System Sensor 2100ARFT Installation Instructions Manual

CAUTION
Note
System Sensor™ Smoke Sensor Model 2100ARFT
Document Number: 466-1747 Rev. C September 2000
Product Summary
The System Sensor Smoke Sensor Model 2100ARFT (smoke alarm) is a Learn Mode, wireless, photoelectric smoke sensor with a self-contained alarm siren, a low-bat­tery annunciator, and a status light. The smoke al arm is par t of a security/fire alarm system and communicates with the system control panel.
Each smoke alarm uses two 3-volt lithium batteries. The batteries are shipped in the unit with a pull tab inserted at the positive terminal. Remove the pull tab and reinstall the batteries as needed, observing correct polarity.
The detector provides the following features: Fixed/rate of rise 135° F temperature heat detector
trips an alarm when the temperature reaches 135° F or higher, or when the temperature rises rapidly.
Freeze detector sends a trouble signal when the ambi-
ent temperature around the detector drops below 40° F. This could indicate a heating problem on the premises. System sirens sound trouble beeps, and if the condition continues for one hour, the panel reports to central monitoring station.
ITI Part No. 60-838-95, 60-838-95R
Installation Instructions
Not compatible with CareTaker® versions with software versions 3.0 or earlier. Not compatible with Commander® 2000 and custom versions with software versions 4.0 or earlier.
Plus
and custom
Equipment Needed
Phillips screwdriver. Pocket-sized slotted screwdriver.
Programming
This section describes the basic steps for adding the sensor to panel memory. For more detailed programming informa­tion, refer to the specific panel installation instructions.
Note
Freeze detector only compatible with Concord™, Con­cord Express™, Ultragard®, and Advent® systems. Simon® systems will only r es pond on site with troubl e beeps and will not report the trouble condition to the central monitoring station.
Installation Guidelines
This equipment should be installed in accordance with
the National Fire Protection Association’s Standard 72 and/or Standard 74 (National Fire Protection Associa­tion, Batterymarch Park, Quincy, MA 02269).
Avoid installing the unit until all construction is com-
pleted. The mounting ring may be pre-installed.
Leave the orange dust cover on the unit until sheet
rocking and sanding are completed; otherwise, dust can get into the unit and cause false alarms.
Note
The orange dust cover must be removed for the unit to detect smoke.
Figure 1. Mounting Bracket
To add the smoke alarm to panel memory:
1. Put the panel in Program Mode/Learn Sensors.
2. Select a sensor group and sensor number.
3. Remove mounting bracket to trip tamper.
4. The panel will indicate that the sensor has been learned.
5. Exit from program mode.
Reinstall smoke unit on mounting bracket. This restores the tamper to normal—it may take the micro­processor in the smoke unit up to 12 seconds to restore the tamper.
Mounting Guidelines
Selecting a suitable location is critical to the operation of smoke alarms/detectors. This equipment should be installed
System Sensor™ Smoke Sensor Model 2100ARFT
1
Mounting Guidelines
in accordance with the National Fire Protection Associa­tion’s (NFPA) Standard 72, Chapter 8.
NFPA 72, A-8-1.2.1.a Where to Locate the Required
Smoke Alarms/Detectors in Existing Construction. The
major threat from fire in a family living unit occurs at night when everyone is as leep. The principal threat to persons in sleeping areas comes from fires in the remainder of the unit. Therefore, a smoke alarm(s)/ detector(s) is best located between the bedroom areas and the rest of the unit. In units with only one bedroom area on one floor, the smoke alarm(s)/detector(s) should be located as shown in Figure 2.
BEDROOMBEDROOMKITCHENDINING
LIVING ROOM
SMOKE ALARMS/DETECTORS FOR MINIMUM PROTECTION SMOKE ALARMS/DETECTORS FOR ADDITIONAL PROTECTION HEAT ACTIVATED ALARMS/DETECTORS
Figure 2.Family units with one bedroom area.
BATH
BEDROOM
In family units with more than one bedroom area or with bedrooms on more than one floor, more than one smoke alarm/detector is required, as shown in Figure 3.
KITCHEN
DINING ROOM
TV ROOM
BATHROOM
BEDROOM
Figure 3.Family units with more than one bedroom
area.
LIVING ROOM
SMOKE ALARMS/DETECTORS FOR MINIMUM PROTECTION
SMOKE ALARMS/DETECTORS FOR ADDITIONAL PROTECTION
HEAT ACTIVATED ALARMS/DETECTORS
BEDROOM
BEDROOM
BEDROOM
BASEMENT
BEDROOM
KITCHEN
GARAGE
BEDROOM
LIVING ROOM
SMOKE ALARMS/DETECTORS FOR MINIMUM PROTECTION SMOKE ALARMS/DETECTORS FOR ADDITIONAL PROTECTION HEAT ACTIVATED ALARMS/DETECTORS
Figure 4.Multilevel residence.
NFPA 72, A-8-1.2.1.b Where to Locate the Required Smoke Alarms/Detectors in New Construction. All of
the smoke alarms/detectors specified in A-8-1.2.1.a for existing construction are required, and, in addition, a smoke detector is required in each bedroom.
NFPA 72, A-8-1.2.1.c Are More Smoke Alarms/ Detectors Desirable? The required number of smoke alarms/detectors might not provide reliable early warning protection for those areas separated by a door from the areas protected by the require d smoke a larms/ detectors. For this reason, it is recommended that the householder consider the use of additional smoke alarms/detectors for those areas for increased protection. The additional areas include the basement, bedrooms, dining room, furnace room, utility room, and hallways not protected by the required smoke alarms/detectors. The installation of smoke alarms/ detectors in kitchens, attics (finished or unfinished), or garages is not normally recommended, as these locations occasionally experience conditions that can result in improper operation.
Important !
Regulations perta in in g to smo ke al ar m/d ete ctor in sta l­lations vary from state to state. For more information, contact your local fire department or local authority having jurisdiction.
In addition to smoke alarms/detectors outside of the sleeping areas, Chapter 8 requires the installation of a smoke alarm/detector on each additional story of the family living unit, including the basement. These installations are shown in Figure 4. The living area smoke alarm/detector should be installed in the living room or near the stairway to the upper leve l, or i n both locations. The basement smoke alarm/detector should be installed in close proximity to the stairway leading to the floor above. Where installed on an open-joisted ceiling, the alarm/detector should be positioned relative to the stairway so as to intercept smoke coming from a fire in the basement before smoke enters the stairway.
2
DO NOT mount a smoke alarm to a dr op ceiling tile;
mount it to a metal runner (see figure 5).
Figure 5.Smoke alarm mounted to drop ceiling.
Mount all smoke alarms within 100 feet of the panel or
receiver.
Install a minimum of two smoke alarms in any house-
hold, no matter how small it is.
Put a smoke alarm in the hallway outside of every bed-
room area. A minimum of two smoke alarms are required in homes with two bedroom areas.
System Sensor™ Smoke Sensor Model 2100ARFT
Mounting
Put a smoke alarm on every level of a multi-level resi-
dence.
Install basement alarms on the ceiling at the bottom of
the basement stairwell.
Install smoke alarms on the ceiling as close to the cen-
ter of the room as possible. If this is not practical, install it on the ceiling no closer than 4 inches (10 cm) from any wall or corner (see figure 6).
If ceiling mounting is not practical, install on an inside
wall between 4 and 6 inches (10 and 15 cm) from the ceiling (see figure 6).
Put smoke alarms at both ends of a bedroom hallw ay if
the hallway is more than 30 feet (9 meters) long. Large rooms over 900 square feet require more than a single sensor.
NO CLOSER THAN 4
DEAD AIR
SPACE
Figure 6.Smoke alarm mounting locations
BEST IN CENTER
OF CEILING
BEST LOCATION ACCEPTABLE LOCATION
"
(10 cm)
FROM SIDE WALL
MOUNT ON WALL
AT LEAST 4
"
FROM CEILING
NO MORE
"
(15 cm)
THAN 6
FROM CEILING
(10 cm)
Areas with rough ceilings or short, transom-type walls
coming down from the ceiling require additional smoke alarms.
Install second-floor smoke alarms on the ceiling at the
top of the first-to-second floor stairwell. Be sure no door or other obstruction blocks the path of smoke to the unit.
In rooms with sloped, peaked, or gabled ceilings,
install smoke alarms 3 feet (0.9 meter) measured down on the slant from the highest point of the ceiling (see figure 7).
HORIZONTAL
DISTANCE
FROM PEAK
3 FEET
(.9M)
roofs, or smoke blocked by a closed door.
Alarms may not detect smoke on other levels of the
building.
Alarms may not warn in time when fires are caused by
smoking in bed, explosions, improper storage of flam­mables, overloaded electrical circuits, or other hazard­ous conditions.
Do Not Install Smoke Alarms in the Following Locations:
In or near areas where combustion particles are nor-
mally present such as kitchens; in garages where there are particles of combustion in vehicle exhausts; near furnaces, hot water heaters, or gas space heaters.
On the ceiling in rooms next to kitchens where there is
no transom between the kitchen and these rooms.
In damp or very humid areas, or next to bathrooms with
showers. Install sensors at least 5 feet (1.5 meters) away from bathrooms.
In very cold or very hot areas. In dusty, dirty, or insect-infested areas. Near fresh air inlets or returns or excessively drafty
areas. Air conditioners, heaters, fans, and fresh air intakes and returns can drive smoke away from smoke alarms.
In dead air spaces at the top of a peaked ceil in g or wall /
ceiling intersect. Dead air may prevent smoke from reaching a smoke alarm.
Near fluorescent light fixtures. Install smoke alarms at
least 10 feet (3 meters) away from fluorescent light fixtures.
Mounting
The mounting bracket must be separated from the unit before you begin.
To mount the smoke alarm:
1. Secure the mounting bracket directly onto wood sur­faces using No. 8, 1½ inch wood screws. If mounting onto plaster or dry wall, use appropriate anchors.
2. Align the arrows on the mounting bracket with the raised marks on the smoke alarm. Turn the smoke alarm clockwise until it locks in place.
Figure 7.Sloped, peaked, or gabled ceilings
Limitations
All alarms are subject to possible compromise or failure-to­warn for a variety of reasons, for example:
Smoke alarms cannot det ect smoke i n chimne ys, w alls,
System Sensor™ Smoke Sensor Model 2100ARFT
Testing
Test each smoke alarm every week to verify that its siren and signal integrity are ad equate. Refer to the s pecific pa nel installation instructions for system response and sensor testing.
To test the smoke alarm:
1. Put the panel in sensor test mode. Although not neces­sary for this model, it is a good practice to maintain. Refer to the specific panel installation instructions for details.
3
Loading...
+ 4 hidden pages