Telaire Airestat 5030, Airestat 5031 Specifications

GE
Sensing
Telaire Accessories
Telaire accessories are part of the Telaire product line. Telaire has joined other GE high-technology sensing businesses under a new name–GE Industrial, Sensing.
g
Calibration Kits, Enclosures, Software, Cables
Calibration Kits
The Calibration Kit Model 2075 includes all of the necessary components for calibrating the Telaire®7001 and Ventotstat 8000 and 8100 series models. The kit is housed in a carrying case with only one replacement part (calibration gas) required. Each 16 liter gas bottle can perform up to 20 calibrations. Calibration Kit Model 2076 calibrates the Vaporstat 9002.
Accessory Enclosures
GE Sensing offers three enclosures to expand the Ventostat and Vaporstat installation options: Model 1508 Aspiration Box, Model 1505 Splash Resistant Enclosure, Model 1551 Outdoor Air Enclosure.
Software
Windows based VG Graphing Software allows you to easily download your IAQ measurements and customize graphs.
2080 CO
2
View Logging Software
CO2View is a Windows based program that interfaces with the 8000 and 7000 series sensors. This easy to use program displays and graphs real-time CO2levels at a user adjustable interval.
UIP 2072
Make adjustments and modify your 8000 series CO
2
sensor parameters.
7001 Accessories
The Telaire 7001 hand held CO
2
and temperature monitor is equipped with an output for recording data. The cable, Model 2070, can be used with devices that accept a 0 to 4V signal
A relative humidity and datalogging kit with graphing software, Model 2077, is available to long term monitoring.
Part 62933 is an adapter for international operation.
GE
Sensing
Calibration Process
The calibration is simple and can be done in just a few minutes. Each CO2model has a calibration process similar to the following:
• Connect the tubing assembly to the sensor and connect the regulator to the gas bottle.
• Initiate the calibration process by using the sensor buttons and display.
• The process is automatically run by the sensor and will signal upon completion.
• Last, disconnect the tubing and gas regulator.
2075 Components
The Calibration Kit Model 2075 includes:
• Instruction sheet
• One bottle of nitrogen gas
• Tubing assembly
• Gas regulator with guage
• Carrying case.
Calibrates the following models:
• Ventostat 8000 and 8100 Series
• Telaire 7000 Series
The illustration shows the complete set-up for
calibrating a sensor with display.
2076 Components
The Calibration Kit Model 2076 includes:
• Instruction sheet
• One bottle of pure nitrogen gas
• Tubing assembly
• Gas regulator with guage
• Carrying case.
• Flow Meter
Calibrates the following models:
• Vaporstat 9002
Calibration Kits 2075 and 2076
combustion fumes in parking garages, tunnels and loading docks. This enclosure features a temperature control circuit and internal heaters to maintain the sensor within its normal operating temperature range, even if temperatures outside the enclosure are as low as –20°F (-29°C). Four diffusion ports allow for entry of CO2. Response time of the sensor is slowed approximately 30 minutes to measure a 90% step change in concentrations. Enclosure is designed to screw directly to a wall. CO2sensor not included.
Power consumption
24V, 1.5 Amp (maximum) – including sensor
Enclosures are compatible with all Ventostat 8000 series (except the 8003 and 8009) and Vaporstat 9002 models.
1508 Aspiration Box
The Model 1508 is designed for in-duct sampling of CO
2
concentrations at flow rates greater than 400 fpm. Clear cover allows for observation of the sensor. Enclosure is screwed to the duct with probe inserted into airstream. Air sampling probe is 1 in (25.4 mm) diameter and 8 in (203.2 mm) long. Enclosure (ABS plastic) has knockouts for conduit connection. CO2Sensor not included.
1505 Splash Resistant Enclosure
The Model 1505 is designed to protect the sensor in damp or wet environments which might occur in agricultural, industrial or food processing environments. This enclosure (ABS plastic) is designed to protect the sensor from dripping or sprayed water. The transparent cover allows for viewing of the sensor/display. Four diffusion ports allow for entry of CO
2
. Knockouts are provided for conduit connection. Response time of the sensor is slowed to approximately 30 minutes to measure a 90% step change in concentrations. Enclosure is designed to screw directly to a wall. CO2sensor not included.
1551 Outside Air Enclosure
The Model 1551 is a rugged weatherproof enclosure (ABS plastic), designed to allow the 8000 series sensor to operate in an outdoor environment and/or where ambient temperatures are below freezing. The 1551 is ideal for monitoring outside air or CO2as a surrogate for
Pin
Designations
1. AC+
/ DC+
2. AC-
/ GN D
GE
Sensing
Enclosures Specifications
Tubing on 1508 Only
PinD
1.NotU
2.NotU
3.R
4.R
esignations
5.R elayNorm
6.4-20mA sed
elayCom
7.Signal sed
elay
8.0-10V
N orm
Pin
Open
Ground
mon
Output
1.AC+/D Output
2. Closed
Designation
AC-/GN
Po
18
w
18-42
-36
100
er
70
C+
R
VA
m
D
m
equ
VDC
A
C
A
s
Peak,
avg
rms
ire m
@
or
e nt
2
s
4VDC
Mounting Bracket
(Pre-Installed on 1551)
Any of the Ventostat 8000 Series Sensors
Cover
Spouts on
1505 and 1551 Only
7 in
(177.8 mm)
3.5 in (88.9 mm)
10.5 in (266.7mm)
Extension Tube
on 1508 Only
1.13 in (28.7 mm)
1.13 in (28.7 mm) and 1.7in (43.18 mm)
0.88 in (22.35 mm)
7 in (177.8 mm)
6.5 in (165.1 mm)
Cover Removed
3.75 in (95.25 mm)
4.25 in (107.95 mm)
Loading...