Super Systems AC20 User Manual

Super Systems
Instruction Manual
Model AC20
Part No. 31069 - Standard Atmosphere Controller  with expanded event capability
August 2004
INDEX
MOUNTING REQUIREMENTS ..................................................... 1
OUTLINE AND CUT OUT DIMENSIONS ...................................... 2
CONNECTION DIAGRAMS ......................................................... 3
PRELIMINARY HARDWARE SETTINGS .................................... 14
SECURITY CODE SETTING MODE ........................................... 17
RUN TIME AND CONFIGURATION MODES .............................. 20
General notes about graphic symbols ............................. 20
Keyboard description ....................................................... 20
CONFIGURATIO N MODE.......................................................... 22
RUN TIME MODE ...................................................................... 44
Display function ................................................................ 44
Indicators.......................................................................... 46
Bargraph description ........................................................ 48
Direct access to the set point........................................... 49
Manual function ................................................................ 49
Special output features ..................................................... 50
Burn off procedure ............................................................51
Probe test procedure........................................................ 53
Serial link ......................................................................... 54
Lamp test ......................................................................... 55
SMART function................................................................ 55
COF and H2F adjustment diagram .................................... 57
Parameter protection ........................................................ 58
RUN TIME PARAMETER MODIFICATION ...................................58
ERROR MESSAGES ................................................................. 83
GENERAL INFORMATION ......................................................... 85
MAINTENANCE ......................................................................... 93
DEFAULT PARAMETERS ........................................................ A.1
ALGORITHMS........................................................................ B.1
CALIBRATION PROCEDURE................................................... B.1
MOUNTING REQUIREMENTSMOUNTING REQUIREMENTS
MOUNTING REQUIREMENTS
MOUNTING REQUIREMENTSMOUNTING REQUIREMENTS
This instrument is intended for permanent installation, for indoor use only, in an electrical panel which encloses the rear housing, exposed terminals and wiring on the back. Select a location, for instrument mounting, where minimum vibrations are present and the ambient temperature is within 0 and 50 °C (32 and 122°F). The instrument can be mounted on a panel up to 15 mm thick with a cutout 92 x 92. For outline and cutout dimensions refer to Fig. 2. The surface texture of the panel must be better than 6,3 µm. The instrument is shipped with rubber panel gasket (50 to 60 Sh). To assure the IP65 and NEMA 4X protection, insert the panel gasket between the instrument and the panel as shown in fig. 1. While holding the instrument against the panel proceed as follows:
1) insert the gasket in the instrument case;
2) insert the instrument in the panel cutout;
3) pushing the instrument against the panel;
4) insert the mounting brackets as shown in fig.1;
5) with a screwdriver, turn the screws with a torque between
0.3 and 0.4 Nm.
Screws
Bracket
Fig. 1
1
Bracket
Gasket
Panel
OUTLINE AND CUT OUT DIMENSIONSOUTLINE AND CUT OUT DIMENSIONS
"
OUTLINE AND CUT OUT DIMENSIONS
OUTLINE AND CUT OUT DIMENSIONSOUTLINE AND CUT OUT DIMENSIONS
+0.03 +0.8
3.62" (92 mm )
+0.03
+0.8
3.62" (92 mm )
(125 mm)
4.92" (125 mm)
4.92
Fig. 2. OUTLINE AND CUT-OUT DIMENSIONS
3.78" (96 mm)
0.6" (15mm) max
4.17" (108.5 mm)
5" (128 mm)
0.06" (1.5 mm)
3.8" x 3.8" (97 x 97 mm) gasket
0.63"
(16 mm)
2
CONNECTION DIAGRAMSCONNECTION DIAGRAMS
CONNECTION DIAGRAMS
CONNECTION DIAGRAMSCONNECTION DIAGRAMS
Fig. 3. REAR TERMINAL BLOCK
3
CONNECTIONSCONNECTIONS
CONNECTIONS
CONNECTIONSCONNECTIONS Connections are to be made when the instrument housing is
installed in its proper location.
A) PROBE SENSOR INPUT (MAIN INPUT)A) PROBE SENSOR INPUT (MAIN INPUT)
A) PROBE SENSOR INPUT (MAIN INPUT)
A) PROBE SENSOR INPUT (MAIN INPUT)A) PROBE SENSOR INPUT (MAIN INPUT)
12
13
+
_
Shield
Sensor
MEASURING INPUTSMEASURING INPUTS
MEASURING INPUTS
MEASURING INPUTSMEASURING INPUTS NOTENOTE
NOTE: Any external component (like zener barriers etc.)
NOTENOTE connected between sensor and input terminals may cause errors in measurement due to excessive and/or not balanced line resistance or possible leakage currents.
12
13
+
_
G
Fig. 4 MAIN INPUT WIRING NOTESNOTES
NOTES:
NOTESNOTES
1) This input is isolated from others measuring inputs and digital inputs.
2) Don’t run input wires together with power cables.
3) When a shielded cable is used, it should be connected at one point only.
4
Sensor
A.1) TEMPERATURE (THERMOCOUPLE) INPUTA.1) TEMPERATURE (THERMOCOUPLE) INPUT
A.1) TEMPERATURE (THERMOCOUPLE) INPUT
A.1) TEMPERATURE (THERMOCOUPLE) INPUTA.1) TEMPERATURE (THERMOCOUPLE) INPUT
1
+
_
3
Shield
1
+
_
3
Shield
Fig. 5 TEMPERATURE INPUT WIRING NOTESNOTES
NOTES:
NOTESNOTES
1) This input is not isolated from others measuring inputs and digital inputs.
2) Don’t run input wires together with power cables.
3) For TC wiring use proper compensating cable preferable shielded.
4) When a shielded cable is used, it should be connected at one point only.
A.2) AUXILIARY INPUT (CARBON MONOXIDE)A.2) AUXILIARY INPUT (CARBON MONOXIDE)
A.2) AUXILIARY INPUT (CARBON MONOXIDE)
A.2) AUXILIARY INPUT (CARBON MONOXIDE)A.2) AUXILIARY INPUT (CARBON MONOXIDE)
5
6
Shield
5
6
Fig. 6 AUXILIARY INPUT WIRING NOTESNOTES
NOTES:
NOTESNOTES
1) This input is not isolated from others measuring inputs and digital inputs. A double or reinforced insulation between instrument output and power supply must be assured by the external instrument.
5
+
mA,
or
_
V
+
mA
or
_
V
G
2) Don’t run input wires together with power cables.
3) Pay attention to the line resistance; a high line resistance may cause measurement errors.
4) When shielded cable is used, it should be grounded at one side only to avoid ground loop currents.
5) The input impedance is equal to: < 5 Ω for 20 mA input > 200 k for 5 V input > 400 k for 10 V input
B) LOGIC INPUTSB) LOGIC INPUTS
B) LOGIC INPUTS
B) LOGIC INPUTSB) LOGIC INPUTS
DIG. 1
8
DIG. 2
9
DIG. 3
10
11
IN 1
57
IN 2
58
IN 3
59
IN 4
60
56
Fig. 7.A - LOGIC INPUTS DIG 1 TO DIG 3 AND IN1 TO IN4 WIRING
6
IN 5
46
IN 6
47
IN 7
48
IN 8
49
45
Fig. 7.B - LOGIC INPUTS IN5 TO IN8 WIRING Logic inputs from IN1 to In8 are optional. NOTESNOTES
NOTES:
NOTESNOTES
1) Do not run logic input wiring together with power cables.
2) Use an external dry contact capable of switching 0.5 mA, 5 V DC.
3) The instrument needs 110 ms to recognize a contact status variation.
4) The logic inputs are
NOT NOT
NOT isolated from measuring inputs.
NOT NOT
C.1) RELAY OUTPUTSC.1) RELAY OUTPUTS
C.1) RELAY OUTPUTS
C.1) RELAY OUTPUTSC.1) RELAY OUTPUTS
OUT 1
OUT 2
OUT 3
Fig. 8.A RELAY OUTPUTS 1, 2, 3 WIRING
7
23
24
25
26
27
28
29
NC
C
NO
C
NO
C
NO
OUT 4
30
31
OUT 5
15
14
OUT 10
OUT 11
OUT 12
OUT 13
OUT 14
61 62 63 64
65
66
Fig. 8.B RELAY OUTPUTS 4, 5 and 10 TO 14 WIRING
C
NO
C
NO
NO - OUT 10
NO - OUT 11 NO - OUT 12 NO - OUT 13
NO - OUT 14
C - OUT 10 to 14
NO - OUT 15
OUT 15
OUT 16
OUT 17
OUT 18
OUT 19
Fig. 8.C RELAY OUTPUTS 15 TO 19 WIRING Outputs from OUT 10 to OUT 19 are optional. The contact rating from OUT 1 and OUT 2 is 3A/250V AC on resistive load. The contact rating from OUT 3 and OUT 4 is 2A/250V AC on resistive load. The contact rating of OUT 5 is 1A/250V AC on resistive load. The contact rating from OUT 10 to OUT 19 is 0.5 A/250V AC on resistive load. The number of operations is 1 x 105 at specified rating.
8
50
NO - OUT 16
51
NO - OUT 17
52
NO - OUT 18
53
NO - OUT 19
54
C - OUT 15 to 19
55
NOTES:NOTES:
NOTES: 1) To avoid electrical shock, connect
NOTES:NOTES:
All relay contacts are protected by varistor against inductive load with inductive component up to 0.5 A.
The following recommendations avoid serious problems which may occur, when relay output drives inductive loads.
INDUCTIVE LOADSINDUCTIVE LOADS
INDUCTIVE LOADS
INDUCTIVE LOADSINDUCTIVE LOADS High voltage transients may occur switching inductive loads. Through the internal contacts these transients may introduce disturbances which can affect the performance of the instrument. For all the outputs, the internal protection (varistor) assures a correct protection up to 0.5 A of inductive component. The same problem may occur when a switch is used in series with the internal contacts as shown in Fig. 9.
power line at the end of the wiring procedure.
2) For power connections use No 16 AWG or larger wires rated for at last 75 °C.
3) Use copper conductors only.
4) Don’t run input wires together with power cables.
5) When a relay output is used to drive a low power signal (PLC input, alarm annunciator, etc..) it is necessary to use an external relay with a gilded contact.
C
R
LOAD
Fig. 9 EXTERNAL SWITCH IN SERIES WITH THE INTERNAL
CONTACT In this case it is recommended to install an additional RC network across the external contact as show in Fig. 9. The value of capacitor (C) and resistor (R) are shown in the following table.
LOAD
(mA)
<40 mA <150 mA <0.5 A
Anyway the cable involved in relay output wiring must be as far away as possible from input or communication cables.
9
C
(µF)
0.047
0.1
0.33
(Ω)
100
22 47
R
P.
OPERATING
(W)
VOLTAGE
1/2
260 V AC
2
260 V AC
2
260 V AC
LINE
C.2) VOLTAGE OUTPUTS FOR SSR DRIVEC.2) VOLTAGE OUTPUTS FOR SSR DRIVE
C.2) VOLTAGE OUTPUTS FOR SSR DRIVE
C.2) VOLTAGE OUTPUTS FOR SSR DRIVEC.2) VOLTAGE OUTPUTS FOR SSR DRIVE
+
OUT 1
24
_
+
__
_
__
25
SOLID STATE
RELAY
+
OUT 2
26
_
+
__
_
__
27
SOLID STATE
RELAY
Fig. 10 SSR DRIVE OUTPUT WIRING Logic level 0Logic level 0
Logic level 0: Vout < 0.5 V DC.
Logic level 0Logic level 0 Logic level 1Logic level 1
Logic level 1:
Logic level 1Logic level 1
- 14 V
+ 20 % @ 20 mA
- 24 V
+ 20 % @ 1 mA.
Maximum current = 20 mA
NOTENOTE
NOTE: These outputs are not insulated.
NOTENOTE A double or reinforced insulation between instrument output and power supply must be assured by the external solid state relay.
C.3) ANALOG OUTPUTSC.3) ANALOG OUTPUTS
C.3) ANALOG OUTPUTS
C.3) ANALOG OUTPUTSC.3) ANALOG OUTPUTS
+
OUT 6
16
_
17
+
20 mA
_
Shield
+
16
OUT 6
_
17
Fig. 11.A OUTPUT 6 WIRING
10
+
_
20 mA
G
+
OUT 7
18
_
19
+
_
20 mA20 mA
Shield
+
18
OUT 7
_
19
Fig. 11.B OUTPUT 7 WIRING NOTESNOTES
NOTES:
NOTESNOTES
1) Do not run analog output wires together with AC power cables.
2) Out 6 and 7 are isolated outputs.
3) The maximum load is equal to 600 Ω.
+
_
G
D) SERIAL INTERFACED) SERIAL INTERFACE
D) SERIAL INTERFACE
D) SERIAL INTERFACED) SERIAL INTERFACE RS-485 interface allows you to connect up to 30 devices with one remote master unit.
I N S
T R U M
E N
T
Fig. 12 - RS-485 WIRING The cable length must not exceed 1.5 km at 9600 BAUD. NOTESNOTES
NOTES:
NOTESNOTES
1) This is an isolated RS 485 serial interface.
2) The following report describes the signal sense of the voltage appearing across the interconnection cable as defined by EIA for RS-485. a) The ” A ” terminal of the generator shall be negative with
respect to the ” B ” terminal for a binary 1 (MARK or OFF) state.
11
22
21
20
A/A'
B/B'
COMMON
A'/A
B'/B
M
A S T E R
b) The ” A ” terminal of the generator shall be positive with
respect to the ” B ” terminal for a binary 0 (SPACE or ON).
3) The EIA standard establishes that by RS-485 interface it is possible to connect up to 30 devices with one remote master unit. The serial interface of these instruments is based on “High input impedance” transceivers; this solution allows you to connect up to 127 devices (based on the same transceiver type) with one remote master unit.
E) POWER LINE WIRINGE) POWER LINE WIRING
E) POWER LINE WIRING
E) POWER LINE WIRINGE) POWER LINE WIRING
N (L2)
32
POWER LINE 100 V to
240 V A.C (50/60Hz)
33
L (L1)
Line
Fig. 13 POWER LINE WIRING NOTESNOTES
NOTES:
NOTESNOTES
1) Before connecting the instrument to the power line, make sure that line voltage corresponds to the description on the identification label.
2) To avoid electrical shock, connect power line at the end of the wiring procedure.
3) For supply connections use No 16 AWG or larger wires rated for at last 75 °C.
12
Neutral
4) Use copper conductors only.
5) Don’t run input wires together with power cables.
6) The power supply input is fuse protected by a sub miniature fuse rated T, 1A, 250 V. When fuse is damaged, it is advisable to verify the power supply circuit, so that it is necessary to send back the instrument to your supplier.
7) The safety requirements for Permanently Connected Equipment say:
- a switch or circuit-breaker shall be included in the building
installation;
- it shall be in close proximity to the equipment and within
easy reach of the operator;
- it shall be marked as the disconnecting device for the
equipment.
NOTENOTE
NOTE: a single switch or circuit-breaker can drive more than
NOTENOTE one instrument.
8) When a neutral line is present please connect it to the 32 terminal.
13
PRELIMINARY HARDWARE SETTINGSPRELIMINARY HARDWARE SETTINGS
PRELIMINARY HARDWARE SETTINGS
PRELIMINARY HARDWARE SETTINGSPRELIMINARY HARDWARE SETTINGS
How to remove the instrument from its caseHow to remove the instrument from its case
How to remove the instrument from its case
How to remove the instrument from its caseHow to remove the instrument from its case
1) Switch off the instrument.
2) Push gently the lock A on the right.
3) While the lock A is maintained out, slide out the right side of the instrument (see fig. 14.a)
B
4) Push gently the lock C on the left.
5) While the lock C is maintained out, slide out the instrument (see fig. 14.b)
D
Fig. 14.a
A
B
Fig. 14.b
14
C
D
J103 SETTINGJ103 SETTING
J103 SETTING
J103 SETTINGJ103 SETTING J103 (see fig. 15) must be set as follows:
J103 1-2 open 3-4 open 5-6 open 7-8 open 5-7 close 6-8 close
AUXILIARY INPUT SELECTIONAUXILIARY INPUT SELECTION
AUXILIARY INPUT SELECTION
AUXILIARY INPUT SELECTIONAUXILIARY INPUT SELECTION Set J102 (see fig. 15) according to the desired input type as shown in the following table.
J102 INPUT TYPE
5 V 10 V 20 mA 1-2 close open open 3-4 close close open 5-6 open open close 7-8 open open close 5-7 open close open 6-8 open open open
1 3 5 7
J102
2 4 6 8
1 3 5 7
J103
2 4 6 8
CPU card
Fig.15
15
Operative mode and Hardware lockOperative mode and Hardware lock
Operative mode and Hardware lock
Operative mode and Hardware lockOperative mode and Hardware lock
1) By V101 (see fig. 16) it is possible to select one of the following operative modes: a) run time mode without configuration mode b) run time and configuration modes c) security code setting mode Set V101 according to the following table:
Modes V101.1 V101.2 V101.3 V101.4 a OFF ON ON ON b OFF ON OFF ON c OFF ON OFF OFF
2) When run time mode is selected (mode a or b), V101.3 allows you to activate/deactivate the hardware lock for configuration parameters. If V101.3 is ON, the lock is activated. If V101.3 is OFF, the lock is deactivated. When the lock is activated, no one of the configuration parameter can be modified.
3) All the others switch combinations are reserved.
ON DIP
1 2 3 4
V101
Fig. 16
16
SECURITY CODE SETTING MODESECURITY CODE SETTING MODE
SECURITY CODE SETTING MODE
SECURITY CODE SETTING MODESECURITY CODE SETTING MODE General notesGeneral notes
General notes
General notesGeneral notes
The instrument parameters are divided in two families and each family is divided in groups.
- The first family encompasses all the run time parameters.
- The second family comprises all the configuration parameters. A specific security code enables the parameter modification of each family. For run time parameters, it is possible to select which groups of them will be protected by the security code and in this case it is necessary to set the run time security code before to modify one or more parameters of a protected group. The configuration security code protects all configuration parameters and it will be necessary to set the configuration security code before to start the configuration parameters modification. For configuration parameters an hardware lock is also available.
Security code settingSecurity code setting
Security code setting:
Security code settingSecurity code setting
1) Remove the instrument from its case.
2) Set the internal dip switch V101 as follows:
- V101.1 = OFF - V101.2 = ON
- V101.3 = OFF - V101.4 = OFF
3) Re-insert the instrument.
4) Switch on the instrument. The display will show:
The upper display shows that the security code setting mode is selected while the lower display shows the firmware version.
5) Push the FUNC pushbutton.
17
Run time security codeRun time security code
Run time security code
Run time security codeRun time security code The display will show:
Run time groups protected by security codeRun time groups protected by security code
Run time groups protected by security code
Run time groups protected by security codeRun time groups protected by security code The display will show:
NoteNote
Note: the middle display shows the current status of the run
NoteNote time security code ("0", "1" or "On"). By and push-button, set "S.run" parameter as follows:
0 No protection (it is always possible to modify all run
time parameters);
1 always protected (it is never possible to modify a run
time parameter);
from 2 to 250 security code for run time parameter
protection.
NOTESNOTES
NOTES:
NOTESNOTES
1) The selected value of a security code cannot be displayed anymore and, coming back to the "S.run" parameter, the display will show "On" when "S.run" is different from 0 or 1, "0" when "S.run" is equal to 0, "1" when "S.run" is equal to 1. When the security code is forgotten, a new value can be set.
2) When "S.run" is different from 0 or 1, the "run time default " and the "run time hidden" groups are always protected by security code.
By this parameter it is possible to set if the run time group 1 will be protected or not by the run time security code. By and push-button, set "Gr1" parameter as follows:
nO No protection (it is always possible to modify run time
group 1 parameters).
Yes the run time group 1 parameter modification will be
protected by security code. Push the FUNC push-button; the instrument memorizes the new setting and goes to the next parameter.
NOTESNOTES
NOTES: 1) This selection may be performed only if a run time
NOTESNOTES
security code has been set (from 2 to 250).
2) The above described selection may be repeated for all groups of the run time mode.
18
Configuration security codeConfiguration security code
Configuration security code
Configuration security codeConfiguration security code The display will show:
NoteNote
Note: the middle display shows the current status of the
NoteNote
configuration security code ("0", "1" or "On").
By and push-button, set "S.CnF" parameter as follows:
0 No protection (it is always possible to modify all
configuration parameters);
1 always protected (it is never possible to modify a
configuration parameter);
from 2 to 250 security code for configuration parameter
protection.
NOTESNOTES
NOTES:1) The selected value of a security code cannot be
NOTESNOTES
displayed anymore and, coming back to the "S.CnF" parameter, the display will show "On" when "S.CnF" is different from 0 or 1, "0" when "S.CnF" is equal to 0, "1" when "S.CnF" is equal to 1. When the security code is forgotten, a new value can be set.
2) At the end of the security code setting, set the V101 as described at page16.
RUN TIME AND CONFIGURATION MODESRUN TIME AND CONFIGURATION MODES
RUN TIME AND CONFIGURATION MODES
RUN TIME AND CONFIGURATION MODESRUN TIME AND CONFIGURATION MODES
The hardware selection described in "Operative mode and hardware lock" paragraph allows you to start one of the two following operative modes:
- run time mode
- configuration mode. At power up, the instrument starts in the same mode it was prior
to the power OFF.
General note about graphic symbols used forGeneral note about graphic symbols used for
General note about graphic symbols used for
General note about graphic symbols used forGeneral note about graphic symbols used for mnemonic code visualization.mnemonic code visualization.
mnemonic code visualization.
mnemonic code visualization.mnemonic code visualization. The instrument displays some characters with special symbols. The following table shows the correspondence between the symbols and the characters.
19
symbol character
"
"k " "m " "V " "W " "Z
"J
"
Keyboard descriptionKeyboard description
Keyboard description
Keyboard descriptionKeyboard description MENU = is used to select a parameter group.
FUNC = When the instrument is in "normal display mode" it
changes the indication on the lower display (see "display function").
During parameter modification, it allows you to
memorize the new value of the selected parameter and go to the next parameter (increasing order).
MAN = When the instrument is in "normal display mode",
pushing MAN push-button for more than 1 s, it is possible to enable or disable the manual function.
During parameter modification, it allows you to scroll
back the parameters and groups without memorizing the new setting.
= During parameter modification, it allows you to
increase the value of the selected parameter.
During MANUAL mode, it allows you to increase the
output value.
TST + MAN = By pressing these keys it is possible to start the
BURNOFF function.
TST + FUNC = By pressing these keys it is possible to start the
PROBE TEST function.
+MENU = Are used to start the lamp test function (the
command is accepted when push-buttons are kept depressed for more than 5 s and the instrument is in normal display mode)
+FUNC or +FUNC
During parameter modification they allow you to increase/decrease the value under modification with higher rate.
+MAN or +MAN
During parameter modification they allow you to jump to the max or min programmable value.
= During parameter modification, it allows you to
decrease the value of the selected parameter.
During MANUAL mode, it allows to decrease
the output value.
20
NOTESNOTES
NOTES:
NOTESNOTES
1) All the actions explained above which requires two or more push-buttons must follow exactly the push-button sequence shown.
2) A 10 or 30 seconds time out (see "CnF.6 - t.out" [C.I08]) can be selected for parameter modification during run time mode. If, during parameter modification, no push-button is depressed for more than 10 (30) seconds, the instrument goes automatically to the “normal display mode” and the modification (if carried out) of the last displayed parameter will be lost.
CONFIGURATION MODECONFIGURATION MODE
CONFIGURATION MODE
CONFIGURATION MODECONFIGURATION MODE
Switch on the instrument. The instrument will start in the same way it was prior to the power down (configuration mode or run time mode).
If the instrument starts in configuration mode, push the MENU pushbutton and go to the "Configuration group 1" (see page 25). If the instrument starts in run time mode, by keeping depressed the MENU push-button for more than 5 seconds the instrument will show:
where:
- the upper display shows the selected parameter family;
- the middle display shows the selected action;
- the lower display shows the firmware version. If no push-button is depressed for more than 10 s (or 30 s according to "CnF.6 - "t.out" [time out selection" C.I08] parameter setting), the instrument automatically returns to the normal display mode.
21
By or push-button it is possible to select between:
= (monitor) this selection allows you to monitor but
not to modify the value assigned to the configuration parameters.
= (modify) this selection allows you to monitor and to
modify the value assigned to the configuration parameters.
NOTESNOTES
NOTES:
NOTESNOTES
1) During monitor mode, the instrument continues to operate as in run time mode.
2) When modify mode is started, the instrument stops the control and:
- sets to OFF the control outputs;
- turns to OFF the bargraph displays;
- sets analog retransmissions to the retransmitted initial scale
value;
- sets to OFF the alarms;
- disables the serial link;
- the time out will be disabled.
3) When the modify mode is disabled by V101 (V101.3), the or push-button pressure has no effect.
MONITOR MODEMONITOR MODE
MONITOR MODE
MONITOR MODEMONITOR MODE During the run time mode, it is possible to monitor but not modify all configuration parameters. When it is desired to verify the instrument configuration, proceed as follows:
1) By or push-button select the monitor mode.
2) Push the MENU push-button the display will show:
it shows that configuration group 1 is selected and it
encompasses all the input parameters. The configuration parameter "Monitor mode" follows the "Modify mode" sequence.
NOTESNOTES
NOTES:
NOTESNOTES
1) During monitor mode, the instrument continues to operate as
in run time mode.
2) During monitor mode, if no push-button is depressed for more
than 10 s (or 30 s according to "CnF.6 - t.out" [C.I08]
parameter setting), the instrument returns automatically to the
normal display mode.
22
MODIFY MODEMODIFY MODE
MODIFY MODE
MODIFY MODEMODIFY MODE
1) By or push-button select the modify mode.
2) Push the MENU push-button. If a security code is applied to the configuration parameter, the instrument will show:
3) By and push-button set a value equal to the security code assigned to the configuration mode (see "Configuration security code " at page 19). If the code is different from the security code, the instrument automatically returns to the first configuration display otherwise the display will show:
The modify mode is started. This display allows you to load the default configuration parameter (table 1 or table 2). For more details see chapter "Default parameter" (see Appendix A).
4) By or push-button select the OFF indication and push the MENU push-button. The display will show:
This is the starting display of the first group of configuration parameters.
NOTESNOTES
NOTES:
NOTESNOTES
1) In the following pages we will describe all the parameters of the instrument but the instrument will show only the parameters related with the specific hardware and in accordance with the specific instrument configuration [i.e. setting OUT 6 as "nonE" (not used), all the parameters related with this output will be automatically skipped].
23
2) During configuration parameters modify mode, the upper display shows the selected parameter group, the lower display shows the mnemonic code of the selected parameter while the central display shows the value or status assigned to the selected parameter.
3) For an easy consultation of this manual, a sheet named "Reference parameter guide" with all the parameter visualizations is enclosed. The groups of configuration parameters are identified by the "C" letter followed by A, B etc. The "code" formed by the group and the row (i.e. C.D01 where "C.D" is configuration group1 and "01" is the row 1) is reported, in the user manual, before each parameter description and allows you to quickly find out the respective parameter.
CONFIGURATION GROUP 1 [C.Dxx]CONFIGURATION GROUP 1 [C.Dxx]
CONFIGURATION GROUP 1 [C.Dxx]
CONFIGURATION GROUP 1 [C.Dxx]CONFIGURATION GROUP 1 [C.Dxx] INPUT CONFIGURATION
Push the FUNC push-button C.D01- Line frequencyC.D01- Line frequency
C.D01- Line frequency
C.D01- Line frequencyC.D01- Line frequency Upper display: CnF.1 Lower display: Ln.Fr Range: 50 Hz
60 Hz
C.D02- Controlled variable selectionC.D02- Controlled variable selection
C.D02- Controlled variable selection
C.D02- Controlled variable selectionC.D02- Controlled variable selection Upper display: CnF.1 Lower display: PV.SL Ranges: CP = Carbon potential (span limits within 0.00% to 2.00%). dP = Dew point (span limits within -100 to 100 °F or -75 to 40°C). ñV = Sensor output in mV (span limits within 0 to 1500 mV).
O2 = Oxygen value as primary control variable ( The span limits are 0.0 to 25.0)
24
NOTES:NOTES:
NOTES:
NOTES:NOTES:
1) Changing the controlled variable, the following parameters: "CnF.6 - brG.L" [C.I03] and "CnF.6 - brG.H" [C.I04] (Bargraph initial and full scale values); "CnF.2 - O6.Lr" [C.E06] and "CnF.2 - O6.Hr" [C.E07] (Out 6 retransmission initial and full scale values); "CnF.2 - O7.Lr" [C.E11] and "CnF.2 - O7.Hr" [C.E12] (Out 7 retransmission initial and full scale values); "Gr.5 - rL" [R.E10] and "Gr.5 - rH" [R.E11] (set point low and high limits); will be forced to the span limits of the new selected variable.
2) SP, SP2, SP3, SP4 values and alarm thresholds, if out of the limits for the new selected variable, will be forced to the low limit value.
C.D03- Filter on probe sensor input (Main input)C.D03- Filter on probe sensor input (Main input)
C.D03- Filter on probe sensor input (Main input)
C.D03- Filter on probe sensor input (Main input)C.D03- Filter on probe sensor input (Main input) Upper display: CnF.1 Lower display: Pb.FL Ranges: from 0 (no filter) to 8 seconds. NOTES:NOTES:
NOTES:
NOTES:NOTES:
1) This is a first order digital filter applied on probe sensor input value.
2) This filter can affect the control action, the alarms, the SMART algorithm and the process variable retransmission.
C.D04 - Temperature input - TC type selectionC.D04 - Temperature input - TC type selection
C.D04 - Temperature input - TC type selection
C.D04 - Temperature input - TC type selectionC.D04 - Temperature input - TC type selection Upper display: CnF.1 Lower display: tP.In Ranges:
1 = TC K From -100 t o 1370 °C 2 = TC S From -50 to 17 6 0 °C 3 = TC R From -50 to 1760 °C 4 = TC K From -150 to 2500 °F 5 = TC S From -60 to 32 0 0 °F
6 = TC R From -60 to 3200 °F 7= TC B From 0 to 1820 °C 8= TC B From 32 to 3300 °F NOTE:NOTE:
NOTE: When the controlled variable selected is dP, the span
NOTE:NOTE:
limits of the following parameters: "CnF.6 - brG.L" [C.I03] and "CnF.6 - brG.H" [C.I04] (Bargraph initial and full scale values); "CnF.2 - O6.Lr" [C.E06] and "CnF.2 - O6.Hr" [C.E07] (Out 6 retransmission initial and full scale values); "CnF.2 - O7.Lr" [C.E11] and "CnF.2 - O7.Hr" [C.E12] (Out 7 retransmission initial and full scale values); "Gr.5 - rL" [R.E10] and "Gr.5 - rH" [R.E11] (set point low and high limits); will be forced to:
-100 to 100 °F if the temperature input has been changed from a °C to a °F type;
-75 to 40 °C if the temperature input has been changed from a °F to a °C type.
25
C.D05 - Temperature input offset adjustmentC.D05 - Temperature input offset adjustment
C.D05 - Temperature input offset adjustment
C.D05 - Temperature input offset adjustmentC.D05 - Temperature input offset adjustment Upper display: CnF.1 Lower display: OFSt Range: from -500 to 500 NOTENOTE
NOTE: The offset value is algebraically added to temperature
NOTENOTE
input value.
Read-out
OFSt
Real curve
Adjusted curve
Input
C.D06 - Filter on temperature input valueC.D06 - Filter on temperature input value
C.D06 - Filter on temperature input value
C.D06 - Filter on temperature input valueC.D06 - Filter on temperature input value Upper display: CnF.1 Lower display: tP.FL Ranges: from 0 (no filter) to 8 seconds.
NOTES:NOTES:
NOTES:
NOTES:NOTES:
1) This is a first order digital filter applied to the temperature input value.
2) When "dP" or "CP" or O2 are selected as the controlled variable, this filter can affect the control action, the alarms, the SMART algorithm and the process variable retransmission.
C.D07 - Auxiliary input functionC.D07 - Auxiliary input function
C.D07 - Auxiliary input function
C.D07 - Auxiliary input functionC.D07 - Auxiliary input function
Lower display: A.In.F Range: nonE = Input not used CO = Input used for CO measurement rSP = Input used as remote set point Available: Always Note:The scalable for CO measurement is fixed from 000 to 100 When CO input is not used the CO value will be set to 20 The scalable for rSP measurement is fixed to:
0.00 / 2.00 if carbon potential is selected as primary control variable or
0 /100 °F (-18 / 40 °C) if dew point is selected as primary control variable or 0 / 1500 if sensor output in mV is selected as primary control variable
0.0/ 25.0 if oxygen value is selected as primary control variable
C.D08 - Auxiliary input type selectionC.D08 - Auxiliary input type selection
C.D08 - Auxiliary input type selection
C.D08 - Auxiliary input type selectionC.D08 - Auxiliary input type selection
Lower display: A.In.t Range: 0-20 = 0÷20 mA
4-20 = 4÷20 mA 0- 5 = 0÷ 5 V
1- 5 = 1÷ 5 V 0-10 = 0÷10 V 2-10 = 2÷10 V
Available: When auxiliary input is used
26
C.D09 - TIME CONSTANT FOR FILTER ON REMOTEC.D09 - TIME CONSTANT FOR FILTER ON REMOTE
C.D09 - TIME CONSTANT FOR FILTER ON REMOTE
C.D09 - TIME CONSTANT FOR FILTER ON REMOTEC.D09 - TIME CONSTANT FOR FILTER ON REMOTE SETPOINT VALUE (CnF.1)SETPOINT VALUE (CnF.1)
SETPOINT VALUE (CnF.1)
SETPOINT VALUE (CnF.1)SETPOINT VALUE (CnF.1) Lower display: A.I.FL Range: From 0(filter OFF) to 8 s Available: When auxiliary input is used as remote set point Note: First order filter with selected time constant
C.D10 - REMOTE SETPOINT ACTIVITY MODE (CnF.1)C.D10 - REMOTE SETPOINT ACTIVITY MODE (CnF.1)
C.D10 - REMOTE SETPOINT ACTIVITY MODE (CnF.1)
C.D10 - REMOTE SETPOINT ACTIVITY MODE (CnF.1)C.D10 - REMOTE SETPOINT ACTIVITY MODE (CnF.1) Lower display: A.I.Añ Range: norñ = The remote set point is activated by external contact(or is always activated if none contacts are configured for this feature) and the value is limited at its min/max value when out of range Cnd.A = The remote set point activation is controlled by status of auxiliary input. (The device works with local set point when auxiliary input is out of range while it works with remote set point when auxiliary input is in range)
Available: When auxiliary input is used as remote set point
C.D11 - LOCAL / REMOTE SETPOINT OPERATINGC.D11 - LOCAL / REMOTE SETPOINT OPERATING
C.D11 - LOCAL / REMOTE SETPOINT OPERATING
C.D11 - LOCAL / REMOTE SETPOINT OPERATINGC.D11 - LOCAL / REMOTE SETPOINT OPERATING MODE (CnF.1)MODE (CnF.1)
MODE (CnF.1)
MODE (CnF.1)MODE (CnF.1) Lower display: L.r.Oñ Range: ALG = The local setpoint will be aligned to last remote setpoint value when transfer from remote to local setpoint action is performed through external contact
n.ALG = The local setpoint will be not be changed when transfer from remote to local setpoint action is performed (The programmed ramp (Grd1/Grd2) may be activated)
Available: When auxiliary input is used as remote set point and (“A.I.Añ = norñ) Note :If transfer from remote to local setpoint is due to auxiliary input status(“A.I.Añ = Cnd.A) the local setpoint beenbeen
been aligned.
beenbeen
27
will neverwill never
will never
will neverwill never
CONFIGURATION GROUP 2 [C.Exx]CONFIGURATION GROUP 2 [C.Exx]
CONFIGURATION GROUP 2 [C.Exx]
CONFIGURATION GROUP 2 [C.Exx]CONFIGURATION GROUP 2 [C.Exx]
OUTPUTS CONFIGURATION
C.E01 - OUT 1 functionC.E01 - OUT 1 function
C.E01 - OUT 1 function
C.E01 - OUT 1 functionC.E01 - OUT 1 function Upper display: CnF.2 Lower display: O1.Fn Range: nonE = Output not used
ñAin = Time proportional main control output SECn = Time proportional secondary control output ALr.1 = Alarm 1 output
C.E02 - OUT 2 functionC.E02 - OUT 2 function
C.E02 - OUT 2 function
C.E02 - OUT 2 functionC.E02 - OUT 2 function Upper display: CnF.2 Lower display: O2.Fn Range: nonE = Output not used
ñAin = Time proportional main control output SECn = Time proportional secondary control output ALr.2 = Alarm 2 output
C.E03 - OUT 3 functionC.E03 - OUT 3 function
C.E03 - OUT 3 function
C.E03 - OUT 3 functionC.E03 - OUT 3 function Upper display: CnF.2 Lower display: O3.Fn Range: nonE = Output not used
ñAin = Time proportional main control output SECn = Time proportional secondary control output ALr.3 = Alarm 3 output
C.E04 - OUT 6 functionC.E04 - OUT 6 function
C.E04 - OUT 6 function
C.E04 - OUT 6 functionC.E04 - OUT 6 function Upper display: CnF.2 Lower display: O6.Fn Range: nonE = Output not used
ñAin = Main control output (linear) SECn = Secondary control output (linear) PV.rt = Process variable retransmission SP.rt = Operative set point retransmission
C.E05 - OUT 6 rangeC.E05 - OUT 6 range
C.E05 - OUT 6 range
C.E05 - OUT 6 rangeC.E05 - OUT 6 range This parameter is available only when OUT 6 ("O6.Fn" [C.E04]) is different from "nonE". Upper display: CnF.2 Lower display: O6.rn Range: 0-20 = 0-20 mA
4-20 = 4-20 mA
28
Loading...
+ 84 hidden pages