ti.com
12.3.6LED Indicators
Ref. DesignatorSilk Screen TextFunction
D2612VP_ONThis LED turns green when 12 V is present on the primary side.
D2FAILUREThis LED turns red when a fault is detected.
D3P_GOODby PMBUS_CMD_POWER_GOOD_ON and
D5AC_P_FAIL_OUTThis LED is not used.
Figure 28. Serial Port Interface in the Converter
Table 5. LED Status Lights
This LED turns green when the output voltage is within the thresholds defined
PMBUS_CMD_POWER_GOOD_OFF[1].
The UCD3138PSFBEVM-027 is controlled by a control card, the UCD3138CC64EVM-030, through two
40-pin connectors, P1 and P2. Table 6 lists the definitions of P1 and P2 on the UCD3138PSFBEVM-027
board.
Header Pin No.Usage Description
P1-1DPWM_0ADPWM0A, slope generation
P1-2DPWM_0BDPWM0B, controls the secondary-sync FET, QSYN1, 3.
P1-3DPWM_1ADPWM1A, slope generation
P1-4DPWM_1BDPWM1B, controls the secondary-sync FET, QSYN2, 4.
P1-5DPWM_2ADPWM2A, controls the primary-side FET, QT2.
P1-6DPWM_2BDPWM2B, controls the primary-side FET, QB2.
P1-7DPWM_3ADPWM3A, controls the primary-side FET, QB1.
P1-8DPWM_3BDPWM3B, controls the primary-side FET, QT1.
P1-9DGNDDigital ground (GND)
P1-10DGNDDigital ground (GND)
P1-11GPIO08ON/OFF
P1-12GPIO09/FLT1BGPIO_ORING_CTR
P1-13GPIO10Failure
P1-14GPIO11/FLT2BP_GOOD
P1-15GPIO28Not used
P1-16GPIO29Not used
P1-17GPIO30Not used
P1-18GPIO31Not used
P1-19GPIO32/FLT4AI_FAULT
P1-20GPIO33/ FLT4BLATCH_ENABLE
P1-21GPIO26Not used
P1-22GPIO22Not used
P1-23GPIO24Not used
P1-24GPIO23Not used
P1-25GPIO18/PWM1AC_FAIL
P1-26GPIO19/PWM2ACFAILIN
P1-27GPIO20Not used
P1-28GPIO21Not used
P1-29GPIO34Not used
P1-30GPIO35Not used
P1-31GPIO16/SCI_TXSCI transmit
P1-32GPIO17/SCI_RXSCI receive
P1-33GPIO25Not used
P1-34GPIO27Not used
P1-35GPIO27Not used
P1-36RESET*Not used
P1-37DGNDDigital ground (GND)
P1-38DGNDDigital ground (GND)
P1-39VauxSExternal 12-V DC supply
P1-40Not used
P2-01AGNDAnalog ground (GND)
P2-02ADCREFinNot used
Not connected to
UCD3040
Description of the Digital Phase-Shifted Full-Bridge Converter
The reference firmware that is provided with the EVM is intended to demonstrate basic phase-shifted fullbridge DC-DC converter functionality, as well as some basic PMBus communication and primary-tosecondary communication. The firmware is used as an initial platform for particular applications. This
section provides a brief introduction to the firmware.
12.4.1Firmware Infrastructure overview
The firmware includes one startup routine and three program threads. The startup routine initializes the
controller setup for the targeted operation functions or status. Please contact TI for detailed initialization
information.
As shown in Figure 34, the three program threads are (1) the fast-interrupt request (FIQ); (2) the timerinterrupt request (IRQ); and (3) the background loop. These threads are described as:
1. Fast Interrupt (FIQ)
•Critical or time-sensitive tasks are within the FIQ. Functionally, FIQ events are the highest priority
and are addressed as soon as possible.
2. Timer Interrupt (IRQ)
•The majority of the firmware tasks occur during the IRQ. IRQ events occur synchronously every
100 µs.
3. Background Loop
•Non time-sensitive tasks are implemented in the background loop. Background Loop items are
addressed whenever FIQ and IRQ events are not handled.
Description of the Digital Phase-Shifted Full-Bridge Converter
Figure 29. Firmware Structure Overview
12.4.2Tasks Within FIQ
FIQ events have the highest priority and are addressed as soon as possible. The FIQ includes critical and
time-sensitive tasks. The firmware included with the EVM includes two functions called by the FIQ:
•Constant Power and Constant Current
•Cycle-by-cycle current limit
The FIQ interrupt is called to respond every four switching cycles.
Description of the Digital Phase-Shifted Full-Bridge Converter
12.4.3Tasks Within IRQ and State Machine
Almost all firmware tasks occur during the IRQ. The exceptions are the serial interface and PMBus tasks,
which occur in the Background Loop; and the overcurrent protection (OCP), which is handled by the FIQ.
The IRQ is called to respond every 100 µs.
At the heart of the IRQ function is the power-supply State Machine implemented with switch command.
Figure 30 shows the structure of the State Machine. At a higher level, this State Machine allows the digital
controller to optimize the performance of the power supply based on the exact State Machine functions of
the digital controller.
www.ti.com
12.4.4Tasks Within Background Loop
12.4.5System Normal Operation
34
Figure 30. State Machine
The background loop handles all PMBus communication as well as processing and transmitting data
through the UART. The data flash is managed with a dual-bank approach. This provides redundancy in
the event of a power interruption during the programming of data flash. Once new data-flash values have
been written, a function called erase_task() initiates in the background loop to erase the old values. The
erase_task() is called until all of the old DFLASH segments are erased. Erasing the data flash in segments
allows the processor to handle other tasks instead of waiting for the entire data flash to be erased before
completing other tasks.
The EVM is designed to operate in peak-current-mode control under normal operation conditions. The
EVM operates with output voltage in regulation across the load range. If the load power continues to
increase beyond the rated value, then an overload condition occurs. In such a case, the system enters
protection operation by entering CPCC mode. If load power still continues to increase, output shutdown is
triggered.
Peak-current-mode control is used in this EVM. The primary-side peak current is used to create control,
and is sensed through current transformer T2. The slope compensation is realized within the digitalcontroller internal setup which is re-programmable to adapt to required applications. External slope
compensation is also used with component place-holders in place. Please contact TI for information on
how to re-program the internal slope compensation and how to set up the external slope compensation.
12.4.5.2Other Possible Control Modes
Voltage-Mode Control and Average Current-Mode Control are also possible. To change the EVM into
these controls, both hardware and firmware require modifications. Please contact TI for more information
on how to make these modifications.
12.4.6System Operation in Protection
12.4.6.1Faults and Warnings
The system is equipped with a variety of programmable fault and warning options. Table 5 lists the LEDs
used to indicate a fault. Table 7 lists the basic faults and warnings available in the EVM along with the
corresponding action required by these events. Each of these parameters is modified through the GUI.
Table 7. Faults and Warnings
SignalTypeWarningFault Response
VOUT
VIN
IOUTOverReportReport and latch off
IINOverReportCycle-by-cycle limiting
SR (QSYN3)
Temperature
OverReportReport and latch off
UnderReportReport
OverReportReport and latch off
UnderReportReport and latch off
OverReportReport and latch off
Description of the Digital Phase-Shifted Full-Bridge Converter
Description of the Digital Phase-Shifted Full-Bridge Converter
Reporting a fault includes the appropriate setting of the PMBus alert line, status byte, and status word.
Faults and warnings are reset by toggling the unit off and then on. Alternatively, as long as the system
does not latch off, the Clear Faults button clears any faults or warnings (see Figure 31). Faults and
warnings are also cleared by toggling the control line the on-off switch.
www.ti.com
Figure 31. Faults and Warnings
12.4.6.2Cycle-By-Cycle Current Limit
Current transformer T2 senses the primary-side current. Figure 32 shows the sensing circuit. This current
is used for cycle-by-cycle current limit, peak-current-mode control, or flux balancing of the main
transformer. The primary-peak current is limited within the primary MOSFET current ratings by the cycleby-cycle current limit. R31 and C17 are used as a low-pass filter before the current signal feeds to the
UCD3138. The current signal is sent into UCD3138 through AD06 to create cycle-by-cycle current-limit
control. To prevent switching spikes from triggering the comparator, a blanking time is programmed.
Description of the Digital Phase-Shifted Full-Bridge Converter
12.4.6.3Constant Power and Constant Current Operation
Both hardware and firmware in this EVM support CPCC operation. Figure 33 illustrates the behavior of the
output voltage and output current (V
OUT
versus I
). The dashed lines represent an extended view.
OUT
The EVM is delivered already programmed with a constant-power threshold of a few watts over 360 W
and a constant-current threshold of 33 A (typical). These limits are adjustable through the GUI and a new
setting can be saved to data flash. The maximum hardware capability limits the current within 35 A. The
dashed lines represent exceeding the constant power to a higher current, although the maximum current
of this EVM is limited to 35 A. Figure 34 shows the GUI default values of these controls.
In addition to setting the previously described thresholds, enabling or disabling the CPCC feature and
configuring a fault timer is also possible. Whenever the State Machine detects CPCC operation a timer
starts. If the timer reaches the time limit specified in Figure 34, the system latches off until the on
command toggles off and on again, or recycles the input power.
Figure 33. CCPCC Operation
Figure 34. CPCC Default Values Adjusted Through GUI
Description of the Digital Phase-Shifted Full-Bridge Converter
12.4.6.4Output Over Voltage
When the output voltage exceeds 15.6 V, Q7-B turns on then Q7-A turns on because the Q7-A base is
low. OVP_LATCH is pulled low, which is detected by the controller. The output voltage is shut down and
latched. Figure 35 shows the circuit.
The input over voltage is detected based on the winding on the auxiliary power supply as described in
Section 12.3.3. The detected signal is sent to AD08 to create a fault process.
12.4.6.6Over Temperature
Over temperature includes UCD3138 internal-temperature sensing and external added-temperature
sensing. A temperature-sensing element on U10, LM60C, determines the external overtemperature
condition. The temperature signal feeds into the controller through AD07. U10 is located on the top-side of
the board next to the QSYNC3 heat sink. At this location U10 senses the temperature of the secondaryside MOSFETs.
At light load, the burst operation enables when the switching duty cycle is small. The significant benefit of
this operation is the reduction of power loss. The associated disadvantage is higher output voltage-ripple
and larger output voltage-dip when the load has a sudden demand. But the higher ripple and the larger dip
disadvantages are corrected by the convenience and flexibility of the digital control. For example, nonlinear control from digital control solves the large dip during load transient. The higher ripple is also
reduced by narrowed duty cycle on and off-limit for burst operation control. Figure 37 shows the burst
operation timing diagram.
NOTE: The burst operation mode is still in development for this EVM. Please contact TI for the latest
development information.
Description of the Digital Phase-Shifted Full-Bridge Converter
Description of the Digital Phase-Shifted Full-Bridge Converter
12.5.2Current-Sharing Operation
The UCD3138 supports three major current-sharing techniques:
•Average current-sharing, or PWMbus current-sharing
•Master and slave current-sharing
•Droop-Mode Current-Sharing, or Analog bus current-sharing
This EVM uses average current-sharing. The average-current-sharing technique uses a share bus to
balance and evenly distribute the current on each paralleled converter as shown in Figure 38. The share
bus is called ISHARE in this EVM design. Therfore, when making load current sharing, ISHARE from each
board must be connected together. ISHARE connection is located on J2 terminal pin 3 and through R91
and C12 fed into AD02. The load current is connected to AD13 after a low-pass filter (R85 and C49) from
ISEC. The current-sharing module is integrated in the UCD3138, and the ISHARE bus is controlled
properly by UCD3138 internal functions.
This current-sharing-operation feature is used for normal operation in steady state with average-currentsharing approach. In CPCC, the current sharing is inherently valid and does not rely on the averagecurrent-sharing approach. This feature is not available during start, burst operation, or cycle-by-cycle
current limit.
The oring control circuit is shown in Figure 39. Q6 and Q10 are oring FETs used for hot-swapping
operation. Less power-conduction loss occurs when using oring MOSFETs instead of oring diodes. The
oring MOSFETs are controlled by the oring-control IC U1, TPS2411. By sensing the voltage between the
drain and source of the oring FETs, U1 quickly turns off the oring FETs to avoid reverse current drawn
from the output voltage bus. Pull down the gate-drive signal to turn off oring FETs by pulling Pin5 high,
which is controlled by the UCD3138. Through output voltage remote sensing, the voltage drop on the load
wire is compensated to ensure the voltage at the load point is accurate. +RS and –RS are connected to
+VO and 12V_RETURN through the resistors, R55 and R54, respectively.
Description of the Digital Phase-Shifted Full-Bridge Converter
Description of the Digital Phase-Shifted Full-Bridge Converter
12.6 Loop Compensation Using PID Control
Proportional, integral, and derivative (PID) control is usually used in the feedback-loop compensation in
digitally-controlled power converters. This section describes several aspects of how to use PID control.
12.6.1Transformation of Digital-PID Coefficients to Poles and Zeros in the s-Domain
PID control in the UCD3138 control-law algorithm (CLA) for control loop is formed in the z-domain using
Equation 1.
Converting Equation 1 to the s-domain equivalent using the bilinear transform results in two forms. One
form is with two real zeros and one real pole as shown in Equation 2.
K0is the gain of the frequency domain pole at the origin, and K0is also represented as the angular
frequency when the integrator Bode-plot gain crosses over with 0 dB. K0is also used as a method for
initially designing feedback-loop compensation (see reference 5 in Section 15 for more details).
The second form is when the two zeros are presented with complex conjugates as shown in Equation 3.
www.ti.com
(1)
(2)
(3)
Two complex conjugate zeros are expressed as,
(4)
(5)
(6)
The factor of Q is in the range of 0 to infinite. The two complex conjugate zeros become the two real zeros
when Q is less than or equal to 0.5 (Q ≤ 0.5). Therefore, Equation 2 is a unique form of Equation 3. In this
sense, Equation 3 can be used in either case across the range of Q.
A low-pass filter usually exists in a control loop of its feedback path. The low-pass filter adds a pole to the
loop as shown in Equation 7.
The close-loop transfer function is shown in Equation 8.
For example, GM(s) is the transfer function associated to the phase-shifted full-bridge power-modulator
circuit.
The parameters are calculated with the assumption that the sensor-sampling cycle, Ts, is much smaller
than the time constant in relation to the converter-voltage feedback-loop bandwidth, TLC. As a general
rule, choose the sampling frequency as shown in Equation 9.
When the above assumption is true, the delayed effect from the sampling is ignored and the parameters
are determined after the position of the poles and zeros is known. Table 8 summarizes the poles and
zeros in a form relating the z-domain to the s-domain.
Description of the Digital Phase-Shifted Full-Bridge Converter
12.6.2Tuning PID Coefficients for Loop Compensation
When making fine-tuned adjustments to the feedback control loop, knowing how each PID parameter
affects the control loop characteristics without using the complicated equations in Table 8 is beneficial.
Use Table 9 and Figure 40 as a quick reference for tuning PID coefficients.
Table 9. Tuning PID Coefficients
Control ParametersImpact on Bode Plot
K
p
K
i
K
d
αIncreasing α shifts the second pole and the second zero to the right.
Ts= 1 / ƒ
s
Increasing Kppushes up the minimum gain between the two zeros, moving
the two zeros apart.
Increasing Kipushes up the integration curve at low frequencies, provides a
higher low-frequency gain, and moves the first zero to the right.
Increasing Kdshifts the second zero left with no impact on the second pole.
Increasing the sampling frequency ƒsshifts the whole Bode plot to the right.
www.ti.com
Figure 40. Tuning PID Parameters
13Evaluating the EVM with GUI
The collective graphical user interface (GUI) is called TI's Fusion Digital Power Designer (FDPD). The GUI
serves as the interface for several families of TI's digital-control ICs including the UCD31xx family, (such
as UCD3138). The GUI is divided into two main categories, Designer GUI and Device GUI. Each
UCD31xx EVM relates to a particular Designer GUI allowing users to re-tune and re-configure a particular
EVM with existing hardware and firmware. Device GUI relates to the accessing of internal registers and
memories of a particular device.
The UCD3138PSFBEVM-027 is used with the UCD3138CC64EVM-030 control card where the UCD3138
device is placed. The firmware for control is loaded onto UCD3138CC64EVM-030 board through the
Device GUI. The user’s guide, Using the UCD3138CC64EVM-030 (SLUU886), describes the GUI
installation. The Designer GUI is installed at the same time as installing the Device GUI.
As previously mentioned, there are two types of GUI: Device GUI and Designer GUI. The Device GUI is
categorized as low-level GUI. From the Device GUI, device registers are accessed if the device is in ROM
mode and the PMBus communication is established. This GUI is used to download the code when the
device is blank during the initial programming. Also, at the flash mode, a designer can send PMBus
commands to read or write the data. The Designer GUI is an interface between a host and a user. It
supports some of the PMBus commands to configure, monitor, and design the loop compensator
contained in the UCD3138 digital controller.
13.1.1Hardware Setup
Evaluating the EVM with GUI
Figure 41. Test Setup
In Section 5.2, Figure 5 and Figure 6 show a basic setup for a power stage test with the EVM. To evaluate
the EVM with GUI, the control card must first connect to a GPIO-to-USB adapter card, HPA172, then to a
host computer. The following lists the steps for an evaluation:
1. Connect the input voltage source to the input connectors shown in Figure 5. Use 14 AWG wire or
equivalent.
2. Connect the output load to the board. Use a 14-AWG wire or equivalent.
3. Plug the control card UCD3138CC64EVM-030 (PWR030) into UCD3138PSFBEVM-027 with the
orientation in Figure 5 and Figure 6.
4. Confirm that the control card does not have a jumper on J2, and install a jumper on J6.
5. Connect the USB-to-GPIO (HPA172) adaptor to the control card as shown in Figure 41, and connect
the other end of USB-to-GPIO adapter to the host computer
6. Move the ON/OFF control switch, S1, on the phase-shifted full-bridge board, to the OFF position. See
Figure 5 to locate S1 on the phase-shifted full-bridge board.
7. Configure the load to draw 1 A.
8. Apply 380 V to the input with a 2-A current limit set on the input source.
9. Launch the Fusion Digital Power Designer GUI. See Section 13.1.2 for instructions on how to install
the GUI.
10. Turn on the board output by switching S1 to the ON position
13.1.2GUI Installation
Download the GUI software from www.ti.com. Before the GUI is executed, install the software on the host
PC. More details about the TI GUI, FDPD, can be found in the user’s guide or manual. Please contact TI
for the FDPD document. The GUI contains manuals for use with the UCD3138. To find the manuals, use
the following sequence:
Copy over the TI Fusion Digital Power Designer zipped file onto the host computer and unzip the file (TI-Fusion-Digital-Power-Designer-xx.zip) to open the installer file, TI-Fusion-Digital-Power-Designer-xxx.exe.
The xxx in the file name refers to the GUI release version.
Double click the executable installer file and follow the instructions to complete installation. In general,
accept all the installation defaults. In order to have all of the GUI functions available, check all the boxes
under Select Additional Tasks as shown in Figure 42.
www.ti.com
Help > Documentation and Help Center > UCD3138
46
Figure 42. GUI Installation
After the installation, a quick launch button appears next to the start menu in the taskbar section
containing shortcuts to commonly-used applications. Figure 43 shows the TI FDPD icon after the
installation. Other icons, such as UCD3K Device GUI, are displayed on the desktop. For more information
on the GUI installation, see the UCD3138CC64EVM-030 user’s guide (SLUU886).
Turn off the DC power source before connecting the USB-to-GPIO adaptor to
avoid electrical shock.
Connect one end of the ribbon cable to the module, and connect the other end to the USB-to-GPIO
(HPA172) interface adapter. Connect the mini connector of the USB cable to the USB interface adapter.
Then connect the other end to the USB port on the host computer, as shown in Figure 41.
13.1.4Launch the Designer GUI
Click the quick-launch shortcut icon located in the taskbar next to the start menu. When launched, the GUI
searches for a device attached to the PMBus. If the attached device is found and communication between
the GUI and device is successful, a similar-looking screen as shown in Figure 44 is seen. The following
sections describes how to evaluate the module using the GUI.
The Designer GUI has four tabs on the left side of the workspace, as shown in Figure 44: Configure,
Design, Monitor, and Status. After launching the GUI, the default tab is the Monitor tab. To open one of
the three tabs, simply click on the desired tab.
Each tab of the EVM GUI has a different role. Configure configures the EVM settings through PMBus
command. Design creates tuning control-loop parameters. Monitor monitors the board operation. Status
shows faults and warnings that may occur.
13.2 Operation Monitoring
When the designer GUI launches, the Monitor tab is presented by default as shown in Figure 44. This tab
provides a quick overview of operation status with some changeable settings. This tab also provides an
oscilloscope-type plot view in real-time operation. The number of scope windows is adjusted by checking
or un-checking the square boxes in the upper-left of the Monitor tab. Click on a box to show or hide the
selected scope-plot windows.
www.ti.com
13.3 Operation Status
Click the Status tab below the Monitor tab (see Figure 44) to view the EVM operation status shown as in
Figure 45. All grayed entries are candidates that can be implemented. Those candidates in black
represent current-operation status which indicate potential operation issues with either warning or fault
indications. If a fault occurred, the corresponding entry is highlighted in red. Warnings, although not
considered faults, remind the user that those entries could require attention.
The Configure tab allows the user to conveniently adjust the EVM feature setup without directly accessing
the firmware. This tab also navigates the user through the various features of the converter within the GUI.
Evaluating the EVM with GUI
Figure 46. GUI Supported PMBus Commands
13.4.1GUI Supported PMBus Commands
Figure 47 shows the various GUI-based PMBus commands supported by the current version of the
firmware. Use the built-in Isolated Bit mask generator to easily add additional standard commands. This
tool generates a coded index that the GUI reads from the device to determine which PMBus commands
are supported. To add a standard command, modify the bit mask and the GUI automatically displays the
new command. For additional details on using this tool, please contact TI.
In the Configure tab, changing the configuration is simple. For example, to configure CPCC, access the
CPCC control by clicking the drop-down arrow next to the Value/Edit box on the CPCC[MFR 36] line as
shown in Figure 47. As previously mentioned, the maximum current is 35 A and the maximum power is
360 W. Please contact TI if any uncertainty exists that must be resolved. The CPCC feature is disabled by
default.
Firmware Development for Phase-Shifted Full-Bridge Power Converter
13.5 Tuning the Control Loop Using GUI Design
The GUI is equipped with 3 different ways to program the UCD3138 digital control-loop compensator.
Table 10 lists the three options, (a) complex zeros using K0, fz, Qz, and fp; (b) real zeros using K0, fz1, fz2,
and fp; (c) device PID using Kp, Ki, Kd, and α.
In option (c), the compensator is described by device PID. In this context, Kp, Ki, Kdand α are the raw
register values used to configure the positions of the poles and zeros of the compensator. SC is a gain
scaling term. Although SC is normally set to zero, it provides additional gain for situations where the
power-stage gain is low. PRD is used to configure the minimum operating period, and KCOMP is used to
configure the maximum operating period. In the context of the compensator they are gain terms modifing
the overall transfer function by a fixed value. Knowing the proper way to configure PRD and KCOMP
varies based on the control topology implemented is important.
Table 10. Programming Digital Control Loop
System NameTransfer Functions
Complex zeros
(K0, ƒz, Qz, ƒp)
Real zeros
(K0, ƒz1, ƒz2, ƒp)
Device PID
(Kp, Ki, Kd, α)
14Firmware Development for Phase-Shifted Full-Bridge Power Converter
Please contact TI for additional information regarding the UCD3138 firmware development for a digital
phase-shifted full-bridge converter control.
15References
1. UCD3138 Datamanual, Highly Integrated Digital Controller for Isolated Power (SLUSAP2)
2. UCD3138CC64EVM-030 Evaluation Module and User’s Guide, Programmable Digital Power ControllerControl Card Evaluation Module (SLUU886)
3. Reference Guide, UCD3138 Digital Power Peripherals Programmer’s Manual (SLUU995)
4. Reference Guide, UCD3138 Monitoring and Communications Programmer’s Manual (SLUU996)
5. Reference Guide, UCD3138 ARM and Digital System Programmer’s Manual (SLUU994)
Texas Instruments (TI) provides the enclosed Evaluation Board/Kit/Module (EVM) under the following conditions:
The user assumes all responsibility and liability for proper and safe handling of the goods. Further, the user indemnifies TI from all claims
arising from the handling or use of the goods.
Should this evaluation board/kit not meet the specifications indicated in the User’s Guide, the board/kit may be returned within 30 days from
the date of delivery for a full refund. THE FOREGOING LIMITED WARRANTY IS THE EXCLUSIVE WARRANTY MADE BY SELLER TO
BUYER AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED, IMPLIED, OR STATUTORY, INCLUDING ANY WARRANTY OF
MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE. EXCEPT TO THE EXTENT OF THE INDEMNITY SET FORTH
ABOVE, NEITHER PARTY SHALL BE LIABLE TO THE OTHER FOR ANY INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL
DAMAGES.
Please read the User's Guide and, specifically, the Warnings and Restrictions notice in the User's Guide prior to handling the product. This
notice contains important safety information about temperatures and voltages. For additional information on TI's environmental and/or safety
programs, please visit www.ti.com/esh or contact TI.
No license is granted under any patent right or other intellectual property right of TI covering or relating to any machine, process, or
combination in which such TI products or services might be or are used. TI currently deals with a variety of customers for products, and
therefore our arrangement with the user is not exclusive. TI assumes no liability for applications assistance, customer product design,
software performance, or infringement of patents or services described herein.
REGULATORY COMPLIANCE INFORMATION
As noted in the EVM User’s Guide and/or EVM itself, this EVM and/or accompanying hardware may or may not be subject to the Federal
Communications Commission (FCC) and Industry Canada (IC) rules.
For EVMs not subject to the above rules, this evaluation board/kit/module is intended for use for ENGINEERING DEVELOPMENT,
DEMONSTRATION OR EVALUATION PURPOSES ONLY and is not considered by TI to be a finished end product fit for general consumer
use. It generates, uses, and can radiate radio frequency energy and has not been tested for compliance with the limits of computing
devices pursuant to part 15 of FCC or ICES-003 rules, which are designed to provide reasonable protection against radio frequency
interference. Operation of the equipment may cause interference with radio communications, in which case the user at his own expense will
be required to take whatever measures may be required to correct this interference.
General Statement for EVMs including a radio
User Power/Frequency Use Obligations: This radio is intended for development/professional use only in legally allocated frequency and
power limits. Any use of radio frequencies and/or power availability of this EVM and its development application(s) must comply with local
laws governing radio spectrum allocation and power limits for this evaluation module. It is the user’s sole responsibility to only operate this
radio in legally acceptable frequency space and within legally mandated power limitations. Any exceptions to this are strictly prohibited and
unauthorized by Texas Instruments unless user has obtained appropriate experimental/development licenses from local regulatory
authorities, which is responsibility of user including its acceptable authorization.
For EVMs annotated as FCC – FEDERAL COMMUNICATIONS COMMISSION Part 15 Compliant
Caution
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause
harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the
equipment.
FCC Interference Statement for Class A EVM devices
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to
cause harmful interference in which case the user will be required to correct the interference at his own expense.
FCC Interference Statement for Class B EVM devices
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment
generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause
harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If
this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
For EVMs annotated as IC – INDUSTRY CANADA Compliant
This Class A or B digital apparatus complies with Canadian ICES-003.
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the
equipment.
Concerning EVMs including radio transmitters
This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this
device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired
operation of the device.
Concerning EVMs including detachable antennas
Under Industry Canada regulations, this radio transmitter may only operate using an antenna of a type and maximum (or lesser) gain
approved for the transmitter by Industry Canada. To reduce potential radio interference to other users, the antenna type and its gain should
be so chosen that the equivalent isotropically radiated power (e.i.r.p.) is not more than that necessary for successful communication.
This radio transmitter has been approved by Industry Canada to operate with the antenna types listed in the user guide with the maximum
permissible gain and required antenna impedance for each antenna type indicated. Antenna types not included in this list, having a gain
greater than the maximum gain indicated for that type, are strictly prohibited for use with this device.
Cet appareil numérique de la classe A ou B est conforme à la norme NMB-003 du Canada.
Les changements ou les modifications pas expressément approuvés par la partie responsable de la conformité ont pu vider l’autorité de
l'utilisateur pour actionner l'équipement.
Concernant les EVMs avec appareils radio
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est
autorisée aux deux conditions suivantes : (1) l'appareil ne doit pas produire de brouillage, et (2) l'utilisateur de l'appareil doit accepter tout
brouillage radioélectrique subi, même si le brouillage est susceptible d'en compromettre le fonctionnement.
Concernant les EVMs avec antennes détachables
Conformément à la réglementation d'Industrie Canada, le présent émetteur radio peut fonctionner avec une antenne d'un type et d'un gain
maximal (ou inférieur) approuvé pour l'émetteur par Industrie Canada. Dans le but de réduire les risques de brouillage radioélectrique à
l'intention des autres utilisateurs, il faut choisir le type d'antenne et son gain de sorte que la puissance isotrope rayonnée équivalente
(p.i.r.e.) ne dépasse pas l'intensité nécessaire à l'établissement d'une communication satisfaisante.
Le présent émetteur radio a été approuvé par Industrie Canada pour fonctionner avec les types d'antenne énumérés dans le manuel
d’usage et ayant un gain admissible maximal et l'impédance requise pour chaque type d'antenne. Les types d'antenne non inclus dans
cette liste, ou dont le gain est supérieur au gain maximal indiqué, sont strictement interdits pour l'exploitation de l'émetteur.
【【Important Notice for Users of EVMs for RF Products in Japan】】
This development kit is NOT certified as Confirming to Technical Regulations of Radio Law of Japan
If you use this product in Japan, you are required by Radio Law of Japan to follow the instructions below with respect to this product:
1. Use this product in a shielded room or any other test facility as defined in the notification #173 issued by Ministry of Internal Affairs and
Communications on March 28, 2006, based on Sub-section 1.1 of Article 6 of the Ministry’s Rule for Enforcement of Radio Law of
Japan,
2. Use this product only after you obtained the license of Test Radio Station as provided in Radio Law of Japan with respect to this
product, or
3. Use of this product only after you obtained the Technical Regulations Conformity Certification as provided in Radio Law of Japan with
respect to this product. Also, please do not transfer this product, unless you give the same notice above to the transferee. Please note
that if you could not follow the instructions above, you will be subject to penalties of Radio Law of Japan.
(address) 24-1, Nishi-Shinjuku 6 chome, Shinjuku-ku, Tokyo, Japan
For Feasibility Evaluation Only, in Laboratory/Development Environments. Unless otherwise indicated, this EVM is not a finished
electrical equipment and not intended for consumer use. It is intended solely for use for preliminary feasibility evaluation in
laboratory/development environments by technically qualified electronics experts who are familiar with the dangers and application risks
associated with handling electrical mechanical components, systems and subsystems. It should not be used as all or part of a finished end
product.
Your Sole Responsibility and Risk. You acknowledge, represent and agree that:
1. You have unique knowledge concerning Federal, State and local regulatory requirements (including but not limited to Food and Drug
Administration regulations, if applicable) which relate to your products and which relate to your use (and/or that of your employees,
affiliates, contractors or designees) of the EVM for evaluation, testing and other purposes.
2. You have full and exclusive responsibility to assure the safety and compliance of your products with all such laws and other applicable
regulatory requirements, and also to assure the safety of any activities to be conducted by you and/or your employees, affiliates,
contractors or designees, using the EVM. Further, you are responsible to assure that any interfaces (electronic and/or mechanical)
between the EVM and any human body are designed with suitable isolation and means to safely limit accessible leakage currents to
minimize the risk of electrical shock hazard.
3. Since the EVM is not a completed product, it may not meet all applicable regulatory and safety compliance standards (such as UL,
CSA, VDE, CE, RoHS and WEEE) which may normally be associated with similar items. You assume full responsibility to determine
and/or assure compliance with any such standards and related certifications as may be applicable. You will employ reasonable
safeguards to ensure that your use of the EVM will not result in any property damage, injury or death, even if the EVM should fail to
perform as described or expected.
4. You will take care of proper disposal and recycling of the EVM’s electronic components and packing materials.
Certain Instructions. It is important to operate this EVM within TI’s recommended specifications and environmental considerations per the
user guidelines. Exceeding the specified EVM ratings (including but not limited to input and output voltage, current, power, and
environmental ranges) may cause property damage, personal injury or death. If there are questions concerning these ratings please contact
a TI field representative prior to connecting interface electronics including input power and intended loads. Any loads applied outside of the
specified output range may result in unintended and/or inaccurate operation and/or possible permanent damage to the EVM and/or
interface electronics. Please consult the EVM User's Guide prior to connecting any load to the EVM output. If there is uncertainty as to the
load specification, please contact a TI field representative. During normal operation, some circuit components may have case temperatures
greater than 60°C as long as the input and output are maintained at a normal ambient operating temperature. These components include
but are not limited to linear regulators, switching transistors, pass transistors, and current sense resistors which can be identified using the
EVM schematic located in the EVM User's Guide. When placing measurement probes near these devices during normal operation, please
be aware that these devices may be very warm to the touch. As with all electronic evaluation tools, only qualified personnel knowledgeable
in electronic measurement and diagnostics normally found in development environments should use these EVMs.
Agreement to Defend, Indemnify and Hold Harmless. You agree to defend, indemnify and hold TI, its licensors and their representatives
harmless from and against any and all claims, damages, losses, expenses, costs and liabilities (collectively, "Claims") arising out of or in
connection with any use of the EVM that is not in accordance with the terms of the agreement. This obligation shall apply whether Claims
arise under law of tort or contract or any other legal theory, and even if the EVM fails to perform as described or expected.
Safety-Critical or Life-Critical Applications. If you intend to evaluate the components for possible use in safety critical applications (such
as life support) where a failure of the TI product would reasonably be expected to cause severe personal injury or death, such as devices
which are classified as FDA Class III or similar classification, then you must specifically notify TI of such intent and enter into a separate
Assurance and Indemnity Agreement.
Texas Instruments Incorporated and its subsidiaries (TI) reserve the right to make corrections, enhancements, improvements and other
changes to its semiconductor products and services per JESD46, latest issue, and to discontinue any product or service per JESD48, latest
issue. Buyers should obtain the latest relevant information before placing orders and should verify that such information is current and
complete. All semiconductor products (also referred to herein as “components”) are sold subject to TI’s terms and conditions of sale
supplied at the time of order acknowledgment.
TI warrants performance of its components to the specifications applicable at the time of sale, in accordance with the warranty in TI’s terms
and conditions of sale of semiconductor products. Testing and other quality control techniques are used to the extent TI deems necessary
to support this warranty. Except where mandated by applicable law, testing of all parameters of each component is not necessarily
performed.
TI assumes no liability for applications assistance or the design of Buyers’ products. Buyers are responsible for their products and
applications using TI components. To minimize the risks associated with Buyers’ products and applications, Buyers should provide
adequate design and operating safeguards.
TI does not warrant or represent that any license, either express or implied, is granted under any patent right, copyright, mask work right, or
other intellectual property right relating to any combination, machine, or process in which TI components or services are used. Information
published by TI regarding third-party products or services does not constitute a license to use such products or services or a warranty or
endorsement thereof. Use of such information may require a license from a third party under the patents or other intellectual property of the
third party, or a license from TI under the patents or other intellectual property of TI.
Reproduction of significant portions of TI information in TI data books or data sheets is permissible only if reproduction is without alteration
and is accompanied by all associated warranties, conditions, limitations, and notices. TI is not responsible or liable for such altered
documentation. Information of third parties may be subject to additional restrictions.
Resale of TI components or services with statements different from or beyond the parameters stated by TI for that component or service
voids all express and any implied warranties for the associated TI component or service and is an unfair and deceptive business practice.
TI is not responsible or liable for any such statements.
Buyer acknowledges and agrees that it is solely responsible for compliance with all legal, regulatory and safety-related requirements
concerning its products, and any use of TI components in its applications, notwithstanding any applications-related information or support
that may be provided by TI. Buyer represents and agrees that it has all the necessary expertise to create and implement safeguards which
anticipate dangerous consequences of failures, monitor failures and their consequences, lessen the likelihood of failures that might cause
harm and take appropriate remedial actions. Buyer will fully indemnify TI and its representatives against any damages arising out of the use
of any TI components in safety-critical applications.
In some cases, TI components may be promoted specifically to facilitate safety-related applications. With such components, TI’s goal is to
help enable customers to design and create their own end-product solutions that meet applicable functional safety standards and
requirements. Nonetheless, such components are subject to these terms.
No TI components are authorized for use in FDA Class III (or similar life-critical medical equipment) unless authorized officers of the parties
have executed a special agreement specifically governing such use.
Only those TI components which TI has specifically designated as military grade or “enhanced plastic” are designed and intended for use in
military/aerospace applications or environments. Buyer acknowledges and agrees that any military or aerospace use of TI components
which have not been so designated is solely at the Buyer's risk, and that Buyer is solely responsible for compliance with all legal and
regulatory requirements in connection with such use.
TI has specifically designated certain components as meeting ISO/TS16949 requirements, mainly for automotive use. In any case of use of
non-designated products, TI will not be responsible for any failure to meet ISO/TS16949.
ProductsApplications
Audiowww.ti.com/audioAutomotive and Transportation www.ti.com/automotive
Amplifiersamplifier.ti.comCommunications and Telecomwww.ti.com/communications
Data Convertersdataconverter.ti.comComputers and Peripheralswww.ti.com/computers
DLP® Productswww.dlp.comConsumer Electronicswww.ti.com/consumer-apps
DSPdsp.ti.comEnergy and Lightingwww.ti.com/energy
Clocks and Timerswww.ti.com/clocksIndustrialwww.ti.com/industrial
Interfaceinterface.ti.comMedicalwww.ti.com/medical
Logiclogic.ti.comSecuritywww.ti.com/security
Power Mgmtpower.ti.comSpace, Avionics and Defensewww.ti.com/space-avionics-defense
Microcontrollersmicrocontroller.ti.comVideo and Imagingwww.ti.com/video
RFIDwww.ti-rfid.com
OMAP Applications Processorswww.ti.com/omapTI E2E Communitye2e.ti.com
Wireless Connectivitywww.ti.com/wirelessconnectivity