System Sensor 2100S, 2100TS User Manual

D200-54-00 1 I56-710-14R
2100S and 2100TS Photoelectronic Smoke Detectors
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Before Installing
Please thoroughly read System Sensor manual I56-407, Guide for Proper Use of System Smoke Detectors, which pro­vides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available at no charge from System Sensor.
NOTICE: This manual shall be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained regularly following NFPA 72 requirements. The detector should be cleaned at least once a year.
General Description
Model 2100S is a 2-wire photoelectronic smoke detector that uses a state-of-the-art optical sensing chamber. This detector is designed to provide open area protection and to be used with compatible UL-listed panels only. Model 2100TS features a restorable, built-in, fixed-temperature (135°F) thermal detector.
Specifications
Diameter: 5.5 inches (140 mm) Height (including mounting bracket): 1.9 inches (48 mm) Weight: 5.3 oz. (150 g) Operating Temperature Range: Model 2100S: 32° to 120°F (0° to 50°C)
Model 2100TS: 32° to 100°F (0° to 38°C) Operating Humidity Range: 10% to 93% Relative Humidity, Noncondensing Latching Alarm: Reset by momentary power interruption Heat Sensor (Model 2100TS only): 135°F Fixed Temperature Electronic Thermistor
Electrical Ratings
System Voltage – Nominal: 12 or 24 VDC
Minimum: 8.5 VDC
Maximum: 35 VDC Maximum Ripple Voltage: 30% of nom. Voltage (peak to peak) Start-up Capacitance: 0.02 µF maximum Standby Current: 50 µA maximum Alarm Ratings: 4.2 VDC minimum at 10 mA.
6.6 VDC maximum at 130 mA.
(Alarm current must be limited to 130 mA maximum by the control panel. If
used, the RA400Z Remote Annunciator operates within the specified detector
alarm currents.) Reset Voltage: 2.5 VDC minimum Reset Time: 0.3 seconds maximum Start-up Time: 30 seconds maximum (after 60 second reset)
Installation of these detectors is simplified by the use of a mounting bracket and a plug-in screw terminal block that can be prewired to the system, allowing the detector to be easily installed or removed. The detector’s sensitivity can be tested in place using the MOD400R Test Module.
An LED on the detector provides a local visual indication of the detector’s status. If power is applied to the detector, and it is functioning normally in standby mode within the listed sensitivity ranges, the status LED blinks once every ten sec­onds. The LED also provides a visual indication that main­tenance is required. If the LED stops blinking, the detector is either not powered, out of the listed sensitivity range, and/or unable to function properly. The test switch will not operate if the detector is below the insensitive limit. The LED will also latch on when the detector is in alarm.
D200-54-00 2 I56-710-14R
The detectors also include an output that allows an option­al Model RA400Z Remote Annunciator to be connected.
Mounting
Each 2100S and 2100TS detector is supplied with a mount­ing bracket that permits the detector to be mounted:
1. To a single gang box, or
2. Directly to a 31/2-inch or 4-inch octagonal box, or
3. To a 4 inch square electrical box by using a plaster ring.
4. Directly to the ceiling using drywall anchors, if permit­ted by local codes and/or the authority having jurisdic­tion.
Tamper-resistance Feature
This detector includes a tamper-resistant feature that pre­vents its removal from the bracket without the use of a tool. To make the detector tamper-resistant, remove the smaller tab by breaking it at the scribed line on the tamper-resist­ant tab on the detector mounting bracket (see Figure 2), then install the detector. To remove the detector from the bracket once it has been made tamper resistant, use a small screwdriver to depress the tamper-resistant tab, locat­ed in the slot on the mounting bracket, and turn the detec­tor counterclockwise.
Wiring Installation Guidelines
All wiring must be installed in compliance with the National Electrical Code, applicable local codes, and any special requirements of the local authority having jurisdic­tion. Proper wire gauges should be used. The conductors used to connect smoke detectors to control panels and
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;;;;;;;;
Figure 1. Surface mounting of 2100S smoke detec­tor on 3 1/2-inch and 4-inch octagonal box:
A78-2563-00
accessory devices should be color-coded to reduce the like­lihood of wiring errors. Improper connections can prevent a system from responding properly in the event of a fire.
The screw terminal block will accept 14 – 22 gauge wire. For best system performance, all wiring should be installed in separate grounded conduit; do not mix fire system wiring in the same conduit as any other electrical wiring. Tw isted pair may be used to provide additional protection against extraneous electrical interference.
Wire connections are made by stripping about 1/4inch of insulation from the end of the feed wire, inserting the wire into the appropriate terminal, and tightening the screw to secure the wire in place.
System Sensor smoke detectors are marked with a compat­ibility identifier located as the last digit of a five digit code stamped on the back of the product. Connect detectors only to compatible control units as indicated in System Sensor’s compatibility chart which contains a current list of UL list­ed compatible control units and detectors. A copy of this list is available from System Sensor upon request.
Installation
Remove power from the control unit or initiating-device circuits before installing detectors.
1. Wire the plug-in screw terminal block per Figure 3 and plug the terminal block into the detector.
2. Align the arrows on the detector with the arrows on the mounting bracket.
3. Turn the detector clockwise in the mounting bracket until it clicks into place.
4. After all detectors have been installed, apply power to the control unit or initiating-device circuits.
5. Test the detector as described in TESTING. (See page 3.)
6. Reset the detector at the system control panel.
7. Notify the proper authorities the system is in operation.
Figure 2. 2100S and 2100TS smoke detector mounting bracket:
A78-2333-01
TAMPER SLOT (DEPRESS TAB TO REMOVE DETECTOR)
TAMPER RESISTANT TAB (CUT OFF SMALL TAB TO ACTIVATE TAMPER-RESIST FEATURE)
ALIGNMENT ARROWS
C
O
V
E
R
R
E
M
O
V
A
L
C
O
V
E
R
R
E
M
O
V
A
L
WARNING
D200-54-00 3 I56-710-14R
Dust covers are an effective way to limit the entry of dust into smoke detector sensing chambers. However, they may not completely prevent airborne dust particles from enter­ing the detector. Therefore, System Sensor recommends the removal of detectors before beginning construction or other dust producing activity. Be sure to remove dust covers from any sensors that were left in place during construction as part of returning the system to service.
Testing
the smoke detector system is undergoing mainte­nance and will temporarily be out of service. Disable the zone or system undergoing mainte-
nance to prevent unwanted alarms. Detectors must be tested after installation and following periodic maintenance. Test the 2100S as follows: A. Test Switch
1. A recessed test switch is located on the detector hous­ing (See Figure 4).
2. Push and hold the recessed test switch with a 0.18 inch maximum diameter tool such as an allen wrench or small screwdriver.
3. The detector’s LED should light within 5 seconds.
OPTIONAL CLASS A WIRING
EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER
UL LISTED
COMPATIBLE
CONTROL
PANEL
INITIATING
LOOP
+
RA400Z
REMOTE
ANNUNCIATOR
+ –
RA400Z
REMOTE
ANNUNCIATOR
+ –
+ +
– LED
+
+ +
– LED
+
Figure 3. Wiring diagram for the 2100S and 2100TS detector:
A78-2331-02
B. Test Module (System Sensor Model No. MOD400R).
The MOD400R test module can be used with a DMM or analog voltmeter to check the detector sensitivity as described in the test module’s manual.
C. Smoke Entry Test
Hold a smoldering punk stick or cotton wick at the side of the detector and gently blow smoke through the detector until the unit alarms.
D. Direct Heat Method (Model 2100TS only – Hair dryer of
1000-1500 watts). Direct the heat toward either of the side thermistors. Hold the heat source about 12 inches from the detector in order to avoid damage to the plastic. The detector will reset only after it has had sufficient time to cool and the
power source has been momentarily interrupted. Both smoke and heat detection testing are recommended for verifying system protection capability.
A detector that fails to activate with any of the above tests should first be cleaned as outlined in the MAINTENANCE section which follows. If the detector still fails to activate, it should be returned for repair.
Notify the proper authorities the system is back on line.
Figure 4. Top and side views showing position of test switch:
PUSH RECESSED SWITCH WITH A
0.18 MAX. DIAMETER TOOL
LED
TEST MODULE SOCKET
RECESSED TEST SWITCH
C
O
V
E
R
R
E
M
O
V
A
L
C
O
V
E
R
R
E
M
O
V
A
L
A78-2564-05
CAUTION
D200-54-00 4 I56-710-14R
©
2001 System Sensor
Three-Year Limited Warranty
System Sensor warrants its enclosed smoke detector to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this smoke detector. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the smoke detector which is found to be defective in materials or work­manship under normal use and service during the three year period com­mencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Repair
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental dam­ages for breach of this or any other Warranty, expressed or implied what­soever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
Maintenance
NOTE: Before removing the detector, notify the proper
authorities that the smoke detector system is undergoing maintenance and will temporarily be out of service. Disable the zone or system under­going maintenance to prevent unwanted alarms.
1. Remove cover by turning counter-clockwise in the direc­tion of arrow.
2. Vacuum the cover carefully.
3. Remove the sensing chamber cover (See Figure 5).
4. Clean the sensing chamber by vacuuming or blowing out dust and particles.
5. Replace the sensing chamber cover, aligning the arrow on the top of the chamber cover with the arrow on the housing.
6. Replace the cover by placing it over the sensing cham ber cover and twisting until it snaps into place.
7. Reinstall the detector.
8. Notify the proper authorities the system is back in operation.
Figure 5. Removal of cover and screen for cleaning:
A78-2565-07
Please refer to insert for the Limitations of Fire Alarm Systems
REMOVABLE SCREEN/COVER (PART NO. C58-357-XX)
SENSING CHAMBER COVER
HOUSING
Loading...