System Sensor 1112/24D Installation And Maintenance Instructions Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1112/24D Ionization Smoke Detector
1-800-SENSOR2, FAX: 630-377-6495
IMPORTANT: OBSERVE POLARITY
This detector requires that you observe polarity when wiring. If wiring polarity is not observed on the initiating loop, the unit will send an alarm signal to the control panel to signify incorrect wiring.
Figure 1. Wiring diagram for the 1112/24D detector:
+
POWER
TO
DETECTORS
UL LISTED CONTROL
PANEL
+ +
N.O.
C
+
+ +
N.O.
C
+
EOL POWER SUPERVISION RELAY (SHOWN ENERGIZED) A77-716B 12/24V
EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER
LOOP
+ –
OPTIONAL CLASS A WIRING
NOTE
: Observe polarity in power and initiating loops when wiring.
INITIATING
Before Installing
Please thoroughly read System Sensor Manual I56-407, Guide for Proper Use of System Smoke Detectors, which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available at no charge from System Sensor.
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained following NFPA 72 requirements. The detector should be cleaned at least once a year.
General Description
The 1112/24D is a 4-wire ionization smoke detector that uses a state-of-the-art sensing chamber. This detector is designed to provide open area protection.
A78-2336-05
Installation of this detector is simplified by the use of an adapter bracket and a plug-in screw terminal block that can be prewired to the system, allowing the detector to be easily installed or removed for cleaning. The detector sensitivity can be tested in place using the MOD400R Test Module.
An LED on the detector provides local visual indication of the detector status. If power is applied to the detector, and it is functioning normally in standby, the status LED blinks every five seconds. The LED also latches on in alarm.
The 1112/24D also features visual indication that mainte­nance is required; if the sensing chamber drifts out of its sensitivity limits, the LED ceases to blink.
D200-63-00 1 I56-931-06
Specifications
Diameter: 5.5 inches (140 mm) Height (including adapter bracket): 1.7 inches (43 mm) Weight: 5.3 oz. (150 g) Operating Temperature Range: 32° to 120° F (0° to 50°C) Operating Humidity Range: 10% to 93% Relative Humidity, Noncondensing Latching Alarm: Reset by momentary power interruption Relay Contact Rating– Resistive Load: 0.1A @ 35VDC
Electrical Ratings
System Voltage nominal: 12 or 24 VDC; 8.5 VDC minimum; 35 VDC maximum Maximum Ripple Voltage: 30% of nominal voltage (peak to peak) Reset Voltage: 0.8 VDC minimum Standby Current: 50 µA maximum Alarm Current: 17 mA typical, 23 mA maximum @ 12V; 19 mA typical, 25 mA maximum @ 24V Reset Time: 0.3 seconds maximum Start-up Time: 30 seconds maximum (after 60 second reset)
Figure 2. Surface mounting 1112/24D detector on 31/2 inch and 4 inch octagonal box:
A78-2563-00
Figure 3. 1112/24D detector mounting bracket:
TAMPER RESISTANT TAB (CUT OFF SMALL TAB TO ACTIVATE TAMPER-RESIST FEATURE)
ALIGNMENT ARROWS
A78-2333-02
Mounting
Each 1112/24D detector is supplied with a mounting bracket that permits the detector to be mounted:
pair may be used to provide additional protection against electrical interference.
1. To a single gang box, or
2. Directly to a 31/2-inch or 4-inch octagonal box, or
3. To a 4-inch square electrical box by using a plaster ring.
Smoke detectors and alarm system control panels have specifications for allowable loop resistance. Consult the control panel specifications for the total loop resistance al-
Wiring Installation Guidelines
lowed for the control panel being used before wiring the detector loops.
CAUTION
Be certain to observe polarity when wiring.
All wiring must be installed in compliance with the Na­tional Electrical Code, applicable local codes, and any spe­cial requirements of the local authority having jurisdiction. Proper wire gauges should be used. The conductors used to connect smoke detectors to control panels and accessory devices should be color-coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from responding properly in the event of a fire.
The screw terminal block accepts 14 – 22 gauge wire. For best system performance, all wiring should be installed in separate grounded conduit. Do not mix fire system wiring in the same conduit as any other electrical wiring. Twisted
D200-63-00 2 I56-931-06
Wire connections are made by stripping about 1/4 inch of insulation from the end of the feed wire, inserting the wire into the appropriate terminal, and tightening the screw to secure the wire in place.
Tamper-Resist Feature
This detector includes a tamper-resist feature that prevents its removal from the bracket without the use of a tool. To make the detector tamper-resistant, remove the smaller tab by breaking it at the scribed line on the tamper resistant tab on the detector mounting bracket (see Figure 3), then in­stall the detector. To remove the detector from the bracket once it has been made tamper resistant, use a small screw­driver to depress the tamper-resistant tab, located in the
Loading...
+ 2 hidden pages