System Sensor 2100ARFT Installation Instructions Manual

CAUTION
Note
System Sensor™ Smoke Sensor Model 2100ARFT
Document Number: 466-1747 Rev. C September 2000
Product Summary
The System Sensor Smoke Sensor Model 2100ARFT (smoke alarm) is a Learn Mode, wireless, photoelectric smoke sensor with a self-contained alarm siren, a low-bat­tery annunciator, and a status light. The smoke al arm is par t of a security/fire alarm system and communicates with the system control panel.
Each smoke alarm uses two 3-volt lithium batteries. The batteries are shipped in the unit with a pull tab inserted at the positive terminal. Remove the pull tab and reinstall the batteries as needed, observing correct polarity.
The detector provides the following features: Fixed/rate of rise 135° F temperature heat detector
trips an alarm when the temperature reaches 135° F or higher, or when the temperature rises rapidly.
Freeze detector sends a trouble signal when the ambi-
ent temperature around the detector drops below 40° F. This could indicate a heating problem on the premises. System sirens sound trouble beeps, and if the condition continues for one hour, the panel reports to central monitoring station.
ITI Part No. 60-838-95, 60-838-95R
Installation Instructions
Not compatible with CareTaker® versions with software versions 3.0 or earlier. Not compatible with Commander® 2000 and custom versions with software versions 4.0 or earlier.
Plus
and custom
Equipment Needed
Phillips screwdriver. Pocket-sized slotted screwdriver.
Programming
This section describes the basic steps for adding the sensor to panel memory. For more detailed programming informa­tion, refer to the specific panel installation instructions.
Note
Freeze detector only compatible with Concord™, Con­cord Express™, Ultragard®, and Advent® systems. Simon® systems will only r es pond on site with troubl e beeps and will not report the trouble condition to the central monitoring station.
Installation Guidelines
This equipment should be installed in accordance with
the National Fire Protection Association’s Standard 72 and/or Standard 74 (National Fire Protection Associa­tion, Batterymarch Park, Quincy, MA 02269).
Avoid installing the unit until all construction is com-
pleted. The mounting ring may be pre-installed.
Leave the orange dust cover on the unit until sheet
rocking and sanding are completed; otherwise, dust can get into the unit and cause false alarms.
Note
The orange dust cover must be removed for the unit to detect smoke.
Figure 1. Mounting Bracket
To add the smoke alarm to panel memory:
1. Put the panel in Program Mode/Learn Sensors.
2. Select a sensor group and sensor number.
3. Remove mounting bracket to trip tamper.
4. The panel will indicate that the sensor has been learned.
5. Exit from program mode.
Reinstall smoke unit on mounting bracket. This restores the tamper to normal—it may take the micro­processor in the smoke unit up to 12 seconds to restore the tamper.
Mounting Guidelines
Selecting a suitable location is critical to the operation of smoke alarms/detectors. This equipment should be installed
System Sensor™ Smoke Sensor Model 2100ARFT
1
Mounting Guidelines
in accordance with the National Fire Protection Associa­tion’s (NFPA) Standard 72, Chapter 8.
NFPA 72, A-8-1.2.1.a Where to Locate the Required
Smoke Alarms/Detectors in Existing Construction. The
major threat from fire in a family living unit occurs at night when everyone is as leep. The principal threat to persons in sleeping areas comes from fires in the remainder of the unit. Therefore, a smoke alarm(s)/ detector(s) is best located between the bedroom areas and the rest of the unit. In units with only one bedroom area on one floor, the smoke alarm(s)/detector(s) should be located as shown in Figure 2.
BEDROOMBEDROOMKITCHENDINING
LIVING ROOM
SMOKE ALARMS/DETECTORS FOR MINIMUM PROTECTION SMOKE ALARMS/DETECTORS FOR ADDITIONAL PROTECTION HEAT ACTIVATED ALARMS/DETECTORS
Figure 2.Family units with one bedroom area.
BATH
BEDROOM
In family units with more than one bedroom area or with bedrooms on more than one floor, more than one smoke alarm/detector is required, as shown in Figure 3.
KITCHEN
DINING ROOM
TV ROOM
BATHROOM
BEDROOM
Figure 3.Family units with more than one bedroom
area.
LIVING ROOM
SMOKE ALARMS/DETECTORS FOR MINIMUM PROTECTION
SMOKE ALARMS/DETECTORS FOR ADDITIONAL PROTECTION
HEAT ACTIVATED ALARMS/DETECTORS
BEDROOM
BEDROOM
BEDROOM
BASEMENT
BEDROOM
KITCHEN
GARAGE
BEDROOM
LIVING ROOM
SMOKE ALARMS/DETECTORS FOR MINIMUM PROTECTION SMOKE ALARMS/DETECTORS FOR ADDITIONAL PROTECTION HEAT ACTIVATED ALARMS/DETECTORS
Figure 4.Multilevel residence.
NFPA 72, A-8-1.2.1.b Where to Locate the Required Smoke Alarms/Detectors in New Construction. All of
the smoke alarms/detectors specified in A-8-1.2.1.a for existing construction are required, and, in addition, a smoke detector is required in each bedroom.
NFPA 72, A-8-1.2.1.c Are More Smoke Alarms/ Detectors Desirable? The required number of smoke alarms/detectors might not provide reliable early warning protection for those areas separated by a door from the areas protected by the require d smoke a larms/ detectors. For this reason, it is recommended that the householder consider the use of additional smoke alarms/detectors for those areas for increased protection. The additional areas include the basement, bedrooms, dining room, furnace room, utility room, and hallways not protected by the required smoke alarms/detectors. The installation of smoke alarms/ detectors in kitchens, attics (finished or unfinished), or garages is not normally recommended, as these locations occasionally experience conditions that can result in improper operation.
Important !
Regulations perta in in g to smo ke al ar m/d ete ctor in sta l­lations vary from state to state. For more information, contact your local fire department or local authority having jurisdiction.
In addition to smoke alarms/detectors outside of the sleeping areas, Chapter 8 requires the installation of a smoke alarm/detector on each additional story of the family living unit, including the basement. These installations are shown in Figure 4. The living area smoke alarm/detector should be installed in the living room or near the stairway to the upper leve l, or i n both locations. The basement smoke alarm/detector should be installed in close proximity to the stairway leading to the floor above. Where installed on an open-joisted ceiling, the alarm/detector should be positioned relative to the stairway so as to intercept smoke coming from a fire in the basement before smoke enters the stairway.
2
DO NOT mount a smoke alarm to a dr op ceiling tile;
mount it to a metal runner (see figure 5).
Figure 5.Smoke alarm mounted to drop ceiling.
Mount all smoke alarms within 100 feet of the panel or
receiver.
Install a minimum of two smoke alarms in any house-
hold, no matter how small it is.
Put a smoke alarm in the hallway outside of every bed-
room area. A minimum of two smoke alarms are required in homes with two bedroom areas.
System Sensor™ Smoke Sensor Model 2100ARFT
Mounting
Put a smoke alarm on every level of a multi-level resi-
dence.
Install basement alarms on the ceiling at the bottom of
the basement stairwell.
Install smoke alarms on the ceiling as close to the cen-
ter of the room as possible. If this is not practical, install it on the ceiling no closer than 4 inches (10 cm) from any wall or corner (see figure 6).
If ceiling mounting is not practical, install on an inside
wall between 4 and 6 inches (10 and 15 cm) from the ceiling (see figure 6).
Put smoke alarms at both ends of a bedroom hallw ay if
the hallway is more than 30 feet (9 meters) long. Large rooms over 900 square feet require more than a single sensor.
NO CLOSER THAN 4
DEAD AIR
SPACE
Figure 6.Smoke alarm mounting locations
BEST IN CENTER
OF CEILING
BEST LOCATION ACCEPTABLE LOCATION
"
(10 cm)
FROM SIDE WALL
MOUNT ON WALL
AT LEAST 4
"
FROM CEILING
NO MORE
"
(15 cm)
THAN 6
FROM CEILING
(10 cm)
Areas with rough ceilings or short, transom-type walls
coming down from the ceiling require additional smoke alarms.
Install second-floor smoke alarms on the ceiling at the
top of the first-to-second floor stairwell. Be sure no door or other obstruction blocks the path of smoke to the unit.
In rooms with sloped, peaked, or gabled ceilings,
install smoke alarms 3 feet (0.9 meter) measured down on the slant from the highest point of the ceiling (see figure 7).
HORIZONTAL
DISTANCE
FROM PEAK
3 FEET
(.9M)
roofs, or smoke blocked by a closed door.
Alarms may not detect smoke on other levels of the
building.
Alarms may not warn in time when fires are caused by
smoking in bed, explosions, improper storage of flam­mables, overloaded electrical circuits, or other hazard­ous conditions.
Do Not Install Smoke Alarms in the Following Locations:
In or near areas where combustion particles are nor-
mally present such as kitchens; in garages where there are particles of combustion in vehicle exhausts; near furnaces, hot water heaters, or gas space heaters.
On the ceiling in rooms next to kitchens where there is
no transom between the kitchen and these rooms.
In damp or very humid areas, or next to bathrooms with
showers. Install sensors at least 5 feet (1.5 meters) away from bathrooms.
In very cold or very hot areas. In dusty, dirty, or insect-infested areas. Near fresh air inlets or returns or excessively drafty
areas. Air conditioners, heaters, fans, and fresh air intakes and returns can drive smoke away from smoke alarms.
In dead air spaces at the top of a peaked ceil in g or wall /
ceiling intersect. Dead air may prevent smoke from reaching a smoke alarm.
Near fluorescent light fixtures. Install smoke alarms at
least 10 feet (3 meters) away from fluorescent light fixtures.
Mounting
The mounting bracket must be separated from the unit before you begin.
To mount the smoke alarm:
1. Secure the mounting bracket directly onto wood sur­faces using No. 8, 1½ inch wood screws. If mounting onto plaster or dry wall, use appropriate anchors.
2. Align the arrows on the mounting bracket with the raised marks on the smoke alarm. Turn the smoke alarm clockwise until it locks in place.
Figure 7.Sloped, peaked, or gabled ceilings
Limitations
All alarms are subject to possible compromise or failure-to­warn for a variety of reasons, for example:
Smoke alarms cannot det ect smoke i n chimne ys, w alls,
System Sensor™ Smoke Sensor Model 2100ARFT
Testing
Test each smoke alarm every week to verify that its siren and signal integrity are ad equate. Refer to the s pecific pa nel installation instructions for system response and sensor testing.
To test the smoke alarm:
1. Put the panel in sensor test mode. Although not neces­sary for this model, it is a good practice to maintain. Refer to the specific panel installation instructions for details.
3
Maintenance
Note
Simon and Advent panels respond to test button acti­vations only when in sensor test mode.
!
WARNING
Commander and CareTaker panels will go into alarm if not in sensor test when the test button is pressed.
2. Press and hold the test button on the smoke alarm for 3 to 4 seconds.
Test Switch
Indicator Light Pulsing: Normal/Thermal Alarm Fast Blink: Smoke Alarm None: Call for Service
Figure 8.Smoke Alarm Test Switch and Indicator Light.
A78-2332-03
The sensor should immediately transmit a test alarm signal, causing the siren inside the smoke alarm to sound and the status light to flash rapidly while the test button is pressed. Refer to the specific panels installation instructions for system response details.
Note
After verifying that the siren and signal integrity are adequate, you may want to cover the center opening with your thumb. This will help reduce the siren noise until the test is completed.
Maintenance
Note
For UL installations, use the following battery brands: Sanyo CR123A, Panasonic CR123A, or Duracell DL123A. These can be obtained through Interactive Technologies, Inc. Do not mix brands.
Cleaning
Clean the smoke alarm chamber at least once each year.
REMOVABLE HOUSING
REMOVABLE SCREEN
SENSING CHAMBER COVER
SENSING CHAMBER
BASE
Figure 9.Smoke Alarm diagram
To clean the smoke alarm chamber:
1. Place the panel in sensor test mode.
2. Remove smoke alarm from mounting ring.
3. Remove the batteries.
4. Separate housing from base.
5. Remove screen and chamber housing.
6. Vacuum screen, chamber housing, and chamber.
7. Reassemble smoke alarm.
8. Re-install the batteries.
9. Attach smoke alarm to mounting ring.
10. Test operation as describe in the “Testing” section.
Replacing Batteries
When the batteries need to be replaced, the unit transmits a signal to the panel. If the batteries are not replaced within 7 days, the unit will chirp every 44 seconds until the unit shuts down in 7-8 days.
Note
If you test the smoke alarm or it goes into alarm dur­ing this initial 7-day period, chirp delay is can­celed.The unit will th e n b e gin chirping continuously at 44 second intervals until the unit shuts down in 7-8 days.
Constant exposure to high or low temperatures or high humidity may reduce battery life. Replace both batteries when the smoke alarm or panel notifies you that the batteries are low.
4
Servicing
In the event that the smoke alarm needs servicing, send it to: Interactive Technologies, Inc., 2266 Second St. North, North St. Paul, MN 55109.
Emergencies
Develop plans for a variety of emergency situations. Periodically discuss and rehearse emergency plans that include the following:
Know the normal state of doors and windows; open,
closed, or locked.
Use a different escape route if closed doors feel hot to
the touch.
Emphasize that everyone should escape as quickly as
possible. Do not stop to gather any belongings.
Crawl and hold your breath as much as possible to help
reduce smoke inhalation during your escape.
System Sensor™ Smoke Sensor Model 2100ARFT
Emergencies
N
Meet at a designated outdoor location. Emphasize that no one should return to the premises if
there is a fire.
Notify fire department from a neighbor’s phone.
!
WARNING
If you arrive at the premises and hear sirens, do not attempt to enter the building. Call for emer­gency assistance from a neighbor’s phone.
Floor Plan Example
Figure 10 is an example of a multi le ve l f lo or plan. Use it as a guide and draw your floor plan on the next page.
SMOKE ALARMS/DETECTORS FOR MINIMUM PROTECTION SMOKE ALARMS/DETECTORS FOR ADDITIONAL PROTECTIO HEAT ACTIVATED ALARMS/DETECTORS
A smoke detector should be located on each level.
BEDROOM BEDROOM
BATH
BEDROOM
BASEMENT
BEDROOM BEDROOM LIVING ROOM
Smoke detectors should be located between the sleeping area and the rest of the family living unit.
RECREATION
ROOM
KITCHEN
BASEMENT
DINING ROOM
ATTIC
LIVING ROOM
BEDROOMBEDROOM
KITCHEN
LIVING ROOM
Your Floor Plan
When establishing your escape routes, consider the following guidelines:
Show all building levels. Show all exits, (two exits per room are recommended). Show the location of all components of the fire system. Show the locations of any fire extinguishers, hoses,
ladders, etc.
TV
ROOM
BEDROOM
DINING ROOM
LIVING ROOM
KITCHEN
BEDROOM
BEDROOM
In family living units with more than one sleeping area, locate a smoke
BATH
detector at each area.
Figure 10.Examples of a floor plans.
System Sensor™ Smoke Sensor Model 2100ARFT
5
Emergencies
Draw you floor plan in this space.
6
System Sensor™ Smoke Sensor Model 2100ARFT
Troubleshooting
Security
Automation
Fire Protection
Access Control
www.itii.com
T: 651/777-2690 F: 651/779-4890
I
nteractive Technologies, Inc.
2266 Second Street North North Saint Paul, MN 55109-2900
1-800-777-1415
WIRELESS
Troubleshooting
The panel fails to indicate that the sensor has been learned.
Check panel programming. If necessary, reprogram the
sensor following the steps outlined in the Programming section.
Check sensor batteries.
The sensor fails to transmit an alarm signal when in test mode.
Check sensor batteries. Check panel programming. If necessary, reprogram the
sensor following the steps outlined in the Programming section.
Specifications
Compatibility: 60-838-95 Advent, Commander 2000 and
Custom Versions with software versions 4.1 and later, UltraGard and Custom Versions, CareTaker Plus and Custom Versions with software versions 4.0 and later, Concord, Concord Express, Simon, Quik Bridge Loop Receivers, and Quik Bridge® Repeater.
60-838-95R Concord, Concord Express, Simon,
Current: 12.5µA typical
Sensitivity Test: Use canned smoke SM-200 or
Dimensions: 2.0 × 5.0 (without mounting
Temperature Range:
Operating 32° to 100°F (0° to 38°C) Storage -4° to 140°F (-20° to 60°C)
Humidity: 90% non-condensing Power Source: Two 3-volt lithium batteries of the
Sensitivity Levels:
Nominal: 1.00%/ft - 3.54%/ft obscuration Nominal Supervisory: 2.25%/ft obscuration Nominal Close to Alarm:
Nominal at Alarm: LED blinks once per second.
and Quik Bridge Loop Receivers.
28µA peak
54.8mA in alarm (average)
equivalent
bracket)
2.0 × 5.5 (with mounting brac ket)
same type. UL-approved typ es: Sanyo CR123A, Panasonic CR123A, Duracell DL123A.
LED stops blinking at 44 sec. intervals.
Notices
Agency Listings
UL 217—Residential Installations UL 268—Commercial Installations CUL—S531 - M87 Standard for Smoke Alarms
FCC Part 15 Information to the User
Changes or modifications not expressly approved by Interactive Technolo­gies, Inc. can void the user’s authority to operate the equipment.
This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions:
This device may not cause harmful interference. This device must accept any interference received, including interfer-
ence that may cause undesired operation.
Changes or modifications not expressly approved by Interactive Technolo­gies, Inc. can void the user’s authority to operate the equipment.
FCC ID: B4Z-764A-SMOKE CANADIAN IC: 867-102-1644 Patent No.: 4,855,713 and 5,686,885 and 5,686,896 and 5,761,206
ITI Advent, CareTaker, Commander, UltraGard, Quik Bridge, and Simon are registered trademarks of Interactive Technologies, Inc. Concord, Con­cord Express, and Learn Mode are trademarks of ITI. System Sensor is a trademark of System Sensor.
System Sensor™ Smoke Sensor Model 2100ARFT
7
Loading...