System Sensor 1412A, 1424A Installation And Maintenance Instructions Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
1412A and 1424A Direct Wire Ionization Smoke Detectors
Specifications
Diameter: 5.5 inches (14 cm) Height: 3.12 inches (8.0 cm) Weight: 0.7 lb (310 gm) Operating Temperature: 0° to +49°C (32° to 120°F) Operating Humidity: 10% to 93% Relative Humidity Non-condensing Locking Alarm: Reset by momentary power interruption.
Relay Contact Ratings
Resistive or Inductive (60% power factor) load Form A: 2.0A @ 30VAC/DC Form C: 2.0A @ 30VAC/DC
Electrical Ratings: 1412A 1424A
System Voltage: 12 24 DC (4V Maximum Ripple) Supply Voltages: 11.3 20 VDC Minimum
17.3 29 VDC Maximum Reset Voltages: .73 .8 VDC Minimum Standby Current: 100 100 µA Maximum Alarm Currents: 35.2 21.3 mA Minimum
77.0 40.6 mA Maximum
The alarm and auxiliary relay operate within the specied voltage ratings.
Reset Time: 0.3 0.3 Seconds Start-up Time: 30 30 Seconds
6581 Kitimat Rd., Unit #6, Mississauga, Ontario, L5N 3T5
1-800-SENSOR2, FAX: 905-812-0771
WWW.SYSTEMSENSOR.CA
Before Installing
Please thoroughly read the System Sensor manual I56­407-XX, Guide for Proper Use of System Smoke Detec- tors, which provides detailed information on detector spacing, placement, zoning, wiring, and special appli­cations. Copies of this manual are available at no charge from System Sensor. Please also refer to CAN/ULC-S524, Standard for the Installation of Fire Alarm Systems and CEC Part 1, Sec. 32..
General Description
System Sensor 1412A and 1424A dual-chamber ionization smoke detectors utilize state-of-the-art, unipolar sensing chambers. These detectors are designed to provide open area protection, and to be used with ULC-listed 4-wire control panels. The 1412A for 12 volt panels operates at 12VDC, and the 1424A for 24 volt panels operates at 24VDC. The detectors’ operation and sensitivity can be tested in place. These detectors are latching type system detectors. When latched in alarm, the detectors must be reset by a momentary power interruption.
An LED on the detector provides a local indication of the
Each detector contains one Form A (SPST-NO) contact for connection to the alarm-initiating circuit, and one Form C (SPDT-NO/NC) set of auxiliary contacts. Supervision of detector power is accomplished by installing a Power Su­pervisory End-of-Line Relay Module (A77-716) at the end of the detector power loop. When power is applied to and through the detectors, the EOL Power Supervisory Module is energized. Its relay contacts close and provide a closed series circuit in the control panel’s alarm-initiating loop. A power failure or a break in the detector power loop de­energizes the EOL Module. The relay contacts open and trigger a trouble signal at the control panel.
D400-08-00 REV#-002 1 I56-1007-000
CAUTION
TAMPER
RESISTANT
TAB
TO MAKE DETECTOR TAMPER RESISTANT,
BREAK OFF TAB EXTENSION
AT SCRIBED LINE
Figure 1. Flush mounting of detector on 4 inch oc-
COMMON N/O N/C
AUXILIARY
CONTACTS
FORM C
4
5
6
7
8
2
1
+
-
POWER
ALARM
CONTACTS
FORM A
N/O
COMMON N/O N/C
(OPTIONAL) RELEASING
DEVICE
4
5
6
7
8
2
1
+
-
COMMON N/O N/C
(OPTIONAL) RELEASING
DEVICE
4
5
6
7
8
2
1
+
EOL POWER SUPERVISION RELAY MODULE A77-716B
SUGGESTED EOL RESISTOR
CLASS A OPTIONAL WIRING
INITIATING
LOOP
POWER
TO
DETECTORS
ULC LISTED
COMPATIBLE
CONTROL
PANEL
+
-
+
-
-
tagonal box:
Figure 2. Detector mounting bracket:
A78-1554-02 A78-534-00
Mounting
Each 1412A and 1424A detector is supplied with a mount­ing bracket kit that permits the detector to be mounted:
1. Directly to a 3-1/2 inch or 4 inch octagonal, 1-1/2 inch deep electrical box, or
2. To a 4 inch square electrical box by using a plaster ring with the supplied mounting bracket kit.
Spacing
Spacing of 30 ft. on a smooth ceiling as per CAN/ULC­S536. Where conditions or response requirements vary, other spacing may apply.
Wiring Installation Guidelines
All wiring must be installed in compliance with the Na­tional Electrical Code and the applicable local codes, and any special requirements of the local authority having jurisdiction. Proper wire gauges should be used. The con­ductors used to connect smoke detectors to control panels and accessory devices should be color-coded to prevent wiring mistakes. Improper connections can prevent a sys-
tem from responding properly in the event of a re.
NOTE: Refer to releasing device manufacturer’s instal-
lation instruction for proper connections.
NOTE: Contacts are shown in stand-by mode and will
transfer in alarm condition.
For system supervision: for terminals 1, 2, 7, and 8, do not use looped wire under terminals. Break wire run to provide system supervision of connections.
For signal wiring (the wiring between interconnected de­tectors), it is recommended that the wire be no smaller than 18 gauge. Wire sizes up to 12 gauge wire may be used. For best system performance, the power (+) and (–) loop wires should be twisted pair and installed in separate grounded conduit to protect the loop from extraneous elec­trical interference.
Smoke detectors and alarm system control panels have
specications for allowable loop resistance. Consult the control panel manufacturer’s specications for the total
loop resistance allowed for the particular model control panel being used before wiring the detector loops. Wire connections are made by stripping about 3/8" of insu­lation from the end of the wire (use strip gauge molded in base), sliding the bare end of the wire under the clamping
Figure 3. Wiring diagram for models 1412A and 1424A detectors used with Class A or Class B four-wire control panels.
D400-08-00 REV#-002 2 I56-1007-000
A78-1811-00
A78-1554-01
Loading...
+ 2 hidden pages