APPENDIX A – WIRING DIAGRAM OF SERIES 9205 ----------------------------------------------------------------------------------- 169
APPENDIX B – GUIDE TO BUILDING A RECIPE ------------------------------------------------------------------------------------------ 171
APPENDIX C – SETUP FOR CARBON / DUAL TEMPERATURE FOR QUENCH CONTROL -------------------------------------- 179
APPENDIX D – 9205 INSTRUMENT ALARMS ------------------------------------------------------------------------------------------- 181
APPENDIX E – FACTORY DEFAULT SETTINGS FOR THE 9205 CONTROLLER ---------------------------------------------------- 183
REVISION HISTORY ---------------------------------------------------------------------------------------------------------------------------- 234
Series 9205 Operations Manual Rev A 4
!
!
Installation Safety Requirements
Safety Symbols
Various symbols are used on the instrument; they have the following meaning:
Caution, (refer to the accompanying documents)
Functional earth (ground) terminal!
The functional earth connection is required for safety purposes and to ground RFI
filters.
Personnel
Installation must only be carried out by technically qualified personnel.
Enclosure of live parts
To prevent hands or metal tools from touching parts that may be electrically live (powered), the
controller must be installed in an enclosure.
Caution:
Live sensors
Do not connect live (powered) sensors to any signal input on the controller. Live
sensors are sensors that must be connected to the main's supply. The controller has
transient protection circuits connected between the inputs and the earth connection
that might be damaged by live (powered) sensors.
Series 9205 Operations Manual Rev A 5
Wiring
It is important to connect the controller in accordance with the wiring data given in this handbook.
Take particular care not to connect AC supplies to the low voltage power supply input. Use copper
wires for 24V DC power supply to the instrument. Ensure that the wiring of installations comply
with all local wiring regulations. For example in the United Kingdom use the latest version of the
IEE wiring regulations, (BS7671). In the USA use NEC Class 1 wiring methods.
Power Isolation
The installation must include a power isolating switch or circuit breaker. This device should be in
close proximity to the controller, within easy reach of the operator and marked as the
disconnecting device for the instrument.
Earth leakage current
Due to RFI Filtering there is an earth leakage current of less than 0.5mA. This may affect the
design of an installation of multiple controllers protected by Residual Current Device, (RCD) or
Ground Fault Detector, (GFD) type circuit breakers.
Over current protection
To protect the internal PCB tracking within the controller against excess currents, the AC power
supply to the controller and power outputs must be wired through a fuse or circuit breaker
specified in the technical specification.
Voltage rating
The maximum continuous voltage applied between any of the following terminals must not
exceed 24V DC
• relay or triac output to logic, DC or sensor connections;
• any connection to ground.
The controller should not be wired to VAC. The 24V DC power supply voltage across the
connections and between the power supply and ground must not exceed 2.5kV. Where occasional
voltage over 2.5kV are expected or measured, the power installation to both the instrument
supply and load circuits should include a transient limiting device.
These units will typically include gas discharge tubes and metal oxide varistors that limit and
control voltage transients on the supply line due to lightning strikes or inductive load switching.
Devices are available in a range of energy ratings and should be selected to suit conditions at the
installation.
Series 9205 Operations Manual Rev A 6
Conductive pollution
Electrically conductive pollution must be excluded from the cabinet in which the controller is
mounted. For example, carbon dust is a form of electrically conductive pollution. To secure a
suitable atmosphere in conditions of conductive pollution, fit an air filter to the air intake of the
cabinet. Where condensation is likely, for example at low temperatures, include a
thermostatically controlled heater in the cabinet.
Over-temperature protection
When designing any control system it is essential to consider what will happen if any part of the
system should fail In temperature control applications the primary danger is that the heating will
remain constantly on. Apart from spoiling the product, this could damage any process machinery
being controlled, or even cause a fire. Reasons why the heating might remain constantly on
include:
• the temperature sensor becoming detached from the process;
• thermocouple wiring becoming a short circuit;
• the controller failing with its heating output constantly on;
• an external valve or contactor sticking in the heating condition;
• the controller set point set too high.
Where damage or injury is possible, we recommend fitting a separate over temperature
protection unit with an independent temperature sensor, which will isolate the heating circuit.
Please note that the alarm relays within the controller will not give protection under all failure
conditions.
Installation requirements for EMC
To ensure compliance with the European EMC directive certain installation precautions are
necessary as follows:
• When using relay or triac outputs it may be necessary to fit a filter suitable for suppressing
the emissions. The filter requirements will depend on the type of load. For typical
applications we recommend Schaffner FN321 or FN612.
Routing of wires
To minimize the pick-up of electrical noise, the wiring for low voltage dc should be routed away
from high-current power cables. Where it is impractical to do this, use shielded cables with the
shield grounded at one end.
Series 9205 Operations Manual Rev A 7
Chapter 1 - Overview
The 9205 is SSi’s versatile atmosphere programmable controller with Ethernet, RS485 Modbus,
and DF1 communications to various slave devices such as temperature controllers, flow meters,
and PLCs. This instrument can be used to address many thermal processing applications where
temperature and carbon control along with event I/O management are necessary. The 9205 has
math block capability allowing custom calculations and custom Modbus mapping for
communications
The 9205 recipe programmer includes 24 independent steps per recipe with operational codes
(opcodes) to enable effective process control. The 9205 also supports multiple user interface
screens for more flexibility. Screen sizes include 3.5”, 5.7” and 12.1”. Functionality added to the
screens include “stylus” notes entry, user defined data points and trend charts for paperless
chart recording, zoom and pan touch screen control on the charting screen, and remote data
retrieval through Ethernet.
Series 9205 Operations Manual Rev A 8
Approximate Box Dimensions
2.75" x 4" x 4.5"
Power Requirements
24VDC, 4 Watts
Digital Output Rating
300VAC / 1 AMP
Analog Output Load Rating
1000 Ohms (Total)
Controller Enclosure Rating
IP10 – hand protected
Number of RS232 Ports
Two (2)
Number of Ethernet Ports
One (1)
Number of RS485 Host Ports
One (1)
Number of RS485 Slave Ports
Two (2)
Number of Internal Relays
Eight (8)
Number of Analog Inputs
Three (3)
Number of Analog Outputs
Two (2)
Number of Digital Inputs
Four (4)
Number of Control Loops
Three (3)
!
The Model 9205 is powered by 24 VDC, not LINE Voltage. Please be careful when connecting
power to this controller. Connecting anything other than 24 VDC will cause serious damage.
The variety of input and output combinations allows SSi to configure the Model 9205 to control
temperature and atmosphere.
The product is available in three different screen sizes. 3.5”, 5.7” and 12”.
Mounting
The Series 9205 Operator Interface mounts into a panel or on a plate by using the enclosed
mounting brackets. A rectangular cutout is required; the size of the cutout is determined by the
operator interface size. These units, along with an optional SSi SR3, 6, or 9 analog input board,
will mount on a commercially available DIN rail. This can be mounted on the sub-panel on the
side of an enclosure for the convenience of the control system.
Series 9205 Operations Manual Rev A 9
Dimensional Drawings
Series 9205 Controller Dimensions
24V DC Power Supply Dimensions
Series 9205 Operations Manual Rev A 10
3.5” Operator Interface Cutout dimensions
5.7” Operator Interface Cutout dimensions
12” Operator Interface Cutout dimensions
Series 9205 Operations Manual Rev A 11
Wiring
Wiring to the Series 9205 operator interface can be done using 232 or 485 to two connectors, comm1 (232)
or comm3 (485). The terminal strip on the lower right rear corner of the operator interface is used to
connect 24VDC power. The DB-9 port A connection is used to connect the display via 232 to the Series 9205
PID controller. The controller is connected via RS485 communication to the single-loop controllers.
Electrical Installation
The Model 9205 requires 24VDC, 4 Watt, single-phase power. A 24 VDC power supply is required
and is generally included as part of the Model 9205 system. This power supply has a universal
input that can accept between 60 and 265VAC. Power should be applied in accordance with the
electrical drawings that have been supplied. Since each installation is unique to the site, the
customer is responsible for providing adequate power and making it available to the Model 9205
power supply.
SSi requirement:
MOV’s must be wired across the isolation relay coil terminals on all isolation relays that are
connected to solenoids.
when the solenoid is wired to them.
Further… MOVs must be connected across the HOT and NEUTRAL wires
IT IS AN ABSOLUTE MUST to have the MOVs at BOTH
LOCATIONS.
Series 9205 Operations Manual Rev A 12
Pin Out
9205 Pin Out
A wiring diagram of the Series 9205 controller can be found in Appendix B.
Ancillary Items
The following items can be included with the Series 9205: a flash card, a flash card reader, a
touch screen, an RS232 cable, an RS485 cable, a 24V DC DIN rail mount power supply, and a
software CD with Configurator, the Configurator manual, TS Manager, and .NET 2.0. The flash
card is installed in the operator interface and the flash card reader connects to a Windows®
based computer.
The operator interface includes a connection for a mouse and a keyboard. These may be
connected to the operator interface via USB, allowing the operators to use a mouse and keyboard
instead of the touch screen.
Series 9205 Operations Manual Rev A 13
Part
Part Number
31135 or
31137
The following table shows the ancillary items and their part numbers.
3.5" Operator Interface 31296
5.7" Operator Interface 31297
12" Operator Interface 31299
TS Manager/PC Configurator Software 13339
RS485 comms cable for 12.1” and 5.7 “ 20576
RS485 comms cable for 3.5” 20635
Flash Card 31604
Flash Card Reader 13333
RS232 Cable 33027
24V DC Din Rail Mounted Power Supply
9205 Controller 13443
Setup
The Series 9205 setup consists of setting the local time if required. As shipped from the factory
the communications ports are set at 19200 baud in Modbus mode.
Time will be set for local time in Cincinnati, Ohio (EST /EDT) or time zone of location of city and
state on sales order. For instruction on adjusting these values, please see
Configuration
.
Chapter 3 -
Additional Features
The Operator Interface (touch screen) contains a removable compact Flash or SD Card that can
be used to transfer data from the Model 9205 to a computer. It is located on the back of the touch
screen (see
Flash Card & Flash Card Reader section for more details).
Also included is a Utility Software CD that includes SSi’s TS Manager. TS Manager is a utility
program that can be loaded onto any Windows® based computer (operating Windows XP or
higher). This software will allow the computer to read the data from the TS Flashcard, and allow
it to be viewed in a manner that is similar to a strip chart recorder.
Ethernet Connections
The Ethernet connection has three distinct uses. First, should the Operator Interface fail, the
Ethernet connection allows a laptop to be connected via a crossover cable to the Series 9205 DIN
rail mounted unit using Internet Explorer Browser. This connection can act as a LIMITED
Series 9205 Operations Manual Rev A 14
!
FUNCTION “operator interface” until the Operator Interface can be repaired or replaced. The
laptop needs to be operating a Windows XP or higher with Internet Explorer. The default IP
address is
192.168.0.200. If you are experiencing problems please call (513) 772-0060 and talk
with our computer communications personnel. Secondly, the Ethernet port can be used for
communications to a SCADA software package. Call us at (513) 772-0060
if you are interested in
this option. The third use for the Ethernet Port is the primary communications connection for the
Configurator 2.0 Software.
Instrument Start-up
On power-up, the Operator Interface will display a Microsoft Windows desktop screen for a few
seconds and then switch to the default Status screen.
Flash Card & Flash Card Reader
Never remove the flash card when the Operator Interface is “ON”.
To properly shut down the Operator Interface, press the Menu button on the default status
screen. Once the menu has been displayed, select the
to shut down the Operator Interface. See the
Chapter 2 - CONFIGURATION
Shutdown
option. At the prompt, press Yes
section for information
on navigating and using the menu system. This will display a conventional Microsoft Windows
screen. Sliding the black switch to the OFF position (located directly over the green power
connector, on the back of the Operator Interface) or removing the 24VDC plug will turn off the
power to the Operator Interface.
Once the Operator Interface is turned off, remove the compact flash card cover at the top or side
of the display unit, exposing the card. Press the black release button or press card in to eject,
and the card will pop out of the slot. To replace the flash card, simply return the card to the slot
making sure that the release button is in its UP position, and replace the flash card cover to its
proper position. To restore power to the unit, move the black switch to the right or ON position or
connect plug.
Operator Interface Screen Saver
The Operator Interface has a default screen saver. It automatically “blanks” the screen after ten
(10) minutes of non-activity. To disengage the screen saver, simply touch the screen and it will reappear.
Default Status Screen
The Status Display shows the temperature controller
information as well as any auxiliary analog inputs, the
status of the timer, and an overview of the programmer.
There are five active buttons on the Status Display:
Menu, Chart, Recipe, Loops, and Ack.
• The Menu button will display the
configuration menu.
Series 9205 Operations Manual Rev A 15
• The Chart button will display the video recorder screen. Use of the Chart Display is explained
below.
• The Recipe button will switch to the Program Display. This is a companion display to the status
screen and is described below.
• The Loops button will display the main control loop, Temperature, as well as the timer status
and any auxiliary analog inputs.
• The Ack (Alarm Acknowledge) button is used to acknowledge an alarm. The alarm message is
displayed directly under the recipe display. Is this only present when an alarm is going off. This
button only acknowledges 9205 alarms and does not acknowledge any PLC alarms.
When the quench timer is running, the ACK button is replaced with a quench button. This quench
button is used to adjust the quench timer time remaining. In the purple status bar, the quench time
remaining is displayed.
Menu
There are three levels of menus in the Series
9205.
• The first level is the
are functions or operations that are
typically handled by the furnace operator.
This menu is accessed without the need for
a pass code.
• The second level is the
This level requires the entry of a level 1 or
a level 2-pass code.
• The third level is the
This requires the level 2-pass code ONLY.
As shipped, the
level codes are set as
Screen.
Note: Any level can access a lower level screen. For instance, the Administrator level passcode
supervisor
operator level
supervisor level
administrator level
and
administrator
1 and 2 respectively. The pass codes can be changed at the Passcode and Alarm
. These
.
.
can access all of the Supervisor and Operator level screens
The menu items are explained in detail in
Chapter 2 – Configuration.
Chart
The Chart Display shows between 1 hour and 24
hours of process variable data on the screen and
can be scrolled back to view all of the data stored
on the hard drive. The vertical timelines change
as the time changes on the screen. Any trend
charts that have been created through the
Configuration menu are accessible here. See the
Chapter 2 - CONFIGURATION
information on creating trend charts.
section for more
.
The function buttons run along the bottom of the
screen.
Series 9205 Operations Manual Rev A 16
The folder button - -
The Trend Lines button - - will allow the user to
select or de-select the trend lines on the trend chart to
display. If the checkbox next to each trend line is checked,
then that trend line will be displayed.
`
The Datagrid View button - - will display a screen with
the trend data in a grid format instead of with trend lines. The trend data is shown in 1-minute intervals.
Clicking on the
OK button on this screen will close the screen down and return to the Chart Display screen.
The Refresh button - - will refresh the screen’s trend data if the screen is not in real-time mode.
The left-pointing green arrow button - - will move the chart’s view backward in time by the
specified chart interval.
The chart interval button - - will determine the number of hours displayed on the trend chart. The
options are:
The right-pointing green arrow button - - will move the chart’s view forward in time by the specified
chart interval.
The right-pointing arrow with the vertical line next to it button - - will put the chart into real-time
mode if it is not in real-time mode, or take the chart out of real-time mode if it is. When in real-time mode,
the chart will automatically be updated once a minute.
Series 9205 Operations Manual Rev A 17
Chart Sub Menu
There is a sub-menu available by putting a
finger or a stylus anywhere on the chart and
holding it there for a couple of seconds. The
sub-menu will have the following options
available:
Exit.
to zoom in again.
Zoom, Restore, Add Note, Data, and
The Zoom option will allow the user to zoom in on a
particular part of the screen. Once this has been
selected, the user can take a stylus or a finger and create
a box around the desired data. Once the user releases
the stylus or finger, a zoom is no longer possible, and the
user will need to re-select the option from the sub-menu
The Restore option will back out of any zoom options that have been performed and display the chart
screen as it initially was.
The Add Note option allows the operator to enter a note on the chart, similar to writing on a paper chart.
The note shows up when the chart is printed out using the utility software included with the Series 9205
instrumentation. Pressing the
Add Note option displays a screen where the operator can enter the
operator ID or initials and a note. The user has the option to enter a note using the operator interface
keyboard, where he or she will be able to type in the note; or the user can use the Signature mode, which
will allow them to write a note using a stylus.
The Data option will show the trend data as a data grid instead of the trend lines on a chart. This
functionality is exactly the same as if the user pressed the Datagrid View button - - from the chart
screen.
Exit will close out the sub-menu without selecting an item.
Pressing the red ‘X’ in the top right-hand corner of the screen will take the user back to the status screen.
Series 9205 Operations Manual Rev A 18
Recipe
Pressing the Recipe button on the main status
screen displays the recipe screen, which will
allow the user to load up an existing recipe and
start it, or see the currently running recipe.
The recipe screen shows the last program loaded
into the program run buffer and its status. If the
program is running, the active step number is
highlighted green. When the step is highlighted
green, then the recipe is running on that step.
When a step is highlighted yellow, the recipe is in
hold on that step. A red
the bottom left corner of the screen displays an
alarm condition.
Note – the main status screen
Acknowledge button in
will also show the recipe running status, as well
as run time and remaining time for the step as
well as the entire recipe
The recipe screen has a total of seven buttons that will allow the user to load up a recipe, as well as control
the recipe and acknowledge an alarm.
.
•The Advance button will advance the recipe to the next step in the recipe. The user will need to
confirm the advance command.
•The Hold button places the displayed recipe program in hold. Once a decision is made that
affects the recipe, it may be continued by pressing the
put into hold status, the text on the
Hold button will change to “Resume”. When the step is
Resume button.
started up again, the text on the button will change back to “Hold”
hold status, the step will be highlighted yellow. The user will need to confirm the hold or
resume command.
•The Stop button stops the recipe program that is currently running. Stop means exactly that! It
stops the program. It is NOT a hold button. See the description for the hold button above. To restart the program if it has been stopped you must use the
number, and then highlight the segment number of the recipe that you want to start with and
start the recipe again. The user will need to confirm the stop command.
•The Soak button allows you to enter a new value for the time remaining in the current soak or
ramp cycle only – future soak or ramp cycle times cannot be modified. The step must be a
soak or ramp cycle for a change in soak/ramp time to be adjusted.
•The Acknowledge button will acknowledge the alarm. In
most cases, it will be acknowledging
alarm must be acknowledged to allow the program to go
to the next step.
Note – The Acknowledge button is only
end of soak
. The
Load button, enter the recipe
Note – When a recipe is
. When a recipe step is in a
visible when an alarm condition is present. Once the
condition is acknowledged, the
become invisible again
.
Acknowledge button will
•The Load button allows the operator to enter the recipe
number to be run and to view the recipe before pushing
Run button. Pushing the Run button starts the recipe.
the
If a recipe program is running and the operator enters a new recipe program it can be viewed
and modified. The recipe does not become active until the
places the program currently being viewed in the active memory and will begin to run the new
Series 9205 Operations Manual Rev A 19
Run button is pushed. Pressing Run
recipe. To select the recipe to view or edit, click on the recipe number button in the top left
corner of the screen. This will display a screen where the user will be able to load up a valid
recipe (range
button next to the “Step” text and entering the new step number (range
pressing the
While reviewing the program that is about to be run, each step can be modified. Highlight a
1 – 300). The program can be started in any step by clicking on the step number
1 – 24), and then
Run key.
step number and click on the
changed with the drop down list at the top. This list can be sorted
alphabetically by click on the “Alphabetical” checkbox. The
parameters of the opcode can be modified on this screen as well.
See the
Click on the
button to ignore the changes.
Chapter 4 – OPCODES section for details about each opcode.
OK button to accept the changes; click on the Cancel
Edit button. The opcode can be
Note – Any change to the recipe is a
one-time edit, and will not affect the recipe that is saved on the 9205
controller
cancel loading a recipe and return to the main recipe screen.
screen.
. Click on the Cancel button on the Load Recipe screen to
•The Return button returns you to the main status
Loops
This screen will display the program loops for the
9205. Up to three loops can be displayed. The current
process variable is displayed at the top, with each loop
set point displayed beneath the process variable. The
operator can change the process set point by touching
the screen area below the large process variable
numbers. When pressing the Temperature set point, a
numeric keypad is displayed, showing the current
value and allowing the operator to enter a new set
point by simply pressing on the appropriate numeric
keys. Once the correct set point has been entered,
press the
key is pressed the display returns to the
Screen. Another active key within the
button toggles the controller’s mode between Auto and Manual. In the manual mode, pressing the percent
output button on the
output to control the “loop” in a manual mode to be entered. If a timer is running, the status will be
displayed at the top right of the screen. Any load T/Cs that are actively communicating will be listed in the
box to the right of the setpoint/percent output values. If an alarm condition is present, the alarm text will
be displayed below the loop information. If the alarm needs acknowledging, then the
be displayed in the bottom left corner. If the alarm is part of a recipe step, the alarm will need to be
acknowledged before the recipe can move to the next step.
The Loops Screen also allows you to move back to the default Status Screen by pressing the Return.
OK key to make the change. When the OK
Loops
Loops
Screen is the Auto/Man (Auto/Manual) button. Pressing that
Loops
Screen (next to the Auto/Man button) displays a numeric keypad, allowing a %
Alarm Ack button will
Ack (Alarm Acknowledge)
The Ack (Alarm Acknowledge) button will allow the user to acknowledge any alarms that have been
configured, or that have been made part of the recipes that run on the Series 9205. If a recipe has an alarm
as a step, the alarm must be acknowledged before the recipe will continue to the next step.
Series 9205 Operations Manual Rev A 20
!
Data Logging using Flash Card
NOTE: See Warnings with respect to removing the Flash Card.
The Advantech TPC-642S/642-SE touch screen Operator Interface utilizing a Compact Flash
Card allows the unit to data log the parameters set up by a qualified SSi technician. Should a
customer not take the data offline in a timely manner, the data will be over-written, the oldest data being
over-written first. Here is how it works:
1. When the Operator Interface detects that there is less than 5% disk space left on the compact flash
card, an alarm will be displayed on the main interface screen stating "x% disk space remaining (overwrite
at 3%)". In the upper right corner, an ALM is indicated, but because it is not a communications alarm or a
9205 device alarm, the background remains green. This alarm will remain active until more than 5% of
disk space is available for writing data log files.
2. If the user does not copy the log data from the disk, it will eventually fall to 2% disk space. At this point,
the touch screen will select the oldest compressed file and delete it. It then checks to see if 3% remains. It
repeats this procedure until 3% disk space remains. At this point the alarm message changes to
"Overwriting data log data!” Because this allows the system to seesaw between 2% and 3%, it will continue
to display "Overwriting data log data!" until somebody offloads the files.
Technical concerns and details:
1. If there are not enough compressed files to bring the free space up to 3%, the system will hunt down and
kill hourly files. This should only happen if compression would not be running for some reason.
2. If all compressed files and hourly files have been removed and there is still not enough disk space
(perhaps a problem with the compact flash card), the data logger will not write to the disk until the
condition is remedied. (Alarms continue to display).
3. The data log data alarm is the lowest priority. The alarm priorities are touch screen communications,
then 9205 controller/programmer, then disk space.
See the Flash Card Management Section for more information.
Series 9205 Operations Manual Rev A 21
Chapter 2 - CONFIGURATION
Menu (Configuration)
The Configuration Menu is entered through the
Menu key that is part of the four buttons running
along the bottom of the Default Display Screen.
Pressing the Login key at the bottom of the
screen will allow the user to enter a login user
and password.
through the Security menu option in this menu
User names and passwords are case sensitive.
There are three levels of security for the menu
system:
Pressing the
enter a user name and password to log in. When
the menu screen is first displayed, the operatorlevel menu options are visible.
The list of the operator-level menu options is:
The list of supervisor-level menu options is:
The list of administrator-level menu options is:
Operator, Supervisor, and Administrator.
• About
• Maintenance
• Logs
• Probe Manager
• Slave Communications Status
• Load TC/Auxiliary Analog Input
• Manual Event Control
• Shutdown
• About
• Maintenance
• Logs
• Probe Manager
• Slave Communications Status
• Load TC/Auxiliary Analog Input
• Manual Event Control
• Shutdown
• Probe Burnoff Setup
• PID Loop Setup
• Recipe Edit
• Load T/C Configuration
• Trend Chart Edit
• About
• Maintenance
• Logs
• Probe Manager
• Slave Communications Status
• Load TC/Auxiliary Analog Input
• Manual Event Control
• Shutdown
Note – users can be set up
.
Login button will allow the user to
Series 9205 Operations Manual Rev A 22
• Probe Burnoff Setup
• PID Loop Setup
• Recipe Edit
• Load T/C Configuration
• Trend Chart Edit
• Communications Setup
• Slave Instrument Setup
• Zone Assignments
• Furnace Setup
• Default Wait Limits
• Alarm Setup
• Thermocouple Check
• Relay Assignments
• Analog Input Setup
• Analog Output Setup
• Alarm Polarity
• Redundant TC Setup
• Event Hold/Reset
• Security
• Curve Entry
• Alternate PID Setup
• Aux Analog Input Setup
• Calibration
• Configuration
• A/I Module Offset Correction
• Aux Setpoint Configuration
• T/C Extension Correction Curves
• Generic Instrument Setup
• DF1 Configuration
• Tuning Assistant
• PLC Data Matching
• Analog Input Correction Curves
• Instrument Calculation
The SSi code of the day can also be used to log in to the menu system. No user name will need to be
entered when entering this code. Currently, the menu list is identical to the administrator-level list. The
SSi code of the day is typically used for in-house configuration prior to shipment. The code can only be
provided by Super Systems at (513) 772-0060.
To select any of the menu options, highlight that item by clicking on it, and click on the Detail button.
The Return button will return the user to the default display screen.
Series 9205 Operations Manual Rev A 23
About
The About screen displays important information on
the 9205 controller that the touch screen is
communicating with. The
firmware version of the controller itself.
SSi 9205 field shows the
Serial
Number shows the serial number of the controller.
Interface Revision shows the current version of the
touch screen interface.
The remaining fields show versions of various DLL
(dynamic link library) files that the touch screen
software uses to operate. These fields may be
needed for troubleshooting if you need to contact
SSi for technical support.
Maintenance
From the Maintenance Status menu, you can view a list of scheduled and completed maintenance items.
Maintenance items are added from the Configuration -> Maintenance menu. See the
Configuration section
on page 61 for more information.
Logs
The Logs screen will allow the user to view three
different types of logs –
System, Alarms, and
Cycle.
Clicking on the button that displays the log type
System Log, Alarm Log, or Cycle Log) will allow
(
the user to select the type of log file to view.
The green directional arrows will display the
previous items in the log or the next items in the
log, if the log items are longer than one screen.
The drop down list in between the directional
arrows will allow the user to select the date of the
log items to view.
The Return button will return the user to the
menu screen.
Series 9205 Operations Manual Rev A 24
Log Types
The System Log tracks the startup and shutdown activity of the touch screen as well as when
communications to the controller are established.
The Alarm Log tracks all alarms—those that are internal to the controller and those that are generated by
the PLC. This log tracks the alarm generated, its start time, and its end time. This log can be useful for
helping build an alarm history.
The Cycle Log keeps track of charged loads and completed recipes. Specifically, it displays the start time
and date, completed time and date, and recipe number executed. A Utilization button can be pressed to
open a page with information on utilization based a selected date and on the amount of time that the 9205
controller has run a recipe compared to the amount of time it has not run a recipe.
Probe Manager
This option allows the user to register a probe within
the 9205 by entering its serial number. Doing so
starts a tracking history of probe burn-offs,
impedance tests, recovery time, and other probe
parameters. Trends can be monitored this way, and
the impedance of the probe can be traced to help
estimate its life expectancy.
To install a new probe, tap Install New Probe. You
will be asked for the probe serial number. Enter it
and tap
OK.
When Burnoff Report is selected, a list showing
when a burnoff took place will appear, along with probe mV, temperature, and temperature change during
the burnoff. When a burnoff event is selected, a chart will show temperature changes during the burnoff
event.
When Probe Test Report is selected, a list will appear showing test parameters for the selected probe:
time: Impedance kΩ, Recovery Time, Start Temperature, Test mV, and Test Temperature. When a test event
is selected, a chart will show temperature changes during the test.
Tap Return to return to the main menu.
Series 9205 Operations Manual Rev A 25
Slave Communications Status
This page is a display of the current process
variables of each of the slave instruments
communicating with the 9205 controller. These
values are display-only, and cannot be modified from
this screen.
There are five possible messages that can occur to
describe the instrument communications status.
• N/A – No instrument is connected
• Bad – No communications exist
• ??? – Communications exist, but there
are frequent errors
•?OK – Communications exist, but there
are occasional errors
•OK – Communication is established and working properly
For set-up of the auxiliary instruments go to the menu item “
The Return button will return the user to the menu screen.
Load TC/Auxiliary Analog Input
The Load TC/Auxiliary Analog Input screen will show the
values for the load TCs and the auxiliary analog inputs.
These values are display-only, and cannot be modified
from this screen.
Manual Event Control
Events are assignable outputs, used in recipes/programs.
Typically, they are used to signal the recipe is complete, to
turn process gases off and on, and tell the equipment to
do a variety of tasks. The Manual Event Control submenu
allows the user to force the events off or on.
The Manual Event Control menu option shows the user all
of the events (
0 – 47) and their current status. It also
allows the user to manually control the status of any
event by clicking on the value. To change the status,
highlight the specific event and click on the
The user will be able to select either an
Edit button.
On value or an Off
value.
Slave Instrument Setup
”
Series 9205 Operations Manual Rev A 26
WARNING!
Before assigning or changing events, be certain that you are familiar with the function of the event whose
status you are going to change. Changing the status of an event without knowledge of the result can lead to
hazardous situations.
Clicking on the OK button will set the value, while clicking on the Cancel button will cancel the action.
The Return button will return the user to the menu screen.
Shutdown
The Shutdown selection will display a screen asking whether or not to shut down the interface of the Series
9205. When the operator interface is shutdown, the Series 9205 controller is still functioning. IT can be
monitored by connecting the Ethernet connection to a laptop computer, using Internet Explorer, and
assigning a legitimate IP address. Choosing
Yes displays a typical computer desktop screen with the Start
button in the bottom left-hand corner. The power to the operator interface can now be turned off without
upsetting any of the settings. Choosing
No displays the initial Status Screen.
Operator Interface does not shutdown the Series 9205 Controller
.
Note - Shutting down the
Probe Burnoff Setup
When a probe is in a furnace, soot will collect in the
end of the probe, which will have a negative effect
on the performance of the probe. Burnoffs are
used to clean out the built-up carbon by burning it
off of the probe.
Burnoff Time: This is the duration of the burnoff
measured in seconds. SSi recommends a 90
second burnoff, and this will be the default value.
However, it can be adjusted by the operator. Click
OK button to set the new value, or click on
on the
Cancel button to cancel.
the
Rec Wait Time: The amount of time allotted to
allow the probe measurements to return to a stable, accurate range after the burnoff is complete. This is
measured in seconds. The control output is held until this time is elapsed. Clicking on the value will allow
the user to change the value.
Interval: This is the amount of time between the beginning of one burnoff and the beginning of the next
scheduled burnoff, in minutes. Default time for the instrument is 720 minutes (12 hours). However, the
amount of time between burnoffs should be determined by the application.
Minimum Millivolts: The minimum measured millivolt tolerance of the probe required to start a burnoff.
Clicking on the value will allow the user to change the value. SSi recommends the millivolt value gets down
to 200 mV.
Maximum Temperature: The maximum measured temperature allowed during a burnoff. If the
temperature value is exceeded
the burnoff will stop. This is done to help maintain the life and the accuracy
of your probe. SSi recommends a value of 1800 degrees. Clicking on the value will allow the user to change
the value.
Series 9205 Operations Manual Rev A 27
Digital IN 4 Assignment: The value for the digital input 4 assignment. Clicking on the value will allow the
user to change
the value, which can be either event or Start Burnoff.
Burnoff Minimum Millivolts Alarm Setpoint: The minimum millivolt value that must be reached in order for
the “Insufficient mV drop during BO” alarm not to be generated. If the millivolt value does not drop below
the minimum, the alarm will be generated.
Burnoff Maximum Temperature Rise Limit: The maximum number of degrees that the temperature is
allowed to increase before the “Excessive TC rise during BO” alarm is generated.
PID Loop Setup
PID is the tuning parameters entered for each Process
Variable loop.
Prop Band (0 for On/Off)
Proportional Band determines the response to the
current error. The Proportional Band is the percent of
the range of the process variable that will produce
100% output and is the inverse of the proportional gain.
A low Proportional Band value results in a larger
change in output for a given error. Conversely, a high
Proportional Band value results in a smaller change in
output for a given error. If the Proportional Band is too
small, control may oscillate or be otherwise unstable.
If the Proportional Band is too large the control action may be too sluggish in response to changes within
the system. Note: If the Proportional Band is set to 0.0, only on/off control is performed. The range
0 –
3276.0.
Reset
Reset determines the influence of past errors. The Reset, or integral action (expressed in repeats per
minute), sums the error between the process variable and setpoint over time and adds this accumulated
output to the proportional output. A “proportional only” controller generally operates with steady-state
error because some error is required to produce control output. The goal of integral action is to drive the
steady-state error to zero and eliminate this droop.
The range 0 – 327.67.
Rate
Rate adjusts the response to future errors.The Rate, or derivative action (expressed in minutes), is used to
predict system behavior and has a dampening effect. The more the controller tries to change the process
variable the harder the derivative will work to counter that effort. This dampening effect can be valuable in
reducing overshoot but is most often useful when trying to improve control on systems with significant and
predicable lag.
Control Mode
This is the mode of the loop. The values are: Dual Reverse, Single Reverse, Dual Direct, or Single Direct.
Dual – This has two output relays which can increase and decrease to achieve the SP.
Single – This has one relay which works in only one direction to achieve the SP.
Direct - If the PV - SP equals a positive number and the output would bring the PV down toward setpoint
that is direct.
Reverse – If the PV - SP equals a negative number and the output would bring the PV up toward setpoint
then that is reverse
The range 0 – 327.67. NOTE: The rate is not typically used for carbon control.
Series 9205 Operations Manual Rev A 28
Example: If a 12 mA output drives a 0 degree F temperature (PV) UP to a 1200 degree F temperature (SP),
this would be
Temperature Loop is
Integral Preset
This field provides an offset for the starting point for PID control, also referred to as “Load Line” or “Manual
Reset”. The range is
Cycle Time
This field is typically set to the valve travel time multiplied by 1.5. The range is 0 – 500.
Setpoint Change Limit
This is a smart time feature that allows Process Loop to use PB only without Reset until the Process
Variable drops below the percent output set under this category.
It is used to eliminate overshoot.
The Output percentage selected under this category
of the furnace at heat.
The options are: OFF, 80%, 70%, 60%, 50%, 40%, 30%, or 20%.
Example: If the furnace runs at 40% output at heat for the maximum load, the setpoint change limit should
be set to 60%.
Control Low Limit
This is the low limit for the loop. The range is –100 to 100.
Control High Limit
This is the high limit for the loop. The range is –100 to 100.
0 Setpoint Stops Control
If the Setpoint is zero, then all outputs are turned off. The option is either Yes or No.
IN1 high limit shuts down ctrl
If input 1’s high limit is reached, then all outputs are turned off. The value can either be Yes or No.
REVERSE
, and since this would take a
Single Reverse.
–100 to 100.
SINGLE
must
output from the controller, the Mode for the
be above the normal operating output percentage
IN2 high limit shuts down ctrl
If input 2’s high limit is reached, then all outputs are turned off. The value can either be Yes or No.
IN3 high limit shuts down ctrl
If input 3’s high limit is reached, then all outputs are turned off. The value can either be Yes or No.
PID Auto Switch
This is the PID auto switch field. The value can either be Yes or No.
PID auto switch is a feature within the instrument that allows multiple PID Loops to be used for various
temperature ranges. This feature can be extremely helpful when a single PID Loop is not accurate across a
wide temperature range. The most common indication that PID auto switching may improve furnace ability
is failure to pass Temperature Uniformity Surveys (TUS). In many examples, a certain PID Loop may prevent
under- or over-shoot at normal operating temperatures; but produce unacceptable overshoot at lower
temperature.
This feature allows the user to utilize (up to) three distinct loops to obtain more accurate heating curves. In
most applications, it is helpful to use the built-in Tuning Assistant feature to determine appropriate PID
Series 9205 Operations Manual Rev A 29
Loading...
+ 205 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.