Super Systems X5 User Manual

Page 1
Temperature Controller
Model No. 31095 and 31097
Instruction manual PN 31095 PN 31097
Super System inc.
7205 Edington Drive Cincinnati, Ohio 45249 United States
Phone: 513-772-0060 Toll free: 800-666-4330 Fax: 513-772-9466
www.supersystem.com
I 1 I 2 I 3
45.80
50
45.80
Page 2
Information
2
cc
NOTES
ON ELECTRIC
SAFETY AND
ELECTROMAGNETIC
COMPATIBILITY
Please read these instructions carefully before proceeding with the installation of the controller. Class II instrument (for indoor use only).
This controller has been designed in compliance with: Regulations on electrical apparatus (appliance, systems and installations) according to the European Community directive no. 73/23/EEC amended by the European Comunity direc­tive no. 93/68/EEC and the Regulations on the essential protection requirements in electri­cal apparatus EN61010-1 : 93 + A2:95.
Regulations on Electromagnetic Compatibility according to the European Community directive no. 89/336/EEC, amended by the European Community directive no. 92/31/EEC, 93/68/EEC, 98/13/EEC and the following regulations: Regulations on RF emissions
EN61000-6-3 : 2001 residential environments EN61000-6-4 : 2001 industrial environments
Regulation on RF immunity
EN61000-6-2 : 2001 industrial equipment and system
It is the responsibility of the installer to ensure compliance with regulations on safety require­ments and EMC.
The device has no user serviceable parts. Please contact your nearest agent for repair services.
All information and warnings about safety and electromagnetic compatibility are marked with the
B symbol.
Page 3
TABLE OF CONTENTS
Table of contents
1 INTRODUCTION.............................................................................................................page 4
1.1 P
RODUCT CODING..........................................................................................page 5
2 INSTALLATION .................................................................................................................page 6
2.1 DESCRIPTION.........................................................................................................page 6
2.2 ENVIRONMENTAL RATINGS.....................................................................page 8
2.3 PANEL MOUNTING ............................................................................................page 9
3 ELECTRICAL CONNECTIONS................................................................page 10
3.1 TERMINATION BLOCK ...................................................................................page 10
3.2 SUGGESTED WIRES ROUTING ..............................................................page 11
3.3 EXAMPLE OF WIRING DIAGRAM ........................................................page 12
4 OPERATIONS......................................................................................................................page 22
4.1 KEYS FUNCTIONS AND DISPLAY IN
OPERATOR MODE...............................................................................................page 22
4.2 PARAMETER SETTING...................................................................................page 24
4.3 C
ONFIGURATION PROCEDURE............................................................page 25
4.4 PARAMETERISATION - MAIN MENU ...............................................page 34
4.5 PARAMETERS.........................................................................................................page 46
4.6 PARAMETERISATION - ACCESS LEVELS ..................................page 50
5 DISPLAYS..................................................................................................................................page 57
5.1 S
TANDARD DISPLAY.......................................................................................page 57
5.2 FAST ACCESS .........................................................................................................page 57
6 COMMANDS ........................................................................................................................page 58
6.1 KEYPAD COMMANDS ...................................................................................page 59
6.2 DIGITAL INPUTS COMMANDS ............................................................page 58
6.3 COMMANDS FROM SERIAL COMMUNICATION (PLEASE, REFER TO THE SERIAL COMMUNICATIONS MANUAL)
7 TECHNICAL SPECIFICATIONS.............................................................page 63
3
Page 4
1 - Introduction
1 INTRODUCTION
The 31095 has been designed for use in industrial environments. The 31095 is a universal controller with many standard features.
4
Main universal input
Auxiliary input
Digital input
Setpoint
Special function
Digital inputs (IL1,IL2 or IL3) functions
(option)
Resources
PV
AUX
IL1 IL2 IL3
Memory Chip
Data copy/Data store (option)
Modbus RS485 Slave
OP1
OP2
OP3
OP4
OP5
OP6
(option)
Fuzzy tuning
(opt.)
Operating mode
Control Alarms
1 OP1 OP2 OP3 OP4 OP5 OP6
Single action
2 OP5 OP1 OP2 OP3 OP4 OP6
3 OP1 OP2 OP3 OP4 OP5 OP6
4 OP1 OP5 OP2 OP3 OP4 OP6
Double action
5 OP5 OP2 OP1 OP3 OP4 OP6
6 OP5 OP6 OP1 OP2 OP3 OP4
Valve
7
OP1 OP2 OP3 OP4 OP5 OP6
with automatic selection
One shot Auto tuning
One shot Natural Frequency
Retransmission
PV/SP/MV
Page 5
PN MN SN V
~(L-N)
: 31095 : X5-3150-0300 : A0A-0819/1208 : 100÷240V 50/60 Hz - 5W
1.1 MODEL CODE
0
Model:
Power Supply Outputs Serial Options
Line Basic Accessories
0X5 A B C D 3 0
1 - Introduction
The complete code is displayed on the instrument side label.
The information about product coding is accessible from the front panel by means of a particular procedure described in section 5.1 page 53.
Instrument label
www.supersystem.com
Cincinnati, Ohio USA
Basic product code
B C D
Power supply A
X5
I 1 I 2 I 3
45.80
50
45.80
100...240Vac (- 15% + 10%) 24Vac (-25...+12%) or 24Vdc (-15... +25%)
Outputs OP1 - OP2 B
Relay - Relay Triac - Triac
Serial Communications C
None RS485 Modbus/Jbus SLAVE PROFIBUS DP SLAVE RS485 Modbus/Jbus SLAVE
+ PROFIBUS
Options D
None
3
2ndSSR drive/analog
5
output (OP6)
1 5
0 5 7
8
0
4
5
Page 6
2 - Installation
IP 20 Terminal Block
EN61010 - 1 (IEC1010 - 1)
Product code label
Front panel gasket
Mounting clamps
Front panel
IP65 protection
EN 650529 (IEC 529)
Panel
surface
2 INSTALLATION
Installation must be carried out by qualified personnel.
Before proceeding with the installation of this controller, read the instructions in this manual. Pay particular attention to precautions marked with the B symbol, related to the European Community directive on electrical protection and electromagnetic compatibility.
B
To prevent contact with electronically live components, the controller must be
installed in an enclosure or panel.
6
2.1 GENERAL DESCRIPTION
Page 7
2.1.1 DIMENSIONAL DETAILS 2.1.2 PANEL CUT-OUT
96 mm
3.78 in
110 mm
4.33 in
48 mm
1.89 in
10 mm max.
0.39 in max.
10 mm max.
0.39 in max.
65 mm min
2.56 in min
45
+0.6
mm
1.78
+0.023
in
92
+0.8
mm
3.62
+0.031
in
113 mm min
4.45 in min
2 - Installation
7
Page 8
2 - Installation
2.2 ENVIRONMENTAL RATINGS
B
Operating conditions
UL notes [1] Operating surrounding temperature
0…50°C
8
M
T
%Rh
Special conditions
M
T
%Rh
P
Prohibited Conditions
C E
Altitude: up to 2,000 m
Temperature: 0…50°C [1]
Relative humidity: 5…95 % non-condensing
Altitude: > 2,000 m
Temperature: >50°C
Humidity: > 95 %
Conducting atmosphere
Corrosive atmosphere
Explosive atmosphere
Suggestions
Use 24Vac supply version
Use forced air ventilation
Warm up
Use filter
D
Page 9
1
3
2
1
2
1M
1
2
1
2.3 PANEL MOUNTING [1]
2
1
1
2 - Installation
2.3.1 INSERT THE INSTRUMENT
1 Prepare panel cut-out; 2 Check front panel gasket
position;
3 Insert the instrument through
the cut-out.
UL note
[1] For Use on a Flat Surface of a Type 2 and Type 3 ‘raintight’ Enclosure
2.3.2 INSTALLATION SECURING
1 Fit the mounting clamps; 2 Push the mounting clamps
towards the panel surface to secure the instrument.
2.3.3 CLAMP REMOVAL
1 Insert the screwdriver in the
clips of the clamps;
2 Rotate the screwdriver.
.
2.3.4 INSTRUMENT REMOVAL
1 Push and 2 Pull to remove the instrument.
Electrostatic discharges can damage the instrument.
Before removing the instrument the operator must discharge himself to ground.
B
9
Page 10
6
5
4
3
2
1
28
27
30
29
26
25
7
19
31
8
20
32
9
33
10
34
11
23
35
12
24
36
0,5
Nm
16
15
18
17
14
13
21
Rear
terminal
cover
Cable size 1 mm
2
[2]
5.7 mm
0.22 in
3 - Electrical Connections
C
N
L
1
2
3
4
5
6
7
8
9
10
11
12
19
20
23
24
25
26
27
28
29
30
31
32
33
34
35
36
TC
mV/V/mA
NC
CNOOP3
NO
C
NO
OP1
OP2
OP4
DG
OP6 (option)
24V— OUT
1
2
3
A
b
B
RTD
13
14
15
16
17
18
21
22
N/C
LOGIC
INPUT
Profibus
VP
DP
DN
OP5
IN1
C
RS485
(Slave)
POT
0%
REM
NO
C
Ø
L
3 ELECTRICAL
CONNECTIONS
3.1 TERMINAL BLOCK [1]
B
UL notes [1] Use 60/70 °C copper (Cu) conductor only. [2] Wire size 1 mm
10
2
(18 AWG Solid/Stranded)
Terminals
35 screw terminals M3
Option terminals
Holding screw 0.5 Nm
Phillips screwdriver PH1
Flat blade screwdriver
0.8 x 4 mm
Pin connector q 1.4 mm - 0.055 in max.
Fork-shape AMP 165004 Ø 5.5 mm - 0.21 in
Stripped wire L 5.5 mm - 0.21 in
Page 11
6
5
4
3
2
1
28
27
30
29
26
25
7
19
31
8
20
32
9
33
10
34
11
23
35
12
24
36
16
15
18
17
14
13
21
6
5
4
3
2
1
28
27
30
29
26
25
7
19
31
8
20
32
9
33
10
34
11
23
35
12
24
36
16
15
18
17
14
13
21
A B
E C D CD
A B
E C D CD
PRECAUTIONS
The instrument has been designed to work in an harsh and noisy environmental (level IV of the industrial standard IEC 801-4). It is recommended to follow the following suggestions.
A
All the wiring must comply with the local regulations. The supply wiring should be routed away from the power cables. Avoid to place electro­magnetic contactors, power relays and high power motors nearby. Avoid power units in close proximity, especially if controlled in phase angle mode.
Keep the low level sensor input wires away from the power lines and the output wiring. If this is not achiev­able, use shielded cables on the sensor input, with the shield connected to ground.
B
3.2 SUGGESTED WIRES ROUTING
3 - Electrical Connections
B
Conduit for supply and output cables
A = Supply B = Outputs C = Analog inputs D = Analog output E = Digital input
Serial Comm.s
Conduit for low level sensor cables
11
Page 12
3 - Electrical Connections
SupervisoryCommands
RS485
Power supply switch
Alarm
V
~
[3]
C
IL1
IL2
IL3
[6]
[6]
[5]
[5]
[5]
OP3
OP1
OP2
°C
C
Retransm.
I
Pt100
[6]
Transmitter
4…20mA
24V
V ~
Servomotor
Rj
PTC
12
11
10
9
8
7
6
5
4
3
2
1
24
23
20
19
36
35
34
33
32
31
30
29
28
27
26
25
18
17
16
15
14
13
21
3.3 EXAMPLE OF WIRING DIAGRAM (VALVE CONTROL)
12
B
Notes:
1] Ensure that the power supply voltage is
the same as that on the instrument label.
2] Switch ON the power supply only after
all electrical connections have been completed.
3] In accordance with electrical safety reg-
ulations, there must be an easly identifi­able and accessable power disconnect.
4] The instrument is PTC protected.
In case of failure, return the instrument to the manufacturer for repair.
5] To protect internal circuits use:
- 2 A
~ T fuse for Relay outputs (220 Vac)
- 4 A~ T fuse for Relay outputs (110 Vac)
- 1 A~ T fuse for Triac outputs
6] Relay contacts are protected with varis-
tors.
In case of 24 Vac inductive loads, use model A51-065-30D7 varistors (on request).
Page 13
3.3.1 POWER SUPPLY
L
N
25
26
PTC
included
Supply
27
10
11
12
A
B
A
R2
R1
10
11
12
A
b
B
11
12
B
3.3.2 PV CONTROL INPUT
3 - Electrical Connections
B
Switching power supply with mul­tiple isolation and PTC protection.
• Standard version:
Nominal voltage:
100... 240Vac (-15...+10%); Frequency 50/60Hz.
• Low Voltage version:
Nominal voltage: 24Vac (-25...+12%); Frequency 50/60Hz or 24Vdc (-15...+25%); Power consumption 5W max.
A L-J-K-S-R-T-B-N-E-W thermocouple type
• Connect wires with the polarity as shown;
• Always use compensation cable of the correct type for the thermocouple used;
• The shield, if present, must be connected to ground.
B For Pt100 resistance thermometer
• If a 3 wires system is used, always use cables of the same section (1mm2min.), maximum line resistance 20 /line.
• When using a 2 wires system, always use cables of the same section (1.5mm2min.) and put a jumper between terminals 11 and 12
C For T (2x RTD Pt100) Special
A When the distance between the controller and the
sensor is 15m, using a cable of 1.5mm2 section, pro­duces an error on the measure of 1°C.
R1 + R2 must be <320
Wire resistance 150max.
Only for two wires system, put a jumper between ter­minals 11 and 12.
Use wires of the same length and 1.5
2
mm
size.
Maximum line resis­tance 20 /line.
13
Page 14
3 - Electrical Connections
Rj
V,mV
mA
11
12
Rj
24V–
4…20mA
Transmitters
PV
36
11
12
[1]
mA
Rj
24V–
4…20mA
Transmitters
PV
36
11
12
[1]
mA
3.3.2 PV CONTROL INPUT
B
C For mA, mV
Input resistance = 30Ω per mA; Input resistance > 10MΩ per mV; Input resistance = 10kper Volt;
14
C1 With 2 wires transducer
C2 With 3 wires transducer
[1] Auxiliary power supply for exter-
nal transmitter 24Vdc ±20%/30mA max without short circuit protec­tion.
Page 15
3.3.4 AUXILIARY INPUT
19
18
mAmV-V
Rj
Operating travel distance
pot.h
pot.I
Total travel distance
18
17
16
100%
0%
3
7
6
TTL o.c.
Isolated contact
Com.
IL 3
IL 2
C2
C3
5
NPN o.c.
IL 1
C1
A - From Remote Setpoint
Current 0/4…20mA; Input resistance = 30Ω.
Voltage 1…5V, 0…5V, 0…10V; Input resistance = 300kΩ.
B
B - From Potentiometer
For the measure of the posi­tion of the motor or the valve.
3.3.5 DIGITAL INPUT
• The input is active when the logic state is ON, corresponding to the contact closed.
• The input is inactive when the logic state is OFF, corresponding to the contact open.
3 - Electrical Connections
B
15
Page 16
3 - Electrical Connections
3.3.6 OP1 - OP2 - OP3 - OP4 - OP5 - OP6 OUTPUTS (OPTION)
The functionality associated to each of OP1, OP2, OP4, OP5 and OP6 is defined during the configuration of the instrument. The allowed combinations are:
Control outputs Alarms Retransmission
A
B
D
E
F
G
L
where:
Single action
Double
action
Valve drive
Main (Heat) Secondary (Cool) AL1 AL2 AL3 PV / SP / MV
OP1 OP5 OP1 OP2 OP1 OP5 OP5 OP2 OP5 OP6
OP1
s
OP2
OP1 OP2 OP3
OP1 OP3
t
OP2 OP3 OP5
OP3 OP5
OP2 OP3
OP2 OP3
OP3 OP5OP4
AL4
OP4 OP4 OP4 OP4 OP4 OP4
OP6 OP6 OP6 OP6 OP6
OP6
B
OP1 - OP2 OP3 - OP4 OP5 - OP6
16
Relay or Triac output Relay outputs Analog control or retransmission outputs
Page 17
3.3.6-A SINGLE ACTION RELAY
Fuse
Coil of the heat
load contactor
31
32
OP1
[1]
Fuse
Coil of the heat
load contactor
31
32
OP1
[1]
Fuse
Coil of the cool load contactor
32
33
OP2
[1]
Fuse
Coil of the heat
load contactor
31
32
OP1
[1]
Heat
load
Static Relay
8
9
OP5
Cool
load
Static Relay
8
9
OP5
8
9
OP5
Heat load
mA mV,V
Fuse
Coil of the heat
load contactor
31
32
OP1
[1]
8
9
OP5
Cool load
mA mV,V
(TRIAC) CONTROL OUTPUT
B
3.3.6-C DOUBLE ACTION RELAY (TRIAC)/RELAY (TRIAC) CONTROL OUTPUT
3 - Electrical Connections
B
3.3.6-B1 SINGLE ACTION LOGIC CONTROL OUTPUT
3.3.6-B2 SINGLE ACTION ANALOG OUTPUT
B
B
3.3.6-D1 DOUBLE ACTION RELAY (TRIAC)/LOGIC CONTROL OUTPUT
3.3.6-D2 DOUBLE ACTION CONTROL OUTPUT RELAY (TRIAC)/ANALOG CONTROL OUTPUT
B
B
17
Page 18
3 - Electrical Connections
Cool load
Static
Relay
20
21
OP6
8
9
OP5
Heat load
mA mV,V
Heat
load
Static Relay
8
9
OP5
Fuse
Coil of the cool load contactor
32
33
OP2
[1]
Fuse
Coil of the cool load contactor
32
33
OP2
[1]
Heat
load
Static Relay
8
9
OP5
3.3.6-E1 DOUBLE ACTION DIGITAL/RELAY (TRIAC) CONTROL OUTPUT
3.3.6-E2 DOUBLE ACTION ANALOG/RELAY(TRIAC) CONTROL OUTPUT
B
B
Notes for pages 17 - 18 - 19 OP1 - OP2 Relay output
• SPST Relay N.O., 2A/250 Vac
(4A/120Vac)
for resistive load,
• Fuse 2A ac T at 250V, 4A ac T at 110V.
OP1 - OP2 Triac output
• N.O. contact for resistive load of up to 1A/250 Vac max.
• Fuse 1A ac T
Isolated digital outputs OP5-OP6
• 0…24Vdc, ±20%, 30 mA max.
Isolated analog outputs OP5-OP6
• 0/4…20mA, 750/ 15V max. 0/1…5V, 0…10V, 500/ 20mA max.
[1] Varistor for inductive load 24Vac only
3.3.6-F1 DOUBLE ACTION DIGITAL/DIGITAL CONTROL OUTPUT
18
B
Page 19
OP1
33
32
31
OP2
V~
Lower
Raise
M
~
20
21
OP6
Cool load
mAV,mV
3.3.6-F2 DOUBLE ACTION CONTROL OUTPUT
8
9
OP5
Heat load
mA mV,V
8
9
OP5
Heat load
mA mV,V
Cool load
Static
Relay
20
21
OP6
20
21
OP6
Cool load
mAV,mV
Heat
load
Static Relay
8
9
OP5
DIGITAL/ANALOG
B
3 - Electrical Connections
3.3.6-G MOTOR POSITIONER OUTPUT RELAY (TRIAC) / RELAY (TRIAC)
Valve drive PID without potentiometer 3 pole output with N.O. contacts (raise, lower, stop)
3.3.6-F3 DOUBLE ACTION CONTROL OUTPUT ANALOG/DIGITAL
3.3.6-F4 DOUBLE ACTION CONTROL OUTPUT OR SPLIT RANGE ANALOG/ANALOG
B
B
19
Page 20
3 - Electrical Connections
Fuse
AL3 load
28
29
OP3
[1]
30
[1]
AL3 load
V
~
Fuse
NC
C
NO
Fuse
AL1 load
31
32
OP1
[1]
33
OP2
[1]
AL2 load
V
~
Fuse
Fuse
AL4 load
34
35
OP4
[1]
V~
C
SLAVE
13
14
15
20
21
OP6
Cool load
mAV,mV
8
9
OP5
Heat load
mA mV,V
1234
SLAVE
3.3.7 OP1-2-3-4 ALARM OUTPUTS
e The relay/triac output OP1/OP2, can be used
as alarm outputs only if they are not used as control outputs.
20
B
3.3.8 OP5 AND OP6 (OPTION) ANALOG CONTROL OUTPUTS
B
OP5 and OP6 can be configured for control action or PV/SP/MV retransmission:
• Galvanic isolation 500Vac/1 min:
• 0/4…20mA, 750/ 15Vdc max. 0/1…5V, 0…10V, 500/ 20mA max..
Notes: [1] Varistor for inductive load 24Vac only
[2]
A Please, read the user manual:
“Serial communications and config­uration software”.
3.3.9 SERIAL COMMUNICATIONS (OPTION) [2]
• Galvanic isolation 500Vac/1 min;
Compliance to the EIA RS485 standard for Modbus/Jbus;
• Termination setting dip switches.
B
Page 21
3.3.10 PROFIBUS DP (OPTION)
DP
DN
DG
VP
1
2
3
4
DP
DN
DG
VP
Initial PROFIBUS station
DP
DN
DG
VP
Other PROFIBUS stations
DP
DN
DG
VP
Ending PROFIBUS station
220
390
390
220
390
390
33
4-40UNC-2B
5
9
6
1
3 - Electrical Connections
B
Galvanic isolation 500 Vac/1 min
• Compliance to the EIA RS485 standard for PROFIBUS DP;
• Connecting cable: twisted pair cable as per PROFIBUS specifications (e.g. Belden B3079A);
• Max. lenght: 100 m at 12 Mb/s
Termination resistors 220Ω and 390Ω (1/4W, ±5%) for external mounting on the first and end­ing PROFIBUS stations only.
To make the connections easier, a D-Sub type (9 poles) connector, model AP-ADP-PRESA-DSUB/9P is provided Must be used with a 9PIN male ERNI type part no. 103648 or sim­ilar connector.
X5 D-SUB 9 poles Signal
1 3 RxD/TxD-P (DP)
2 8 RxD/TxD-N (DN)
3 5 DGND (DG)
4
6
VP (VP)
Description according to
PROFIBUS specifications
Receive data/transmission data plus
Receive data/transmission data negative
Data transmission potential (ground to 5V)
Supply voltage of the termi­nating resistance-P, (P5V)
Detailed information concerning wiring and cables can be found on the PROFIBUS Product Guide on Internet at:
http://www.profibus.com/online/list
21
Page 22
I 1 I 2 I 3
45.80
45.80
50
4 - Operation
4 OPERATION
4.1.1 KEY FUNCTIONS AND DISPLAYS IN OPERATOR MODE
Digital input status LEDs (yellows)
ó - IL1 active ò - IL2 active ô - IL3 active
Status LEDs (greens)
} Communications running
(serial communications interface)
Ä Tuning running { Manual operating mode Ö Timer á Program Waiting Ü Remote Setpoint active
ú First stored Setpoint active ù Second stored Setpoint active û Third stored Setpoint active
Alarm status LEDs (reds)
Å AL1 ON Ç AL2 ON É AL3 ON Ñ AL4 ON
Auto/Man
22
Over range Under range
8888____ 8888----
PV control input in engineering units
% Control output
or Program status (see page 64)
SP operating Setpoint
(Local/Remote or Stored)
Control output LEDs (red)
å OP1/OP4 ON - ç OP2/OP4 OFF
Run/stop Timer or a program
Entry key for selection and value setting confirmation
Setpoint setting
Menu access
Page 23
4.1.2 KEY FUNCTIONS AND DISPLAY IN PROGRAMMING MODE
35.0
P.b.
4 - Operation
The parameter setting proce-
A
dure has a timeout. If no keys are pressed for, at least 30 seconds, the controller auto­matically switches back to the operator mode.
After selecting the parameter or the code, press $ and % to display or modify the value.
The value is entered when the next parameter is entered, by pressing the è key. The changes are not saved if either the back key ê is pressed or if the instrument is left alone for 30 seconds.
From every parameter, pressing the
í key, the controller
switches to the operator mode.
Parameter value
Parameter mnemonic
Back to the previous parameter
Entry key for selection
and value setting confirmation
Value modification
Access to the menu for:
- Parameter setting
- Configuration
- Access selection
23
Page 24
4 - Operation
275.0
274.8
275.0
274.8
230.0
274.8
240.0
274.8
240.0
°C
Unit
°C
Unit
°f
Unit
°C
Unit
°f
Unit
none
Unit
ph
4.2 PARAMETER SETTING
4.2.1 NUMERIC ENTRY
(i.e. the modification of the Setpoint value from 275.0 to 240.0 )
Press $ or % momentarily to change the value by 1 unit every push. Hold $ or % to change the value at rate that doubles every second. The rate of change decreases when the button is released. The change of the value stops when it has reached the max./ min limit set for the parameter.
In case of Setpoint modification: press
$ or % once to
display the local Setpoint instead of working Setpoint. To evidence this change the display flashes once. Then the Setpoint can be modified
24
Operator mode
working Setpoint displayed
Local Setpoint display
————Decrease
Setpoint modification
————Increase
after 2 s
Setpoint entry.
The operation is acknowledged by one flash of the display.
4.2.2 MNEMONIC CODE SETTING
(e.g. configuration see page 26)
Press the for the selected parameter. Continued pressing of $ or % will display further mnemonics at a rate of one mnemonic every 0.5 s. The mnemonic displayed at the time the next parameter is selected is the one stored and used.
$ or % to display the next or previous mnemonic
Engineering Units Celsius
Degree Fahrenheit
Degree Celsius
Degree Fahrenheit
no units defined
Ph
Page 25
4.3 CONFIGURATION PROCEDURE
Conf
275.8 Menu C.pas
33
OK
Conf
EHit
274.8
InP.
S.P. Out L.inP ALM
Conf Conf
Conf
ConfConf
tiMe
Conf
Operator Mode
Configuration menu
Press the key until
4 - Operation
Enter the configuration
password
from -999...9999
(33 default from factory)
Must be equal to the
value
of the parameter
C.Pas (see page.50)
Configuration
Inputs
Setpoint
Configuration
Output
Configuration
Digital inputs configuration
(see page 26) (see page 27) (see pages 28 and 29) (see page 30)
Alarms
configuration
(see page 30... 33)
NOYES
Timer
configuration
Back to the operator mode
(see page 34)
Exit the
Configuration
25
Page 26
4 - Operation
Conf
InP.
Inp.
Unit
sc.dd
sc.lo
é 0
é 0
sc.Hi
é9999
Sqr
éno
CHar
éno
é0=10
énone
4.3.1 INPUTS CONFIGURATION
26
Input type
see table 1
Engineering Units
see table 2
LINEAR INPUT
ONLY
No. of decimals
0 / 1 / 2 / 3
Low range
from min. range
Sc.Hi
up to
High range
Sc.Lo
from to max. range
Square root
no / yes
Linear inputs characterization
no / yes
Tab. 1 Input type
Value Description
0…600°C
tc. j
0…1200°C
tc. k
0…600°C
tc. l
0…1600°C
tc. s
0…1600°C
tc. r
-200…400°C
tc. t
0…1800°C
tc. b
0…1200°C [1]
tc. n
0…1100°C [2]
tc.ni
0…2000°C
tc.U3
0…2000°C
tc.U5
0…600°C
tc. E
Custom range on request [3]
cuSt
-200…600°C
rtd1
-99.9...300.0°C
rtd2
-50.0…50.0°C
del.t
0…50 mV
M.50
0…300 mV
M.300
0…5 Volt
0=5
1…5 Volt
1=5
0…10 Volt
0=10
0…20 mA
0=20
4…20 mA
4=20
0…2.000 Hz
Frq.L
0…20.000 Hz
Frq.H
PInp.
éInP.
32…1112°F 32…2192°F 32…1112°F 32…2912°F 32…2912°F
-328…752°F 32…3272°F 32…2192°F 32…2012°F 32…3632°F 32…3632°F 32…1112°F
-328…1112°F
-99.9…572.0°F
-58.0…122.0°F
Engineering units
Frequency (option)
Tab. 2 Engineering units
Value Description
Notes:
[1] [2] Ni-Mo thermocouple. [3] Factory default for the
None
none
Degree centigrade
°C
Degree Fahrenheit
°f
mA
MA
mV
MU
Volt
U
bar
bar
PSI
psI
Rh
rh
Ph
ph
Hertz
Hz
NiChroSil-NiSil thermocouple.
custom range is: type K (32... 2448°F).
éUnit
Page 27
Conf
S.P.
S.P.ty
S.P.tr
éLoc
éno
S.P.tM
éP.Sec
éNo
rS.sl
REMOTE
INPUT ONLY
rS.In
é4=20
4.3.2 SETPOINT CONFIGURATION
Tab. 3
Setpoint type
Value Description
Local only
loc
Remote only
reM
Local/remote only
l=r
Local - trim
loc.t
Remote - trim
reM.t
4 - Operation
éS.P.ty
Setpoint type
see table 3
Stored Setpoint Tracking
see page 43
no/ yes
Time units and Setpoint slope
P.Sec/P.Min/ P.Hr
Remote Setpoint input
see table 4
not displayed if the frequency input is present
Remote Setpoint Slope enable [1]
no / yes
[1] Not available with Setpoint
Programmer option
Tab. 4 Rem. Setpoint
Value Description
0…5 Volt
0=5
1…5 Volt
1=5
0…10 Volt
0=10
0…20 mA
0=20
4…20 mA
4=20
érs.In
27
Page 28
4 - Operation
Conf
Out
Cn.ty
M.C.OP
rt. 2
énone
O.rt.2
é4=20
rt.L2
é 0
rt.H2
é9999
éPid:r
éOFF
rt.H1
é9999
rt.L1
é 0
O.rt.1
é4=20
rt. 1
énone
F.Out
éOFF
S.Out
éOFF
C.OP.5
éno
S.C.OP
éOFF
4.3.3 OUTPUT CONFIGURATION
28
Control
type
see table 5
Main output (Heat)
see table 6
Secondary output (Cool)
(Heat/Cool only) see table 7
Cool output on OP5
(Heat/Cool only)
no/yes
Main output safety value
OFF/-100…+100%
Main output forcing value
OFF/-100…+100%
Split range %
(split range only)
0.0…+100%
WITH OP5 ANALOG OUTPUT NOT
USED AS CONTROL OUTPUT
st
1
retransmitted
output selection
none/ P.U./S.P.
1stretransmission output
see table 8
st
retransmission
1 low range
whole range
st
retransmission
1 high range
whole range
WITH OPTIONAL OP6 ANALOG
OUTPUT NOT USED AS COOL CON-
TROL OUTPUT
nd
retransmitted
2 output selection
none/P.U/S.P./M.U.
2ndretransmission output
see table 8
nd
2
retransmission
low range
whole range
nd
2
retransmission
high range
whole range
Page 29
20
4
800 1200 1600
#retr = 4=20 #rt.H = P.U. #rt.L1 = 800 #rt.H1 =1200
mA
°C
Tab. 5
Value Description
Of.re Of.di pid.d pid.r U.dir U.reU H.C.ln H.C.Ol H.C.H2
Tab. 6
Value Description
Off
OP 1
log 0=5
1=5 0=10 0=20 4=20
Control mode
Reverse action Direct action Direct action Reverse action Direct action Reverse action Linear Oil charac. Water charac.
Main Output (Heat)
Not used Relay / Triac Digital 0…5 Volt 1…5 Volt 0…10 Volt 0…20 mA 4…20 mA
On - Off
PID
Modul. valves
Heat/ Cool
Digital signal
DC signal
éCn.ty
éM.C.OP
Tab. 7
Secondary output (Cool)
Value Description
Not used
Off
Relay / Triac
OP 2
Digital
log
0…5 Volt
0=5
1…5 Volt
1=5
0…10 Volt
0=10
0…20 mA
0=20
4…20 mA
4=20
Tab. 8
Retransmission outputs
Value Description
0…5 Volt
0=5
1…5 Volt
1=5
0…10 Volt
0=10
0…20 mA
0=20
4…20 mA
4=20
éS.C.OP
Digital signal
DC signal
éO.rt.1 éO.rt.2
RETRANSMISSION
When OP5 and OP6 outputs are not configured as control output, they can retransmit the PV, SP or MV linearized value.
#rt. 1
Retransmitted signal
none/P.U./ S.P
#rt. 2
#O.rt.I #O.rt.2
The following parameters define the low and high range.
#rt.L1 #rt.L2
/M.U.
Output range
0=5 /1=5 /0=10 0=20 / 4=20
Retransmission low range
4 - Operation
#rt.H1
Retransmission high range
#rt.H2
Example:
• T/C S: range 0…1600°C;
• Output range, 4…20 mA;
• Retransmitted signal PV on 800…1200°C range.
With rt.lI greater than
rt.H1 it is possible to obtain
a reverse scale.
29
Page 30
Conf
L.inp
IL1
IL2
éOFF
éOFF
IL3
éOFF
4 - Operation
Conf
ALM
bloc
éno
Ltch
éno
A1.Ou
éOP1
AL. 1
éOFF
donb
éno
4.3.4 DIGITAL INPUT CONFIGURATION 4.3.5 ALARM CONFIGURATION
30
IL1 digital input function
see table 10
IL2 digital input function
see table 10
IL3 digital input function
see table 10
Tab. 10 Digital Inputs
Value
Off
l=r A.Man s.p. 1 s.p. 2 s.p. 3 keb.I slo.1
H.pU F.Out blck strt tres
end
functions
Description Not used Local/Remote Auto/Man 1ststored Setpoint 2ndstored Setpoint 3rdstored Setpoint Keyboard lock s.p. slope disable Measure hold Output forcing mode Reset blocking Start-Hold timer Reset out timer Quit timer
éIl1 éIl2 éIl3
[1] OP1 and OP2 outputs
can be used as alarm outputs if they are not used as control outputs.
NOT AVAILABLE
OF
AL. 1 = OFF
AL1 alarm type
see table 11
AL1 addressing
OP1 / OP2 [1]
OP3 / OP4
AL1 latching
no / yeS
AL1 start-up disabling
no / yeS
Disables AL1 if a sen­sor break occurs
no / yeS
Page 31
4 - Operation
AL. 4
éOFF
A4.Ou
éOP4
Ltch
éno
bloc
éno
bloc
éno
Ltch
éno
A3.Ou
éOP3
AL. 3
éOFF
bloc
éno
Ltch
éno
A2.Ou
éOP2
AL. 2
éOFF
donb
éno
donb
éno
donb
éno
OF
NOT AVAILABLE
AL. 2 = OFF
AL2 alarm type
see table 11
AL2 addressing
OP1 / OP2 [1]
OP3 / OP4
AL21 latching
no / yeS
AL2 start-up disabling
no / yeS
Disables AL2 if a sen­sor break occurs
no / yeS
OF
NOT AVAILABLE
AL. 3 = OFF
AL3 alarm type
see table 11
AL3 addressing
OP1 / OP2 [1]
OP3 / OP4
AL3 latching
no / yeS
AL3 start-up disabling
no / yeS
Disables AL3 if a sen­sor break occurs
no / yeS
OF
AL4 alarm type
see table 11
NOT AVAILABLE
AL. 4 = OFF
AL4 addressing
OP1 / OP2 [1]
OP3 / OP4
AL4 latching
no / yeS
AL4 start-up disabling
no / yeS
Disables AL4 if a sen­sor break occurs
no / yeS
Tab. 11 Alarm type
Description
Value
Not used or used by the
Off
program (AL3/AL4)
Active High
fs.H
Active Low
fs.l
Active High
deU.H
Active Low
deU.l
Active Out
bno
Active In
bni
Loop break alarm
lba
(AL1 only) Alarm 3 active when
tiMe
Timer ON
éAl 1 éAl 2 éAl 3
éAl 4
Absolute
Deviation
Band
31
Page 32
4 - Operation
Absolute alarm
Active high
é-fsH
Active low
é-fsl
hyd hyu
On
Off
On
Off
Alarm threshold
High rangeLow range
Deviation alarm
Active high
Active low
é-del
hyd hyu
On
Off
On
Off
SP
Alarm threshold
+ range- range
é-deH
Band alarm
Active out
é-bnd
hyd hyu
On
Off
SP
Alarm threshold
full scale
full scale
hyd hyu
SP
SP SP
Ltch
Yes
275.0
3deH
The type of alarm is presented
flashing, on the front panel in
alternation with the PV value.
The red led of the activated alarm output is on.
4.3.6 AL1, AL2, AL3, AL4 ALARM CONFIGURATION [A] OPERATING CONDITIONS
Up to four alarms can be config­ured: AL1, AL2, AL3 and AL4 (see page 31). For each alarm the following selec­tions can be mode:
A the type and the operating condi-
B the functionality of the alarm
C the start-up disabling (blocking)
D alarm inhibition on sensor break E the physical output of the alarm
The outputs can be used for alarms if they are not used as control outputs (see par.
page 20).
It is possible to route up to 4 alarm to a single output (OR of the alarms).
32
tion of the alarm (table 11 page 31)
acknowledge (latching)
#bloc
#OpI #Op2 #Op3 #Op4
#ltch
3.3.7
Alarm occurrence display
This function can be enabled by the configuration software. Please, read the user manual: Serial communication and configu­ration software”.
[B] ALARM ACKNOWLEDGE
FUNCTION
The alarm, once occurred, is presented on the display until acknowledged. The acknowledge operation consists in pressing any key.
After this operation, the alarm leaves the alarm state only when the alarm condition is no longer present.
Page 33
mA
°C
OP1
275.0
A / M
1 2 3
Ilba
4
[C] START-UP DISABLING
SP
Disable
SP
On
Off
Start-up
ramp down
ramp
up
SP
threshold
=
SP± range
Disable
SP
SP
On
Off
Start-up
Bloc
Yes
PV
Process variable PV
AL1
#donb = no
#-FS.H = 300°C
Sensor break
Sensor replacement
AL1
#donb = yes
#Sc.Hi = 500°C
[D] ALARM DISABLING AT SENSOR BREAK
For those alarms that are configured to be different than LBA, it is possible to set the parameter
Set:
#donb
(disable on break).
no To maintain the alarm status when a sensor break is detected. yes To disable the alarm intervention when a sensor break is detected. Once
the sensor has been changed, the alarms that were active before the sensor break are activated again
.
4 - Operation
LOOP BREAK ALARM (LBA)
When the controller connection to the sensor is discontinued or other faults are detected in the control loop, AL1 alarm becomes active after a predefined time of
1... 9999 s from the detection of the failure (see page 37). When a sensor failure occours, the LBA interventrion is immedi­ate. The alarm state ceases when the fault condition is no longer present.
eIn case of ON-OFF control, the
LBA alarm is not active.
33
Page 34
4 - Operation
Menu
S.P.
Menu
AL
275.0
274.8
Menu
time
t.dop
t.Act
pid
s.p.s.U
t.h.s.U
Op.Hs
tiMe
cont
é Off
éEHpd
t.Mod
é 0:5
é Off
é 0:5
é 0:5
START-UP FUNCTION
(only if t.Mod = 1)
TIMER FUNCTION
(only with AL3 enabled)
4.3.7 TIMER CONFIGURATION
Timer and Start-up Menu
Timer Action
t.Modnot
(only if
Offor to 1)
equal to (see table 2 page 37)
Timer OP function
std
34
Back to
EHpd
Enable/disble PID
t.Mod= 7)
(with
0= disble 1 = enable
t.Mod parameter
Timer/Start-up operating mode
(see table 1 page 37)
Hold time
0…500 min.
Start-up Setpoint
S.P. LS.P. H
Output high limit during Start-up
5.0…100.0%
4.4 PARAMETERIZATION - MAIN MENU
Operator mode
The parameter setting procedure has a timeout. If no keys are pressed for, at least, 30 seconds, the controller switches back, auto­matically, to the operator mode.
Setpoint menu
(see page 36)
Time menu
(see pages 37)
A
Alarm
menu
(see page 41)
Page 35
Menu
Tune
Menu
PId
Menu
InP
Menu
Conf
Menu
AccS
Menu
CoMM
Menu
Out
After having selected the parameter or the code, press $ or % to modify the value (see page
24) The value is entered when the next parameter is selected, by pressing the è key.
Pressing í go back to the Operator mode
4 - Operation
PID
menu
(see page 42)
Tuning
menu
(see page 43)
Input
menu
(see page 43)
Output
menu
(see page 44)
Communication
menu
(see page 45)
Access
menu
(see page 54)
Configuration
menu
(see page 25)
35
Page 36
4 - Operation
Menu
S.P.
L=r
éLoc
SL. u
SL. d
éOFF
éOFF
S.P. H
éH.réange
S.P. L
éL.réange
Bias
é 0
rtio
é 1:00
S.P. 2
S.P. 3
é 0
é 0
S.P. 1
é 0
S.Sel
énone
Setpoint menu
LOCAL ONLY
#Loc
INDEX
LOCAL/REMOTE,
REMOTE OR PROGRAMMED
#L=r #reM #Prog
INDEX
4.4.1 PARAMETERIZATION - SETPOINT MENU
Setpoint selection local/remote
Loc / reM
Depending on the configuration index shown on page 27, the following parameters may or may not be present. [1] The units of the slope parameters are Digit/s, digit/min digit/h
LOCAL WITH TRIM OR
REMOTE WITH TRIM
#Loc.t #reM.t
INDEX
36
Stored Setpoint selection
none/ S.LOC/ S.S.P1 / S.S.P2/ S.S.P3
1st stored Setpoint
full scale
2nd stored Setpoint
full scale
3th stored Setpoint
full scale
Ratio Setpoint
-9.99…99.99
Remote Setpoint bias
full scale
Setpoint low limit
full scale
Setpoint high limit
full scale
Slope up
0ff/1…9999 digit/
[1]
Slop down
0ff/1…9999
0ff/1…9999
digit/.. digit/ [1]
Page 37
4.4.4.2 TIMER FUNCTION
AThe Timer cannot be
enabled with Heat/Cool control.
To enable this function, perform the following: 1 In order to use this AL3 func-
tion, index qmust be set to
0 in configuration (see page 22)
2 To select one of the 6 possible
functioning modes of the Timer, set the value of the fol­lowing 2 parameters in para­meterization (see p. 29).
Timer/Start-up
#t.Mod
This parameter can be defined: (see table 1)
- counting start time
- control output status at the end of the counting
table 1
Timer/Start-up counting mode Value Disabled Start-up function
Counting start time
When inside the band
When launched
When launched. Control disabled
When launched stand-by Setpoint
Now the other parameter values can be entered:
operating mode
OFF
End mode
Control mode Output to 0 Control mode Output to 0
Control mode
Control mode
1
2 3 4 5
6
7
#t.Act
This parameter can be defined: (see table 2)
- time units
- starting mode
- OP3 status when the timer is running.
When the timer is not running, the OP3 takes the opposite status.
table 2
Time units
Minutes
[1] If used by Timer [2] Using this selection, manual
starting mode is also possible.
Timer Action
Starting mode
Manual by keypad Auto at Power ON [2]
[1] OP3
status
On Off On Off
Value
4 5 6 7
4 - Operation
#tdop
standard/extended Standard: tdop = 0 OP3 is set to 1 at timer lauch and reset 0 on time elapsing. Extended: tdop = 1 OP3 is set to 1 at time elapsing and set to 0 by reset command.
#Pid
Yes:
PID is enabled when time function is enabled.
Extended:
PID is disabled and output is maintained at zero.
Timer OP function
std/eHpd
P.I.D enable yes/no
37
Page 38
4 - Operation
tdop = 1
tdop = 0
Timer start
counting
Time
elapsed
#tiMe
Timer launch
Process variable PV
Output OP [2]
OP3
±tbs
band
#t.Mod = 2
Reset
±tbr band
SP
OP3
Timer start
counting
Time
elapsed
tdop = 1
tdop = 0
#tiMe
Timer launch
Setpoint
OP3
#t.Mod =3
Process variable PV
Output OP [2]
±tbs
band
Reset
±tbr band
SP
OP3
OP = 0
tdop = 1
tdop = 0
#tiMe
Timer launch
SP
Process variable PV
Output OP [2]
#t.Mod = 4
OP3
Reset
OP3
OP = 0
4.4.4.2 TIMER FUNCTION
TIMER COUNTING MODES
A - Counting start time inside the band,
end in control mode.
The time counting starts only when the error is inside a ±1 digit band. The control action is not affected by the Timer function.
B - Counting start time inside the band,
end with control output forced to zero.
The time counting starts only when the error is inside a ±1 digit band. At the end, the con­trol output is forced to zero [1].
C - Counting start time = timer launch
time, end in control mode.
The time counting starts when the timer is launched. The control action is not affected by the Timer function.
Notes [1] When the Timer is not running the control output is forced to zero. [2] When the PID enable parameter is set to “0” (PID disabled) the OP output is set to “0”.
38
Page 39
TIMER COUNTING MODES
tdop = 1
tdop = 0
#tiMe
Timer launch
#t.Mod = 5
Process variable PV
Output OP [2]
OP3
Reset
OP3
OP = 0
tdop = 1
tdop = 0
#tiMe
Timer launch
SP
#t.Mod = 6
Process variable PV
Output OP [2]
OP3
Reset
OP3
OP = 0
tdop = 1
tdop = 0
#tiMe
Timer launch
#s.p. 2
#t.Mod =7
SP
Process variable PV
Output OP [2]
OP3
Reset
OP3
OP = 0
D - Counting start time = timer launch time,
end with control output forced to zero.
The time counting starts when the timer is launched. At the end, the control output is forced to zero [1].
E - No control action during
the counting time.
The time counting starts when the timer is launched and the control output is forced to zero. At the end, the control action starts.
4 - Operation
F - Control action with stand-by Setpoint
during the counting time.
The time counting starts when the timer is launched and the control action use the Stand-by Setpoint. At the end, the control action use the working Setpoint.
Notes [1] When the Timer is not running the control output is forced to zero. [2] When the PID enable parameter is set to “0” (PID disabled) the OP output is set to “0”.
39
Page 40
4 - Operation
End
850
850
850
RUN
4.4.4.2 TIMER FUNCTION (OPTION)
POWER FAILURE
If there is a power failure dur­ing the Timer execution, the value of the elapsed time is lost.
Depending on Timer action
#t.act selection, when the
controller restarts you can have two different situations:
• with automatic mode
(
#t.act = 6,7), the Timer
function starts again and the counting time is re-initialized.
• with manual mode
(
#t.act = 4,5), the control
output is forced to zero, if
#tMod = 3 e 5; otherwise
the control action restarts using the working Setpoint
40
TIMER START
See the Timer starting procedure on page 50 (chapter 6.2.2)
DISPLAY
When the Timer is running, the
Ö LED is on.
TIMER REMAINING TIME
When the timer is running it is possible to see the remaining time and to modify it.
To change the value of Time Remaining, it is necessary to put (from the time menu) the parameter t.sts in HOLD.
When the user exits the menu, it is possible through the up (S) and down (G) keys to change the Time Remaining.
To restart the timer, select the t.sts parameter in Time Menu and set it to RUN.
Page 41
4.4.2 PARAMETERIZATION - ALARMS MENU
Menu
AL
hy.3u
é 1
hy.3d
é 1
hy.4u
é 1
hy.4d
é 1
hy.2d
é 1
hy.2u
é 1
hy.Iu
é 1
4---
é 0
3---
é 0
2---
é 0
1---
é 0
tf1-
é 1
hy.Id
é 1
tf3-
é 1
tf2-
é 1
tf4-
é 1
4 - Operation
Alarms menu
Alarm threshold 1 [1] see table
Alarm threshold 2 [1] see table
Alarm threshold 3 [1] see table
Alarm threshold 4 [1] see table
Alarm 1 hysteresis asymmetric upper
0…5% Span in engineering units
Alarm 1 hysteresis asymmetric lower
0…5% Span in engineering units
Alarm 1 delay
OFF/1...9999
Alarm 2 hysteresis asymmetric upper
0…5% Span in engineering units
Alarm 2 hysteresis asymmetric lower
0…5% Span in engineering units
Alarm 2 delay
OFF/1...9999
Alarm 3 hysteresis asymmetric upper
0…5% Span in engineering units
Alarm 3 hysteresis asymmetric lower
0…5% Span in engineering units
Alarm 3 delay
OFF/1...9999
Alarm 4 hysteresis asymmetric upper
0…5% Span in engineering units
Alarm 4 hysteresis asymmetric lower
0…5% Span in engineering units
Alarm 4 delay
OFF/1...9999
[1] A code, specifying the No. and the
alarm type that has been config­ured (see page 31), is displayed. At this point, the user must enter the threshold value, according to the following table.
Type and value Mode
Absolute
full scale
Deviation
full scale
Band
full scale
L.B.A.
1…9999 s
Timer
ON on timer signal
Active high
Active low
Active high
Active low
Active out
Active in
Active high
Alarm 3 active on timer signal
No. and Param.
-fs.H
-fs.l
-de.H
-de.l
-bno
-bni
-lba
-ton
41
Page 42
4 - Operation
Menu
PID
OK
t.d. C
é 12:0
t.i. C
é 60
P.b. C
é 5:0
M.reS
é 50:0
O.C.
é 1:00
d.Err
ééOFF
t.d.
é 12:0
t.i.
é 60
P.b.
é 5:0
4.4.3 PARAMETERIZATION - PID MENU (not shown for ON-OFF control action)
Menu PID
42
Proportional band
0.5…999.9%c.s.
Integral time
0ff/1
9999 s
Derivative time
0ff/0.1
999.9 s
Error dead band
0ff/0.1...10.0 digits
Overshoot control
0.01…1.00 (not displayed if Heat/Cool)
Manual reset
0ff/1…100% output
(not displayed if Heat/Cool)
Heat / Cool
Algorithm
NO
YES
Proportional band Cool channel
0.5…999.9%c.s.
Cool Integral time
0ff/1
9999 s
Cool Derivative time
0ff/0.1
999.9 s
Page 43
Menu
Tune
Yes
No
t.d.
t.i.
p.b.
tune
éno
for AT
OK
4.4.4 PARAMETERIZATION
Menu
InP
T.SaM
é 0:11
In.Sh
é 0
t.FiL
éOFF
TUNING MENU (not shown for ON-OFF control action)
4 - Operation
4.4.5 PARAMETERIZATION
INPUT MENU
Tuning menu
Initial
[1] These values are not automatically stored on the PID
menu parameters
tune start
(One shot tune)
no/yes
P.b.,t.i.,t.d.
Calculated Proportional band [1] (display only)
(available when adap­tive tune is selected)
Calculated Integral time [1] (display only)
(available when adap­tive tune is selected)
Calculated derivative time [1] (display only)
(available when adap­tive tune is selected)
Input menu
Filter time constant
(user enabled/disabled)
Off/0.2…99.9 seconds
Measure bias
-60…60 digit
Sampling time
0.1…10.0 seconds
43
Page 44
4 - Operation
Menu
Out
Op.hy
é 1
ST.tM
St.OP
é Off
é 10
OP.r
é Off
OP. H
é100:0
OP. L
é 0:0
MU.hy
MU.tM
é 0:5
é 60
Op.rC
é Off
OP.C.H
t.c. C
é 10:0
é100:0
d.bnd
é 0:5
t.c.
é 10:0
4.4.6 PARAMETERIZATION - OUTPUT MENU
On-Off
Algorithm
44
Output menu
PID
Algorithm
Output hysteresis
0…5% Span in engineering units
Cycle time
(time proportional only)
0.2…100.0 s
Control Output low limit
(not available in Heat/Cool configuration) 0…100%
Control output high limit
0…100%
Control output rate limit
(user enabled/disabled)
0ff/0.01…99.99%s
Control Output soft start value
(user enabled/disabled)
0ff/1…100%
Soft start function activation time
1…9999 s
Valve drive
algorithm
Motor travel time
15…600 seconds
Minimum output step
0.1…5.0%
Heat / Cool
Algorithm
Dead band
0.0…5.0%
Cool cycle time
(time proportional only)
0.2…100.0 s
Cool control output high limit
(PID only)
0.0…100.0%
Cool output rate limit
(user enabled/disabled)
0ff/0.01…99.99%s
Page 45
PAr.y
bdr.S
é9600
énone
Add.S
é 1
PAr.y
é 3
Pro.S
bdr.S
é9600
éJbuS
Add.S
é 1
Pro.S
éJbuS
Add.P
é 3
Menu
CoMM
Serial
communication
menu
4.4.7 PARAMETERIZATION - SERIAL COMMUNICATION MENU
Depending on serial communication choosen (see model code on page 5), there are the following parameters:
RS485 Modbus/Jbus
SLAVE + PROFIBUS DP
Index c= 7-8
4 - Operation
RS485 Modbus/Jbus
SLAVE
SLAVE address communication
(if option installed)
0ff / 1…247
SLAVE baud rate
1200/2400
/9600/19200
4800
SLAVE communication protocol
MbuS / jbuS / SSIM
Parity
none/EVEn/odd
Index c= 5
SLAVE address communication
(if option installed)
0ff / 1…247
SLAVE baud rate
1200/2400
/9600/19200
4800
Communication protocol
MbuS / jbuS
Parity
none/EVEn/odd
PROFIBUS DP address
3…124
45
Page 46
4 - Operation
Setpoint change
Target Setpoint = 350°C
t
t = 10
#
sL. u = 10
digit/minute
Example
Initial Setpoint = 250°C
4.5 PARAMETERS
For a simpler use of the con­troller, the parameters have been organized in menus, according to their functional area.
46
4.5.1 SETPOINT MENU
#s.P. L #s.P. H
High and low limit of the SP. The minimum span (S.P.L - S.P.H) must be greater than 100 digit.
#sl. u #sl. d
This parameter specifies the maximum rate of change of the Setpoint. Adjustable in digit/s,digit/min and digit/hour (see page 27)
When the parameter is this function is disabled and the new Setpoint is reached immediately after being entered.
Setpoint low limit Setpoint high limit
Setpoint ramp up
Setpoint ramp down
OFF,
Otherwise, the Setpoint value is obtained according to the con­figured rate of change.
The new Setpoint value is called "Target Setpoint". It can be dis­played by means the parameter
#t.S.P.
(see procedure at page 53).
When Remote Setpoint is con­figured, we suggest to disable
#sl. u and #sl. d parameters Off.
#S.P. 1 #S.P. 2 #S.P. 3
Values of the three Setpoints, that are activated by mean of logic inputs, communication parameters, and keyboard. The Setpoint active is indicated by the ú, ù or û green LED.
See page 56 for further explana­tion.
#rs.sl
To enable or disable slopes when the remote Setpoint is active.
1st stored Setpoint 2nd stored Setpoint 3th stored Setpoint
Remote Setpoint Slope enable
Page 47
4 - Operation
bias = 20 ratio = 0.1
ratio = –0.1
Remote
signal
Range
600
100
20
0
Remote
Setpoint span
10V
bias = 100
a b
a´ b´
-200 °C
HR
a (b
´ ) b (a´ )
LR
#S.P.tr
Stored Setpoint Tracking
(see chapter 4.3.2 at page 27) Two different operation mode can be set: A Stand-by mode The selection of any memorized SP (SP1, SP2, SP3) does not overwrite the previous local Setpoint when the memorized SP is no longer active. The pre-
# no
vious local SP in unchanged.
B- Tracking mode #yeS The use of any memorized SP (SP1, SP2, SP3) overwrites the local SP value.
The previous Local Setpoint value will be lost.
#rtio
Remote Setpoint Ratio
Ratio is the coefficient which defines the remote Setpoint span with respect to the input span.
#bias
Remote Setpoint
Bias defines the starting point of analog Remote Setpoint in engi­neering units corresponding to the low limit (current or voltage) of the remote signal.
PV = Process Variable LR = PV low limit HR = PV high limit SR = Remote Setpoint a (a´) = SR starting point b (b´) = SR ending point
47
Page 48
4 - Operation
biaS = starting point = a
rtio =
E.g.: biaS= 20
rtio =
b - a
HR - LR
100 - 20
600 - (-200)80800
= 0.1=
biaS = starting point = a´
rtio =
E.g.: biaS= 100
rtio =
b´ - a´
HR - LR
20 - 100
600 - (-200)
-80
800
= -0.1=
4.5.1 SETPOINT MENU
If SR starting point is lower than the ending point, both expressed in engineering units:
If SR starting point is higher than the ending point, both expressed in engineering units
Working Setpoint (SP) as com­bination of Local Setpoint (SL) and remote signal
Loc.t (table 3, page 27)
Setpoint
SP = SL + (rtio • REM) + biaS
48
4.5.2 ALARM MENU
Setpoint reM.t (table 3, page 27)
SP = REM + (rtio • SL) + bias SIGN = Remote signal % SPAN = HR-LR
SIGN * SPAN
REM =
E.g.:Local Setpoint (SL) with an
Setpoint type = Loc.t
rtio
Remote Setpoint (SR) with an internal Trim with multiplying coefficient of 1/5: Setpoint type =
rtio
Remote Setpoint range equal to the Input range: Setpoint type =
rtio
100
external Trim with multiply­ing coefficient of 1/10:
= 0.1; biaS=0
reM.t
= 0.2; biaS=0
Loc.t
= 1; biaS=LR
SL =0
(see also pages 32 and 33)
#hy-u #hy-d
Example with high absolute alarm
On
Off
The parameter can be set between 0 and 5% of the con­figured Span and set in Engineering units. e.g. Range = -200…600°C Span = 800°C Max. Hysteresis = 5% 800°= 40°C
For symmetrical hysteresis set
Asymmetric upper alarm hysteresis Asymmetric lower alarm hysteresis
Alarm threshold
#hy-d
=
#hy-u
Alarm
#tF1
Delay time for alarm activation.
delay
OFF: alarm activated immediately
1...9999 seconds: alarm acti­vated only if the condition per­sists for the set time
#hy-d = #hy-u
Page 49
4.5.3 PID MENU
STEP response
SP
End of the tuning
operating and
setting of the new
calculated terms
Start of autotune
operation
Setpoint change
PV variable
Control output
Not present with On-Off main output or Timer PID = 0.
Proportional Band Cool Proportional
Band
Integral Time
Cool integral Time
#p.b. #p.b. C
This parameter specifies the proportional band coefficient that multiplies the error (SP - PV)
#t.i. #t.i. C
This is the integral time value that specifies the time required by the integral term to generate an output equivalent to the proportional term. When Off, the integral term is not included in the control algorithm.
#t.d. #t.d. C
This is the time required by the proportional term P to reach the level of D. When Off it is not included in the control algorithm.
#O.C.
(Automatically disabled when the adaptive tune is running) This parameter specifies the span of action of the overshoot control. Setting lower values (1.00—>0.01) the overshoot generated by a Setpoint change is reduced. The overshoot con­trol doesn’t affect the effective­ness of the PID algorithm. Setting 1, the overshoot control is disabled.
Derivative Time
Cool Derivative Time
Overshoot control
#M.res
This term specifies the value of the control output when PV = SP, in a PD only algorithm (lack of the Integral term).
#d.err
Inside this band for (PV - SP), the control output does not change to protect the actuator (output Stand-by).
Manual reset
Error
Dead Band
4 - Operation
4.5.4 TUNING MENU (not shown for ON-OFF main control output)
See page also 57
Two tuning method are provided:
• Initial one shoot Fuzzy-Tuning
• Continuous, self learning
Adaptive Tuning
The Fuzzy-Tuning automatically
determines the best PID term with behaviour respect to the process.
The controller provides 2 types of “one shot” tuning algorithms, that automatically are selected according to the process con­ditions when the tune operation is started.
49
Page 50
4 - Operation
0
PV
63.2%
Filter time
Time
Fuzzy-Tuning is selected when, at the start of the autotune operation, the PV is far from the Setpoint (more than 5% of the span). This method has the advantage of fast calculation with a reasonable accuracy in the term calculated.
Natural frequency
tuning start
PV variable
Control output
Natural frequency is selected when the PV is close to the SP.
This method has the advantage of better accuracy in the terms calculated with reasonable speed.
The Fuzzy Tuning automati­cally determines the best method to use to calculate the PID term, according the
50
End of the tuning
operating and
setting of the new
calculated terms
process conditions.
The self-learning adaptive auto­tune is not intrusive. It does not
affect the process during the phase of calculation.
Continuous adaptive tune
Perturbation
New parameters
Continuous adaptive tune is particularly suitable for con­trolling process whose control characteristics change with time or are not linear in rela­tion to the Setpoint values.
It does not require any operation by the user. It continuously sam­ples the process response to the various perturbations, determin­ing the frequency and the ampli­tude of the signals. On the basis of this data and their statistical values stored in the instrument,
it modifies the PID term para­meters.
It is the ideal for all applications where it is required to continu­ously change the PID terms parameters in order to adjust the PID to the changes of the process dynamic conditions.
In case of power OFF with the Adaptive Tune enabled, the val­ues of the PID terms parame­ters are stored, in order to be reused at the next power ON.
At power on the Adaptive Tune starts automatically.
4.5.5 INPUT MENU
Input
#t.fil
Time constant, in seconds, of the RC input filter on the PV input. When this parameter is
filter
Off the filter is bypassed.
#In.sh
This value is added to the mea­sured PV input value. Its effect is to shift the whole PV scale of its value (±60 digits).
#t.SaM
Sampling time, in seconds, of the instrument. This parameter is normally used when control­ling slow process, increasing the sampling time from 0.1... 10 s.
Measure Bias
Sampling Time
Page 51
4.5.6 OUTPUT MENU
SP On
hy
#
#Op.hy
The parameter can be set between zero and 5% of the configured Span and set in Engineering units. e.g. Range = -200…600°C
Span = 800°C Max. Hyst. = 5% 800° = 40°C
#t.c. #t.c. C
This is the cycle time of the logic control output. The PID control output is provided by the pulse width modulation of the waveform.
#Op. l
It specifies the minimum value of the control output signal. It is also applied in manual mode.
Control output
hysteresis
Control output cycle time Cool
cycle time
Control Output low limit
#Op. H #Op.C.H
This specifies the maximum value the control output. It is also applied in manual mode.
#Op.r #Op.rC
This value, specified in %/sec­onds, with a range from 0.01 to
99.99%/s provides the maxi­mum rate of change of the out­put. When set to Off this func­tion is disabled.
#st.Op
This specifies the value at which the control output is set during the soft start phase.
Control output high limit
Cool output high limit
Heat output maximum rate
Cool output maximum rate
Soft start of the control output
Soft-Start
phase
#st.Op
Soft start time
#Op.r
Speed in %/s
Time
Travel time
Minimum step
#st.tM
This value specifies the time the soft start phase lasts. The start up phase starts at power up of the controller.
OP
100%
tart-up
#MU.tM
Provides the time required for the motor positioner to go from the 0% position to 100%
#MU.hy
This specifies the minimum allowed time activation of the output to a motor positioner that produces a sensible effect. It is related to the deadband of the positioner.
4 - Operation
#d.bnd
This parameter specifies the width of the deadband between the Cool and the Heat outputs.
eat / Cool Algorithm
Heat 100%
Op.H.
100%
Heat output
Heat/Cool deadband
Heat Cool
SP
d.bnd
P.b. / CP.b.
0
0
#OpC.H
100%
Cool output
51
Page 52
4 - Operation
4.5.7 SERIAL COMMUNICATION MENU (OPTION)
RS485 address
#Add.S #Add.P
All instruments connected to the same supervisor must have dif­ferent addresses. If set serial comm.s is not active.
communication
- 1…247
SLAVE Profibus DP
address
- 3…124
Off the
#Prot
Two serial communication options are available:
A - Modbus/Jbus SLAVE
The parameters value can be read and when possible modified.
Protocol
selection
Mbus Modbus Jbus Jbus sSi Modbus SSI
• The list of data transfer (profile file) is user configurable. It can be set by means the configuration software [1]
Notes:
A Please, read the user
[1]
manual: “Serial communications and configuration soft­ware”.
#bdr.S
This provides the baud rate in the range 1200... 19200 bit/s.
#PAr.y
May be set even (
odd). If None is set, parity will
( be excluded.
52
SLAVE
Baud rate
Parity
EVEn) or odd
B - PROFIBUS DP SLAVE
(Process Field bus protocol) Industrial standard for peripher­al devices connection to a machine in a plant. The protocol installed in this con­troller offers the following advan­tages against the standard nor­mally supplied by other suppliers:
• Communications baudrate
Up to 12 Mb/s with electric
isolation.
Page 53
4.5.8 TIME MENU
tsts
850
RUN
t.bs
60
RUN
t.HH
234
RUN
t.MM
25
RUN
t.br
60
RUN
Timer functions
res/run/End/ hold
(reset/run/quit/hold)
Time set (in hour)
0...9999
Time set (in minutes)
0...9999
Band at timer start
0...100
Band during timer counting
0...100
Time band Start
#t.bs #t.br
These two commands set the band at start time count and the band for the timer running.
0… 100
Time band Run
0… 100 (only for t.Mod = 2, 3)
4 - Operation
53
Page 54
4 - Operation
4.6 PARAMETERIZATION - ACCESS MENU - PASSWORD - CALIBRATION
274.8
275.8
AccS
Menu
11
A.pas
54
Operator mode
Press until
Access menu
Enter password
for access enable
from -999 to 9999
(11 default value from factory)
If the password entered corre-
sponds to the one stored in the
A.pas[A] parameter, the
access configuration page is
displayed.
go back to the Operator
Pressing í
mode
YES
NO
OK
[1] With the level of access set to full, all
the related parameters are displayed.
fUll
Ac.le
none
EHec
yes
Access to all the levels [1]
Execute the following operations
A/M enable
yes/nO
E.AMn
Oper
Ac.le
C.pas
EHec
33
C.pas
Operator level Access
Change the Configuration password
Enter the Configuration password
Page 55
Edit
Ac.le
Access to the edit level
X5
45.80
50
45.80
During the up-download of the data to/from the Memory chip, the controller display shows the segment clockwise rotation of the digits.
C.pot
EHec
4 - Operation
Calibrate the potentiometer
(if present)
A.pas
EHec
II
A.pas
Change the Access pass­word
Enter [A] the Access password
load
EHec
Load the data from Memory chip
Confirm and return
back to the
Operator mode
stor
EHec
Download the data to Memory chip
O
pot.l
255
pot.H
The valve goes to low scale
When the indication
(the valve) is stopped,
confirm the calibra-
tion value using
$ or %
The valve goes to full scale
55
Page 56
4 - Operation
Menu
pId
p.b.
35.0
Ac.le
Oper
With the access level Edit, the user defines which groups and parameters are accessible to the operator
After selecting and confirming the access level Edit, enter in the parameters menu. The code of the access level is displayed on the front panel.
Press the the proper level.
$% keys to select
Group of parameters Code Access level
read Hide
Group of parameters Code Access level
AItr fast read
Hide
Visible
Not visible (hidden)
Visible and changeable
Included in “Fast view”
Visible only
Not visible (hidden) and not changeable
The parameters in the access level
fast are recalled on the
front panel through the pro­cedure of fast parameter access illustrated in par. 5.2
page 57. The maximum num­ber of fast parameters is 10.
At the end of the parameter list of the selected group, the controller exits from the Edit access level.
Therefore, the Edit level must be selected for each group of parameters
The access level of groups and parameters is activated through:
Access level operator
56
Confirm
Page 57
275.0
274.8
63
275.0
274.8
63
rel.
00A
Hard
3150
Out
30.0
t.s.p.
300.0
Op
63.0
°C
274.8
tune
no
s.sel
none
3fs.H
365.8
ABCD
Product
identification
codes
Manual mode
Operator mode Automatic mode
Fastview
parameters
5 DISPLAYS
5.1 STANDARD DISPLAY
5 - Displays
5.2 FAST VIEW
(fast access to the parameters)
Software release
Base product code
(see page 5)
Engineering units
Main output
(during the program run only)
Target Setpoint value
local mode only
(not displayed if the Slopes are disabled)
Virtual valve position
(0...100%)
Back to the Operator modeBack to the Operator mode
One shot tune start
no/yes
Alarm 3 threshold
(high absolute alarm)
full scale
Stored Setpoint selection
none/s.LOC/ s.s.p.I/s.s.p.2/ s.s.p.3
With this procedure, up to 10 parameters, selected through the fast view (see par 4.6 page
56) are displayed and can be modified by the operator without requiring the standard parameter setting procedure. Press
$% in order to
modify the parameters. The value is entered by pressing è key.
On left side, please find a sample list of parameters on Fast view menu.
57
Page 58
6 - Commands
6 COMMANDS
The commands can be
entered in 3 ways:
COMMANDS TO THE CONTROLLER AND OPERATING PHASES
58
6.1 KEYPAD
see page 55
• Setpoint modification
• Manual mode
• Local/remote selection
• Stored Setpoint display
• Tune Run / Stop
• Program start/stop (see page 66)
6.2 DIGITAL INPUTS
see page 58
6.3 SERIAL
COMMUNICATIONS
see the manual on this topic
Page 59
6.1 KEYPAD COMMANDS
275.0
274.8
63
350.0
274.8
350.0
274.8
275.0
274.8
63
275.0
274.8
35
275.0
274.8
63
AUTO AUTO
SP = PV
OPMAN=OPAUTO
SP (PV)
O
Y
0
0
MAN
Op.r
SP
change OP
100% Setpoint SP
with
100% output OP
OPAUTO=OPMAN
PV
OP
6.1.1 SETPOINT MODIFICATION 6.1.2 AUTO/MANUAL MODE
6 - Commands
The Setpoint is directly modi­fied with the $% keys.
Once entered, the new value is checked and becomes operating after 2 seconds. The end of this phase is flagged by flashing momentarily the display with SP.
Select
Operator mode
Example of Setpoint modifica­tion from 275.0 to
350.0
Modified Setpoint value
after 2 seconds
Flash momentarily the SP value to confirm that it has become operating. back to the opera­tor mode
The new value is immediately
working without any confirm.
Back to the operator mode
manual
green
{
led on
Modification of control
output value
A
Modify
the output
value
The bumpless action is present switching between AUTO, MAN and vice versa.
AIn case of power failure, the
AUTO/MAN status and the output value remain stored in the controller memory.
Operator mode
(automatic)
59
Page 60
6 - Commands
Menu
S.P.
275.0
274.8
l=r
l=r
loc
l=r
reM
loc
s.sel
s.sel
S.LOC
s.sel
s.s.p.1
s.s.p.3
s.sel
none
6.1.3 LOCAL/ REMOTE SELECTION 6.1.4 STORED SETPOINTS SELECTION (see also pages 42, 43)
The Setpoint is directly modified with the $% keys. Once entered, the new value is checked and becomes operational after 2 seconds. The end of this phase is flagged by flashing momen­tarily the display with SP.
Stored Setpoint displays
Local/remote
selection
remote
Back to the
operator mode
60
Select
Select
local
The selected
Setpoint becomes
operating pressing the
è
When in Remote,
the green led
Ü
is on
1st stored
Setpoint
2nd stored
Setpoint
3th stored
Setpoint
Back to the operator mode
The selected Setpoint
becomes operating
pressing the
è key.
The three
ú ù û
leds flag the Setpoint
operating.
Page 61
275.0
274.8
Menu
Tune
tune
tune
no
tune
yes
no
6.1.5 TUNE RUN / STOP
6 - Commands
This controller is provided with 2 different Tuning algorithm:
• Fuzzy tune (one shot tune)
for calculating the optimal PID term parameters.
Adaptive Tune (continuous tune) for a continuous calculation of the PID term parameters.
Operator mode
press until
Tuning menu
Press until
Fuzzy Tune
start-up
Confirm
yes
to start
Confirm
no
to stop
After the execution of the tuning, the calculated values are automatically presented in the PID menu.
The command start/stop is executed pressing the
è key.
When the controller is
calculating the PID
parameters, the green
Ä led is ON.
61
Page 62
6 - Commands
6.2 DIGITAL INPUTS
COMMANDS
A function is assigned through the configuration procedure to each IL1, IL3 and IL3 digital input. (see the parameters set­ting at tab. 10 at page 30). The configured function is acti­vated when the digital input (free voltage contact or open collec­tor output) is in the On state (closed). It is deactivated by set­ting the input to the Off state (open). The activation of the function through the digital input has the highest priority than through the keypad or through the serial communication.
62
6.2.1 DIGITAL INPUTS COMMANDS FOR LOCAL-REMOTE SETPOINT
Function
None
Set manual mode
Keyboard lock
PV measure hold
Setpoint slopes inhibition
Output forcing mode
1st stored Setpoint
2nd stored Setpoint
3th stored Setpoint
Set Remote mode
Reactivation of blocking
Start-Hold timer
Reset Out 3
End timer
Parameter
value
#OFF #A.Man
#keb.I #H.pU #Slo.1 #F.Out
#s.p. 1 #s.p. 2 #s.p. 3 #l=r #bLcK
#strt #tres #End
Performed operation
Off On
Not used
Automatic Manual
Unlock Locked
Normal
operation
Rate limiting
is active
Normal
output
Local 1st SP
Local 2nd SP
Local 3th SP
Local Remote
PV is hold
Normal
operation
Forced
output
Reactivation
of blocking
Start-Hold timer
Reset Output 3 connected to the timer
Abort timer
Notes
With the keypad locked the commands from digital inputs and serial communications are still operating
The value of PV is “frozen” at the time the digital input goes to the close state
When the input is in the on state, the Setpoint is changed in steps
With ON command the output is equal to the forced value (see page 28)
The permanent closure forces the chosen stored value. Setpoint modification is not possible. The impulsive closure, selects the stored value. Setpoint modification is allowed. If more than one digital input is selecting a Setpoint, the last to be activated is the operating one (see page 43)
The blocking function is activated on closing the com­mand from digital inputs
Page 63
8 TECHNICAL SPECIFICATIONS
Features
at 25°C env. temp.
Total configurability
(see chapter 4.3 page 25)
PV Input
(see pages13,14 and page 26)
Description
From keypad or serial communication the user selects:
- the type of input A/D converter with resolution of 160,000 points
Common characteristics
Update measurement time: 50 ms Sampling time: 0.1… 10.0 s Configurable Input shift: - 60… + 60 digit Input filter with enable/disable: 0.1… 99.9 seconds
Accuracy
Resistance thermometer (forT: R1+R2 must be <320Ω)
0.25% ±1 digits for temperature sensors
0.1% ±1 digits (for mV and mA)
Pt100a 0°C (IEC 751) °C/°F selectable
L, J, T, K, R, B, N, E,W3, W5
Thermocouple
(IEC 584) Rj >10M °C/°F selectable
DC input (current) 4... 20mA, 0... 20mA Rj =30
0... 50mV, 0... 300mV Rj >10M
DC input (voltage)
1... 5, 0... 5, 0... 10V Rj>10k
Frequency (option)
0... 2,000/0... 20,000Hz
Low level 2V High level 4... 24V
- the type of Setpoint
- the type of control algorithm
- the type of output
2 or 3 wires connection Burnout (with any combination)
Internal cold junction compensation con NTC Error 1°C/20°C ±0.5°C Burnout
Burnout. Engineering units conf. decimal point position with or without Init. Scale -999… 9999 Full Scale -999… 9999 (min. range of 100 digits)
8 - Technical Specifications
- the type and functionality of the alarms
- control parameter values
- access levels
Between 100…240Vac the error is minimal
Max. wire Res: 20max. (3 wires)
Input drift: 0.1°C/10° T
<0.1°C/10Wire Res.
env
Line: 150max. Input drift: <2µV/°C. T
<5µV/10Wire Res.
Input drift: <0.1%/20°C T
<5µV/10Wire Res.
env.
env.
63
Page 64
8 - Technical Specifications
Features
at 25°C env. temp.
Auxiliary inputs
Digital inputs
3 logic
Operating mode and Outputs
64
Description
Remote Setpoint
Not isolated accuracy 0.1%
Current: 0/4...20mA: Rj = 30
Voltage: 1... 5, 0... -5, 0... 10V: Rj = 300k
Potentiometer 100... 10k
The closure of the external contact produces any of the following actions:
Auto/Man mode change, Local/Remote Setpoint mode change, 3 Stored Setpoint activation, keyboard lock, measure hold, slope inhibit and output forcing
Program Hold/Run (if option installed), Program Selection and Skip to Next Segment
Single action
1 single or double action PID loop or On/Off with 1, 2,3 or 4 alarms
Double action Heat / Cool
Valve drive
Bias in engineering units and ± range Ratio: -9.99… +99.99 Local + Remote Setpoint
Feedback valve position
Control output Alarm Alarm Alarm Alarm Retransmission
Main
(Heat)
OP1
Relay/Triac
OP5
Analog/Digital
OP1
Relay/Triac
OP1
Relay/Triac
OP5
Analog/Digital
OP5
Analog/Digital
OP1
Relay/Triac
Secondary
(Cool)
OP2
Relay/Triac
OP5
Analog/Digital
OP2
Relay/Triac
OP6
Analog/Digital
OP2
Relay/Triac
AL1 AL2 AL3 AL4 PV / SP
OP1
Relay/Triac
OP1
Relay/Triac
OP1
Relay/Triac
OP2
Relay/Triac
OP2
Relay/Triac
OP2
Relay/Triac
OP2
Relay/Triac
OP3
Relay
OP3
Relay
OP3
Relay
OP3
Relay
OP3
Relay
OP3
Relay
OP3
Relay
OP4
Relay
OP4
Relay
OP4
Relay
OP4
Relay
OP4
Relay
OP4
Relay
OP4
Relay
OP5
Analog/Digital
OP5
Analog/Digital
OP5
Analog/Digital
OP6
Analog/Digital
OP6
Analog/Digital
OP6
Analog/Digital
OP6
Analog/Digital
OP6
Analog/Digital
OP6
Analog/Digital
Page 65
Features
at 25°C env. temp.
Control mode
8 - Technical Specifications
Description
Algorithm Proportional band (P) 0.5…999.9% Integral time (I) 1…9999 s Derivative time (D) 0.1…999.9 s Error dead band 0.1…10.0 digit Overshoot control 0.01…1.00 Manual reset 0…100% Cycle time (Time proportional only) 0.2…100.0 s Min./Max output limits 0…100% separately adjustable Control output rate limit 0.01…99.99%/s Soft-start output value 1…100% - Time 1…9999 s Output safety value -100…100% Control output forcing value -100…100% Control output hysteresis 0…5% Span in engineering units On-Off algorithm Dead band 0.0…5.0% Cool proportional band (P) 0.5…999.9% Cool integral time (I) 1…9999 s Cool derivative time (D) 0.1…999.9 s Cool cycle time (Time proportional only) 0.2…100.0 s Control output high limit 0…100% Cool output max. rate 0.01…99.99%/s Motor travel time 15…600 s Motor minimum step to 0.1…5.0% Feedback potentiometer 100…10k
PID with overshoot control or On-off - PID with valve drive algorithm, for controlling motorised positioners
OFF = O
Single action PID algorithm
OFF = O
OFF = O
OFF = O
Double action PID algorithm (Heat / Cool)
Valve drive PID algorithm Raise/Stop/Lower
65
Page 66
8 - Technical Specifications
Features
at 25°C env. temp.
OP1 - OP2 outputs
Description
SPST Relay N.O., 2A/250Vac (4A/120Vac) for resistive load Triac, 1A/250Vac for resistive load
OP3 output SPDT relay N.O., 2A/250Vac (4A/120Vac) for resistive load
OP4 output RSPST relay N.O. 2A/250Vac (4A/120Vac) for resistive load
Analog/digital OP5 and OP6 (option) outputs
Control or PV/SP retransmission
Galvanic isolation Short circuit protected Resolution 12 bit Accuracy
: 500 Vac/1 min
: 0.1 %
Hysteresis 0…5% Span in engineering units
Active high
Action type
AL1 - AL2 - AL3 - AL4 alarms
Action
Active low
Special functions
Sensor break, heater break alarm
Acknowledge (latching), activation inhibit (blocking)
Connected to Timer or program (if options installed) (only OP3-OP4)
Local + 3 memorized
Setpoint
Remote only
Local and Remote
Local with trim
Up and down ramps 0.1...999.9 digit/minute or digit/hour (OFF=0) Low limit: from low range to high limit High limit: from low limit to high range
Remote with trim
66
Analog: 0/1... 5V, 0…10V, 500/20mA max.,
0/4... 20mA, 750/15V max.
Digital: 0/24Vdc ±10%; 30mA max. for solid state relay
Deviation threshold ±range
Band threshold 0… range
Absolute threshold whole range
Page 67
Features
at 25°C env. temp.
Tuning
Description
Fuzzy-Tuning type .The controller selects automatically the best method according to the process conditions
Adaptive Tune
of the PID parameters
self-learning, not intrusive, analysis of the process response to perturbations and continuously calculation
Step response Natural frequency
Auto/Man station Standard with bumpless function, by keypad, digital input or serial communications
RS485 isolated, SLAVE Modbus/Jbus protocol, 1200, 2400, 4800, 9600, 19.200 bit/s, 3 wires
Serial comm. (option)
RS485 isolated, MASTER Modbus/Jbus protocol, 1200, 2400, 4800, 9600, 19.200 bit/s, 3 wires RS485 asynchronous/isolated, PROFIBUS DP protocol, from 9600 bit/s at 12MB/s selectable, max. lenght 100m (at 12 Mb/s)
Auxiliary Supply +24Vdc ± 20% 30mA max. - for external transmitter supply
Detection of out of range, short circuit or sensor break with automatic activation of the safety strategies and alerts on display
Safety and forcing value -100...100% separately adjustable Parameter and configuration data are stored in a non volatile memory for an unlimited time Password to access the configuration and parameters data - Fast wiew
100... 240Vac (-15% +10%) 50/60Hz or 24Vac (-15% +25%) 50/60Hz and 24Vdc (-15% +25%)
Compliance to EN61010-1 (IEC 1010–1), installation class 2 (2500V) pollution class 2, instrument class II
Compliance to the CE standards (see page 2)
File E323812
IP65 front panel
1
/8 DIN - 48 x 96, depth 110 mm, weight 380 g max.
Operational safety
General characteristics
Measure input
Control output Parameters Access protection Power supply
(PTC protected) Safety Electromagnetic
compatibility UL and cUL Approval Protection EN60529
(IEC 529) Dimensions
8 - Technical Specifications
Power consumption 5W max.
67
Page 68
Factory default parameters
FACTORY DEFAULT PARAMETERS
Parameter Parameter Name Default value User settings Notes
S.SEL
SP.1
SP.2
S.P.L
S.P.H
Sl.u
Sl.d
rtio
biaS
1
2
3
4
Hy.1u
Hy.1d
68
Setpoint selection NONE
1st stored Setpoint 0
2nd stored Setpoint 0
Setpoint low limit PV.LO
Setpoint high limit PV.HI
Setpoint ramp up OFF
Setpoint ramp down OFF
Ratio remote Setpoint 1.00
Remote Setpoint Bias 0
AL1 alarm threshold 0
AL2 alarm threshold 0
AL3 alarm threshold 0
AL4 alarm threshold 0
AL1 alarm hysteresis Up 1
AL1 alarm hysteresis Down 1
Page 69
Factory default parameters
Parameter Parameter Name Default value User settings Notes
tFl1
Hy.2u
Hy.2d
tFl2
Hy.3u
Hy.3d
tFl3
Hy.4u
Hy.4d
tFl4
t.Mod
t.act
t.dOP
t.hSu
S.P.S.u
OP.hS
Pid
P.b.
AL1 delay 1
AL2 alarm hysteresis Up 1
AL2 alarm hysteresis Down 1
AL2 delay 1
AL3 alarm hysteresis Up 1
AL3 alarm hysteresis Down 1
AL3 delay 1
AL4 alarm hysteresis Up 1
AL4 alarm hysteresis Down 1
AL4 delay 1
Timer Operating Mode 0
Timer Action 4
Timer OP Function 1
Hold time 0
Start Up time 0
Output limit during Startup 0
PID Enable/disable 1
Proportional band 3.0
69
Page 70
Factory default parameters
Parameter Parameter Name Default value User settings Notes
t.i.
t.d.
d.Err
O.C.
O.C.r.b.
MreS
P.b. C
t.i. C
t.d. C
tune
AdPt
t.Fil
In.Sh
t.SaM
OP.Hy
t.c.
OP.L
OP.H
70
Integral time 60
Derivative time 12.0
Error Dead Band OFF
Overshoot Control 0.8
Overshoot Control relative band 1.0
Manual Reset 50
Cool proportional band 3.0
Cool integral time 60
Cool derivative time 12.0
Start/Stop One shot tuning (0=Stop 1=Run) NO
Start/Stop Adaptive tuning (0=Stop 1=Run) NO
Input filter 2.0
Input shift OFF
Sampling time 0.1
Output Hysteresis 1
Cycle time 5.0
Control ouput low limit 0.0
Control output high limit 100.0
Page 71
Factory default parameters
Parameter Parameter Name Default value User settings Notes
OP.r
St.OP
St.tM
M.t
M.hy
d.bnd
tc.C
OP.C.H
OP.rC
Add.S
dr.S
Pro.S
Par.y
MaSt
dr.M
Pro.M
Add.P
C.PAS
Control output maximum speed OFF
Soft start output high value OFF
Soft start time 10
Output minimum step Servomotor 60
Output minimum step Servomotor 0.5
Heat/Cool Dead band 0.5
Cool cycle time 5.0
Cool output maximum value 100.0
Cool output maximum speed OFF
Communication SLAVE address 247
SLAVE Baud rate 9600
SLAVE Communication protocol MBUS
Parity NON E
Enable MASTER NO
MASTER Baud rate 9600
MASTER Communication protocol MBUS
PROFIBUS DP address 3
Configuration password 33
71
Page 72
Factory default parameters
Parameter Parameter Name Default value User settings Notes
A.PAS
In
Unit
SC.dd
SC.lo
SC.Hi
Sqr
Char
S.P.ty
S.P.tr
S.P.T
.In
72
Access password 11
Input type selection 0 - 10
Engineering units NONE
Number of decimals (0... 3) 0
Low range 0
High range 9999
Square root (0 = OFF, 1 = ON) NO
Linear input characterization NO
Setpoint type LOC
Stored Setpoint tracking NO
Time units and Setpoint slope P.SEC
Remote Setpoint input 4 - 20
Page 73
WARRANTY
We guarantee this product to be free from defects in material and workmanship for 3 years from the date of shipment. The warranty above shall not apply for any failure caused by the use of the product not in accordance with the instructions in this manual.
Warranty
73
Page 74
Icons table
ICONS TABLE
Main universal input Digital input
Thermocouple Isolated contact
RTD (Pt100) NPN open collector
Delta Temp (2x RTD) TTL open collector
mA and mV
Custom Local
Frequency Stand-by
Setpoint
Digital input connected functions
Auto/Manual
Run, Hold, Reset and program selection
PV hold
Setpoint slopes inhibition
Output
SPST Relay
74
Auxiliary input
Current transformer Outputs lock
mA Remote setpoint Start-up function
Volt Remote setpoint Timer function
Feedback potentiometer
Keypad lock
Memorized
Remote
Setpoint programmer
Triac
SPDT Relay
mA
mA mV
Logic
Loading...