System Sensor 1400A Direct Wire Installation And Maintenance Instructions Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
1400A Direct Wire Ionization Smoke Detector
Specifications
Diameter: 5.5 inches (140 mm) Height: 3.12 inches (80 mm) Weight: 0.7 lb. (310 g) Operating Temperature: 0o to +49oC (32oF to 120oF) Latching Alarm: Reset by momentary power interruption. Operating Humidity: 10% to 93% Relative Humidity, Noncondensing
Electrical Ratings:
System Voltage: 12/24 VDC Maximum Ripple Voltage: 4 Volts peak to peak Start-up Capacitance: 20 pf Maximum Standby Ratings: 8.5 VDC Minimum 35 VDC Maximum 100 uA Maximum Alarm Ratings: 4.2 VDC Minimum at 10 mA
6.6 VDC Minimum at 100 mA Alarm current must be limited to 100 mA maximum by the control panel. If used,
the RA400ZA Remote Annunciator operates within the specied detector alarm cur-
rents. Reset Voltage: 2.5 VDC Minimum Reset Time: 0.3 S Maximum Start-up Time: 35 S Maximum
6581 Kitimat Rd., Unit #6, Mississauga, Ontario, L5N 3T5
1-800-SENSOR2, FAX: 905-812-0771
www.systemsensor.ca
Before Installing
Please thoroughly read the System Sensor manual I56­407-XX, Guide for Proper Use of System Smoke Detec- tors. This manual provides detailed information on detector spacing, placement, zoning, wiring, and special appli­cations. Copies of this manual are available at no charge from System Sensor. Please also refer to CAN/ULC-S524, Standard for the Installation of Fire Alarm Systems and CEC Part 1, Sec. 32..
General Description
System Sensor 1400A dual-chamber ionization smoke de­tectors utilize state-of-the-art, unipolar sensing chambers. These detectors are designed to provide open area pro­tection, and to be used with compatible ULC-listed, 2-wire control panels only. The detector’s operation and sensitiv­ity can be tested in place.
Each detector includes an LED that provides a local visual indication of the detector’s status. The LED blinks every ten seconds as an indication that power is applied to the detector and lights continuously in alarm. These detectors also have the latching alarm feature. The alarm can be re­set only by a momentary power interruption.
The detector also has provision for the connection of an optional Model RA400ZA Remote Annunciator. The RA400ZA provides a visual indication of an alarm and mounts to a single gang box.
Spacing
CAN\ULC-S524 denes the spacing requirements for
smoke detectors. Typically, this is 30 feet when the detec­tors are installed on a smooth ceiling. However, ALL instal­lations must comply with CAN/ULC-S524 and/or special
requirements of the authority having jurisdiction.
Mounting
Each 1400A detector is supplied with a mounting bracket kit that permits the detector to be mounted:
D400-07-00 REV#-002 1 I56-1006-002
WARNING
CAUTION
TAMPER
RESISTANT
TAB
TO MAKE DETECTOR TAMPER RESISTANT,
BREAK OFF TAB EXTENSION
AT SCRIBED LINE
Figure 1. Surface mounting of Model 1400A de­tector on 3-1/2 and 4 inch octagonal box:
Figure 2. Model 1400A detector mounting bracket:
A78-1554-02
control panel manufacturer’s specications for the total
loop resistance allowed for the control panel being used before wiring the detector loops.
Begin electrical connections by stripping about 3/8" insu­lation from the end of the wire. Then, slide the bare end of the wire under the clamping plate and tighten the clamping plate screw. A wiring diagram for a typical 2-wire detector system is shown in Figure 3.
NOTE: Break the wire at each terminal to ensure that the
connections are supervised. Do NOT loop the wire under the terminals.
Tamper-resistant Feature
This detector includes a tamper-resistant feature that ef­fectively prevents removal of the detector without the use of a tool. To make the detector tamper-resistant, break off the smaller tab at the scribed line on the tamper resistant tab, on the detector mounting bracket (see Figure 2), then install the detector. To remove the detector from the brack­et once it has been made tamper resistant, use a small screwdriver to depress the tamper-resistant tab located in the slot on the mounting bracket and turn the detector counterclockwise for removal.
Installation
1. Directly to a 3-1/2 inch or 4 inch octagonal, 1-1/2 inch
A78-534-00
Disconnect the power to the alarm system control unit be­fore installing detectors.
deep electrical box, or
2. To a 4 inch square electrical box by using a plaster ring
with the supplied mounting bracket kit.
1. Wire the detector following the installation guidelines.
2. Line up arrows on the detector with the arrows on the mounting bracket.
Installation Wiring Guidelines
3. Rotate the detector clockwise until it clicks into place.
4. After all detectors have been installed, apply power to the control unit.
5. Test the detector as described under TESTING.
6. Reset the detector at the system control panel.
7. Notify the proper authorities that the system is in op­eration.
errors. Improper connections can prevent a system from
responding properly in the event of a re.
For signal wiring (the wiring between interconnected de­tectors), it is recommended that the wire be no smaller than AWG 18. However, the screws and clamping plate can accommodate wire sizes up to AWG 12. The use of
Dust covers can be used to help limit dust entry to the detector, but they are not a substitute for removing the detector during building construction. Remove any dust covers before placing system in service.
twisted pair wiring for the power (+ and -) loop is recom­mended to minimize the effects of electrical interference.
Smoke detectors and alarm system control panels have
Testing
Before testing the detector, look for the presence of the
ashing LED. If it does not ash, power has been lost to
specications for allowable loop resistance. Consult the
D400-07-00 REV#-002 2 I56-1006-002
Loading...
+ 2 hidden pages