System Sensor 1112/24D Installation And Maintenance Instructions Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1112/24D Ionization Smoke Detector
1-800-SENSOR2, FAX: 630-377-6495
IMPORTANT: OBSERVE POLARITY
This detector requires that you observe polarity when wiring. If wiring polarity is not observed on the initiating loop, the unit will send an alarm signal to the control panel to signify incorrect wiring.
Figure 1. Wiring diagram for the 1112/24D detector:
+
POWER
TO
DETECTORS
UL LISTED CONTROL
PANEL
+ +
N.O.
C
+
+ +
N.O.
C
+
EOL POWER SUPERVISION RELAY (SHOWN ENERGIZED) A77-716B 12/24V
EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER
LOOP
+ –
OPTIONAL CLASS A WIRING
NOTE
: Observe polarity in power and initiating loops when wiring.
INITIATING
Before Installing
Please thoroughly read System Sensor Manual I56-407, Guide for Proper Use of System Smoke Detectors, which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available at no charge from System Sensor.
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained following NFPA 72 requirements. The detector should be cleaned at least once a year.
General Description
The 1112/24D is a 4-wire ionization smoke detector that uses a state-of-the-art sensing chamber. This detector is designed to provide open area protection.
A78-2336-05
Installation of this detector is simplified by the use of an adapter bracket and a plug-in screw terminal block that can be prewired to the system, allowing the detector to be easily installed or removed for cleaning. The detector sensitivity can be tested in place using the MOD400R Test Module.
An LED on the detector provides local visual indication of the detector status. If power is applied to the detector, and it is functioning normally in standby, the status LED blinks every five seconds. The LED also latches on in alarm.
The 1112/24D also features visual indication that mainte­nance is required; if the sensing chamber drifts out of its sensitivity limits, the LED ceases to blink.
D200-63-00 1 I56-931-06
Specifications
Diameter: 5.5 inches (140 mm) Height (including adapter bracket): 1.7 inches (43 mm) Weight: 5.3 oz. (150 g) Operating Temperature Range: 32° to 120° F (0° to 50°C) Operating Humidity Range: 10% to 93% Relative Humidity, Noncondensing Latching Alarm: Reset by momentary power interruption Relay Contact Rating– Resistive Load: 0.1A @ 35VDC
Electrical Ratings
System Voltage nominal: 12 or 24 VDC; 8.5 VDC minimum; 35 VDC maximum Maximum Ripple Voltage: 30% of nominal voltage (peak to peak) Reset Voltage: 0.8 VDC minimum Standby Current: 50 µA maximum Alarm Current: 17 mA typical, 23 mA maximum @ 12V; 19 mA typical, 25 mA maximum @ 24V Reset Time: 0.3 seconds maximum Start-up Time: 30 seconds maximum (after 60 second reset)
Figure 2. Surface mounting 1112/24D detector on 31/2 inch and 4 inch octagonal box:
A78-2563-00
Figure 3. 1112/24D detector mounting bracket:
TAMPER RESISTANT TAB (CUT OFF SMALL TAB TO ACTIVATE TAMPER-RESIST FEATURE)
ALIGNMENT ARROWS
A78-2333-02
Mounting
Each 1112/24D detector is supplied with a mounting bracket that permits the detector to be mounted:
pair may be used to provide additional protection against electrical interference.
1. To a single gang box, or
2. Directly to a 31/2-inch or 4-inch octagonal box, or
3. To a 4-inch square electrical box by using a plaster ring.
Smoke detectors and alarm system control panels have specifications for allowable loop resistance. Consult the control panel specifications for the total loop resistance al-
Wiring Installation Guidelines
lowed for the control panel being used before wiring the detector loops.
CAUTION
Be certain to observe polarity when wiring.
All wiring must be installed in compliance with the Na­tional Electrical Code, applicable local codes, and any spe­cial requirements of the local authority having jurisdiction. Proper wire gauges should be used. The conductors used to connect smoke detectors to control panels and accessory devices should be color-coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from responding properly in the event of a fire.
The screw terminal block accepts 14 – 22 gauge wire. For best system performance, all wiring should be installed in separate grounded conduit. Do not mix fire system wiring in the same conduit as any other electrical wiring. Twisted
D200-63-00 2 I56-931-06
Wire connections are made by stripping about 1/4 inch of insulation from the end of the feed wire, inserting the wire into the appropriate terminal, and tightening the screw to secure the wire in place.
Tamper-Resist Feature
This detector includes a tamper-resist feature that prevents its removal from the bracket without the use of a tool. To make the detector tamper-resistant, remove the smaller tab by breaking it at the scribed line on the tamper resistant tab on the detector mounting bracket (see Figure 3), then in­stall the detector. To remove the detector from the bracket once it has been made tamper resistant, use a small screw­driver to depress the tamper-resistant tab, located in the
slot on the mounting bracket (see Figure 4), and rotate the
I
N
T
A
P
T
O
N
O
D
detector counterclockwise.
Installation
WARNING
Remove power from the control unit or initiating device cir­cuits before installing detectors.
1. Wire the plug-in screw terminal block per Figure 3 and plug the terminal block into the detector.
2. Align the arrows on the detector with the arrows on the mounting bracket.
3. Rotate the detector clockwise in the mounting bracket until it clicks into place.
4. After all detectors have been installed, apply power to the control unit or initiating device circuits.
NOTE: This detector has a feature that will signal an
alarm at the control panel if wiring polarity is incorrect.
5. Test the detector as described in TESTING.
6. Reset the detector at the system control panel.
7. Notify the proper authorities the system is in operation.
CAUTION
Dust covers are an effective way to limit the entry of dust into smoke detector sensing chambers. However, they may not completely prevent airborne dust particles from enter­ing the detector. Therefore, System Sensor recommends the removal of detectors before beginning construction or other dust producing activity. Be sure to remove dust covers from any sensors that were left in place during construction as part of returning the system to service.
Testing
NOTE: Before testing, notify the proper authorities that
the smoke detector system is undergoing mainte­nance and, therefore, will be temporarily out of service. Disable the zone or system undergoing
maintenance to prevent unwanted alarms. Detectors must be tested after installation and following pe­riodic maintenance. Test the 1112/24D as follows:
A. Test Switch
1. A recessed test switch is located on the detector hous­ing (See Figure 4).
2. Press and hold the recessed test switch with a 0.18 inch maximum diameter tool such as an allen wrench or small screwdriver.
3. The detector’s LED should light within 5 seconds.
B. Test Module (System Sensor Model No. MOD400R).
The MOD400R test module can be used with a DMM or analog voltmeter to check the detector sensitivity as de­scribed in the test module’s manual.
C. Smoke Entry Test
Hold a smoldering punk stick or cotton wick at the side of the detector and gently blow smoke through the de­tector until the unit alarms.
A detector that fails to activate with any of the above tests should first be cleaned as outlined in MAINTENANCE. If the detector still fails to activate, return it for repair.
Notify the proper authorities the system is back in operation.
Figure 4. Top and side views showing location of test switch:
LED
TEST MODULE SOCKET
D200-63-00 3 I56-931-06
RECESSED TEST SWITCH
A78-2564-01A
PUSH RECESSED SWITCH WITH A
0.18 MAX. DIAMETER TOOL
A78-2564-00C
Maintenance
NOTE: Before removing the detector, notify the proper au-
thorities that the smoke detector system is under­going maintenance and will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms.
1. Remove the detector housing by gently prying the four housing tabs on the bottom of the base with a small­bladed screwdriver and pull the housing from the base.
2. Vacuum the screen carefully without removing it.
3. Remove the screen by pulling it straight away from the sensing chamber (see Figure 5).
4. Clean the sensing chamber by vacuuming or blowing out dust and particles.
5. Replace the screen by placing it over the sensing cham­ber. Rotate the screen until is snaps into place.
6. Replace the housing by aligning the three triangular slots on the base with their counterparts on the housing. Gen­tly press the housing until it locks in place.
7. Reinstall the detector.
8. Notify the proper authorities that the system is back in operation.
Figure 5. Removal of cover and screen for cleaning:
REMOVABLE HOUSING
REMOVABLE SCREEN
SENSING CHAMBER
BASE
A78-2565-03
The Limitations of Property Protection Smoke Detectors
This smoke detector is designed to activate and initiate emergency ac­tion, but will do so only when it is used in conjunction with an authorized fire alarm system. This detector must be installed in accordance with NFPA standard 72. Smoke detectors will not work without power. AC or DC powered smoke detectors will not work if the power supply is cut off.
Smoke detectors will not sense fires which start where smoke does not reach the detectors. Smoldering fires typically do not generate a lot of
heat which is needed to drive the smoke up to the ceiling where the smoke detector is usually located. For this reason, there may be large de­lays in detecting a smoldering fire with either an ionization type detector or a photoelectric type detector. Either one of them may alarm only after flaming has initiated which will generate the heat needed to drive the smoke to the ceiling. Smoke from fires in chimneys, in walls, on roofs or on the other side of a closed door(s) may not reach the smoke detector and alarm it. A detector cannot detect a fire developing on another level of a building quickly or at all. For these reasons, detectors shall be located on every level and in
every bedroom within a building. Smoke detectors have sensing limitations, too. Ionization detectors and
photoelectric detectors are required to pass fire tests of the flaming and smoldering type. This is to ensure that both can detect a wide range of types of fires. Ionization detectors offer a broad range of fire sensing capa-
Three-Year Limited Warranty
System Sensor warrants its enclosed smoke detector to be free from de­fects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this smoke detector. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the smoke detector which is found to be defective in materials or work­manship under normal use and service during the three year period com­mencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Repair Depart-
WARNING
bility but they are somewhat better at detecting fast flaming fires than slow smoldering fires. Photoelectric detectors sense smoldering fires better than flaming fires which have little, if any, visible smoke. Because fires de­velop in different ways and are often unpredictable in their growth, nei­ther type of detector is always best, and a given detector may not always provide early warning of a specific type of fire. In general, detectors cannot be expected to provide warnings for fires re­sulting from inadequate fire protection practices, violent explosions, es­caping gases which ignite, improper storage of flammable liquids like cleaning solvents which ignite, other similar safety hazards, arson, smok­ing in bed, children playing with matches or lighters, etc. Smoke detectors used in high air velocity conditions may have a delay in alarm due to dilu­tion of smoke densities created by frequent and rapid air exchanges. Addi­tionally, high air velocity environments may create increased dust contamination, demanding more frequent maintenance. To keep your equipment in excellent working order, ongoing maintenance is required per the manufacturer’s recommendations and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA 72, the National Fire Alarm Code, shall be followed. A preventative maintenance agreement should be arranged through the local manufacturer’s represen­tative. Though smoke detectors are designed for long life, they may fail at any time. Any smoke detector, fire alarm equipment, or any component of that system which fails shall be repaired or replaced as soon as possible.
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifica­tions, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or conse­quential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
D200-63-00 4 I56-931-06
© System Sensor 1998
Loading...