Diameter: 5.5 inches (140 mm)
Height (including mounting bracket): 1.7 inches (43 mm)
Weight: 5.3 oz. (150 g)
Operating Temperature Range
Model 2112/24B: 32° to 120°F (0° to 50°C)
Model 2112/24TB: 32° to 100°F (0° to 39°C)
Operating Humidity Range: 10% to 93% Relative Humidity, Noncondensing
Latching Alarm: Reset by momentary power interruption
Heat Sensor (2112/24TB only): 135°F Fixed Temperature Electronic Thermistor
Electrical Ratings
System Voltage (nominal): 12 or 24 VDC
Minimum: 8.5 VDC
Maximum: 35 VDC
Maximum Ripple Voltage: 30% of nom. Voltage (peak to peak)
Standby Current: 50 µA maximum
Alarm Current: 17 mA typical, 23 mA max. at 12V
19 mA typical, 25 mA max. at 24V
Reset Voltage: 0.8 VDC minimum
Reset Time: 0.3 seconds maximum
Start-up Time: 30 seconds maximum (after 60 sec. reset)
EOL Relay: A77-716B, 12/24 Volt
Alarm Initiation Contact Ratings
Resistive or inductive load (60% power factor)
Form A: 0.5A @ 30 VAC/DC
A Division of Pittway
1-800-SENSOR2, FAX: 630-377-6495
Before Installing
Please thoroughly read the System Sensor manual I56-407,
Guide for Proper Use of System Smoke Detectors, which
provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of
this manual are available at no charge from System Sensor.
NOTICE: This manual should be left with the owner/user
of this equipment.
IMPORTANT: This detector must be tested and maintained
following NFPA 72 requirements. The detector should be
cleaned at least once a year.
General Description
Model 2112/24B is a 4-wire photoelectronic smoke detector
that uses a state-of-the-art optical sensing chamber. This
detector is designed to provide open area protection. Model
D200-62-00 1 I56-932-01
2112/24TB features a restoreable, built-in, xed-temperature (135°F) thermal detector.
Installation of these detectors is simplied by the use of a
mounting bracket and a plug-in screw terminal block that
can be prewired to the system, allowing the detector to be
easily installed or removed for cleaning. The detector’s
sensitivity can be tested in place using the MOD400R Test
Module.
An LED on the detector provides a local visual indication of
the detector’s status. If power is applied to the detector, and
it is functioning normally in standby, the status LED blinks
every ten seconds. The LED also latches on in alarm.
Models 2112/24B and 2112/24TB feature a visual indication
that maintenance is required – if the sensing chamber drifts
out of its sensitivity limits, the LED ceases to blink.
D
O
N
O
T
P
A
I
N
T
TAMPER SLOT
(DEPRESS TAB TO
REMOVE DETECTOR)
TAMPER RESISTANT TAB
(CUT OFF SMALL TAB TO
ACTIVATE TAMPER-RESIST
FEATURE)
ALIGNMENT
ARROWS
Figure 1. Surface mounting of 2112/24B smoke de-
WARNING
tector on 3 1/2 inch and 4 inch octagonal box:
A78-2563-00
wiring errors. Improper connections can prevent a system
from responding properly in the event of a re.
The screw terminal block accepts 14 – 22 gauge wire. For
best system performance, all wiring should be installed in
separate grounded conduit. Do not mix re system wiring
in the same conduit as any other electrical wiring. Twisted
pair may be used to provide additional protection against
electrical interference.
Smoke detectors and alarm system control panels have
specications for allowable loop resistance. Consult the
control panel specications for the total loop resistance
allowed for the control panel being used before wiring the
detector loops.
Mounting
Each 2112/24B and 2112/24TB detector is supplied with a
mounting bracket that permits the detector to be mounted:
1. To a single gang box, or
2. Directly to a 3-1/2 inch or 4 inch octagonal box, or
3. To a 4 inch square electrical box by using a plaster ring.
Tamper-resistant Feature
This detector includes a tamper-resistant feature that prevents its removal from the bracket without the use of a
tool. To make the detector tamper-resistant, remove the
smaller tab by breaking it at the scribed line on the tamper
resistant tab on the detector mounting bracket (see Figure
2), then install the detector. To remove the detector from
the bracket once it has been made tamper resistant, use
a small screwdriver to depress the tamper-resistant tab,
located in the slot on the mounting bracket, and turn the
detector counterclockwise.
Wiring Installation Guidelines
All wiring must be installed in compliance with the National Electrical Code, applicable local codes, and any special requirements of the local authority having jurisdiction.
Proper wire gauges should be used. The conductors used
to connect smoke detectors to control panels and accessory
devices should be color-coded to reduce the likelihood of
Wire connections are made by stripping about 1/4 inch of
insulation from the end of the feed wire, inserting the wire
into the appropriate terminal, and tightening the screw to
secure the wire in place.
Installation
Remove power from the control unit or initiating device
circuits before installing detectors.
1. Wire the plug-in screw terminal block per Figure 3 and
plug the terminal block into the detector.
2. Align the arrows on the detector with the arrows on the
mounting bracket.
3. Turn the detector clockwise in the mounting bracket until it clicks into place.
4. After all detectors have been installed, apply power to
the control unit or initiating device circuits.
5. Test the detector as described in TESTING.
6. Reset the detector at the system control panel.
7. Notify the proper authorities the system is in operation.
Figure 2. 2112/24B and 2112/24TB smoke detector mounting bracket:
D200-62-00 2 I56-932-01
A78-2333-01
CAUTION
Figure 3. Wiring diagram for the 2112/24B and 2112/24TB detector:
D
O
N
O
T
P
A
I
N
T
LED
RECESSED TEST
SWITCH
TEST MODULE
SOCKET
PUSH RECESSED
SWITCH WITH
A
0.1" MAX. DIAMETER TOOL
P
W
R
OPTIONAL CLASS A WIRING
EOL RESISTOR
SPECIFIED BY
PANEL
MANUFACTURER
EOL POWER
SUPERVISION
RELAY (SHOWN
ENERGIZED)
A77-716 12/24V
POWER
TO
DETECTORS
UL LISTED
CONTROL
PANEL
INITIATING
LOOP
+
+
P
W
R
+
+
N.O.
C
+
+
N.O.
C
B. Test Module (System Sensor Model No. MOD400R).
Dust covers are an effective way to limit the entry of dust
into smoke detector sensing chambers. However, they may
not completely prevent airborne dust particles from entering the detector. Therefore, System Sensor recommends
the removal of detectors before beginning construction or
other dust producing activity. Be sure to remove dust covers
from any sensors that were left in place during construction
as part of returning the system to service.
The MOD400R test module can be used with a DMM
or analog voltmeter to check the detector sensitivity as
described in the test module’s manual.
C. Smoke Entry Test
Hold a smoldering punk stick or cotton wick at the side
of the detector and gently blow smoke through the de-
tector until the unit alarms.
D. Direct Heat Method (Model 2112/24TB only – Hair dryer
of 1000-1500 watts).
Testing
NOTE: Before testing, notify the proper authorities that the
smoke detector system is undergoing maintenance
and will be temporarily out of service. Disable the
zone or system undergoing maintenance to prevent
Direct the heat toward either of the side thermistors.
Hold the heat source about 12 inches from the detector
in order to avoid damage to the plastic. The detector will
reset only after it has had sufcient time to cool and the
power source has been momentarily interrupted.
unwanted alarms.
Both smoke and heat detection testing are recommended
Detectors must be tested after installation and following
for verifying system protection capability.
periodic maintenance. Test the 2112/24 as follows:
A. Test Switch
1. A recessed test switch is located on the detector housing (See Figure 4).
A detector that fails to activate with any of the above tests
should rst be cleaned as outlined in MAINTENANCE. If
the detector still fails to activate, return it for repair.
2. Press and hold the recessed test switch with a 0.1
inch maximum diameter tool such as an allen wrench
or small screwdriver.
Notify the proper authorities the system is back in
operation.
3. The detector’s LED should light within 5 seconds.
A78-2336-01
Figure 4. Top and side views showing position of test switch:
D200-62-00 3 I56-932-01
A78-2564-00
WARNING
REMOVABLE
HOUSING
REMOVABLE
SCREEN
BASE
SENSING
CHAMBER
Maintenance
NOTE: Before removing the detector, notify the proper
authorities that the smoke detector system is undergoing maintenance and will be temporarily out
of service. Disable the zone or system undergoing
maintenance to prevent unwanted alarms.
NOTE: (Model 2112/24TB only) Before removing the de-
tector cover, note the position of the thermistors.
Make sure the thermistors are not bent over when
the housing is replaced.
1. Remove the detector housing by gently prying the four
housing tabs on the bottom of the base with a smallbladed screwdriver and pull the housing from the base.
Use caution to avoid damaging the thermistors (2112/
24TB only).
2. Vacuum the screen carefully without removing it.
3. Remove screen assembly, pulling straight out (Figure 5).
4. Clean the sensing chamber by vacuuming or blowing out
dust and particles.
5. Replace the screen by orienting it so that the arrow
on the top aligns with the arrow on the printed circuit
board. Carefully press the screen assembly onto the
sensing chamber, making sure it ts tightly.
6. Replace the housing by aligning the three triangular
slots on the base with their counterparts on the housing.
Gently press the housing until it locks in place. Check
to make sure that the thermistors are in the upright position (2112/24TB).
7. Reinstall the detector.
8. Notify the proper authorities that the system is back in
operation.
Figure 5. Removal of Cover and Screen for Cleaning
A78-2565-00
This smoke detector is designed to activate and initiate emergency action, but will do so only when it is used in conjunction with an authorized
re alarm system. This detector must be installed in accordance with
NFPA standard 72.
Smoke detectors will not work without power. AC or DC powered
smoke detectors will not work if the power supply is cut off.
Smoke detectors will not sense res which start where smoke does
not reach the detectors. Smoldering res typically do not generate a lot
of heat which is needed to drive the smoke up to the ceiling where the
smoke detector is usually located. For this reason, there may be large delays in detecting a smoldering re with either an ionization type detector
or a photoelectric type detector. Either one of them may alarm only after
aming has initiated which will generate the heat needed to drive the
smoke to the ceiling.
Smoke from res in chimneys, in walls, on roofs or on the other side of a
closed door(s) may not reach the smoke detector and alarm it. A detector
cannot detect a re developing on another level of a building quickly or
at all. For these reasons, detectors shall be located on every level and in
every bedroom within a building.
Smoke detectors have sensing limitations, too. Ionization detectors and
photoelectric detectors are required to pass re tests of the aming and
smoldering type. This is to ensure that both can detect a wide range of
System Sensor warrants its enclosed smoke detector to be free from defects in materials and workmanship under normal use and service for a
period of three years from date of manufacture. System Sensor makes no
other express warranty for this smoke detector. No agent, representative,
dealer, or employee of the Company has the authority to increase or alter
the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any
part of the smoke detector which is found to be defective in materials or
workmanship under normal use and service during the three year period
commencing with the date of manufacture. After phoning System Sensor’s
toll free number 800-SENSOR2 (736-7672) for a Return Authorization
number, send defective units postage prepaid to: System Sensor, Repair
The Limitations of Property Protection Smoke Detectors
Three-Year Limited Warranty
types of res. Ionization detectors offer a broad range of re sensing capability but they are somewhat better at detecting fast aming res than
slow smoldering res. Photoelectric detectors sense smoldering res better than aming res which have little, if any, visible smoke. Because res
develop in different ways and are often unpredictable in their growth, neither type of detector is always best, and a given detector may not always
provide early warning of a specic type of re.
In general, detectors cannot be expected to provide warnings for res
resulting from inadequate re protection practices, violent explosions,
escaping gases which ignite, improper storage of ammable liquids like
cleaning solvents which ignite, other similar safety hazards, arson, smoking in bed, children playing with matches or lighters, etc. Smoke detectors
used in high air velocity conditions may have a delay in alarm due to
dilution of smoke densities created by frequent and rapid air exchanges.
Additionally, high air velocity environments may create increased dust
contamination, demanding more frequent maintenance.
Smoke detectors cannot last forever. Smoke detectors contain electronic
parts. Even though smoke detectors are made to last over 10 years, any
part can fail at any time. Therefore, smoke detectors shall be replaced after
being in service for 10 years. The smoke detector system that this detector is used in must be tested regularly per NFPA 72. This smoke detector
should be cleaned regularly per NFPA 72 or at least once a year.
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174.
Please include a note describing the malfunction and suspected cause
of failure. The Company shall not be obligated to repair or replace units
which are found to be defective because of damage, unreasonable use,
modications, or alterations occurring after the date of manufacture. In no
case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence
or fault. Some states do not allow the exclusion or limitation of incidental
or consequential damages, so the above limitation or exclusion may not
apply to you. This Warranty gives you specic legal rights, and you may
also have other rights which vary from state to state.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.