System Sensor 2112TL, 1112/24B, 1112/24BA Installation And Maintenance Instructions Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
2112TL Photoelectronic
3825 Ohio Avenue, St. Charles, Illinois 60174
Smoke Detector
Specifications
Diameter: 5.5 inches (140 mm) Height (including mounting bracket): 1.7 inches (43 mm) Weight: 5.3 oz. (150 g)
Operating Temperature Range: 32° to 100°F (0° to 37.7°C)
Operating Humidity Range: 10% to 93% relative humidity, noncondensing Latching Alarm: Reset by momentary power interruption
Heat Sensor: 135°F fixed temperature electronic thermistor
Electrical Ratings
System Voltage Nominal: 12 VDC
Minimum: 9.5 VDC
Maximum: 14 VDC Maximum Ripple Voltage: 30% of nom. voltage (peak to peak) Alarm Current (at 12 V): 13 mA maximum Reset Voltage: 0.8 VDC minimum Reset Time: 0.3 seconds maximum Start-up Time: 30 seconds maximum (after 30 second reset)
A Division of Pittway
1-800-SENSOR2, FAX: 630-377-6495
Before Installing
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained following NFPA 72 requirements. The detector should be cleaned at least once a year.
General Description
The Model 2112TL is a 4-wire photoelectronic smoke detec­tor that uses a state-of-the-art optical sensing chamber. This detector is designed to provide open area protection. It
features restorable, built-in, fixed-temperature (135°F)
thermal sensors.
NOTE: The alarm and supervisory outputs are not to be
used as relay contacts.
In addition, an LED on the detector provides a local visual indication of the detector’s status. If power is applied to the detector, and it is functioning normally in standby, the sta­tus LED blinks every ten seconds. The LED latches on in alarm and quits flashing when the detector deviates from its sensitivity range.
D200-66-00 1 I56-997-02
,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
Figure 1. Surface mounting of 2112TL smoke detec­tor on 31/2-inch and 4-inch octagonal box:
A78-2563-00
Mounting
The 2112TL detector is supplied with a mounting bracket that permits the detector to be mounted:
1. To a single gang box, or
2. Directly to a 31/2-inch or 4-inch octagonal box, or
3. To a 4 inch square electrical box by using a plaster ring.
The screw terminal block accepts 14 – 22 gauge wire. For best system performance, all wiring should be installed in separate grounded conduit. Do not mix fire system wiring in the same conduit as any other electrical wiring. Twisted pair may be used to provide additional protection against electrical interference.
Smoke detectors and alarm system control panels have specifications for allowable loop resistance. Consult the control panel specifications for the total loop resistance al­lowed for the control panel being used before wiring the detector loops.
Wire connections are made by stripping about 1/4 inch of insulation from the end of the feed wire, inserting the wire into the appropriate terminal, and tightening the screw to secure the wire in place.
Tamper-resistant Feature
This detector includes a tamper-resistant feature that pre­vents its removal from the bracket without the use of a tool. To make the detector tamper-resistant, remove the smaller tab by breaking it at the scribed line on the tamper resistant tab on the detector mounting bracket (see Figure 2), then install the detector. To remove the detector from the bracket once it has been made tamper resistant, use a small screw­driver to depress the tamper-resistant tab, located in the slot on the mounting bracket, and turn the detector coun­terclockwise.
Wiring Installation Guidelines
All wiring must be installed in compliance with the Na­tional Electrical Code, applicable local codes, and any spe­cial requirements of the local authority having jurisdiction. Proper wire gauges should be used. The conductors used to connect smoke detectors to control panels and accessory devices should be color-coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from responding properly in the event of a fire.
Figure 2. Smoke detector mounting bracket:
TAMPER SLOT (DEPRESS TAB TO REMOVE DETECTOR)
Installation
WARNING
Remove power from the control unit or initiating device cir­cuits before installing detectors.
1. Wire the plug-in screw terminal block per Figure 3 and plug the terminal block into the detector.
2. Align the arrows on the detector with the arrows on the mounting bracket.
3. Turn the detector clockwise in the mounting bracket un­til it clicks into place.
4. After all detectors have been installed, apply power to the control unit or initiating device circuits.
5. Test the detector as described in TESTING.
6. Reset the detector at the system control panel.
7. Notify the proper authorities the system is in operation.
TAMPER RESISTANT TAB (CUT OFF SMALL TAB TO ACTIVATE TAMPER-RESIST FEATURE)
D200-66-00 2 I56-997-02
ALIGNMENT ARROWS
A78-2333-04
Figure 3. Wiring diagram for the 2112TL detector:
+
POWER
TO
DETECTORS
(See Note 1)
+
UL LISTED CONTROL
PANEL
INITIATING
LOOP
+ –
Note1: This terminal is not electrically connected to the detector's circuit.
It is used for wiring consistency only. Power to the detector is applied across the "+" and "Z-
Z+ Z-
IN
Power Supervision
}
Z-
OUT
IN" terminals.
OPTIONAL CLASS A WIRING
+ Z+ Z­Z-
EOL RESISTOR SPECIFIED BY
IN
OUT
PANEL MANUFACTURER
A78-2336-04
CAUTION
Dust covers are an effective way to limit the entry of dust into smoke detector sensing chambers. However, they may not completely prevent airborne dust particles from enter­ing the detector. Therefore, System Sensor recommends the removal of detectors before beginning construction or other dust producing activity. Be sure to remove dust covers from any sensors that were left in place during construction as part of returning the system to service.
Testing
NOTE: Before testing, notify the proper authorities that
the smoke detector system is undergoing mainte­nance and will be temporarily out of service. Dis­able the zone or system undergoing maintenance
to prevent unwanted alarms. Detectors must be tested after installation and following periodic maintenance. Test the 2112TL as follows: A. Test Switch
1. A recessed test switch is located on the detector hous­ing (See Figure 4).
2. Press and hold the recessed test switch with a 0.18 inch maximum diameter tool such as an allen wrench
or small screwdriver.
3. The detector’s LED should light within 5 seconds.
B. Smoke Entry Test
Hold a smoldering punk stick or cotton wick at the side of the detector and gently blow smoke through the de­tector until the unit alarms.
C. Direct Heat Method (Hair dryer of 1000-1500 watts).
Direct the heat toward either of the side thermistors. Hold the heat source about 12 inches from the detector in order to avoid damage to the plastic. The detector will reset only after it has had sufficient time to cool and the
power source has been momentarily interrupted. Both smoke and heat detection testing are recommended for verifying system protection capability.
A detector that fails to activate with any of the above tests should first be cleaned as outlined in MAINTENANCE. If the detector still fails to activate, return it for repair. Notify the proper authorities the system is in operation.
Maintenance
It is recommended that the detector be removed from its mounting base to facilitate cleaning.
Figure 4. Top and side views showing position of test switch:
LED
D200-66-00 3 I56-997-02
RECESSED TEST SWITCH
A78-2564-02A
PUSH RECESSED SWITCH WITH A
0.18 MAX. DIAMETER TOOL
A78-2564-00C
The detector is cleaned as follows: NOTE: Before removing the detector, notify the proper au-
thorities that the smoke detector system is under­going maintenance and will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms.
1. Remove the detector cover by prying away the four side tabs with a small-bladed screwdriver, and then pulling the cover from the base.
2. Vacuum the screen carefully without removing it. If fur­ther cleaning is required continue with Step 3, otherwise skip to Step 8.
3. Remove the screen assembly by pulling it straight out (see Figure 5).
4. Remove the sensing chamber cover by pulling it straight out.
5. Clean the vaned chamber piece by vacuuming or blow­ing out dust and particles.
6. Replace the sensing chamber cover, aligning the arrow
on the top with arrow on the printed circuit board.
7. To replace the screen, place it over the chamber as-
sembly, turning it until it snaps into place.
8. Replace the cover using the test module socket and
The Limitations of Property Protection Smoke Detectors
This smoke detector is designed to activate and initiate emergency ac­tion, but will do so only when it is used in conjunction with an authorized fire alarm system. This detector must be installed in accordance with NFPA standard 72. Smoke detectors will not work without power. AC or DC powered smoke detectors will not work if the power supply is cut off.
Smoke detectors will not sense fires which start where smoke does not reach the detectors. Smoldering fires typically do not generate a lot of
heat which is needed to drive the smoke up to the ceiling where the smoke detector is usually located. For this reason, there may be large de­lays in detecting a smoldering fire with either an ionization type detector or a photoelectric type detector. Either one of them may alarm only after flaming has initiated which will generate the heat needed to drive the smoke to the ceiling. Smoke from fires in chimneys, in walls, on roofs or on the other side of a closed door(s) may not reach the smoke detector and alarm it. A detector cannot detect a fire developing on another level of a building quickly or at all. For these reasons, detectors shall be located on every level and in
every bedroom within a building. Smoke detectors have sensing limitations, too. Ionization detectors and
photoelectric detectors are required to pass fire tests of the flaming and smoldering type. This is to ensure that both can detect a wide range of
LEDs to align the cover and then gently pushing it un­til it locks into place.
9. Reinstall the detector.
10. Test the detector as described in TESTING.
11. Reconnect disabled circuits.
12. Notify the proper authorities the system is back on line.
Figure 5. Removal of cover and screen for cleaning:
REMOVABLE HOUSING
REMOVABLE SCREEN
SENSING CHAMBER COVER
SENSING CHAMBER
BASE
WARNING
types of fires. Ionization detectors offer a broad range of fire sensing capa­bility but they are somewhat better at detecting fast flaming fires than slow smoldering fires. Photoelectric detectors sense smoldering fires better than flaming fires which have little, if any, visible smoke. Because fires de­velop in different ways and are often unpredictable in their growth, nei­ther type of detector is always best, and a given detector may not always provide early warning of a specific type of fire. In general, detectors cannot be expected to provide warnings for fires re­sulting from inadequate fire protection practices, violent explosions, es­caping gases which ignite, improper storage of flammable liquids like cleaning solvents which ignite, other similar safety hazards, arson, smok­ing in bed, children playing with matches or lighters, etc. Smoke detectors used in high air velocity conditions may have a delay in alarm due to dilu­tion of smoke densities created by frequent and rapid air exchanges. Addi­tionally, high air velocity environments may create increased dust contamination, demanding more frequent maintenance. Smoke detectors cannot last forever. Smoke detectors contain electronic parts. Even though smoke detectors are made to last over 10 years, any part can fail at any time. Therefore, smoke detectors shall be replaced after being in service for 10 years. The smoke detector system that this detector is used in must be tested regularly per NFPA 72. This smoke detector should be cleaned regularly per NFPA 72 or at least once a year.
A78-2565-02
System Sensor warrants its enclosed smoke detector to be free from de­fects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this smoke detector. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the smoke detector which is found to be defective in materials or work­manship under normal use and service during the three year period com­mencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Repair Depart-
D200-61-00 4 I56-997-02
Three-Year Limited Warranty
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifica­tions, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or conse­quential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
© System Sensor 1997
Loading...