
INSTALLATION AND MAINTENANCE INSTRUCTIONS
2112TL Photoelectronic
3825 Ohio Avenue, St. Charles, Illinois 60174
Smoke Detector
Specifications
Diameter: 5.5 inches (140 mm)
Height (including mounting bracket): 1.7 inches (43 mm)
Weight: 5.3 oz. (150 g)
Operating Temperature Range: 32° to 100°F (0° to 37.7°C)
Operating Humidity Range: 10% to 93% relative humidity, noncondensing
Latching Alarm: Reset by momentary power interruption
Heat Sensor: 135°F fixed temperature electronic thermistor
Electrical Ratings
System Voltage Nominal: 12 VDC
Minimum: 9.5 VDC
Maximum: 14 VDC
Maximum Ripple Voltage: 30% of nom. voltage (peak to peak)
Alarm Current (at 12 V): 13 mA maximum
Reset Voltage: 0.8 VDC minimum
Reset Time: 0.3 seconds maximum
Start-up Time: 30 seconds maximum (after 30 second reset)
A Division of Pittway
1-800-SENSOR2, FAX: 630-377-6495
Before Installing
Please thoroughly read System Sensor manual I56-407,
Guide for Proper Use of System Smoke Detectors, which provides detailed information on detector spacing, placement,
zoning, wiring, and special applications. Copies of this
manual are available at no charge from System Sensor.
NOTICE: This manual should be left with the owner/user
of this equipment.
IMPORTANT: This detector must be tested and maintained
following NFPA 72 requirements. The detector should be
cleaned at least once a year.
General Description
The Model 2112TL is a 4-wire photoelectronic smoke detector that uses a state-of-the-art optical sensing chamber.
This detector is designed to provide open area protection. It
features restorable, built-in, fixed-temperature (135°F)
thermal sensors.
Installation of this detector is simplified by the use of the
mounting bracket and plug-in screw terminal block that
can be prewired to the system, allowing the detector to be
easily installed or removed for cleaning.
The 2112TL features transistors that provide alarm, power
supervisory, and sensitivity status signals for complete
smoke detector performance.
NOTE: The alarm and supervisory outputs are not to be
used as relay contacts.
In addition, an LED on the detector provides a local visual
indication of the detector’s status. If power is applied to the
detector, and it is functioning normally in standby, the status LED blinks every ten seconds. The LED latches on in
alarm and quits flashing when the detector deviates from
its sensitivity range.
D200-66-00 1 I56-997-02

,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
Figure 1. Surface mounting of 2112TL smoke detector on 31/2-inch and 4-inch octagonal box:
A78-2563-00
Mounting
The 2112TL detector is supplied with a mounting bracket
that permits the detector to be mounted:
1. To a single gang box, or
2. Directly to a 31/2-inch or 4-inch octagonal box, or
3. To a 4 inch square electrical box by using a plaster ring.
The screw terminal block accepts 14 – 22 gauge wire. For
best system performance, all wiring should be installed in
separate grounded conduit. Do not mix fire system wiring
in the same conduit as any other electrical wiring. Twisted
pair may be used to provide additional protection against
electrical interference.
Smoke detectors and alarm system control panels have
specifications for allowable loop resistance. Consult the
control panel specifications for the total loop resistance allowed for the control panel being used before wiring the
detector loops.
Wire connections are made by stripping about 1/4 inch of
insulation from the end of the feed wire, inserting the wire
into the appropriate terminal, and tightening the screw to
secure the wire in place.
Tamper-resistant Feature
This detector includes a tamper-resistant feature that prevents its removal from the bracket without the use of a tool.
To make the detector tamper-resistant, remove the smaller
tab by breaking it at the scribed line on the tamper resistant
tab on the detector mounting bracket (see Figure 2), then
install the detector. To remove the detector from the bracket
once it has been made tamper resistant, use a small screwdriver to depress the tamper-resistant tab, located in the
slot on the mounting bracket, and turn the detector counterclockwise.
Wiring Installation Guidelines
All wiring must be installed in compliance with the National Electrical Code, applicable local codes, and any special requirements of the local authority having jurisdiction.
Proper wire gauges should be used. The conductors used to
connect smoke detectors to control panels and accessory
devices should be color-coded to reduce the likelihood of
wiring errors. Improper connections can prevent a system
from responding properly in the event of a fire.
Figure 2. Smoke detector mounting bracket:
TAMPER SLOT
(DEPRESS TAB TO
REMOVE DETECTOR)
Installation
WARNING
Remove power from the control unit or initiating device circuits before installing detectors.
1. Wire the plug-in screw terminal block per Figure 3 and
plug the terminal block into the detector.
2. Align the arrows on the detector with the arrows on the
mounting bracket.
3. Turn the detector clockwise in the mounting bracket until it clicks into place.
4. After all detectors have been installed, apply power to
the control unit or initiating device circuits.
5. Test the detector as described in TESTING.
6. Reset the detector at the system control panel.
7. Notify the proper authorities the system is in operation.
TAMPER RESISTANT TAB
(CUT OFF SMALL TAB TO
ACTIVATE TAMPER-RESIST
FEATURE)
D200-66-00 2 I56-997-02
ALIGNMENT
ARROWS
A78-2333-04

Figure 3. Wiring diagram for the 2112TL detector:
+
POWER
TO
DETECTORS
–
(See Note 1)
–
+
UL LISTED
CONTROL
PANEL
INITIATING
LOOP
+
–
Note1: This terminal is not electrically connected to the detector's circuit.
It is used for wiring consistency only. Power to the detector is applied across
the "+" and "Z-
Z+
Z-
IN
Power
Supervision
}
Z-
OUT
IN" terminals.
OPTIONAL CLASS A WIRING
–
+
Z+
ZZ-
EOL RESISTOR
SPECIFIED BY
IN
OUT
PANEL
MANUFACTURER
A78-2336-04
CAUTION
Dust covers are an effective way to limit the entry of dust
into smoke detector sensing chambers. However, they may
not completely prevent airborne dust particles from entering the detector. Therefore, System Sensor recommends the
removal of detectors before beginning construction or other
dust producing activity. Be sure to remove dust covers from
any sensors that were left in place during construction as
part of returning the system to service.
Testing
NOTE: Before testing, notify the proper authorities that
the smoke detector system is undergoing maintenance and will be temporarily out of service. Disable the zone or system undergoing maintenance
to prevent unwanted alarms.
Detectors must be tested after installation and following
periodic maintenance. Test the 2112TL as follows:
A. Test Switch
1. A recessed test switch is located on the detector housing (See Figure 4).
2. Press and hold the recessed test switch with a 0.18
inch maximum diameter tool such as an allen wrench
or small screwdriver.
3. The detector’s LED should light within 5 seconds.
B. Smoke Entry Test
Hold a smoldering punk stick or cotton wick at the side
of the detector and gently blow smoke through the detector until the unit alarms.
C. Direct Heat Method (Hair dryer of 1000-1500 watts).
Direct the heat toward either of the side thermistors.
Hold the heat source about 12 inches from the detector
in order to avoid damage to the plastic. The detector will
reset only after it has had sufficient time to cool and the
power source has been momentarily interrupted.
Both smoke and heat detection testing are recommended
for verifying system protection capability.
A detector that fails to activate with any of the above tests
should first be cleaned as outlined in MAINTENANCE. If
the detector still fails to activate, return it for repair.
Notify the proper authorities the system is in operation.
Maintenance
It is recommended that the detector be removed from its
mounting base to facilitate cleaning.
Figure 4. Top and side views showing position of test switch:
LED
D200-66-00 3 I56-997-02
RECESSED TEST
SWITCH
A78-2564-02A
PUSH RECESSED
SWITCH WITH A
0.18″ MAX. DIAMETER TOOL
A78-2564-00C

The detector is cleaned as follows:
NOTE: Before removing the detector, notify the proper au-
thorities that the smoke detector system is undergoing maintenance and will be temporarily out of
service. Disable the zone or system undergoing
maintenance to prevent unwanted alarms.
1. Remove the detector cover by prying away the four side
tabs with a small-bladed screwdriver, and then pulling
the cover from the base.
2. Vacuum the screen carefully without removing it. If further cleaning is required continue with Step 3, otherwise
skip to Step 8.
3. Remove the screen assembly by pulling it straight out
(see Figure 5).
4. Remove the sensing chamber cover by pulling it straight out.
5. Clean the vaned chamber piece by vacuuming or blowing out dust and particles.
6. Replace the sensing chamber cover, aligning the arrow
on the top with arrow on the printed circuit board.
7. To replace the screen, place it over the chamber as-
sembly, turning it until it snaps into place.
8. Replace the cover using the test module socket and
The Limitations of Property Protection Smoke Detectors
This smoke detector is designed to activate and initiate emergency action, but will do so only when it is used in conjunction with an authorized
fire alarm system. This detector must be installed in accordance with
NFPA standard 72.
Smoke detectors will not work without power. AC or DC powered
smoke detectors will not work if the power supply is cut off.
Smoke detectors will not sense fires which start where smoke does not
reach the detectors. Smoldering fires typically do not generate a lot of
heat which is needed to drive the smoke up to the ceiling where the
smoke detector is usually located. For this reason, there may be large delays in detecting a smoldering fire with either an ionization type detector
or a photoelectric type detector. Either one of them may alarm only after
flaming has initiated which will generate the heat needed to drive the
smoke to the ceiling.
Smoke from fires in chimneys, in walls, on roofs or on the other side of a
closed door(s) may not reach the smoke detector and alarm it. A detector
cannot detect a fire developing on another level of a building quickly or at
all. For these reasons, detectors shall be located on every level and in
every bedroom within a building.
Smoke detectors have sensing limitations, too. Ionization detectors and
photoelectric detectors are required to pass fire tests of the flaming and
smoldering type. This is to ensure that both can detect a wide range of
LEDs to align the cover and then gently pushing it until it locks into place.
9. Reinstall the detector.
10. Test the detector as described in TESTING.
11. Reconnect disabled circuits.
12. Notify the proper authorities the system is back on line.
Figure 5. Removal of cover and screen for cleaning:
REMOVABLE
HOUSING
REMOVABLE
SCREEN
SENSING
CHAMBER
COVER
SENSING
CHAMBER
BASE
WARNING
types of fires. Ionization detectors offer a broad range of fire sensing capability but they are somewhat better at detecting fast flaming fires than
slow smoldering fires. Photoelectric detectors sense smoldering fires better
than flaming fires which have little, if any, visible smoke. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is always best, and a given detector may not always
provide early warning of a specific type of fire.
In general, detectors cannot be expected to provide warnings for fires resulting from inadequate fire protection practices, violent explosions, escaping gases which ignite, improper storage of flammable liquids like
cleaning solvents which ignite, other similar safety hazards, arson, smoking in bed, children playing with matches or lighters, etc. Smoke detectors
used in high air velocity conditions may have a delay in alarm due to dilution of smoke densities created by frequent and rapid air exchanges. Additionally, high air velocity environments may create increased dust
contamination, demanding more frequent maintenance.
Smoke detectors cannot last forever. Smoke detectors contain electronic
parts. Even though smoke detectors are made to last over 10 years, any
part can fail at any time. Therefore, smoke detectors shall be replaced after
being in service for 10 years. The smoke detector system that this detector
is used in must be tested regularly per NFPA 72. This smoke detector
should be cleaned regularly per NFPA 72 or at least once a year.
A78-2565-02
System Sensor warrants its enclosed smoke detector to be free from defects in materials and workmanship under normal use and service for a
period of three years from date of manufacture. System Sensor makes no
other express warranty for this smoke detector. No agent, representative,
dealer, or employee of the Company has the authority to increase or alter
the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the repair or replacement of any part of
the smoke detector which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll
free number 800-SENSOR2 (736-7672) for a Return Authorization number,
send defective units postage prepaid to: System Sensor, Repair Depart-
D200-61-00 4 I56-997-02
Three-Year Limited Warranty
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please
include a note describing the malfunction and suspected cause of failure.
The Company shall not be obligated to repair or replace units which are
found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case
shall the Company be liable for any consequential or incidental damages
for breach of this or any other Warranty, expressed or implied whatsoever,
even if the loss or damage is caused by the Company’s negligence or fault.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to
you. This Warranty gives you specific legal rights, and you may also have
other rights which vary from state to state.
© System Sensor 1997