LED ON 5005
& 5007 MODELS
Measurement & Control Solutions
Mounting the 5000 Series
1. Remove the front cover by pressing the release button located on the
bottom of the cover.
2. Use the appropriate mounting holes and screws to secure the base to
the mounting surface.
3. Pass the wiring through the wiring slot and make the necessary
wiring connections on the 7-pin connector, described below.
Pin Assignments for the 7-Pin Connector
1 – ground
2 – CO2 (0 to 10V)
3 – 24 Volt input
4 – thermistor output
5 – Not Used (Set point potentiometer/PWM output)
6 – Not Used (LED override input)
Telaire Airestat 5000 Series CO2/Temperature Sensors
(Models 5001, 5003, 5005 and 5007)
User Instructions
7 – Not used (Bypass)
LED Indicator (Models T5005 and T5007)
The LED has three colors (red, yellow, and green) indicating particular
PPM levels:
Green - CO
concentration is within acceptable limits.
Yellow - CO
hysteresis. As CO2 levels decrease to within acceptable limits ,the
yellow light will remain on until 100 ppm past the threshold, and return
to green at 900 ppm.
Red - CO
is beyond acceptable limits. As CO
red light will remain on until 100 ppm past the threshold, and turn back
to yellow at 1400 ppm.
levels are less than 1000 ppm, indicating CO2
2
levels between 1000 and 1500 ppm, with 100 ppm
2
levels are above 1500 ppm, indicating the CO2 concentration
2
levels decrease to within limits, the
2
Calibration and ABC Logic™
The Airestat sensor is factory set with the ABC Logic™ (Automatic
Background Calibration) self calibration feature ON. This feature allows
the sensor to continually re-calibrate itself when the indoor
concentrations drop to outside levels while the building is unoccupied.
Generally, a building must be regularly unoccupied for 4 hours or more
for this self-calibration system to operate properly. Under these
conditions, the ABC Logic™ feature should maintain sensor calibration
over the lifetime of the sensor. The ABC Logic™ feature should be
turned OFF where a building is continuously occupied 24 hours per day,
or where there could be significant sources
CO
2 such as greenhouses, breweries and other industrial and food
of non-occupant related
processing applications.
Warranty
GE Measurement & Control Solutions-Telaire Products will repair a
product that fails to meet the terms provided in the Limited warranty
policy statement. Actual warranty period is 18 months and starts from
the date of manufacture from GE’s facility or point of origin, and varies
based on product category and type of equipment. For all warranty
repairs, GE will cover parts, labor, and standard (ground) shipping
charges.
This product is covered by one or more of the following patents:
5,650,624/5,721,430/5,444,249/5,747,808/5,834,777/5,163,332/
5,340,986/5,502,308/6,344,798/6,023,069/5,370,114/5,601,079/
5,691,704/5,767,776/5,966,077/6,107,925/5,798,700/5,945,924/
5,592,147/6,255,653/6,250,133/6,285,290
T63136-004
September 2011
Page 1 of 2
USA
6860 Cortona Drive
Goleta, CA 93117
Telephone: 805-685-4000
Fax: 805-685-0015
1100 Technology Park Drive
Billerica, MA 01821-4111
Telephone: 800-833-9438
978-437-1000
Fax: 502-479-6722
Web: www.ge-mcs.com
Page 2 Telaire Airestat 5000