Installing the Sensor
!WARNING!
Before performing service or maintenance operations on
the systems, turn OFF main power switches to the unit.
Electric shock can cause personal injury. Please read and
follow the wiring instructions precisely; miswiring may
cause permanent damage to the product.
Basic Installation
1. Separate the case into its front and rear sections.
2. Secure the rear section of the case to the wall or junction box using
the supplied screws, and make necessary wire connections.
3. Mount the Controller on the base by aligning the top clips and then securing to the bottom clips. Secure the Ventostat with the supplied set screw. A one-minute stabilization warmup will take place.
STRIP GAUGE
2
CO
5V-NC
2
CO
V
OUTPUTS
78
10V-NO
J3
GND
6mm / ¼"
RMS
POWER
18 - 30 VAC
18 - 42 VDC
< 2W PEAK
AC-/DC-
2
AC+/DC+
1
J2
UIP
OPTIONS
Telaire T5100 Series
CO2 Sensor
User Instructions
Internal Label for Voltage Version
J2
UIP
OPTIONS
2
CO
I
GND
OUTPUTS
67
Internal Label for 4-20 mA Version
STRIP GAUGE
6mm / ¼"
RMS
POWER
18 - 30 VAC
18 - 42 VDC
< 2W PEAK
AC-/DC-
2
AC+/DC+
1
T63359-002
March 2014
Page 1 of 4
T5100 Wiring Diagrams
!WARNING!
T5100 products have two terminal pins that are connected
inside the sensor to a common/ground: pin #7 on the I/O
terminal blocks and pin #2 on the power block. Do NOT
connect positive (hot) 24 VAC power line to terminal
number #2 of the terminal block.
Caution!
The T5100 products are either 3-wire or 4-wire type configurations, powered by either AC or DC voltage. They are not 2-wire or loop-powered devices. Wiring the units as 2-wire
or loop-powered devices will irreparably damage the sensors
and void the warranty.
Figure 3: Current Wiring for 4-Wire System - AC Power
Figure 1: Current Wiring for 3-Wire System - AC Power
Figure 2: Voltage Wiring for 3-Wire System - AC Power
Figure 4: Voltage Wiring for 4-Wire System - AC Power
Figure 5: Wiring CO2 Sensor Voltage Output to
Honeywell M7415 Damper Actuator with W7459 Logic
Module
Sensing Duct CO2 Concentrations
Duct-Mounting the Enclosures
T5100 products can be installed inside the return air ductwork, if needed. As an alternative, please consider the T8031 unit. When mounting these products inside the ductwork, seal the hole around the wires and leave the duct insulation in place to prevent condensation which may damage the sensor.
Page 2 Telaire T5100 Series