D200-80-00 1 I56-1236-03R
2251 and 2251T Intelligent
Photoelectronic Smoke Sensors
INSTALLATION AND MAINTENANCE INSTRUCTIONS
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Before Installing
This sensor must be installed in compliance with the control panel system installation manual. The installation must
meet the requirements of the Authority Having Jurisdiction
(AHJ). Sensors offer maximum performance when installed
in compliance with the National Fire Protection Association
(NFPA); see NFPA 72.
General Description
Model 2251 is a plug-in type smoke sensor that combines a
photoelectronic sensing chamber with addressable-analog
communications. The sensor transmits an analog representation of smoke density over a communication line to a
control panel. Rotary-decade switches are provided for setting the sensor’s address. Two LEDs on the sensor are controlled by the panel to indicate sensor status. An output is
provided for connection to an optional remote LED annunciator (P/N RA400Z). Model 2251T features a fixed temperature (135°F) heat detector.
The 2251 and 2251T require compatible addressable
communications to function properly. Connect these
sensors to listed-compatible control panels only.
Spacing
System Sensor recommends spacing sensors in compliance
with NFPA 72. In low air flow applications with smooth
ceilings, space sensors 30 feet apart. For specific information regarding sensor spacing, placement, and special
applications, refer to NFPA 72 or the System Sensor Guide
For Proper Use of System Smoke Detectors, available at no
charge from System Sensor (P/N I56-407-XX).
Specifications
Operating Voltage Range: 15 to 32 VDC
Standby Current: 300
µA @ 24 VDC (one communication every 5 sec. with LED blink enabled)
Max. Alarm Current (LED on:) 6.5 mA @ 24 VDC
Operating Humidity Range: 10% to 93% Relative Humidity, noncondensing
Operating Temperature Range: 0° to 49°C (32° to 120°F); 2251
Operating Temperature Range: 0° to 38°C (32° to 100°F); 2251T
Heat Sensor: 135°F Fixed Temperature Electronic Thermistor
Height: 1.7 inches (43 mm) installed in B210LP Base
Diameter: 6.1 inches (155 mm) installed in B210LP Base
4.1 inches (104 mm) installed in B501 Base
Weight: 3.6 oz. (102 g)
Additional Bases Available: All 200/500 Series bases are compatible.
Duct Applications: 2251 and 2251T are listed for use in
ducts. See Duct Applications Guide A05-1004-XX for details
on pendant mount applications. Note: These products are
not listed for use inside duct smoke detectors.
Wiring Instructions
All wiring must be installed in compliance with the
National Electrical Code, applicable local codes, and any
special requirements of the Authority Having Jurisdiction.
Proper wire gauges should be used. The installation wires
should be color-coded to limit wiring mistakes and ease
system troubleshooting. Improper connections will prevent
a system from responding properly in the event of a fire.
Remove power from the communication line before
installing sensors.
All wiring must conform to applicable local codes, ordinances, and regulations.
1. Wire the sensor base (supplied separately) per the
wiring diagram, see Figure 1.
2. Set the desired address on the sensor address switches,
see Figure 2.
3. Install the sensor into the sensor base. Push the sensor
into the base while turning it clockwise to secure it in
place.
4. After all sensors have been installed, apply power to the
control unit and activate the communication line.
5. Test the sensor(s) as described in the TESTING section
of this manual.