System Sensor 2251, 2251T User Manual

D200-80-00 1 I56-1236-03R
2251 and 2251T Intelligent Photoelectronic Smoke Sensors
INSTALLATION AND MAINTENANCE INSTRUCTIONS
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Before Installing
General Description
Model 2251 is a plug-in type smoke sensor that combines a photoelectronic sensing chamber with addressable-analog communications. The sensor transmits an analog represen­tation of smoke density over a communication line to a control panel. Rotary-decade switches are provided for set­ting the sensors address. Two LEDs on the sensor are con­trolled by the panel to indicate sensor status. An output is provided for connection to an optional remote LED annun­ciator (P/N RA400Z). Model 2251T features a fixed tem­perature (135°F) heat detector.
The 2251 and 2251T require compatible addressable communications to function properly. Connect these sensors to listed-compatible control panels only.
Spacing
System Sensor recommends spacing sensors in compliance with NFPA 72. In low air flow applications with smooth ceilings, space sensors 30 feet apart. For specific informa­tion regarding sensor spacing, placement, and special applications, refer to NFPA 72 or the System Sensor Guide For Proper Use of System Smoke Detectors, available at no charge from System Sensor (P/N I56-407-XX).
Specifications
Operating Voltage Range: 15 to 32 VDC Standby Current: 300
µA @ 24 VDC (one communication every 5 sec. with LED blink enabled) Max. Alarm Current (LED on:) 6.5 mA @ 24 VDC Operating Humidity Range: 10% to 93% Relative Humidity, noncondensing Operating Temperature Range: 0° to 49°C (32° to 120°F); 2251 Operating Temperature Range: 0° to 38°C (32° to 100°F); 2251T Heat Sensor: 135°F Fixed Temperature Electronic Thermistor Height: 1.7 inches (43 mm) installed in B210LP Base Diameter: 6.1 inches (155 mm) installed in B210LP Base
4.1 inches (104 mm) installed in B501 Base Weight: 3.6 oz. (102 g) Additional Bases Available: All 200/500 Series bases are compatible.
Duct Applications: 2251 and 2251T are listed for use in ducts. See Duct Applications Guide A05-1004-XX for details on pendant mount applications. Note: These products are not listed for use inside duct smoke detectors.
Wiring Instructions
All wiring must be installed in compliance with the National Electrical Code, applicable local codes, and any special requirements of the Authority Having Jurisdiction. Proper wire gauges should be used. The installation wires should be color-coded to limit wiring mistakes and ease system troubleshooting. Improper connections will prevent a system from responding properly in the event of a fire.
Remove power from the communication line before installing sensors.
All wiring must conform to applicable local codes, ordi­nances, and regulations.
1. Wire the sensor base (supplied separately) per the wiring diagram, see Figure 1.
2. Set the desired address on the sensor address switches, see Figure 2.
3. Install the sensor into the sensor base. Push the sensor into the base while turning it clockwise to secure it in place.
4. After all sensors have been installed, apply power to the control unit and activate the communication line.
5. Test the sensor(s) as described in the TESTING section of this manual.
D200-80-00 2 I56-1236-03R
Dust covers provide limited protection against airborne dust particles during shipping. Dust covers must be removed before the sensors can sense smoke. Remove sen­sors prior to heavy remodeling or construction.
Testing
Before testing, notify the proper authorities that the system is undergoing maintenance, and will temporarily be out of service. Disable the system to prevent unwanted alarms.
All sensors must be tested after installation and periodical­ly thereafter. Testing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors offer maximum per­formance when tested and maintained in compliance with NFPA 72.
The sensor can be tested in the following ways: A. Functional: Magnet Test (P/N M02-04-01 or M02-09-00)
This sensor can be functionally tested with a test mag­net. The test magnet electronically simulates smoke in the sensing chamber, testing the sensor electronics and connections to the control panel.
1. Hold the test magnet in the magnet test area as shown in Figure 3.
2. The sensor should alarm the panel. Two LEDs on the sensor are controlled by the panel to indicate sensor status. Coded signals, transmitted from the panel, can cause the LEDs to blink, latch on, or latch off. Refer to the control panel technical doc­umentation for sensor LED status operation and expected delay to alarm.
CAUTION
A78-2461-00
3
2
1
3
2
1
+
+
UL LISTED COMPATIBLE
CONTROL PANEL
OPTIONAL RETURN LOOP
REMOTE ANNUNCIATOR
+–
B. Smoke Entry: Aerosol Generator (Gemini 501)
The GEMINI model 501 aerosol generator can be used for smoke entry testing. Set the generator to represent 4%/ft to 5%/ft obscuration as described in the GEMINI 501 manual. Using the bowl shaped applicator, apply aerosol until the panel alarms.
C. Direct Heat Method (Hair Dryer of 1000-1500 watts)
2251T only A hair dryer of 1000-1500 watts should be used to test the thermistors. Direct the heat toward either of the two thermistors, holding the heat source approximately 12 inches from the detector in order to avoid damaging the plastic housing. The detector will reset only after it has had sufficient time to cool. Make sure both thermistors are tested individually.
A sensor that fails any of these tests should be cleaned as described under CLEANING, and retested. If the sensor fails after cleaning, it must be replaced and returned for repair.
When testing is complete, restore the system to normal operation and notify the proper authorities that the system is back in operation.