Super Systems e-TRIM User Manual

e-TRIM
OPERATIONS MANUAL
Super Systems Inc.
www.supersystems.com
Shipping Address: 7245 Edington Drive
Cincinnati, OH 45249
513-772-0060
Fax: 513-772-9466
Super Systems Inc.
Super Systems Europe
Super Systems México
Super Systems China
USA Office
Corporate Headquarters:
Shipping Address:
Cincinnati, OH 45249
Phone: (513) 772-0060
http://www.supersystems.com
Units 3 & 4, 17 Reddicap Trading Estate,
Sutton Coldfield, West Midlands
B75 7BU
UNITED KINGDOM
Phone: +44 (0) 121 329 2627
http://www.supersystemseurope.com
Sistemas Superiores Integrales S de RL de CV
Calle 3 Int.: 11.
Zona Ind. Benito Juarez
Querétaro, Qro. Méx.
C.P.: 76120
Phone: +52 (442) 210 2459
http://www.supersystems.com.mx
Super Systems Inc. Page 2 of 27 e-TRIM Operations Manual
No. 335 XianXia Road
Room 308
Shanghai, CHINA
200336
Phone: +86 21 5206 5701/2
http://www.supersystems.com
Table of Contents
E-TRIM OVERVIEW ................................................................................................................................................. 4
E-TRIM TOUCHSCREEN INTERFACE......................................................................................................................... 5
MAIN SCREEN ............................................................................................................................................................... 5
DETAILS ........................................................................................................................................................................ 6
MENU.......................................................................................................................................................................... 6
e-TRIM Menu ........................................................................................................................................................ 7
Offset .................................................................................................................................................................... 7
Status .................................................................................................................................................................... 8
System Setup ......................................................................................................................................................... 9
Board Setup ......................................................................................................................................................... 10
Burner Zones ....................................................................................................................................................... 12
Shutdown ............................................................................................................................................................ 13
Close .................................................................................................................................................................... 13
CHART ....................................................................................................................................................................... 14
CHART SUB MENU ....................................................................................................................................................... 17
WARRANTY .......................................................................................................................................................... 18
APPENDIX A – E-TRIM MODBUS REGISTERS ......................................................................................................... 19
APPENDIX B – SPARE PARTS LIST ......................................................................................................................... 21
APPENDIX C – ELECTRICAL DRAWINGS (FOR REFERENCE ONLY) ........................................................................... 22
APPENDIX D – TYPICAL INSTALLATIONS BASED ON APPLICATION ........................................................................ 24
TYPICAL SET UP OF E-TRIM WITH BIQ FURNACE ................................................................................................................ 24
TYPICAL SET UP OF E-TRIM WITH CONTINUOUS FURNACE .................................................................................................... 25
EXAMPLE SETUP OF E -TRIM IN A CUSTOM INSTALLATION .................................................................................................... 26
REVISION HISTORY ............................................................................................................................................... 27
Super Systems Inc. Page 3 of 27 e-TRIM Operations Manual

e-TRIM Overview

WARNING:
772-0060 for questions about mounting and cooling.
IMPORTANT: When first warming up, the 02 percentage for each burner will read 99.99%. This is
sensor. Call Super Systems Inc. technical support at 513-772-0060 for assistance.
e-TRIM is designed to be installed on indirect fired burners. With e-TRIM, the operator will be able to monitor and alarm based on a desired oxygen percentage during high fire. The system will provide continuous indication of oxygen and will warn the operator when the burner is outside of the desired oxygen band.
Additionally, e-TRIM is equipped with a critical alarm. This alarm is designed to provide an audible and visual indication when a burner is either not lit or running extremely lean.
Typical settings are as follows: Desired percent on high fire is 2% per the DOE, which would provide 10% excess air. The band alarm should be set to 1%. When on high-fire, if the reading is below 1% or above 3%, the screen will show an out-of-band condition. Additionally, SSi recommends the critical alarm be set to 8%. When on high fire, if the reading goes above 8% and the trim delay expires, the horn will sound. This is notification that a burner that is not lit or is extremely lean.
It is recommended that the desired oxygen percentage be verified with the burner manufacturer prior to adjusting. It is important to make sure that the Carbon Monoxide PPM limit is not increased when adjusting the burner.
e-TRIM electronics enclosure must not be exposed to temperatures above 120°F (49°C). It should not be mounted on the furnace unless proper cooling is installed. Contact SSi at 513-
Sensor installation: The sensor should be mounted on the exhaust leg of the burner prior to any gaps or possible air drafts. The sensor should be installed in a location that will not exceed 1000° F on high fire.
Sensor Mounting: The thread for the e-TRIM O
sensor is M18 x 1.5. It is a metric thread.
2
Please refer to the electrical print provided with the panel for all wire terminations.
expected, and the value will change to an appropriate value within 30 to 60 seconds. If the 02 percentage should read 99.99% at any time other than during the warm-up period or if it remains 99.99% after the first two minutes of operation, there may be a problem with the
Examples of e-TRIM installations are shown in Appendix D – Typical Installations Based on Application.
Super Systems Inc. Page 4 of 27 e-TRIM Operations Manual

e-TRIM Touchscreen Interface

NOTE:
OK **coms** Alarm Pending
**Out of Band**
**Critical Alarm** Critical Alarm Ack’d

Main Screen

This manual was written with oxygen readings from the ambient air, not in a valid run-
time environment.
This is the main screen for the e-TRIM Touchscreen software. Once the software has booted up, this screen will be displayed. This screen will list the Burners, along with the % Oxygen reading, the Status of each burner, and the status of high fire or low fire. The possible messages are:
– everything (coms, burner conditions, etc.) is ok.
- there is bad communication to the sensor board. – there is an out of band condition, and the system is waiting for the
delay timer to expire.
- The burner is out of band. Status Disabled – The board has been
disabled.
- There is a critical alarm active. – The critical alarm is active, but the alarm has been acknowledged.
The yellow icon signals that the burner is on high fire.
Super Systems Inc. Page 5 of 27 e-TRIM Operations Manual

Details

NOTE:
Toggle
Close
time environment.
This will display a details screen for the e-TRIM system.
The on the screen at one time, and each burner will have its oxygen reading and status displayed on the screen. Clicking on the
Clicking on the
Clicking on the burner number will display some details about the specific burner: The board address, baud rate, board version, TC type, TC temperature, Cold Junction temperature, diagnostic, and percent oxygen.
Menu This will display the menu, which will allow the user to configure the e-TRIM system. See the section e-TRIM Menu for instructions on using the menu.
This manual was written with oxygen readings from the ambient air, not in a valid run-
Details
screen is basically an expanded version of the main screen. Four burners are shown
button will close the
button will display the next four burners, etc.
Details
screen.
Super Systems Inc. Page 6 of 27 e-TRIM Operations Manual

e-TRIM Menu

NOTE:
Toggle
Set
time environment.
This screen is the main menu for the e- TRIM system. Currently, there are seven options:
This manual was written with oxygen readings from the ambient air, not in a valid run-
Offset
Status
System Setup
Board Setup
Burner Zones
Shutdown
Close

Offset

The offset screen displays the %O2 and Offset percentage for eight burners at a time. Pressing the press the
Super Systems Inc. Page 7 of 27 e-TRIM Operations Manual
button will show the other eight burners. To change the offset of one of the burners,
button and select the burner number.
This screen will display:
Offset=
-20.9%
20.9%
Click the
This option will allow the user to enter an offset for each specific burner to match an external calibration source such as a hand held oxygen monitor. Adjustments should only be made when on high fire for more than 120 seconds.
To change an offset for a specific burner, select the burner from the drop-down list. The button below the list will show the current offset. Click on this button to change the offset. The range is
to
button to enter the offset percentage. Click OK to save it.
.

Status

Status
The the controller.
Super Systems Inc. Page 8 of 27 e-TRIM Operations Manual
screen shows the addresses of the connected boards that are communicating with
The O
0 to
60,000 seconds (0 minutes to 1,000 minutes)
NOTE:
Master High Fire, Individual High Fire,
Editable
Zones
Boards are the active circuit boards that are obtaining the oxygen measurement from
2
each sensor.
The O
Retransmission Boards (optional) are the circuit boards that provide an analog output (4-
2
20mA) of the oxygen measurement from each sensor. The electrical connections should be made in accordance with the electrical schematic located at the back of this manual, with 4 to 20mA corresponding proportionally to 0 to 25% oxygen. The ability to retransmit the oxygen signal requires circuit boards that are not part of the standard system. For additional information regarding this feature, please contact Super Systems Inc. (513-772-0060).

System Setup

This option will allow the user to make changes to the current system settings. Currently, there are six options to modify.
Alarm Delay This setting is the number of seconds that the system will wait before showing an out of band alarm condition, if an alarm condition is present. This is entered in seconds. The range is
.
Alarm Band This setting is the band for the boards’ setpoint. If the setpoint is 3%, and the band is 2%, then an alarm indication condition will not be present until the reading goes under 1% or above 5%. This is entered in percentages. The range is 0% to 20.9%.
The alarm band will not sound the horn and is for indication only. Output 7 can be wired to an external horn or light if needed (see the electrical prints for termination details).
Master High Fire/Individual High Fire/Editable Zones Clicking on this button will toggle between
. The Master High Fire setting will allow the controller to see the one digital input signal
and
as a high fire signal for all burners. Individual high fire will put the burners in groups of 4, each group being a separate zone. Editable Zones will allow the user to determine the burner and zone configuration. The high fire digital input is required for the e-TRIM system to provide band
Super Systems Inc. Page 9 of 27 e-TRIM Operations Manual
Loading...
+ 18 hidden pages