INSTALLATION AND MAINTENANCE INSTRUCTIONS
1412A and 1424A Direct Wire
Ionization Smoke Detectors
Specifications
Diameter: 5.5 inches (14 cm)
Height: 3.12 inches (8.0 cm)
Weight: 0.7 lb (310 gm)
Operating Temperature: 0° to +49°C (32° to 120°F)
Operating Humidity: 10% to 93% Relative Humidity Non-condensing
Locking Alarm: Reset by momentary power interruption.
Relay Contact Ratings
Resistive or Inductive (60% power factor) load
Form A: 2.0A @ 30VAC/DC
Form C: 2.0A @ 30VAC/DC
Electrical Ratings: 1412A 1424A
System Voltage: 12 24 DC (4V Maximum Ripple)
Supply Voltages: 11.3 20 VDC Minimum
17.3 29 VDC Maximum
Reset Voltages: .73 .8 VDC Minimum
Standby Current: 100 100 µA Maximum
Alarm Currents: 35.2 21.3 mA Minimum
77.0 40.6 mA Maximum
The alarm and auxiliary relay operate within the specied voltage ratings.
Reset Time: 0.3 0.3 Seconds
Start-up Time: 30 30 Seconds
6581 Kitimat Rd., Unit #6, Mississauga, Ontario, L5N 3T5
1-800-SENSOR2, FAX: 905-812-0771
WWW.SYSTEMSENSOR.CA
Before Installing
Please thoroughly read the System Sensor manual I56407-XX, Guide for Proper Use of System Smoke Detec-
tors, which provides detailed information on detector
spacing, placement, zoning, wiring, and special applications. Copies of this manual are available at no charge
from System Sensor. Please also refer to CAN/ULC-S524,
Standard for the Installation of Fire Alarm Systems and
CEC Part 1, Sec. 32..
General Description
System Sensor 1412A and 1424A dual-chamber ionization
smoke detectors utilize state-of-the-art, unipolar sensing
chambers. These detectors are designed to provide open
area protection, and to be used with ULC-listed 4-wire
control panels. The 1412A for 12 volt panels operates
at 12VDC, and the 1424A for 24 volt panels operates at
24VDC. The detectors’ operation and sensitivity can be
tested in place. These detectors are latching type system
detectors. When latched in alarm, the detectors must be
reset by a momentary power interruption.
An LED on the detector provides a local indication of the
detector’s status. If power is applied to the detector, and
the detector is functioning properly in standby, the status
LED will blink every 10 seconds. In alarm, the LED will be
latched on continuously until the detector is reset.
Each detector contains one Form A (SPST-NO) contact
for connection to the alarm-initiating circuit, and one Form
C (SPDT-NO/NC) set of auxiliary contacts. Supervision of
detector power is accomplished by installing a Power Supervisory End-of-Line Relay Module (A77-716) at the end
of the detector power loop. When power is applied to and
through the detectors, the EOL Power Supervisory Module
is energized. Its relay contacts close and provide a closed
series circuit in the control panel’s alarm-initiating loop. A
power failure or a break in the detector power loop deenergizes the EOL Module. The relay contacts open and
trigger a trouble signal at the control panel.
D400-08-00 REV#-002 1 I56-1007-000
TAMPER
RESISTANT
TAB
TO MAKE DETECTOR TAMPER RESISTANT,
BREAK OFF TAB EXTENSION
AT SCRIBED LINE
Figure 1. Flush mounting of detector on 4 inch oc-
COMMON
N/O
N/C
AUXILIARY
CONTACTS
FORM C
4
5
6
7
8
2
1
+
-
POWER
ALARM
CONTACTS
FORM A
N/O
COMMON
N/O
N/C
(OPTIONAL)
RELEASING
DEVICE
4
5
6
7
8
2
1
+
-
COMMON
N/O
N/C
(OPTIONAL)
RELEASING
DEVICE
4
5
6
7
8
2
1
+
EOL
POWER
SUPERVISION
RELAY
MODULE
A77-716B
SUGGESTED
EOL
RESISTOR
CLASS A OPTIONAL WIRING
INITIATING
LOOP
POWER
TO
DETECTORS
ULC LISTED
COMPATIBLE
CONTROL
PANEL
+
-
+
-
-
tagonal box:
Figure 2. Detector mounting bracket:
A78-1554-02 A78-534-00
Mounting
Each 1412A and 1424A detector is supplied with a mounting bracket kit that permits the detector to be mounted:
1. Directly to a 3-1/2 inch or 4 inch octagonal, 1-1/2 inch
deep electrical box, or
2. To a 4 inch square electrical box by using a plaster ring
with the supplied mounting bracket kit.
Spacing
Spacing of 30 ft. on a smooth ceiling as per CAN/ULCS536. Where conditions or response requirements vary,
other spacing may apply.
Wiring Installation Guidelines
All wiring must be installed in compliance with the National Electrical Code and the applicable local codes, and
any special requirements of the local authority having
jurisdiction. Proper wire gauges should be used. The conductors used to connect smoke detectors to control panels
and accessory devices should be color-coded to prevent
wiring mistakes. Improper connections can prevent a sys-
tem from responding properly in the event of a re.
NOTE: Refer to releasing device manufacturer’s instal-
lation instruction for proper connections.
NOTE: Contacts are shown in stand-by mode and will
transfer in alarm condition.
For system supervision: for terminals 1, 2, 7, and 8, do not
use looped wire under terminals. Break wire run to provide
system supervision of connections.
For signal wiring (the wiring between interconnected detectors), it is recommended that the wire be no smaller
than 18 gauge. Wire sizes up to 12 gauge wire may be
used. For best system performance, the power (+) and (–)
loop wires should be twisted pair and installed in separate
grounded conduit to protect the loop from extraneous electrical interference.
Smoke detectors and alarm system control panels have
specications for allowable loop resistance. Consult the
control panel manufacturer’s specications for the total
loop resistance allowed for the particular model control
panel being used before wiring the detector loops.
Wire connections are made by stripping about 3/8" of insulation from the end of the wire (use strip gauge molded in
base), sliding the bare end of the wire under the clamping
Figure 3. Wiring diagram for models 1412A and 1424A detectors used with Class A
or Class B four-wire control panels.
D400-08-00 REV#-002 2 I56-1007-000
A78-1811-00
A78-1554-01