Telaire T8100NS, T8100NSP Specifications

Ventostat™
®
Amphenol
T8100 NS and NSP Series
CO2 Sensor
Features
• Patented, Absorption Infrared Gas sensing engine provides high accuracy in a compact low cost package.
• Local temperature adjustments with slide pot and night set override control
• Patented ABC Logic™ self-calibration system eliminates the need for manual calibration in most applications.
• Locking screw secures cover and sensor to the mounting bracket for tamper resistance.
• Dual simultaneous analog outputs (V & mA) available for CO
• Sensors are shipped factory calibrated.
.
2
• Lifetime CO using ABC Logic™.
• Mounting plate with two-piece terminal blocks provide quick, easy wiring.
• Gas permeable, water resistant CO filter prevents particulate and water contamination of the sensor.
Advanced Sensors
calibration guarantee when
2
diffusion
2
• Temperature sensor on all models.
• Modern enclosure with customized branding
available.
Ventostat Specifications
Amphenol
Sensing Method
Non-dispersive infrared (NDIR) absorption Gold-plated optics Patented ABC Logic self calibration algorithm
CO2 Measurement Range
T8100 0 to 2000 ppm (0 ppm = 0 V, 4 mA; 2000 ppm = 10/5V, 20 mA)
CO2 Accuracy
±30 ppm or 3% of the reading shown, whichever is higher *
Power Supply Requirements
18-30 VAC RMS, 50/60 Hz, or 18 to 42 VDC, polarity protected
Power Consumption
Typical 0.7 W at nominal voltage of 24V AC RMS
Temperature Dependence
0.2% FS per °C (±0.11% per °F)
Operating Conditions
32°F to 122°F (0°C to 50°C) 0 to 95% RH, non-condensing
Storage Conditions
-40°F to 158°F (-40°C to 70°C)
Flammability Classification
UL94 5VA
Thermistor Type
NTC 10 kW thermistor
Thermistor Accuracy
±1°C (15° to 35°C)
Night Setback Override Button (NS and NSP)
Shorts the thermistor output when depressed
Slide Potentiometer (NSP Only)
Left (stop) 0k Ohms (±5k W) Center 50k Ohms (±7.5k W) Right (stop) 100k Ohms (±10%)
Stability
<2% of FS over life of sensor (15 years)
Pressure Dependence
0.135% of reading per mm Hg
Certifications
CE and RoHS compliant
Signal Update
Every 5 seconds
CO2 Warm-up Time
< 2 minutes (operational) 10 minutes (maximum accuracy)
*C0
accuracy statement excludes standard gas used for
2
calibration that has an accuracy of 2%. In addition, there is a potential digital to analog error of up to 1%.
ABC Logic™ Self Calibration System
ABC Logic™ (Automatic Background Calibration) self calibration allows the sensor to continually recalibrate itself when the indoor concentrations drop to outside levels while the building is unoccupied. Generally a building must be regularly unoccupied for 4 hours or more for this self-calibration system to operate properly. Under these conditions, ABC Logic™ should maintain sensor calibration over the lifetime of the sensor. The ABC Logic™ should be turned OFF where a building is continuously occupied 24 hours per day, or where there could be significant sources of non­occupant related CO2 such as greenhouses, breweries and other industrial and food processing applications.
Output
Analog 0 to 5 V, (100 W output impedance) 0 to 10 V (100 W output impedance) and 4 to 20mA (RL maximum 500 W) available simultaneously for CO2 output
Advanced Sensors
www.amphenol-sensors.com
© 2014 Amphenol Corporation. All Rights Reserved. Specifications are subject to change without notice. Other company names and product names used in this document are the registered trademarks or trademarks of their respective owners.
AAS-920-622A-03/2014