System Sensor 2112-24R, 2112-24TR User Manual

D200-83-00 1 I56-1239-02R
2112/24R and 2112/24TR Photoelectronic Smoke Detectors
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Specifications
Diameter: 5.5 inches (140 mm) Height (including mounting bracket): 1.7 inches (43 mm) Weight: 6.8 oz. (190 g) Operating Temperature Range Model 2112/24R: 32°F to 120°F (0°C to 49°C)
Model 2112/24TR: 32°F to 100°F (0°C to 39°C) Operating Humidity Range: 10% to 93% Relative Humidity, Noncondensing Latching Alarm: Reset by momentary power interruption Heat Sensor (Model 2112/24TR only): 135°F Fixed Temperature Electronic Thermistor
Electrical Ratings
System Voltage (nominal): 12 or 24 VDC
Minimum: 10 VDC
Maximum: 35 VDC Maximum Ripple Voltage: 30% of nom. Voltage (peak to peak) Standby Current: 50 µA maximum Alarm Current: 28 mA typical, 35 mA max. at 12V
36 mA typical, 45 mA max. at 24V Reset Voltage: 0.8 VDC minimum Reset Time: 0.3 seconds maximum Start-up Time: 30 seconds maximum (after 60 sec. reset) EOL Relay: A77-716B, 12/24 VDC Alarm Initiation and Auxiliary Relay: 1A @ 30 VAC Contact Ratings, Resistive Load: 1A @ 30 VDC
Figure 1. Wiring diagram for the 2112/24R and 2112/24TR detector:
A78-2336-16
OPTIONAL CLASS A WIRING
EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER
EOL POWER SUPERVISION RELAY (SHOWN ENERGIZED) A77-716 12/24V
POWER
TO
DETECTORS
UL LISTED
COMPATIBLE
CONTROL
PANEL
INITIATING
LOOP
+
P
W
R
A U X
P
W
R
A U X
+ + –
A A NC
C
NO
+ + –
A A NC
C
NO
ALARM CONTACT
ALARM CONTACT
(OPTIONAL) RELEASING
DEVICE
NC
COMMON
NO
(OPTIONAL) RELEASING
DEVICE
NC
COMMON
NO
D200-83-00 2 I56-1239-02R
Figure 2. Surface mounting of 2112/24R and 2112/24TR smoke detector on 31⁄2-inch and 4-inch octagonal box:
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
A78-2563-01
Figure 3. 2112/24R and 2112/24TR smoke detector mounting bracket:
A78-2333-04
If the LED stops blinking, the unit should be removed for maintenance and inspection.
Mounting
Each 2112/24R and 2112/24TR detector is supplied with a mounting bracket that permits the detector to be mounted:
1. To a single gang box, or
2. Directly to a 31⁄2 inch or 4 inch octagonal box, or
3. To a 4 inch square electrical box by using a plaster ring.
4.
Directly to the ceiling using drywall anchors, if permit­ted by local codes and/or the authority having jurisdic­tion.
Tamper-resistant Feature
This detector includes a tamper-resistant feature that pre­vents its removal from the bracket without the use of a tool. To make the detector tamper-resistant, remove the smaller tab by breaking it at the scribed line on the tamper resistant tab on the detector mounting bracket (see Figure 3), then install the detector. To remove the detector from the brack­et once it has been made tamper resistant, use a small screwdriver to depress the tamper-resistant tab, located in the slot on the mounting bracket, and turn the detector counterclockwise.
Wiring Installation Guidelines
All wiring must be installed in compliance with the National Electrical Code, applicable local codes, and any special requirements of the local authority having jurisdic­tion. Proper wire gauges should be used. The conductors used to connect smoke detectors to control panels and accessory devices should be color-coded to reduce the like­lihood of wiring errors. Improper connections can prevent a system from responding properly in the event of a fire.
The screw terminal block accepts 14 – 22 gauge wire. For best system performance, all wiring should be installed in separate grounded conduit. Do not mix fire system wiring in the same conduit as any other electrical wiring. Twisted pair may be used to provide additional protection against electrical interference.
Before Installing
Please thoroughly read the System Sensor manual I56-407, Guide for Proper Use of System Smoke Detectors, which pro­vides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available at no charge from System Sensor.
NOTICE: This manual shall be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained following NFPA 72 requirements. The detector should be cleaned at least once a year.
General Description
Models 2112/24R and 2112/24TR are 4-wire photoelectron­ic smoke detectors that use a state-of-the-art optical sens­ing chamber. The 2112/24TR also provides restorable, 135˚F fixed-temperature heat detection. The 2112/24TR heat-detection unit is integrated with the photoelectronic sensor.
Installation of this detector is simplified by the use of a mounting bracket and a plug-in screw terminal block that can be prewired to the system, allowing the detector to be easily installed or removed for cleaning. The detector’s sen­sitivity can be tested in place using the MOD400R Test Module.
An LED on the detector provides a local visual indication of the detector’s status. If power is applied to the detector and it is functioning normally in standby within the listed sensitivity ranges, the status LED blinks every ten seconds. The LED also latches on in alarm.
TAMPER SLOT (DEPRESS TAB TO REMOVE DETECTOR)
TAMPER RESISTANT TAB (CUT OFF SMALL TAB TO ACTIVATE TAMPER-RESIST FEATURE)
ALIGNMENT ARROWS