Accessory Enclosures
For the Ventostat 8000 Series
Outside Air
Splash Resistant Enclosure
Telaire® offers three accessory enclosures
that are designed enhance the 8000
Series Ventostat® CO2 Sensor/Controller
in specialized applications.
Model 1508 Aspiration Box:
Designed for in-duct sampling of CO2 in
flow rates greater than 400 fpm.
Model 1505 Splash Resistant Enclosure:
Designed to protect the 8000 series in
damp or wet environments as might occur
in agricultural, industrial or food processing environments.
Duct Mount Aspiration Box
Shown with
Sensor Installed
Model 1551 Outdoor Air Enclosure:
A weatherproof enclosure designed to
allow the 8000 series sensor to operate in
an outdoor environment and/or where
ambient temperatures are below freezing.
Ideal for monitoring outside air or CO2 as a
surrogate for combustion fumes in parking
garages, tunnels and loading docks.
Enclosures are sold separately from CO2
sensor/controllers
F0144-1
A Division of Edwards Systems Technology

PinDesignations
1.AC+
/
DC+
2.AC-
/
GND
1508 Aspiration Box
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
The Model 1508 is designed for
in-duct sampling of CO2 concentrations at flow rates greater
than 400 fpm. Clear cover allows for observation of the sensor. Will accommodate any wall mount model of
Telaire® Ventostat® 8000 series. Enclosure is
screwed to the duct with probe inserted into
airstream. Air sampling probe is 1 in diameter and 8 long. Enclosure (ABS plastic) has
knockouts for conduit connection. Note:
Wiring penetrations must be sealed prior to
use. CO
2 sensor not included.
Tubing on 1508 Only
1505 Splash Resistant Enclosure:
The Model 1505 is designed to
protect the 8000 series in damp or
wet environments as might occur in
agricultural, industrial or food processing environments. This enclosure (ABS
plastic) is designed to protect the sensor from
dripping or sprayed water. Any wall mount
model of the Telaire® 8000 series sensor can
be installed inside the enclosure. The transparent cover allows for viewing of the sensor/
display. Four diffusion ports allow for entry of
CO2. Knockouts are provided for conduit
connection. Response time of the sensor is
slowed to approximately 30 minutes to measure a 90% step change in concentrations.
Enclosure is designed to screw directly to a
wall. CO
2 sensor not included.
1551 Outside Air Enclosure:
The Model 1551 is a rugged weatherproof enclosure (ABS plastic), designed to allow the 8000 series
sensor to operate in an outdoor environment and/or where ambient temperatures are below freezing. The 1551 is ideal for
monitoring outside air or CO2 as a surrogate
for combustion fumes in parking garages, tunnels and loading docks. This enclosure features a temperature control circuit and
internal heaters to maintain the sensor within
its normal operating temperature range, even
if temperatures outside the enclosure are as
low as -20 F (-29°C). Four diffusion ports allow
for entry of CO2. Response time of the sensor is
slowed to approximately 30 minutes to measure a 90% step change in concentrations.
Enclosure is designed to screw directly to a
wall. CO2 sensor not included.
Power Consumption: 24V, 1.5 Amp (max) including Ventostat® 8000 series
Cross Reference: The Model 1551 Outside
Air Enclosure combined with a Telaire
Ventostat® 8000 series meets or exceeds the
performance requirements of the Telaire
®
®
Model 2051 Outside Air Enclosure.
PinDesignations
1.Not Used
2.Not Used
3.Relay Norm
4.Relay Common
5.Relay Norm
6.4-20mA Output
7.Signal Ground
8.0-10V Output
PinDesignations
Open
1.AC+ / DC+
2.AC- / GND
Closed
PowerRequirem
18-36VAC
18-42VDC
100m
70
m
A
A
Peak,
avg@
rmsor
ent
24
s
VDC
Products Compatible with
Accessory Enclosures
8001 8001B
8002 8002B
®
8101 8101B
8102 8102B
Mounting Bracket
(Pre-Installed on the 1551)
8502
6 1/2"
Cover Removed
3 3/4"
4 1/4"
Spouts on
1505 and 1551 Only
7"
Any of the Ventostat
8000 Series Sensors
3.5"
10 1/2”
Cover
Extension Tube
on 1508 Only
1 1/8" and 1 1/16"
7/8"
6489 Calle Real Goleta, CA 93117
805.964.1699 FAX 805.964.2129
1-800-472-6075 - www.telaire.com
It is our intention to keep the product information
1 1/8"
7”
current and accurate. We can not cover specific applications or anticipate all requirements.
All specifications are subject to change without
notice. For more information or questions relative to this Specification Sheet, contact Telaire.
©
Copyright 1998-2000 Telaire
Covered by United States Patents:
5,060,508 and 5,163,332