System Sensor 2112-24R, 2112-24TR User Manual

D200-83-00 1 I56-1239-02R
2112/24R and 2112/24TR Photoelectronic Smoke Detectors
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Specifications
Diameter: 5.5 inches (140 mm) Height (including mounting bracket): 1.7 inches (43 mm) Weight: 6.8 oz. (190 g) Operating Temperature Range Model 2112/24R: 32°F to 120°F (0°C to 49°C)
Model 2112/24TR: 32°F to 100°F (0°C to 39°C) Operating Humidity Range: 10% to 93% Relative Humidity, Noncondensing Latching Alarm: Reset by momentary power interruption Heat Sensor (Model 2112/24TR only): 135°F Fixed Temperature Electronic Thermistor
Electrical Ratings
System Voltage (nominal): 12 or 24 VDC
Minimum: 10 VDC
Maximum: 35 VDC Maximum Ripple Voltage: 30% of nom. Voltage (peak to peak) Standby Current: 50 µA maximum Alarm Current: 28 mA typical, 35 mA max. at 12V
36 mA typical, 45 mA max. at 24V Reset Voltage: 0.8 VDC minimum Reset Time: 0.3 seconds maximum Start-up Time: 30 seconds maximum (after 60 sec. reset) EOL Relay: A77-716B, 12/24 VDC Alarm Initiation and Auxiliary Relay: 1A @ 30 VAC Contact Ratings, Resistive Load: 1A @ 30 VDC
Figure 1. Wiring diagram for the 2112/24R and 2112/24TR detector:
A78-2336-16
OPTIONAL CLASS A WIRING
EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER
EOL POWER SUPERVISION RELAY (SHOWN ENERGIZED) A77-716 12/24V
POWER
TO
DETECTORS
UL LISTED
COMPATIBLE
CONTROL
PANEL
INITIATING
LOOP
+
P
W
R
A U X
P
W
R
A U X
+ + –
A A NC
C
NO
+ + –
A A NC
C
NO
ALARM CONTACT
ALARM CONTACT
(OPTIONAL) RELEASING
DEVICE
NC
COMMON
NO
(OPTIONAL) RELEASING
DEVICE
NC
COMMON
NO
D200-83-00 2 I56-1239-02R
Figure 2. Surface mounting of 2112/24R and 2112/24TR smoke detector on 31⁄2-inch and 4-inch octagonal box:
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
A78-2563-01
Figure 3. 2112/24R and 2112/24TR smoke detector mounting bracket:
A78-2333-04
If the LED stops blinking, the unit should be removed for maintenance and inspection.
Mounting
Each 2112/24R and 2112/24TR detector is supplied with a mounting bracket that permits the detector to be mounted:
1. To a single gang box, or
2. Directly to a 31⁄2 inch or 4 inch octagonal box, or
3. To a 4 inch square electrical box by using a plaster ring.
4.
Directly to the ceiling using drywall anchors, if permit­ted by local codes and/or the authority having jurisdic­tion.
Tamper-resistant Feature
This detector includes a tamper-resistant feature that pre­vents its removal from the bracket without the use of a tool. To make the detector tamper-resistant, remove the smaller tab by breaking it at the scribed line on the tamper resistant tab on the detector mounting bracket (see Figure 3), then install the detector. To remove the detector from the brack­et once it has been made tamper resistant, use a small screwdriver to depress the tamper-resistant tab, located in the slot on the mounting bracket, and turn the detector counterclockwise.
Wiring Installation Guidelines
All wiring must be installed in compliance with the National Electrical Code, applicable local codes, and any special requirements of the local authority having jurisdic­tion. Proper wire gauges should be used. The conductors used to connect smoke detectors to control panels and accessory devices should be color-coded to reduce the like­lihood of wiring errors. Improper connections can prevent a system from responding properly in the event of a fire.
The screw terminal block accepts 14 – 22 gauge wire. For best system performance, all wiring should be installed in separate grounded conduit. Do not mix fire system wiring in the same conduit as any other electrical wiring. Twisted pair may be used to provide additional protection against electrical interference.
Before Installing
Please thoroughly read the System Sensor manual I56-407, Guide for Proper Use of System Smoke Detectors, which pro­vides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available at no charge from System Sensor.
NOTICE: This manual shall be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained following NFPA 72 requirements. The detector should be cleaned at least once a year.
General Description
Models 2112/24R and 2112/24TR are 4-wire photoelectron­ic smoke detectors that use a state-of-the-art optical sens­ing chamber. The 2112/24TR also provides restorable, 135˚F fixed-temperature heat detection. The 2112/24TR heat-detection unit is integrated with the photoelectronic sensor.
Installation of this detector is simplified by the use of a mounting bracket and a plug-in screw terminal block that can be prewired to the system, allowing the detector to be easily installed or removed for cleaning. The detector’s sen­sitivity can be tested in place using the MOD400R Test Module.
An LED on the detector provides a local visual indication of the detector’s status. If power is applied to the detector and it is functioning normally in standby within the listed sensitivity ranges, the status LED blinks every ten seconds. The LED also latches on in alarm.
TAMPER SLOT (DEPRESS TAB TO REMOVE DETECTOR)
TAMPER RESISTANT TAB (CUT OFF SMALL TAB TO ACTIVATE TAMPER-RESIST FEATURE)
ALIGNMENT ARROWS
D200-83-00 3 I56-1239-02R
Smoke detectors and alarm system control panels have specifications for allowable loop resistance. Consult the control panel specifications for the total loop resistance allowed for the control panel being used before wiring the detector loops.
Wire connections are made by stripping about 1⁄4 inch of insulation from the end of the feed wire, inserting the wire into the appropriate terminal, and tightening the screw to secure the wire in place.
Installation
Remove power from the control unit or initiating device cir­cuits before installing detectors.
1. Wire the plug-in screw terminal block per Figure 1 and
plug the terminal block into the detector.
2. Align the arrows on the detector with the arrows on the
mounting bracket.
3. Turn the detector clockwise in the mounting bracket
until it clicks into place.
4. After all detectors have been installed, apply power to
the control unit or initiating device circuits.
5. Test the detector as described in TESTING.
6. Reset the detector at the system control panel.
7. Notify the proper authorities the system is in operation.
Dust covers are an effective way to limit the entry of dust into smoke detector sensing chambers. However, they may not completely prevent airborne dust particles from enter­ing the detector. Therefore, System Sensor recommends the removal of detectors before beginning construction or other dust producing activity. Be sure to remove dust covers from any sensors that were left in place during construction as part of returning the system to service.
CAUTION
WARNING
I
N
T
A
P
T
O
N
O
D
LED
TEST MODULE SOCKET
RECESSED TEST SWITCH
PUSH RECESSED SWITCH WITH A
0.18" MAX. DIAMETER TOOL
Figure 4. Top and side views showing position of test switch:
Testing
NOTE: Before testing, notify the proper authorities that
the smoke detector system is undergoing mainte­nance and will be temporarily out of service. Disable the zone or system undergoing mainte­nance to prevent unwanted alarms.
Detectors must be tested after installation and following periodic maintenance. Test the 2112/24R and 2112/24TR as follows: A. Test Switch
1. A recessed test switch is located on the detector hous­ing (See Figure 4).
2. Press and hold the recessed test switch with a 0.1 inch maximum diameter tool such as an allen wrench or small screwdriver.
3. The detector’s LED should light within 5 seconds.
B. Test Module (System Sensor Model No. MOD400R).
The MOD400R test module can be used with a DMM or analog voltmeter to check the detector sensitivity as described in the test module’s manual.
C. Smoke Entry Test
Hold a smoldering punk stick or cotton wick at the side of the detector and gently blow smoke through the detector until the unit alarms.
D. Direct Heat Method (Model 2112/24TR only – Hair dryer
of 1000-1500 watts) Direct the heat toward either of the side thermistors. Hold the heat source about 12 inches from the detector in order to avoid damage to the plastic. The detector will reset only after it has had sufficient time to cool and the power source has been momentarily interrupted.
Both smoke and heat detection testing are recommended for verifying system protection capability.
A detector that fails to activate with any of the above tests should first be cleaned as outlined in MAINTENANCE. If the detector still fails to activate, return it for repair.
Notify the proper authorities the system is back in operation.
A78-2564-00
D200-83-00 4 I56-1239-02R
©
2001 System Sensor
Three-Year Limited Warranty
System Sensor warrants its enclosed smoke detector to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this smoke detector. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the smoke detector which is found to be defective in materials or work­manship under normal use and service during the three year period com­mencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Repair
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental dam­ages for breach of this or any other Warranty, expressed or implied what­soever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
REMOVABLE HOUSING
REMOVABLE SCREEN
SENSING CHAMBER COVER
BASE
SENSING CHAMBER
A78-2565-02
Figure 5. Removal of cover and screen for cleaning:
Maintenance
NOTE: Before removing the detector, notify the proper
authorities that the smoke detector system is under­going maintenance and will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms.
NOTE: (Model 2112/24TR only) Before removing the detec-
tor cover, note the position of the thermistors. Make sure the thermistors are not bent over when the housing is replaced.
1. Remove the detector housing by gently prying the four housing tabs on the bottom of the base with a small­bladed screwdriver and pull the housing from the base. Use caution to avoid damaging the thermistors, (2112/24TR only).
2. Vacuum the screen carefully without removing it.
3. Remove screen assembly, pulling straight out (see Figure 5).
4. Remove the sensing chamber cover.
5. Clean the sensing chamber by vacuuming or blowing out dust and particles.
6. Replace the sensing chamber cover, aligning the arrow on the cover top with the arrow on the printed circuit board.
7. Replace the screen by placing the screen assembly over the sensing chamber cover and twisting until it snaps into place.
8. Replace the housing by aligning the three triangular slots on the base with their counterparts on the hous­ing. Gently press the housing until it locks in place. Check to make sure that the thermistors are in the upright position.
9. Reinstall the detector.
10. Notify the proper authorities that the system is back in operation.
Please refer to insert for the Limitations of Fire Alarm Systems