System Sensor 2012JA Installation And Maintenance Instructions Manual

2012JA Photoelectric Smoke Alarm with ,QWHJUDO7HPSRUDOTone Sounder
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Smoke Alarm Description
Smoke Alarm Power Requirements
Power input rating to the smoke alarm is 12/24VDC@0.065 amp. Power supply and smoke-alarm installation must conform to the electrical codes in your area and CAN/ULC S553. It is recommended that wiring be performed by a licensed electrician.
Smoke alarm Limitations
This smoke alarm is designed for residential use only. This smoke alarm is self-restoring and does not lock into an alarm condition.
Smoke alarms will not sense a re if the smoke does not reach
the sensor. In order for a smoke alarm to sense smoke, it must be
installed in the immediate vicinity of the re. In addition, smoke from res in chimneys, in walls, on roofs, in remote parts of the building,
or on another level from where the smoke alarm is located, may not reach the smoke alarm quickly enough for occupants to escape unharmed. For this reason, the installer shall install smoke alarms on every level, in every sleeping area, and in every bedroom of the household. Smoke alarms may not be heard. The alarm horn in this smoke alarm meets or exceeds current Underwriter's Laboratories standards. However, if the smoke alarm is not located in the same room as the occupant, or if it is blocked by a closed door or normal noise, the alarm horn may not be heard. In addition,
sound sleepers, or persons who are under the inuence of drugs or
alcohol may not hear the alarm or be able to react to it. Therefore, locate this smoke alarm, which has a sounder rated at 85dBA at 3 meters, on every level, in every sleeping area, and in every bedroom of the household.
In general, smoke alarms may not always warn you about res
caused by carelessness and safety hazards like smoking in bed,
violent explosions, escaping gas, improper storage of ammable
materials, overloaded electrical circuits, children playing with matches, or arson. Smoke alarms are not fool-proof. Like all electronic devices, smoke-alarms have limitations. No type of smoke-alarm can
sense every kind of re every time. In addition, smoke from slow, smoldering res rises slowly and may not reach the smoke alarm until actual ame breaks out. This type of smoke may not reach the
smoke alarm in time for occupants to escape unharmed. Smoke alarms are not a substitute for life or property insurance. Though smoke alarms have been responsible for saving many lives, they are not warranted or implied to protect lives or property in the
event of a re.
To keep your equipment in excellent working order, ongoing maintenance is required per the manufacturer’s recommendations and ULC, a preventative maintenance agreement should be arranged through the local manufacturer’s representative.Though smoke alarms are designed for long life, they may fail at any time. Therefore, smoke alarms shall be replaced after being in service
for 10 years. Any smoke alarm, re alarm equipment, or any
component of that system which fails shall be repaired or replaced as soon as possible.
Where to Install Smoke Alarms
Warning: As a minimum requirement, smoke alarms must be installed in accordance with CAN/ULC-S553. In addition, observe all local and national building and electrical codes.
Proper Smoke Alarm Location:
Figure 1: Recommended smoke alarm protection for single-oor
residence with only one sleeping area
DINING ROOM KITCHEN BEDROOM BEDROOM
BEDROOMLIVING ROOM
SMOKE ALARMS FOR MINIMUM PROTECTION
SMOKE ALARMS FOR MORE PROTECTION AND
REQUIRED IN NEW CONSTRUCTION
6581 Kitimat Rd., Unit #6, Mississauga, Ontario, L5N 3T5
1-800-SENSOR2, FAX: 905-812-0771
www.systemsensor.ca
Specifications:
Supply Voltage Range: 10VDC~30VDC Max. Standby Current: 60µA Max. Alarm Current: 65mA P-Horn Sound Output Level: 85dBA at 3m Max. Interconnected Units: 12 Silence Timeout Period: 8 minutes Silence Mode Indication: Sounder Beeps and LED Flashes Green once every 40 secs. Height: 55mm Diameter: 135mm Weight: 180g Operating Temperature Range 0° to 50° Humidity: 5% to 93% R.H.
1 I56-2012- 4 I56-2012-
Connecting Auxiliary Devices with Relay
This smoke-alarm has a built-in relay which may be used to activate auxiliary devices such as bells, horns, and door closers. The relay contacts automatically close approximately eight (8) seconds after the unit goes
into alarm, and automatically resets approximately ve (5) seconds after
the alarm stops. For wiring refer to Figure 8. Auxiliary voltage and current requirements must be within relay contact ratings and appropriate wiring must be used.
How to Interconnect Smoke Alarms
NOTE:
Interconnect smoke alarms within one household only. If smoke alarms are interconnected between households, nuisance alarms will occur when a smoke alarm in another residence is tested. The model 2012JA has two interconnection modes shown in table 1.
TABLE 1: INTERCONNECTION MODES
Interconnection Mode
Interconnected Terminals
Electronic Horn
Relay
SIGSND SIGSND and
GND
Sound Only the
smoke alarms in local alarm are activated
SIGRLY SIGRLY and
GND
Sound All the
interconnected smoke alarms are activated
Up to twelve 2012JA smoke-alarms may be interconnected. The 2012JA smoke-alarms may also be interconnected with 2012H (A) when they all work at 12VDC supply voltage by using SIGRLY interconnecting terminal. If one smoke alarm senses smoke, all of the interconnected units will sound in SIGSND mode, the relays of the interconnected units will be activated approximately eight seconds after horns sound in SIGRLY mode. After interconnecting the smoke alarms, push and hold the test button for more than 3 seconds on one unit. The alarm horns on all of the other smoke alarms should sound if they are connected correctly. If any interconnected smoke alarm is activated by another unit, it senses smoke, the unit will go into local alarm state with the LED
ashing quickly.
Connect the smoke alarms together by interconnecting all the SIGSND terminals to each other and all GND terminals to each other in SIGSND mode, interconnecting all the SIGRLY and GND terminals to each other in SIGRLY mode. (See Figure 7.) Use 22 guage (#22AWG) or larger two-conductor standard wire. If smoke alarms will not be connected, DO NOT use the SIGSND, SIGRLY and GND terminals.
The LEDs on all smoke alarms should ash once about 40 seconds
when power is turned on to the units.Test smoke alarms after interconnection wiring are complete.
Cautionary Note:
Test interconnection wiring after installation is completed. Test each unit in a system and make sure all other units alarm. FAILURE TO OBSERVE ANY OF THESE CONDITIONS CAN CAUSE SYSTEM MALFUNCTION AND/OR DAMAGE
TO THE ALARMS.
Testing Information
You should test your smoke alarm at least once a week to assure yourself of its operation, as recommended by ULC. Test the smoke
alarm by rmly depressing the test switch located on the smoke
alarm cover (marked “Push and Hold to Test”) FOR MORE THAN 3 SECONDS (See Figure 9). The alarm horn should sound, and the
LED should ash rapidly. When the test switch is pushed and held
for more than 8 seconds, the relay will be activated.
In an interconnected system, all of the smoke alarms should sound their alarm horns when any one of the test buttons is pushed and held for more than 3 seconds. The alarm horn sounds if the smoke alarm is working properly. This is the only way to be sure the
smoke alarm is working. Test the smoke alarm weekly. If the smoke alarm fails to test properly, have it repaired or replaced immediately. DANGER: If the alarm horn sounds an alarm and you are not • testing the smoke alarm, the unit has sensed smoke or combustion particles in the air. THE ALARM HORN IS A
WARNING
OF A POSSIBLY SERIOUS SITUATION. IT REQUIRES YOUR IMMEDIATE ATTENTION.
The alarm could be caused by a nuisance situation. Cooking smoke or a dusty furnace can cause the smoke-alarm to sound. If this happens, open a window or fan the air to remove the smoke or dust. The smoke alarm will turn itself off as soon as the air is completely clear. DO NOT TURN OFF POWER TO THE SMOKE
ALARM. THIS WILL REMOVE YOUR PROTECTION.
Monitoring Your Smoke Alarm
Once the smoke alarm is powered, a green LED ashes once about 40
seconds. This signals that the smoke
alarm is receiving power and is in the detection mode. If the smoke alarm is not operating properly, the green LED will be OFF. (If so, have the smoke alarm repaired or replaced immediately.) When the smoke alarm senses smoke, the green LED will
ash rapidly. If the initiating smoke alarm senses smoke and signals other
interconnected smoke alarms to sound their alarm horns, their LEDs will
stop ashing. See TABLE 2 for specic LED functions.
TABLE 2: SMOKE ALARM STATUS
Smoke alarm Status
Electronic Horn
LED Relay
Normal Standby
Silent Flash every
40 seconds
Open
Silence State Beep every 40
seconds
Flash every 40 seconds
Open
Local Alarm Temporal Tone Flash rapidly Closed after
8 seconds
SIGSND Signal Received
Temporal Tone Off Open
SIGRLY Signal Received
Temporal Tone Of
f Closed after
8 seconds
Failed cham­ber test
Beep every 40 seconds
Flash every 10 seconds
Open
The smoke alarm will automatically return from Alarm to Normal state when the reason for alarm, as the presence of smoke, is completely removed.
As the re is very dangerous for your family, usually you must draw a
family escape plan including a map which shows all your home windows and doors, less than two escape routs, a safe meeting place and other required things in your area. Furthermore your family members should practice the escape plan
at
least twice a year
.
Cleaning and Maintenance DANGER: Electrical Shock Hazard. Turn off power to the smoke alarm at
the main service panel before cleaning the smoke alarm. This smoke alarm has been designed to be as maintenance-free as possible. However, regular testing (see “Testing” above) and periodic maintenance are necessary. To clean the smoke alarm, turn off power and vacuum the outside of the smoke alarm with the soft brush attachment of a vacuum cleaner. Do this at least once every year, preferably every six months. DO NOT ATTEMPT
TO CLEAN THE SMOKE ALARM IN ANY OTHER WAY.
If the smoke alarm requires service, do not attempt to service it yourself ; this will void your warranty. Return the smoke alarm to your local System Sensor distributor or agent. Enclose a note describing what is wrong with the smoke alarm.
Special Note Regarding Smoke Alarm Guards
Smoke alarms are not to be used with alarm guards unless the combination has been evaluated and found suitable for that purpose.
Please refer to insert for the Limitations of Fire Alarm Systems
PUSH TO SILENCE PUSH AND HOLD TO TEST
LED
SILENCE/TEST SWITCH
Figure 9:
Smoke alarms are designed to provide early warning of developing fires at a reasonable cost. They monitor the air and can sense smoke, providing precious minutes for you and your family to escape before a fire spreads. Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household. Model 2012JA is a photoelectric smoke alarm designed for open area protection in a residential building. It has a built-in relay which may be used to activate auxiliary devices such as bells, horns, and door closers. The relay contacts automatically close 8 seconds after the unit goes into alarm, and automatically resets approximately 5 seconds after the alarm stops. A piezoelectric horn in each smoke alarm produces an audible 85dBA temporal tone evacuation signal when the unit alarms or an interconnected one alarms. This temporal tone evacuation signal complies with CAN/ULC-S531-02. The signal consists of 3 beeps each 0.5 seconds long. spaced 0.5 seconds apart, followed by 1.5 seconds of silence. These smoke alarms can be interconnected with the SIGSND and GND terminals for a system of up to 12 units per premises so when one smoke alarm sounds its evacuation signal it causes the other connected smoke alarms to sound as well. They also can be interconnected with the SIGRLY and GND terminals, when any one alarms, all the interconnected units’ relays will be activated approximately 8 seconds after their horns sound. The smoke alarm has a built-in silence/test push button to silence or test. If the silence/test button is pushed for less than 3 seconds, this is a silence instruction, the smoke alarm will reduce its sensitivity and give an audible trouble signal for about 8 minutes. If the silence/test button is pushed and held for more than 3 seconds, this is a test instruction (See “Testing” below for more detailed instructions.).
NOTE: If the smoke alarm is not in alarm but beeps and flashes every 40 seconds, it is in the silence state. To exit this silence state when the unit is not in alarm, press and hold the silence/test button for more than 3 seconds to do a test.
Ver.$
2 I56-2012-007
Figure 2: Recommended smoke alarm protection for single-oor
residence with more than one sleeping area:
BEDROOM
SMOKE ALARMS FOR MINIMUM PROTECTION
SMOKE ALARMS FOR MORE PROTECTION AND REQUIRED IN NEW CONSTRUCTION
BEDROOM
BEDROOM
LIVING ROOM
DINING ROOM
KITCHENF A MIL Y ROOM
NFPA 72, Chapter 2, Section 2-2.1.1.1 states as follows: “Smoke alarms shall be installed outside of each separate sleeping area in the immediate vicinity of the bedrooms and on each additional story of the family living
unit, including basements and excluding crawl spaces and unnished
attics. In new construction, a smoke-alarm also shall be installed in each sleeping room.” The above NFPA standard is a minimum requirement for smoke alarm installation. For better protection, we also require the installation of a smoke alarm inside every bedroom in existing construction.
• Install a minimum of two smoke alarms in any household, no matter
how small it is.
• Put a smoke alarm in the hallway outside of every separate bedroom
area. (See Figure 1.) A minimum of two smoke alarms are required in homes with two bedroom areas. (See Figure 2.)
• Put a smoke alarm on every level of a multi-level residence. (See Figure 3.)
• Install basement smoke alarms on the ceiling at the bottom of the
basement stairwell. (See Figure 3.)
Figure 3: Recommended smoke alarm protection for a multi-level residence:
BEDROOM
BEDROOM BEDROOM
LIVING ROOM
KITCHEN
BASEMENT
GARAGE
SMOKE ALARMS FOR MINIMUM PROTECTION
SMOKE ALARMS FOR MORE PROTECTION AND REQUIRED IN NEW CONSTRUCTION
Install smoke alarms on the ceiling as close to the center of the room as possible. If this is not practical, install it on the ceiling no closer than 4 inches (10 cm) from any wall or corner. (See Figure 4.)
If wall-mounting is permitted by local and state codes, and ceiling
mounting is not practical, install smoke alarms on an inside wall between 4 and 6 inches (10 and 15 cm) from the ceiling. (See Figure
4.)
Figure 4: Recommended smoke alarm mounting locations:
BEST LOCATION
ACCEPTABLE LOCATION
DEAD AIR
SPACE
BEST IN CENTER
OF CEILING
NO CLOSER THAN 4" (10 cm)
FROM SIDE WALL
MOUNT ON WALL
AT LEAST 4" (10 cm)
FROM CEILING
NO MORE THAN 6" (15 cm) FROM CEILING
Put smoke alarms at both ends of a bedroom hallway if the hallway is more than 30 feet (9 meters) long. In addition, large rooms will require more than a single unit if the room is over 900 square feet.
Rooms or areas that do not have smooth ceilings, or which have short, transom-type walls coming down from the ceiling require additional smoke alarms.
Install second-oor smoke alarms on the ceiling at the top of the rst­to-second oor stairwell. Be sure no door or other obstruction blocks
the path of smoke to the unit.
In rooms with sloped, peaked, or gabled ceilings, install smoke alarms
3 feet (0.9 meter) measured down on the slant from the highest point of the ceiling. See Figure 5.
Figure 5: Recommended smoke alarm location in rooms with sloped, gabled or peaked ceilings:
HORIZONTAL
DISTANCE FROM PEAK
3 FEET
(.9M)
Where Smoke Alarms Should NOT Be Installed
In or near areas where combustion particles are normally present
such as kitchens; in garages where there are particles of combustion in vehicle exhausts; near furnaces, hot water heaters, or gas space heaters. Install smoke alarms at least 20 feet (6 meters) away from kitchens and other areas where combustion particles are normally present.
On the ceiling in rooms next to kitchens where there is no transom
between the kitchen and these rooms. Instead, install the smoke alarm on an inside wall, furthest from the kitchen (See Figure 6). Be sure not to install smoke alarms within 4" of the ceiling or any corner or more than 6" from the ceiling.
Figure 6: Recommended smoke alarm locations to avoid air streams with combustion par
ticles:
CORRECT
AIR RETURN
BEDROOM
BATH
BEDROOM
LIVING ROOM
INCORRECT
KITCHEN
STOVE
AIR INLET
In damp or very humid areas, or next to bathrooms with showers. The moisture in humid air can enter the sensing chamber as water vapor, then cool and condense into droplets that cause a nuisance alarm. Install smoke alarms at least 5 feet (1.5 meters) away from bathrooms.
In very cold or very hot rooms or areas. Operating temperature of the
smoke alarm is 40°F to 100°F (4°C to 38°C).
In dusty, dirty, or insect-infested areas. Dust and dirt can build up on
the unit’s sensing chamber and make it overly sensitive, or can block openings to the sensing chamber and keep the unit from sensing smoke.
Near fresh air inlets or returns or excessively drafty areas. Air conditioners,
heaters, fans, and fresh air intakes and returns can drive smoke away from smoke alarms, making the units less effective.
In dead air spaces at the top of a peaked ceiling or wall/ceiling intersect.
Dead air may prevent smoke from reaching a unit.
Near uorescent light xtures. Install smoke alarms at least 10 feet (3
meters) away from such light xtures.
Installation Requirements
Warning: Electrical Shock Hazard.
Turn off power at the main fuse box or circuit breaker to the area of unit installation before beginning installation procedures.
Mount unit to a 4-inch octagonal junction box only. Mount the 12 Volt
D.C. power supply to a 4" square junction box 2-1/8" deep only. (If necessary, add an extension ring if the selected box does not have adequate volume.) The power supply may be mounted remotely from the unit.
All wiring must be performed by a licensed electrician and installed in compliance with the Canadian Electrical Code, applicable local codes, and any special requirements of the local authority having jurisdiction.
Use only the specied wire gauge. Maximum interconnect bus length
is 5,000 feet, #14 – 22 AWG cable.
The smoke alarm includes a tamper-resist feature that, when activated,
requires a tool for smoke alarm removal.
The following smoke alarm installation instructions include how to activate this feature instructions include how to activate this feature.
3 I56-2012-007
Installation Instructions
1.
Turn off power at main service panel.
2.
Using wire connectors, attach either black wire from power supply to
black AC power wire. Attach other black wire from power supply to white
AC neutral wire.
3.
Using wire connectors, connect red and gray power supply output
wires to the bus line wires supplying power to the remote smoke alarms. (See Figure 7.) Use color-coded bus wires.
4.
Mount power supply to junction box and cover junction box with a 4"
square box cover, using box mounting screws.
5.
Install a junction box where you plan to install the unit. (See type and
size for junction box above.)
6.
Install bus line wires from power supply output to junction box. Use #14-18 AWG wire only. See Figure 7 to determine maximum power bus length for wire size and number of interconnected smoke alarms.
7.
Connect color-coded DC power bus wires to power input screw
terminals, located on unit back. If smoke alarms will be interconnected
or the relay used, see following sections for specic installation
instructions.
8.
Remove unit from mounting bracket by turning the unit counter-
clockwise and pulling the unit away from the bracket.
9.
Remove small tab on mounting bracket to activate tamper-resist
feature, if desired. (To release a unit with this feature, push up on locking tab with screwdriver while turning unit counterclockwise.)
10.
Install mounting bracket to junction box.
11.
Connect power wires to unit(s) as shown in Figure 7. Be sure to
tighten each terminal screw to secure wire in place. Tug wire to be sure it is connected properly.
12.
Attach smoke alarm to mounting bracket by aligning arrows on side
of mounting bracket 1-inch to the right of the nib on the unit. Rotate until the arrow and nib line up. (See Figure 8).
13.
After installing all smoke alarms, turn on power at the main service panel.
14.
Check for the green LED to ash about once every 30 to 40 seconds.
This means the unit is receiving power. Check all smoke alarms.
Note:
If the LED does not ash, power is not getting to the smoke
alarm. Check wiring. If LED still does not ash, return the
smoke alarm to the manufacturer for repair.
15. Test each unit in the system. (See “T
esting” below for more detailed
instructions.)
Figure 8:
Figure 7:
INTERCONNECT
SIGRLY GND SIGSND
- +
POWER INPUT
RELAY
NC C NO
DC POWER SUPPLY
MAX. 30V DC, 100VA
(-)
(+)
Black
White
120VAC
INTERCONNECT UP TO 12 SMOKE ALARMS
SIGSND MODE
INTERCONNECT
SIGRLY GND SIGSND
- +
POWER INPUT
RELAY
NC C NO
- +
POWER INPUT
RELAY
NC C NO
INTERCONNECT
SIGRLY GND SIGSND
INTERCONNECT
SIGRLY GND SIGSND
- +
POWER INPUT
RELAY
NC C NO
DC POWER SUPPLY
MAX. 30V DC, 100VA
(-)
(+)
Black
White
120VAC
INTERCONNECT UP TO 12 SMOKE ALARMS
SIGRLY MODE
INTERCONNECT
SIGRLY GND SIGSND
- +
POWER INPUT
RELAY
NC C NO
- +
POWER INPUT
RELAY
NC C NO
INTERCONNECT
SIGRLY GND SIGSND
Maximum power bus length in feet, given number of units (maximum per bus) and wire gauge(AWG) Supply Voltage = 12VDC
Wire Gauge 1 Unit 2 Units 3 Units 4 Units 5 Units 6 Units 7 Units 8 Units 9 Units 10 Units 11 Units 12 Units
14 13587 6795 4529 3397 2718 2266 1941 1699 1510 1358 1234 1134
16 8505 4254 2835 2126 1701 1419 1216 1064 945 852 772 705
18 5360 2679 1787 1339 1071 894 765 670 595 537 488 443
20 3383 1692 1127 847 677 565 483 422 376 338 308 282
22 2114 1057 705 527 422 352 301 264 236 212 191 175
For 24VDC supply voltage, the maximum power bus length is 4 times as long as 12VDC supply voltage. Maximum interconnect bus length: 5000 FT, No. 14-22AWG cable
All wiring must conform to local electrical codes.
Remove
Mounting Bracket
Install
When Installing: Align arrows on mounting
bracket 1" to the right of the nib on the smoke alarm. Rotate until arrow and nib line up .
Loading...