INSTALLATION AND MAINTENANCE INSTRUCTIONS
OPTIONAL CLASS A WIRING
EOL RESISTOR
SPECIFIED BY
PANEL
MANUFACTURER
EOL POWER
SUPERVISION
RELAY (SHOWN
ENERGIZED)
A77-716 12/24V
POWER
TO
DETECTORS
UL LISTED
CONTROL
PANEL
INITIATING
LOOP
+
–
+
–
P
W
R
+
+
–
+
–
+
–
N.O.
C
P
W
R
+
+
–
N.O.
C
: Observe polarity in power and initiating loops when wiring.
NOTE
2112/24D(A) and 2112/24TD(A)
Photoelectronic Smoke Detectors
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
A Division of Pittway
IMPORTANT: OBSERVE POLARITY
This detector requires that you observe polarity when wiring. If wiring polarity is not observed on the
initiating loop, the unit will send an alarm signal to the control panel to signify incorrect wiring.
Figure 1. Wiring diagram for the 2112/24D(A) and 2112/24TD(A) detectors:
Before Installing
Please thoroughly read the System Sensor manual I56-407,
Guide for Proper Use of System Smoke Detectors, which
provides detailed information on detector spacing, place-
can be prewired to the system, allowing the detector to be
easily installed or removed for cleaning. The detector’s
sensitivity can be tested in place using the MOD400R Test
Module.
ment, zoning, wiring, and special applications. Copies of
this manual are available at no charge from System Sensor.
(For installation in Canada, refer to CAN/ULC-S524-M91,
Standard for the Installation of Fire Alarm Systems, and
CEC Part 1, sec. 32.)
NOTICE: This manual should be left with the owner/user
of this equipment.
An LED on the detector provides a local visual indication of
the detector’s status. If power is applied to the detector, and
it is functioning normally in standby, the status LED blinks
every ten seconds. The LED also latches on in alarm.
Models 2112/24D(A) and 2112/24TD(A) feature a visual
indication that maintenance is required – if the sensing
chamber drifts out of its sensitivity limits, the LED ceases
IMPORTANT: This detector must be tested and maintained
to blink.
following NFPA 72 requirements. The detector should be
cleaned at least once a year.
General Description
Model 2112/24D(A) is a 4-wire photoelectronic smoke detector that uses a state-of-the-art optical sensing chamber.
This detector is designed to provide open area protection.
Model 2112/24TD(A) features a restoreable, built-in, xedtemperature (135°F) thermal detector.
Installation of these detectors is simplied by the use of a
mounting bracket and a plug-in screw terminal block that
D200-62-00 1 I56-932-07
Mounting
Each 2112/24D(A) and 2112/24TD(A) detector is supplied
with a mounting bracket that permits the detector to be
mounted:
1. To a single gang box, or
2. Directly to a 31/2-inch or 4-inch octagonal box, or
3. To a 4 inch square electrical box by using a plaster ring.
Tamper-resistant Feature
This detector includes a tamper-resistant feature that pre-
vents its removal from the bracket without the use of a
A78-2336-03
Specications
Diameter: 5.5 inches (140 mm)
Height (including mounting bracket): 1.7 inches (43 mm)
Weight: 5.3 oz. (150 g)
Operating Temperature Range
Model 2112/24D(A): 32° to 120°F (0° to 50°C)
Model 2112/24TD(A): 32° to 100°F (0° to 39°C)
Operating Humidity Range: 10% to 93% Relative Humidity, Noncondensing
Latching Alarm: Reset by momentary power interruption
Heat Sensor (2112/24TD(A) only): 135°F Fixed Temperature Electronic Thermistor
Electrical Ratings
System Voltage (nominal): 12 or 24 VDC
Minimum: 8.5 VDC
Maximum: 35 VDC
Maximum Ripple Voltage: 30% of nom. Voltage (peak to peak)
Standby Current: 50 µA maximum
Alarm Current: 17 mA typical, 23 mA max. at 12V
19 mA typical, 25 mA max. at 24V
Reset Voltage: 0.8 VDC minimum
Reset Time: 0.3 seconds maximum
Start-up Time: 30 seconds maximum (after 60 sec. reset)
EOL Relay: A77-716B, 12/24 Volt
Alarm Initiation Contact Ratings
Resistive Load: 0.1A @ 35 VDC
Figure 2. Surface mounting of 2112/24D(A) smoke
detector on 31/2-inch and 4-inch octagonal box:
A78-2563-00
tool. To make the detector tamper-resistant, remove the
smaller tab by breaking it at the scribed line on the tamper
resistant tab on the detector mounting bracket (see Figure
3), then install the detector. To remove the detector from
the bracket once it has been made tamper resistant, use
a small screwdriver to depress the tamper-resistant tab,
located in the slot on the mounting bracket, and turn the
detector counterclockwise.
Wiring Installation Guidelines
Be certain to observe polarity when wiring.
devices should be color-coded to reduce the likelihood of
wiring errors. Improper connections can prevent a system
from responding properly in the event of a re.
The screw terminal block accepts 14 – 22 gauge wire. For
best system performance, all wiring should be installed in
separate grounded conduit. Do not mix re system wiring
in the same conduit as any other electrical wiring. Twisted
pair may be used to provide additional protection against
electrical interference.
Smoke detectors and alarm system control panels have
specications for allowable loop resistance. Consult the
control panel specications for the total loop resistance
allowed for the control panel being used before wiring the
detector loops.
Wire connections are made by stripping about 1/4 inch of
insulation from the end of the feed wire, inserting the wire
into the appropriate terminal, and tightening the screw to
secure the wire in place.
Installation
All wiring must be installed in compliance with the National Electrical Code, applicable local codes, and any special requirements of the local authority having jurisdiction.
Proper wire gauges should be used. The conductors used
Remove power from the control unit or initiating device
circuits before installing detectors.
to connect smoke detectors to control panels and accessory
D200-62-00 2 I56-932-07