System Sensor 2151 User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
WARNING
2151 Low Profile Photoelectronic Plug-in Smoke Detector
Specifications
Size Height: 1.7 inches (43 mm) Diameter: 4.0 inches (101 mm) Weight: 3.6 oz. (102 g) Operating Temperature Range: 0°C to 49°C (32°F to 120°F) Operating Humidity Range: 10% to 93% Relative Humidity noncondensing Latching Alarm: Reset by momentary power interruption.
Please thoroughly read the System Sensor manual A05­1003, Applications Guide for System Smoke Detectors, which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available from System Sensor.
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: The detector used with this base must be tested and maintained regularly following NFPA 72 require­ments. The detector used with this base should be cleaned at least once a year.
this smoke detector, including 2-wire applications with and without relays and/or current limiting resistors, 4-wire and 120VAC applications.
All bases are provided with screw terminals for power, ground, remote annunciator connections and relay contact connections, if applicable. The electrical ratings for each detector-base combination are also included in the base installation instructions.
Installation
NOTE: All wiring must conform to applicable local codes,
ordinances, and regulations.
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
General Description
The 2151 low-profile photoelectronic detector uses a state­of-the-art optical sensing chamber. This detector is designed to provide open area protection and to be used with com­patible UL listed control panels only. The capability of plug­ging this detector into a variety of special bases makes it more versatile than equivalent direct-wired models.
Two LEDs on each detector provide local 360° visible alarm indication. They flash every ten seconds indicating that power is applied and the detector is working properly. The LEDs latch on in alarm. Remote LED annunciator capability is standard and may be implemented through an optional accessory RA400Z. The alarm can be reset only by a momentary power interruption. This detector may be tested by activating the internal reed switch with a magnet.
Base Selection And Wiring Guide
Refer to the installation instructions for the Plug-in Detector Bases for base selection and wiring instructions. System Sensor has a variety of detector bases available for
NOTE: Verify that all detector bases are installed, that
the initiating-device circuits have been tested, and that the wiring is correct. (Refer to detector base manual for testing procedure.)
Remove power from initiating-device circuits before install­ing detectors.
1. Install detectors: a. Place the detector into the detector base. b. Turn the detector clockwise until the detector drops
into place.
c. Continue turning detector clockwise to lock it in
place.
2. Tamper Resistance: The detector bases can be made tam­per resistant. When capability is enabled, detectors can­not be removed from the base without the use of a tool. See the detector base installation manual of the detector base for details in using this capability.
3. After all detectors have been installed, apply power to the control unit.
D100-04-00 1 I56-581-07R
4. Test the detector using the magnet as described under
CAUTION
CAUTION
LED
LED
EST MODULE
SOCKET
TES
T
MA
G
NE
T
PAINTED
SURFACE
TESTING.
5. Reset the detector at the system control panel.
6. Notify the proper authorities that the system is back on line.
A. Test Magnet (p/n M02-04-01 or M02-09-00)
1. Place the magnet against the cover in the location designated by the raised mark to activate the test fea ture (see Figure 1).
2. The LEDs should latch ON within 5 seconds indicat­ing alarm and annunciating the panel.
-
Dust covers are an effective way to limit the entry of dust into smoke detector sensing chambers. However, they may not completely prevent airborne dust particles from enter­ing the detector. Therefore, System Sensor recommends the removal of detectors before beginning construction or other dust producing activity.
Be sure to remove the dust covers from any sensors that were left in place during construction as part of returning the system to service.
Smoke detectors are not to be used with detector guards unless the combination has been evaluated and found suitable for that purpose.
Testing
Before testing, notify the proper authorities that the smoke detector system is undergoing maintenance and will tem­porarily be out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms. Detectors must be tested after installation and as part of periodic maintenance. Test the 2151 as follows:
NOTE: Before testing the detector, check to ensure the
LEDs blink. If they do not, the detector has lost power (check the wiring) or it is defective (return it for repair).
B. Test Module ( MOD400R) Use the MOD400R with a DMM or voltmeter to check
the detector sensitivity as described in the MOD400R manual.
C. Aerosol Generator (Gemini 501) Set the generator to represent 4% to 5%/ft. obscuration
as described in the Gemini 501 Manual. Using the bowl­shaped applicator, apply aerosol until unit alarms.
Notify the proper authorities that the system is back on line.
Detectors that fail these tests should be cleaned as described under MAINTENANCE and retested. If the detectors still fail these tests, they should be returned for repair.
Maintenance
It is recommended that the detector be removed from its mounting base to facilitate cleaning. The detector is cleaned as follows:
NOTE: Before removing the detector, notify the proper
authorities that the smoke detector system is undergoing maintenance and will be temporarily out of service. Disable the zone or system undergo­ing maintenance to prevent unwanted alarms.
Figure 1. Bottom and side views showing position of test magnet:
D100-04-00 2 I56-581-07R
C0627-00
Loading...
+ 2 hidden pages