INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-3039-003R
2251-COPTIR Intelligent Photoelectric
3825 Ohio Avenue, St. Charles, Illinois 60174
Multi-Criteria Smoke Sensor
SPECIFICATIONS
Operating Voltage Range: 15 to 32 VDC
Standby Current: 300µA @ 24 VDC (one communication every 5 sec. with LED blink enabled)
Max. Alarm Current (LED on:) 7 mA @ 24 VDC
Operating Humidity Range: 10% to 93% Relative Humidity, Non-condensing
Operating Temperature Range: 0°C to 38°C (32°F to 100°F)
Height: 2.7˝ (69 mm) installed in B210LP Base
Diameter: 6.0˝ (155 mm) installed in B210LP Base; 4.0˝ (102 mm) installed in B501 Base
Weight: 4.6 oz. (130 g)
BEFORE INSTALLING
This sensor must be installed in compliance with the control panel system
installation manual. The installation must meet the requirements of the
Authority Having Jurisdiction (AHJ). Sensors offer maximum performance
when installed in compliance with the National Fire Protection Association
(NFPA); see NFPA 72.
GENERAL DESCRIPTION
Model 2251-COPTIR is a plug-in type smoke sensor that is a photoelectronic
sensing chamber combined with carbon monoxide (CO), thermal, infra-red
(IR) sensors and addressable-analog communications. The sensors transmit
an analog representation of smoke density over a communication line to a
control panel. Rotary-decade switches are provided for setting the sensor’s
address.
Two LEDs on the sensor are controlled by the panel to indicate sensor status. An output is provided for connection to an optional remote LED annunciator (P/N RA100Z /RA400Z).
The 2251-COPTIR requires compatible addressable communications to
function properly. Connect these sensors to listed-compatible control panels only.
SPACING
System Sensor recommends spacing sensors in compliance with NFPA 72.
In low air flow applications with smooth ceilings, space sensors 30 feet
apart. For specific information regarding sensor spacing, placement, and
special applications, refer to NFPA 72 or the System Smoke Detector Applica-
tion Guide, available from System Sensor.
TAMPER-RESISTANCE
Models 2251-COPTIR includes a tamper-resistant capability that prevents
removal from the bracket without the use of a tool. Refer to the base manual for details on making use of this capability.
WIRING GUIDE
All wiring must be installed in compliance with the National Electrical
Code, applicable local codes, and any special requirements of the Authority
Having Jurisdiction. Proper wire gauges should be used. The installation
wires should be color-coded to limit wiring mistakes and ease system troubleshooting. Improper connections will prevent a system from responding
properly in the event of a fire.
Remove power from the communication line before installing sensors.
1. Wire the sensor base (supplied separately) per the wiring diagram, see
Figure 1.
2. Set the desired address on the sensor address switches, see Figure 2.
3. Install the sensor into the sensor base. Push the sensor into the base
while turning it clockwise to secure it in place.
4. After all sensors have been installed, apply power to the control unit
and activate the communication line.
5. Test the sensor(s) as described in the TESTING section of this manual.
Dust covers provide limited protection against airborne dust particles during shipping. Dust covers must be removed before the sensors can sense
smoke. Remove sensors prior to heavy remodeling or construction.
FIGURE 1. WIRING DIAGRAM:
REMOTE ANNUNCIATOR
+ –
+
3
CONTROL PANEL
–
UL LISTED COMPATIBLE
–
+
2
1
OPTIONAL RETURN LOOP
FIGURE 2. ROTARY DECADE ADDRESS SWITCHES:
7
8
6
5
9
4
3
2
1
0
TESTING
Before testing, notify the proper authorities that the system is undergoing
maintenance, and will temporarily be out of service. Disable the system to
prevent unwanted alarms.
All sensors must be tested after installation and periodically thereafter. Testing
methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors offer
maximum performance when tested and maintained in compliance with NFPA
72.
The sensor can be tested in the following ways:
A. Functional: Magnet Test (P/N M02-04-01 or M02-09-00)
This sensor can be functionally tested with a test magnet. The test
magnet electronically simulates smoke in the sensing chamber, testing
the sensor electronics and connections to the control panel.
1. Hold the test magnet in the magnet test area as shown in Figure 3.
2. The sensor should alarm the panel.
Two LEDs on the sensor are controlled by the panel to indicate sensor
status. Coded signals, transmitted from the panel, can cause the LEDs
to blink, latch on, or latch off. Refer to the control panel technical
documentation for sensor LED status operation and expected delay to
alarm.
B. Smoke Entry: Aerosol Generator (Gemini 501) or Canned Aerosol
The GEMINI model 501 aerosol generator can be used for smoke entry
testing. Set the generator to represent 4%/ft to 5%/ft obscuration as
described in the GEMINI 501 manual. Using the bowl shaped applicator, apply aerosol until the panel alarms.
Additionally, canned aerosol simulated smoke (canned smoke agent)
may be used for smoke entry testing of the smoke detector. Tested and
approved aerosol smoke products are the Smoke Detector Tester model
25S available from Home Safeguard Industries and Chekkit Smoke Detector Tester models CHEK02 and CHEK06 available from SDi. When
used properly, the canned smoke agent will cause the smoke detector
to go into alarm. Refer to the manufacturer’s published instructions
for proper use of the canned smoke agent.
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
CAUTION: DO NOT LOOP WIRE
UNDER TERMINAL 1 OR 2.
BREAK WIRE RUN TO PROVIDE
SUPERVISION OF CONNECTIONS.
2
3
1
C0100-01
7
8
6
5
9
4
3
2
1
0
C0146-00
D200-29-00 1 I56-3039-003R
Canned aerosol simulated smoke (canned smoke agent) formulas will vary by
manufacturer. Misuse or overuse of these products may have long term adverse effects on the smoke detector. Consult the canned smoke agent manufacturer’s published instructions for any further warnings or caution statements.
For 2251-COPTIR, smoke entry testing should be performed immedi-
ately following the magnet test. Magnet test initiates an approximately
10 minute period when the detector’s signal processing software routines are not active. Failure to first perform the magnet test will introduce a time delay before the detector alarms.
C. Multi-Criteria Method
The Testifire® model 2001 Multi-Stimulus Detector Tester by SDi/No
Climb Products, Ltd can be used to test the 2251-COPTIR in multicriteria mode. This tester is capable of introducing smoke, heat and
carbon monoxide either sequentially or simultaneously. Follow the
manufacturer’s recommendations for proper testing and operation of
the Testifire unit.
D. Direct Heat Method (Hair Dryer of 1000-1500 watts)
A hair dryer of 1000-1500 watts should be used to test the thermistors.
Direct the heat toward either of the two thermistors, holding the heat
source approximately 12 inches from the detector in order to avoid damaging the plastic housing. The detector will reset only after it has had sufficient time to cool. Make sure both thermistors are tested individually.
A sensor that fails any of these tests should be cleaned as described under
CLEANING, and retested. If the sensor fails after cleaning, it must be replaced.When testing is complete, restore the system to normal operation
and notify the proper authorities that the system is back in operation.
CLEANING
Before removing the detector, notify the proper authorities that the smoke
detector system is undergoing maintenance and will be temporarily out of
service. Disable the zone or system undergoing maintenance to prevent unwanted alarms.
1. Remove the sensor to be cleaned from the system.
2. Remove the sensor cover. Use a small flat blade screwdriver to gently
release each of the four cover removal tabs that hold the cover place.
Use caution to avoid damaging the thermistors and other sensors
3. Carefully vacuum the outside of the anti insect screen without removing it from the detector cover.
4. The chamber cover, CO and IR sensors may be removed as a single
assembly. Gently pull the assembly away from the sensing chamber
being careful neither to damage the thermistors, the IR / CO sensor
PCB nor to strain the connector cable to the PCB, then gently folded
away from the optical chamber.
5. Use a vacuum cleaner and/or clean compressed air to remove dust
and debris from the sensing chamber and sensing chamber cover.
6. Re-install the sensing chamber cover assembly by sliding the cover
over the chamber, gently pressing it home until it snaps into place.
7. Re-install the sensor cover. Use the cover removal tabs, LEDs and
thermistors to align the cover with the sensor. Snap the cover into
place.
8. When all sensors have been cleaned and re-installed, restore power to
the loop and test the sensor(s) as described under TESTING.
After completion of maintenance and testing, notify the proper authorities
that the system is operational.
CO SENSOR LIFETIME
The CO cell has an expected lifetime of approximately six years. The detector is programmed to signal the approach of end of this lifetime to the control panel. The CO cell is not a field replaceable component and on failure,
you should contact the system supplier to arrange for replacement of the
cell or the detector itself.
FIGURE 3. TEST MAGNET POSITION:
TEST
MAGNET
C0951-00
FIGURE 4. SENSOR ASSEMBLY:
SENSOR COVER
IR
COVER
REMOVAL
TABS
THERMISTORS
DETECTOR BASE
SENSOR
CO
SENSOR
OPTICAL
CHAMBER
COVER
OPTICAL
CHAMBER
BASE
C0952-00
SPECIAL NOTE REGARDING SMOKE DETECTOR GUARDS
Smoke detectors are not to be used with detector guards unless the combination has been evaluated and found suitable for that purpose.
Please refer to insert for the Limitations of Fire Alarm Systems
System Sensor warrants its enclosed smoke detector to be free from defects in materials and workmanship under normal use and service for a period of three years from
date of manufacture. System Sensor makes no other express warranty for this smoke
detector. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s
obligation of this Warranty shall be limited to the repair or replacement of any part
of the smoke detector which is found to be defective in materials or workmanship
under normal use and service during the three year period commencing with the date
of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-
7672) for a Return Authorization number, send defective units postage prepaid to:
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device
must accept any interference received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed
and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the
user is encouraged to try to correct the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
D200-29-00 2 I56-3039-003R
©2010 System Sensor
THREE-YEAR LIMITED WARRANTY
System Sensor, Returns Department, RA #__________, 3825 Ohio Avenue, St. Charles,
IL 60174. Please include a note describing the malfunction and suspected cause of
failure. The Company shall not be obligated to repair or replace units which are found
to be defective because of damage, unreasonable use, modifications, or alterations
occurring after the date of manufacture. In no case shall the Company be liable for
any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s
negligence or fault. Some states do not allow the exclusion or limitation of incidental
or consequential damages, so the above limitation or exclusion may not apply to you.
This Warranty gives you specific legal rights, and you may also have other rights
which vary from state to state.
FCC STATEMENT