Super Systems X5 Calibration Manual

X5 Controller
Calibration Guide
Step
Function
Action
C.tc.
TC calibration
C.Pt.
RTD calibration
Apply 313.594 Ω to the input – set with or keys
C.mV.
mV calibration
Apply 300 mV to the input – set with or keys
C.Vol
Volts Calibration
C.Ma
mA calibration
Apply 20mA to the input – set with or keys
C.S. V
Remote Setpoint Volts calibration
C.S. mA
Remote Setpoint mA calibration
Introduction The instrument calibration is based on a series of steps. Each step performs the calibration of a particular input or output. It must be done only when strictly necessary and using reference instruments with a high accuracy. Then the instrument must remain switched on at current environmental conditions for at least one hour.
Calibration Procedure Starting from operation mode, press and hold both the “ “(enter) and “ “(menu access) keys. “C.PaS” will
appear. Enter the Configuration Password (default: 33).
NOTE: See the X5 Controller product manual section “4.6 PARAMETERIZATION - ACCESS MENU - PASSWORD
- CALIBRATION” for more details on the Configuration Password.
“C.tc” (T/C calibration) will appear on the lower display while a value will appear on the upper display. Generate a signal using the below table;
adjust the value to be as close to zero as possible: 0 ±2.
use copper wire to source the signal. Press the “ “ or ““ keys to
Apply 50.000mV to the input – set with ∨ or ∧ keys
Apply 10 V to the input – set with ∨ or ∧ keys
Apply 10 V to the input – set with ∨ or
Apply 20mA to the input – set with ∨ or
Table 1 - Calibration types and actions
Wait until the displayed value remains stable: 0 ± (2 to 5).
IMPORTANT: Press the “” key to bypass a calibration step. DO NOT press the “∨ “ or “∧ “keys unless you want to Calibrate that specific step.
When the calibration is correct, press the “” key to go to the next step. It is possible to not modify the calibration. When the step has been displayed on screen DO NOT press the “
” key until out of calibration mode. –OR­After “C.tc.”, press the “” key to re-enter normal operation.
“ or “ “ keys; only press the
keys
keys
Super Systems Inc. X5 Controller: Calibration Guide. (Document #4615; New: 05/01/2014).
Visit us online at http://www.supersystems.com.