INSTALLATION AND MAINTENANCE INSTRUCTIONS
2112TL Photoelectronic
3825 Ohio Avenue, St. Charles, Illinois 60174
Smoke Detector
Specifications
Diameter: 5.5 inches (140 mm) Height (including mounting bracket): 1.7 inches (43 mm) Weight: 5.3 oz. (150 g)
Operating Temperature Range: 32° to 100°F (0° to 37.7°C)
Operating Humidity Range: 10% to 93% relative humidity, noncondensing Latching Alarm: Reset by momentary power interruption
Heat Sensor: 135°F fixed temperature electronic thermistor
Electrical Ratings
System Voltage Nominal: 12 VDC
Minimum: 9.5 VDC
Maximum: 14 VDC Maximum Ripple Voltage: 30% of nom. voltage (peak to peak) Alarm Current (at 12 V): 13 mA maximum Reset Voltage: 0.8 VDC minimum Reset Time: 0.3 seconds maximum Start-up Time: 30 seconds maximum (after 30 second reset)
A Division of Pittway
1-800-SENSOR2, FAX: 630-377-6495
Before Installing
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained following NFPA 72 requirements. The detector should be cleaned at least once a year.
General Description
The Model 2112TL is a 4-wire photoelectronic smoke detec­tor that uses a state-of-the-art optical sensing chamber. This detector is designed to provide open area protection. It
features restorable, built-in, fixed-temperature (135°F)
thermal sensors.
NOTE: The alarm and supervisory outputs are not to be
used as relay contacts.
In addition, an LED on the detector provides a local visual indication of the detector’s status. If power is applied to the detector, and it is functioning normally in standby, the sta­tus LED blinks every ten seconds. The LED latches on in alarm and quits flashing when the detector deviates from its sensitivity range.
D200-66-00 1 I56-997-02
,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
Figure 1. Surface mounting of 2112TL smoke detec­tor on 31/2-inch and 4-inch octagonal box:
A78-2563-00
Mounting
The 2112TL detector is supplied with a mounting bracket that permits the detector to be mounted:
1. To a single gang box, or
2. Directly to a 31/2-inch or 4-inch octagonal box, or
3. To a 4 inch square electrical box by using a plaster ring.
The screw terminal block accepts 14 – 22 gauge wire. For best system performance, all wiring should be installed in separate grounded conduit. Do not mix fire system wiring in the same conduit as any other electrical wiring. Twisted pair may be used to provide additional protection against electrical interference.
Smoke detectors and alarm system control panels have specifications for allowable loop resistance. Consult the control panel specifications for the total loop resistance al­lowed for the control panel being used before wiring the detector loops.
Wire connections are made by stripping about 1/4 inch of insulation from the end of the feed wire, inserting the wire into the appropriate terminal, and tightening the screw to secure the wire in place.
Tamper-resistant Feature
This detector includes a tamper-resistant feature that pre­vents its removal from the bracket without the use of a tool. To make the detector tamper-resistant, remove the smaller tab by breaking it at the scribed line on the tamper resistant tab on the detector mounting bracket (see Figure 2), then install the detector. To remove the detector from the bracket once it has been made tamper resistant, use a small screw­driver to depress the tamper-resistant tab, located in the slot on the mounting bracket, and turn the detector coun­terclockwise.
Wiring Installation Guidelines
All wiring must be installed in compliance with the Na­tional Electrical Code, applicable local codes, and any spe­cial requirements of the local authority having jurisdiction. Proper wire gauges should be used. The conductors used to connect smoke detectors to control panels and accessory devices should be color-coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from responding properly in the event of a fire.
Figure 2. Smoke detector mounting bracket:
TAMPER SLOT (DEPRESS TAB TO REMOVE DETECTOR)
Installation
WARNING
Remove power from the control unit or initiating device cir­cuits before installing detectors.
1. Wire the plug-in screw terminal block per Figure 3 and plug the terminal block into the detector.
2. Align the arrows on the detector with the arrows on the mounting bracket.
3. Turn the detector clockwise in the mounting bracket un­til it clicks into place.
4. After all detectors have been installed, apply power to the control unit or initiating device circuits.
5. Test the detector as described in TESTING.
6. Reset the detector at the system control panel.
7. Notify the proper authorities the system is in operation.