Installation and Basic Operation What Instrument Do I Have? ...................................................................................... 6
1.1 Unpacking Your Controller ...................................................................................................................................................6
Panel Mounting t he Controller ...............................................................................................................................................7
1.3.2
Panel Cut Out Sizes................................................................................................................................................................7
1.3.3
Recommended minimum spacing of c ontrollers .....................................................................................................................7
1.3.4
To Remove the Controller from its Sleeve ...............................................................................................................................7
Thermocoup le Input ..............................................................................................................................................................9
Linear Input (mA or mV) .........................................................................................................................................................9
DC Out put .............................................................................................................................................................................10
Logic Co ntact Closure Inp ut (I/O 1 only) ..................................................................................................................................10
Summary of DC Outputs.......................................................................................................................................................10
General Note About Relays and Inductive Loads ..................................................................................................................11
2.11
Digital Inputs A & B...............................................................................................................................................................11
2.12
Transmitter Power Supply ....................................................................................................................................................11
2.13
Digital Communications........................................................................................................................................................12
2.14
Controller Power Supply.......................................................................................................................................................13
2.15
Example Heat/Cool Wiring Diagram .....................................................................................................................................13
3. Safety and EMC Information ...................................................................................................................... 14
4. Switch On .................................................................................................................................................. 16
4.1 New Controller .....................................................................................................................................................................16
To Re-Enter Quick Code mode..............................................................................................................................................17
4.3
Pre-Configured Controller or Subsequent Starts...................................................................................................................17
4.4
Front Panel Layout ...............................................................................................................................................................18
4.4.1
To Set The Target Temperature..............................................................................................................................................18
Auto, Manual and Off Mode ...................................................................................................................................................20
4.4.5
To Select Auto, Manual or Off Mode .......................................................................................................................................20
5.1 To Enter Level 2 ....................................................................................................................................................................21
5.2
To Return to Level 1 .............................................................................................................................................................21
6. Access to Further Parameters .................................................................................................................... 25
To Select Access Level 3 or Configuration Level.......................................................................................................................26
To Choose Parameter List Headers .........................................................................................................................................27
6.2.2
To Locate a Parameter ...........................................................................................................................................................27
6.2.3
How P arameters are Displayed ..............................................................................................................................................27
6.2.4
To Change a Parameter Value ................................................................................................................................................27
6.2.5
To Return to the HOME Display..............................................................................................................................................27
6.2.6
Time Out ...............................................................................................................................................................................27
Example: To Apply an Offset: ............................................................................................................................................... 35
Example: To Scale a Linear Input ........................................................................................................................................... 35
Input /Output 1 List (IO-1) ...................................................................................................................................................... 37
9.1.2
Remote Digital Setpoint Select and Remote Fail .................................................................................................................... 38
9.1.3
Sense ................................................................................................................................................................................... 38
Po wer Fail............................................................................................................................................................................. 38
9.1.6
Example: To Configure IO-1 Relay to Operate on Alarms 1 and 2: ........................................................................................... 38
9.1.7 Output List 2 (OP-2) ............................................................................................................................................................. 39
9.1.8
Output List 3 (OP-3).............................................................................................................................................................. 39
9.1.9
AA Relay (AA) (Output 4) ...................................................................................................................................................... 40
9.1.10
Digital Inp ut Parameters .................................................................................................................................................. 41
9.2
Current Transformer Input Parameters (Current Transformer is not available) .................................................................... 42
Example: To Set Ramp Rate ............................................................................................................................................... 44
11. Control ...................................................................................................................................................... 45
11.1 Types of Control .................................................................................................................................................................. 45
11.1.1
On/Off Control ................................................................................................................................................................ 45
Control Parameters.............................................................................................................................................................. 46
11.2.1
Proportional Band ‘PB’..................................................................................................................................................... 48
11.2.2
Integral Term ‘TI’.............................................................................................................................................................. 48
11.2.3
Derivative Term ‘TD’ ........................................................................................................................................................ 49
11.2.4
Relative Cool Gain ‘R2G’................................................................................................................................................... 49
11.2.5
High and Low Cutback ..................................................................................................................................................... 50
Control Action ................................................................................................................................................................. 50
To Start Autotune ............................................................................................................................................................ 53
11.3.5
Autotune from Below SP – Heat/Cool ............................................................................................................................... 54
11.3.6
Autotune From Below SP – Heat Only .............................................................................................................................. 55
11.3.7
Autotune at Setpoint – Heat/Cool ......................................................................................................................................... 56
Example: To Configure Heating and Cooling ....................................................................................................................... 60
11.5.1
Effect of Control Action, Hysteresis and Deadband........................................................................................................... 61
To Acknowledge An Alarm ............................................................................................................................................... 64
12.2
Behaviour of Alarms After a Power Cycle ............................................................................................................................. 65
12.2.1
Examp le 1 ........................................................................................................................................................................ 65
12.2.2
Example 2........................................................................................................................................................................ 65
12.2.3
Examp le 3 ........................................................................................................................................................................ 65
Example: To Co nfigure Alarm 1 ........................................................................................................................................ 67
Out of Range Indication ................................................................................................................................................... 68
13. Digital Communications ............................................................................................................................. 69
13.1 Digital Communications Wiring ............................................................................................................................................ 69
13.2 Digital Communications Parameters .....................................................................................................................................70
13.3
Example: To Set Up Instrument Address ..............................................................................................................................71
13.4
DATA ENCODING .................................................................................................................................................................71
To Check mV Input Calibratio n ..........................................................................................................................................81
14.1.3
To Check Thermocouple Input Calibration .........................................................................................................................81
14.1.4
To Check RTD Input Calibration ........................................................................................................................................81
Two Point Offset ..............................................................................................................................................................82
14.2.2
To Apply a Two Point Offset .............................................................................................................................................83
14.2.3
To Remove the Two Point Offset ......................................................................................................................................83
To Calibrate mV Input .......................................................................................................................................................84
14.3.2
To Calibrate Thermocouple Input ......................................................................................................................................85
14.3.3
To Calibrate RTD Input......................................................................................................................................................86
14.3.4
To Calibrate mA Outputs ..................................................................................................................................................87
14.3.5 To Calibrate Remote Setpoint Input ..................................................................................................................................88
14.3.6
To Return to Factory Calibration .......................................................................................................................................89
15. Appendix A TECHNICAL SPECIFICATION .................................................................................................. 91
4
Series 3 Operations Manual
Issue Status of this Manual
Issue 5 of this Handbook applies to software versions 2.09 and above for PID controller and 2.29 and above for Valve Position
controllers and includes:
• Remote Setpoint Input Option RCL
• Triac output
It also applies to firmware versions 2.11 and includes new parameters:
Inverted status word
Rate of change alarms
Setpoint retransmission limits
Input filter
Issue 6 includes parameter ‘AT.R2G’
Issue 7 corrects range limits. Change to definition of LOC.T. Correct description of enumerations for parameter IM.
Issue 8 includes the following changes:
A more detailed description of loop tuning.
Updates to Appendix A, Technical Specification.
5
Operations Manual Series 3
Installation and Basic Operation What Instrument Do I Have?
Thank you for choosing this Series 3 Temperature Controller.
The Series 3 provides precise temperature control of
industrial processes and is available in one standard DIN size:
•1/4 DIN
A universal input accepts various thermocouples, RTDs or
process inputs. Up to four outputs can be configured for
control, alarm or re-transmission purposes. 485
communication is also available.
The controller may have been ordered pre-configured or
setup with defualt configuration..
If the display shows SET 1 the controller was supplied
without parameters and will need to be configured when it
is first switched on.
This Manual takes you through all aspects of installation,
wiring, configuration and use of the controller.
1.1 Unpacking Your Controller
The controller is supplied with
• Sleeve (with the controller fitted in the sleeve)
• Two panel retaining clips and sealing gasket mounted
on the sleeve
•Component packet containing a snubber for relay
output and a 2.49Ω resistor for current inputs.
1.2 Dimensions
General views of the controller are shown below together
with overall dimensions.
6
Series 3 Operations Manual
1.3 Step 1: Installation
This instrument is intended for permanent installation, for
indoor use only, and to be enclosed in an electrical panel
Select a location which is subject to minimum vibrations the
ambient temperature is within 0 and 55oC (32 - 131
humidity 5 to 95% RH non condensing.
The instrument can be mounted on a panel up to 15mm
thick.
To ensure IP65 and NEMA 4 front protection, mount on a
non-textured surface.
Please read the safety information in section 3 before
proceeding.
1.3.1 Panel Mounting the Controller
1. Prepare a cut-out in the mounting panel to the size
shown. If a number of controllers are to be mounted in
the same panel observe the minimum spacing shown.
2. Fit the sealing gasket behind the front bezel of the
controller
3. Insert the controller through the cut-out
4. Spring the panel retaining clips into place. Secure the
controller in position by holding it level and pushing both
retaining clips forward.
5. Peel off the protective cover from the display.
o
F) and
1.3.2 Panel Cut Out Sizes
1.3.3 Recommended minimum spacing of
controllers
10mm (0.4 in)
38mm (1.5 in)
(Not to scal e)
1.3.4 To Remove the Controller from its Sleeve
The controller can be unplugged from its sleeve by easing
the latching ears outwards and pulling it forward out of the
sleeve. When plugging it back into its sleeve, ensure that
the latching ears click back into place to maintain the sealing
7
Operations Manual Series 3
!
2. Step 2: Wiring
2.1 Terminal Layout Series 3 Controller
Ensure that you have the correct supply for your indicator
Key to symbols used in wiring diagrams
Logic ( SSR drive) out put
mA analogue output
Relay output
Triac output
Contact input
Current t ransformer input
8
Series 3 Operations Manual
-
2.2 Wire Sizes
The screw terminals accept wire sizes from 0.5 to 1.5 mm (16
to 22AWG). Hinged covers prevent hands or metal making
accidental contact with live wires. The rear terminal screws
should be tightened to 0.4Nm (3.5lb in).
2.3 Precautions
• Do not run input wires together with power cables
• When shielded cable is used, it should be grounded at
one point only
• Any external components (such as zener barriers, etc)
connected between sensor and input terminals may
cause errors in measurement due to excessive and/or
un-balanced line resistance or possible leakage currents
• Not isolated from the logic outputs & digital inputs
• Pay attention to line resistance; a high line resistance
may cause measurement errors
2.4 Sensor Input (Measuring Input)
2.4.1 Thermocouple Input
+
Positive
V+
V-
Negative
-
•Use the correct compensating cable preferably shielded
2.4.2 RTD Input
VI
PRT
V+
PRT
V-
Lead compensation
•The resistance of the three wires must be the same.
The line resistance may cause errors if it is greater than
22Ω
2.4.3 Linear Input (mA or mV)
V+
V-
2.49Ω
+
+
mA / mV input
-
Shield
• If shielded cable is used it should be grounded in one
place only as shown
• For a mA input connect the 2.49Ω burden resistor
supplied between the V+ and V- terminals as shown
• For a 0-10Vdc input an external input adapter is required
(not supplied).
+
-
100KΩ
806Ω
+
0-10V
Input
-
Sensor break alarm does not operate with this adaptor
fitted.
2.4.4 Two-Wire Transmitter Inputs
Using internal 2 4V power supply ( Series 3)
+
V+
-
V-
3C
3D
2.49Ω
+
-
Using external pow er supply
+
V+
-
V-
2.49Ω
-
Extern al power
supply
+
-
2-Wire
Transmitter
+
-
2-Wire
Transmitter
+
9
Operations Manual Series 3
2.5 Input/Output 1 & Output 2
OP3
Non-isolated
OP4
Non-isolated
1A
2A
+
-
+
-
1A
+
-
+
-
+
-
These outputs can be logic (SSR drive), or relay, or mA dc. In
addition the logic output 1 can be used as a contact closure
input.
For input/output functions, see Quick Start Code in section
4.1.1.
2.5.1 Relay Output (Form A, normally open)
Isolated output 240Vac CAT II
OP1 OP2
1B
2B
2.5.2 Logic (SSR drive) Output
OP1
1A
1B
OP2
2A
2B
• The output switching rate must be set to prevent
damage to the output device in use. See parameter
1.PLS or 2.PLS in section 5.
2.5.3 DC Output
OP1
1A
1B
• Not isolated from the sensor input
• Software configurable: 0-20mA or 4-20mA.
• Max load resistance: 500Ω
• Calibration accuracy: +(<1% of reading + <100µA)
2.5.4 Triac Output
•
Isolated output 240Vac CATII
1(2) A
•Rating: 0.75A rms, 30 to 264Vac resistive
1(2)B
•
• Contact rating: 2A 264Vac
resistive
Not isolated from the sensor
•
input
• Output ON state: 12Vdc at
40mA max
• Output OFF state: <300mV,
<100µA
OP2
2A
2B
2.6 Remote Setpoint Input
• There are two inputs; 4-20mA and 0-10 Volts which can be
HD
HE
HF
0-10 Volts
4-20 mA
Common
fitted in place of digital
communications
• It is not necessary to fit an
external burden resistor to the
4-20mA input
• If the 4-20mA remote setpoint input is connected and
valid (>3.5mA; < 22mA) it will be used as the main
setpoint. If it is not valid or not connected the controller
will try to use the Volts input. Volts sensor break occurs at
<-1; >+11V. The two inputs are not isolated from each
other
• If neither remote input is valid the controller will fall back
to the internal setpoint, SP1 or SP2 and flash the alarm
beacon. The alarm can also be configured to activate a
relay or read over digital communications.
• To calibrate the remote setpoint, if required, see section
15.3.5
• A local SP trim value is available in access level 3.
2.7 Output 3
Output 3 will be a mA output.
DC Output
OP3
3A
3B
• Isolated output 240Vac CAT II
• Software configurable: 0-20mA or 4-
20mA
• Max load resistance: 500Ω
• Calibration accuracy: 0.5%, +100µA
2.8 Summary of DC Outputs
OP1 Non-isolated
OP2 Non-isolated
2.5.5 Logic Contact Closure Input (I/O 1 only)
Not isolated from the sensor input
•
OP1
• Switching: 12Vdc at 40mA max
• Contact open > 500Ω. Contact closed <
1B
10
150Ω
Series 3 Operations Manual
2.9 Output 4 (AA Relay)
Output 4 is a relay..
For output functions, see Quick Start Code in section 4.1.1.
OP4
AA
AB
AC
Relay Output (Fo rm C)
• Contact rating: 2A 264Vac resistive
2.10 General Note About Relays and
Inductive Loads
High voltage transients may occur when switching inductive
loads such as some contactors or solenoid valves. Through
the internal contacts, these transients may introduce
disturbances which could affect the performance of the
instrument.
For this type of load it is recommended that a ‘snubber’ is
connected across the normally open contact of the relay
switching the load. The snubber recommended consists of a
series connected resistor/capacitor (typically 15nF/100Ω). A
snubber will also prolong the life of the relay contacts.
A snubber should also be connected across the output
terminal of a triac output to prevent false triggering under
line transient conditions.
WARNING
When the relay contact is open or it is connected to a high
impedance load, the snubber passes a current (typically
0.6mA at 110Vac and 1.2mA at 240Vac). You must ensure
that this current will not hold on low power electrical
loads. If the load is of this type the snubber should not be
connected.
• Isolated output 240Vac CAT II
• Output: 24Vdc, +/- 10%. 28mA max.
• inside the controller
2.11 Digital Inputs A & B
Digital input A is an optional input in model Series 3. Digital
input B is always fitted in model Series 3.
Dig in A
C
LA
Dig in B
LB
LC
• Not isolated from the current transformer input or the
sensor input
• Switching: 12Vdc at 40mA max
• Contact open > 500Ω. Contact closed < 200Ω
• Input functions: Please refer to the list in the quick
codes.
2.12 Transmitter Power Supply
The Transmitter is fitted as standard in model Series 3.
Transmi tter Supply
3C
3D
24Vdc
11
Operations Manual Series 3
2.13 Digital Communications
Optional.
Digital communications uses the Modbus protocol. The
interface comes standard as EIA485 (2-wire).
Digital communications is not available if Remote
Setpoint is fitted
Cable screen should be grounded at one point only to
prevent earth loops.
•Isolated 240Vac CAT II.
EIA485 Connections
Rx Tx Com
Tx Rx Com
RxB/
TxB
*
RxA/
TxA
220Ω termination
resist or
Com
* EIA2 32/EIA485 2-wire
communicat ions convert er eg
Type K D485
Screen
220Ω termination
resistor on last
controller in the line
Twis ted pair
Daisy Chain to
further
controllers
HD
Common
HE
Rx A(+)
HF
Tx B(-)
12
Series 3 Operations Manual
AA
2.14 Controller Power Supply
1. Before connecting the instrument to the power line,
make sure that the line voltage corresponds to the
description on the identification label.
2. Use copper conductors only.
3. For 24V the polarity is not important
4. The power supply input is not fuse protected. This
should be provided externally
Power Supply
L
Line
N
• High voltage supply: 100 to 240Vac, -15%, +10%, 48 to
• Recommended external fuse ratings are as follows:
Neutral
62Hz
For 100-240Vac, fuse type: T rated 2A 250V.
2.15 Example Heat/Cool Wiring Diagram
This example shows a heat/cool temperature controller
where the heater control uses a SSR and the cooling control
uses a relay.
L
Heater
fuse
Solid State Relay
(e.g. TE10)
N
Heater
Controller fuse
1A
1B
2A
2B
L
N
J
CT
AB
C
AC
LA
VI
HD
V+
HE
V-
HF
J
+
-
T/C
Relay
output
fuse
Snubber*
Cooling or
alarm relay
Safety requirements for permanently connected equipment
state:
• A switch or circuit breaker shall be included in the
building installation
• It shall be in close proximity to the equipment and
within easy reach of the operator
• It shall be marked as the disconnecting device for the
equipment
A single switch or circuit breaker can drive more than
one instrument
13
Operations Manual Series 3
3. Safety and EMC Information
This controller is intended for industrial temperature and
process control applications when it will meet the
requirements of the European Directives on Safety and
EMC. Use in other applications, or failure to observe the
installation instructions of this handbook may impair safety
or EMC. The installer must ensure the safety and EMC of
any particular installation.
Safety
This controller complies with the European Low Voltage
Directive 73/23/EEC, by the application of the safety
standard EN 61010.
Electromagnetic compatibility
This controller conforms with the essential protection
requirements of the EMC Directive 89/336/EEC, by the
application of a Technical Construction File. This instrument
satisfies the general requirements of the industrial
environment defined in EN 61326. For more information on
product compliance refer to the Technical Construction File.
GENERAL
The information contained in this manual is subject to
change without notice. While every effort has been made to
ensure the accuracy of the information, your supplier shall
not be held liable for errors contained herein.
Unpacking and storage
The packaging should contain an instrument mounted in its
sleeve, two mounting brackets for panel installation and an
Installation & Operating guide.
If on receipt, the packaging or the instrument are damaged,
do not install the product but contact Super Systems, Inc. If
the instrument is to be stored before use, protect from
humidity and dust in an ambient temperature range of -30oC
o
to +75
C.
SERVICE AND REPAIR
This controller has no user serviceable parts. Contact Super
Systems, Inc. for repair.
Caution: Charged capacitors
Before removing an instrument from its sleeve, disconnect
the supply and wait at least two minutes to allow capacitors
to discharge. It may be convenient to partially withdraw the
instrument from the sleeve, then pause before completing
the removal. In any case, avoid touching the exposed
electronics of an instrument when withdrawing it from the
sleeve.
Failure to observe these precautions may cause damage to
components of the instrument or some discomfort to the
user.
Electrostatic discharge precautions
When the controller is removed from its sleeve, some of the
exposed electronic components are vulnerable to damage by
electrostatic discharge from someone handling the
controller. To avoid this, before handling the unplugged
controller discharge yourself to ground.
Cleaning
Do not use water or water based products to clean labels or
they will become illegible. Isopropyl alcohol may be used to
clean labels. A mild soap solution may be used to clean
other exterior surfaces of the product.
3.1 Installation Safety Requirements
Safety Symbols
Various symbols may be used on the controller. They have
the following meaning:
Caution, (refer to
!
accompanying documents )
Equipm ent protect ed
throughout by DOU BLE
INSULATION
Helpful hints
Personnel
Installation must only be carried out by suitably qualified
personnel in accordance with the instructions in this
handbook.
Enclosure of Live Parts
To prevent hands or metal tools touching parts that may be
electrically live, the controller must be enclosed in an
enclosure.
Caution: Live sensors
The controller is designed to operate if the temperature
sensor is connected directly to an electrical heating element.
However you must ensure that service personnel do not
touch connections to these inputs while they are live. With a
live sensor, all cables, connectors and switches for
connecting the sensor must be mains rated.
Wiring
It is important to connect the controller in accordance with
the wiring data given in this guide. Take particular care not
to connect AC supplies to the low voltage sensor input or
other low level inputs and outputs. Only use copper
conductors for connections (except thermocouple inputs)
and ensure that the wiring of installations comply with all
local wiring regulations. For example in the UK use the
latest version of the IEE wiring regulations, (BS7671). In the
USA use NEC Class 1 wiring methods.
Power Isolation
The installation must include a power isolating switch or
circuit breaker. This device should be in close proximity to
the controller, within easy reach of the operator and marked
as the disconnecting device for the instrument.
Overcurrent protection
The power supply to the system should be fused
appropriately to protect the cabling to the units.
14
Series 3 Operations Manual
Voltage rating
The maximum continuous voltage applied between any of
the following terminals must not exceed 264Vac:
• relay output to logic, dc or sensor connections;
• any connection to ground.
The controller must not be wired to a three phase supply
with an unearthed star connection. Under fault conditions
such a supply could rise above 264Vac with respect to
ground and the product would not be safe.
Conductive pollution
Electrically conductive pollution must be excluded from the
cabinet in which the controller is mounted. For example,
carbon dust is a form of electrically conductive pollution. To
secure a suitable atmosphere in conditions of conductive
pollution, fit an air filter to the air intake of the cabinet.
Where condensation is likely, for example at low
temperatures, include a thermostatically controlled heater in
the cabinet.
This produ ct has been designed to conform to BS EN61010
installat ion category II, pol lution degree 2 . These are defined as
follows:
Installation Category II (CAT II)
The rated impulse voltage for equipment on nominal 230V supply
is 2500V.
Pollution Degree 2
Normally only non conductive pollution occurs. Occasionally,
independent temperature sensor, which will isolate the
heating circuit.
Please note that the alarm relays within the controller will
not give protection under all failure conditions.
Routing of wires
To minimise the pick-up of electrical noise, the low voltage
DC connections and the sensor input wiring should be routed
away from high-current power cables. Where it is
impractical to do this, use shielded cables with the shield
grounded at both ends. In general keep cable lengths to a
minimum.
however, a temporary conductivity caused by condensation shall
be expected.
Grounding of the temperature sensor shield
In some installations it is common practice to replace the
temperature sensor while the controller is still powered up.
Under these conditions, as additional protection against
electric shock, we recommend that the shield of the
temperature sensor is grounded. Do not rely on grounding
through the framework of the machine.
Over-temperature protection
When designing any control system it is essential to consider
what will happen if any part of the system should fail. In
temperature control applications the primary danger is that
the heating will remain constantly on. Apart from spoiling
the product, this could damage any process machinery being
controlled, or even cause a fire.
Reasons why the heating might remain constantly on
include:
• the temperature sensor becoming detached from the
process
• thermocouple wiring becoming short circuit;
• the controller failing with its heating output constantly
on
• an external valve or contactor sticking in the heating
condition
• the controller setpoint set too high.
Where damage or injury is possible, we recommend fitting a
separate over-temperature protection unit, with an
15
Operations Manual Series 3
4. Switch On
!
The way in which the controller starts up depends on factors
described below in sections 4.1, 4.2 and 4.3.
4.1 New Controller
If the controller is new AND has not previously been
configured it will start up showing the ‘Quick Configuration’
codes. This is a built in tool which enables you to configure
the input type and range, the output functions and the
display format.
Adjust these as follows:.
1. Press any button. The characters will change to ‘-‘, the
first one flashing.
or
2. Press
to change the flashing character to the
required code shown in the quick code tables – see
below. Note: An
xindicates that the option is not
fitted.
3. Press to scroll to the next character.
You cannot scroll to the next character until the current
character is configured.
Incorrect configuration can result in damage to the
process and/or personal injury and must be carried out by a
competent person authorised to do so. It is the
responsibility of the person commissioning the controller to
ensure the configuration is correct
To return to the first character press
4. When all five characters have been configured the
display will go to Set 2.
5. When the last digit has been entered press
4.1.1 Quick Start Code
The quick start code consists of two ‘SETS’ of
five characters. The upper section of the
display shows the set selected, the lower
section shows the five digits which make up
the set.
SET 1
Input ty pe Range Input/O utput 1 Output 2 Output 4
Thermocouple Full range X Unconfigured
B Ty pe B C
J Type J F
K Type K Centigra de J ON/OF F Heating [logic or relay (1)], or PI D 0-20mA heating
L Type L 0 0-100 K ON/OF F Cooling [logic or relay (1)], or P ID 0-20mA cooling
N Type N 1 0-200 Alarm (2): energised in alarm Alar m (2): de-energised in alarm
R Type R 2 0 -400 0 High alarm 5 High alarm Note (2)
S Type S 3 0-600 1 Low alarm 6 Low alarm
T T ype T 4 0-800 2 Deviation high 7 Dev iation high
C Custom 5 0-1000 3 Deviation low 8 Deviat ion low
RTD 6 0-1200 4 D eviation band 9 Deviat ion band
P Pt100 7 0-1400 DC Retransmission (no t O/P4)
Linear 8 0-1600 D 4-20mA Setpoint N 0-20mA Setpoint
M 0-80mV 9 0-1800 E 4-20mA Temperature Y 0-20m A Temperatu re
2 0-20mA Fahrenheit F 4-20mA output Z 0 -20mA output
Input CT Scaling Digital In put A Digita l Input B (2) Output 3 (2) Lo wer Display
Unconfigured
X
10 Amps
1
25 Amps
2
50 Amps
5
100 Amps
6
Note (1)
X
W Alarm acknowledg e H PI D heating or motor valve open (3) P Output
M M anual select C PID cooling or motor valve close (3) R Time remaining
R FEATURE UNAVAILABLE J ON/OFF heating (not show n if VC or VP) E Elapsed time
L Keylock K ON/OFF cooling (not shown if VC or VP) 1 Alarm setpoint
P Setpoint 2 select Alarm Outputs (1)A Load Amps
T FEATURE UNAVAILABLE Energised in alarm De-energised in alarm D D well/Ramp
OP1 = alarm 1 (I/O1)
OP2 = alarm 2
V Recipe 2 /1 select 1 Low alarm 6 Low alarm N None
OP3 = alarm 3
B Remote DOWN button 3 Dev L ow 8 Dev L ow Output meter (2)
OP4 = alarm 4 (AA)
Note (3)
VP, VC o nly
G FEATURE UNAVAILABLE 4 D ev Band 9 Dev Band M Setpoint with
I FEATURE UNAVAILABLE DC outputsAm meter (2)
Q St andby select H 4-20mA heating
C 4-20mA cooling
K 0-20mA cooling
Retransmission output
D 4-20 Setp oint
E 4-20 Measured Temperat ure
F 4-20mA output
N 0-20 Setpoint
Y 0-20 M easured Temp erature
Z 0-20mA output
4.2 To Re-Enter Quick Code mode
If you need to re-enter the ‘Quick Configuration’ mode this
can always be done as follows:
1. Power down the controller
Unconfigured
U Rem ote SP enable 0 High alarm 5 High alarm T ime/Target
A Remote UP button 2 Dev High 7 Dev High C Setpoint with
X Unconfigured T Setpoint (std)
J 0-20mA heating
4.3 Pre-Configured Controller or
Subsequent Starts
A brief start up sequence consists of a self test during which
the software version number is shown followed briefly by the
quick start codes.
2. Hold down the
controller again.
3. Keep the button pressed until code is displayed.
4. Enter the configuration code (this is defaulted to 4 in a
new controller)
5. The quick start codes may then be set as described
previously
Parameters may also be configured using a deeper level
of access. This is described in later chapters of this
handbook.
If the controller is started with the
down, as described above, and the quick start codes are
shown with dots (e.g. J.C.X.X.X), this indicates that the
controller has been re-configured in a deeper level of access
and, therefore, the quick start codes may not be valid. If the
quick start codes are accepted by scrolling to then
the quick start codes are reinstated.
button, and power up the
button held
It will then proceed to Operator Level 1..
You will see the display shown below. It is called the HOME
display.
If the quick start codes do not appear during this start up,
it means that the controller has been configured in a deeper
level of access, see the note in section 4.2. The quick start
codes may then not be valid and are therefore not shown.
17
Operations Manual Series 3
4.4 Front Panel Layout
ALM Alarm active (Red)
OP1 lit when output 1 is ON
OP2 lit when output 2 is ON
OP3 lit when output 3 is ON
OP4 lit when output 4 relay is ON
SPX Alternative setpoint in use (e.g. setpoint 2)
REM Remote digital setpoint. Also flashes when digital
communications active
MAN Manual mode selected
Operator Buttons:
Referred to as the ‘page’ button. From any view -
press to return to the HOME display
Referred to as the ‘scroll’ button. Press to select a new
parameter. If held down it will continuously scroll through
parameters.
Press
decrease a value
a value
Press
and Manual mode.
and(ACK) together to acknowledge an alarm.
Referred to as the ‘arrow down’ button. Press to
Referred to as the ‘arrow up’ button. Press to increase
and
(MODE) together to toggle between Auto
4.4.1 To Set The Target Temperature.
From the HOME display:
Press
Press
The new setpoint is entered when the button is released
and is indicated by a brief flash of display.
to raise the setpoint
to lower the setpoint
4.4.2 Alarms
Process alarms may be configured using the Quick Start
Codes. Each alarm can be configured for:
Full Scale Low The alarm is shown if the proces s value falls below a
set t hreshold
Full Scale High The alarm is shown if t he process value rises above a
set t hreshold
Deviation Low The alarm is shown if the process value deviates below
the setpoint by a set threshold
Deviation High The alarm is s hown if the process valu e deviates above
the setpoint by a set threshold
Deviation Band The alarm is s hown if the process value deviates abov e
or below t he setpoint by a set threshold
If an alarm is not configured it is not shown in the list of
level 2 parameters.
Additional alarm messages may be shown such as
CONTROL LOOP BROKEN. This occurs if the controller
does not detect a change in process value following a
From firmware version 2.11 two further alarm types
have been made available. These are:
Rising rat e of
change
Falling rat e of
change
These alarms cannot be configured by the Quick Start Code
– they can only be configured in Configuration Mode..
4.4.3 Alarm Indication
If an alarm occurs, the red ALM beacon will flash. A
scrolling text message will describe the source of the alarm.
Any output (usually a relay) attached to the alarm will
operate. An alarm relay can be configured using the Quick
Start Codes to be energised or de-energised in the alarm
condition. It is normal to configure the relay to be deenergised in alarm so that an alarm is indicated if power to
the controller fails.
An alarm will be det ected if the rat e of change
(unit s/minute) in a positive direct ion exceeds the alarm
threshold
An alarm will be det ected if the rat e of change
(units/m inute) in a negativ e direction exceeds the alarm
threshold
change in output demand after a suitable delay time.
Another alarm message may be INPUT SENSOR BROKEN
(SBr). This occurs if the sensor becomes open circuit; the
output level will adopt a ‘SAFE’ value which can be set up in
Operator Level 3..
Press
If the alarm is still present the ALM beacon will light
continuously otherwise it will go off.
The action which takes place depends on the type of alarm
and (ACK) together to acknowledge an alarm.
configured:
18
Series 3 Operations Manual
Non
latching
A non latching alarm will reset itself when
the alarm condition is removed. By default
alarms are configured as non-latching, deenergised in alarm.
Auto
Latching
An auto latching alarm requires
acknowledgement before it is reset. The
acknowledgement can occur BEFORE the
condition causing the alarm is removed.
Manual
Latching
The alarm continues to be active until both
the alarm condition is removed AND the
alarm is acknowledged. The
acknowledgement can only occur AFTER
the condition causing the alarm is
removed.
By default alarms are configured as non-latching, deenergised in alarm. To configure latched alarms, refer to
section 12.3.1.
19
Operations Manual Series 3
4.4.4 Auto, Manual and Off Mode
!
The controller can be put into Auto, Manual or Off mode –
see next section.
Auto mode is the normal operation where the output is
adjusted automatically by the controller in response to
changes in the measured temperature.
In Auto mode all the alarms and the special functions (auto
tuning, soft start) are operative
Manual mode means that the controller output power is
manually set by the operator. The input sensor is still
connected and reading the temperature but the control
loop is ‘open’.
In manual mode the MAN beacon will be lit, Band and
deviation alarm are masked
The power output can be continuously increased or
decreased using the
Manual mode must be used with care. The power
level must not be set and left at a value that can damage
the process or cause over-heating. The use of a separate
‘over-temperature’ controller is recommended.
Off mode means that the heating and cooling outputs are
turned off. The process alarm and analogue retransmission
outputs will, however, still be active while Band and
deviation alarm will be OFF.
or
buttons.
4.4.5 To Select Auto, Manual or Off Mode
Pressand hold
second.
This can only be accessed from the HOME display.
1. Auto’ is shown in the upper display.
After 5 seconds the lower display will
scroll the longer description of this
parameter. ie ’ loop mode – auto manual off’
2. Press
to select ‘OFF’. This is shown in the
upper display.
3. When the desired Mode is selected, do
not push any other button. After 2
seconds the controller will return to the
HOME display.
4. If OFF has been selected, OFF will be
shown in the lower display and the heating and cooling
outputs will be off
5. If manual mode has been selected, the MAN beacon
will light. The upper display shows the measured
temperature and the lower display the demanded
output power.
and
(Mode) together for more than 1
to select ‘mAn’. Press again
+
+
The transfer from Auto to manual mode is ‘bumpless’.
This means the output will remain at the current value
at the point of transfer. Similarly when transferring
from Manual to Auto mode, the current value will be
used. This will then slowly change to the value
demanded automatically by the controller.
6. To manually change the power output, press
to lower or raise the output. The output power is
continuously updated when these buttons are pressed
7. To return to Auto mode, press
Then press
to select ‘Auto’.
and
or
together.
20
Series 3 Operations Manual
4.4.6 Level 1 Operator Parameters
A minimal list of parameters are available in operator Level
1 which is designed for day to day operation. Access to
these parameters is not protected by a pass code.
Press to step through the list of parameters. The
4. Press
choose Lev 2 (Level 2)
5. After 2 seconds the
display will show
or
to
mnemonic of the parameter is shown in the lower display.
After five seconds a scrolling text description of the
parameter appears.
The value of the parameter is shown in the upper display.
Press
for 30 seconds the controller returns to the HOME display
or
to adjust this value. If no key is pressed
The parameters that appear depend upon the functions
configured. They are:
Parameter
Mnemonic
WRK.OP WORKING OU TPUT
WKG.SP WORKING
SP1 SETPOINT 1 Alterable
SP2 SETPOINT 2 Alterable
T.REMN TIME REM AINING
A1.xxx ALARM 1 SETPOINT Read only.
A2.xxx ALARM 2 SETPOINT
A3.xxx ALARM 3 SETPOINT
A4.xxx ALARM 3 SETPOINT
LD.AMP LOAD CURRENT Read only. On ly shown if CT
Scrolling Display
and Description
The active output
value
SETPOINT
The active setpoint
value.
Time to end of set
period
Alterability
Read only.
Appears when the controller
is in AUTO or OFF mode.
Read only.
Only shown when the
controller is in MAN or OFF
mode.
Read only
0:00 to 9 9.59 hh:mm or
mm:ss
Only shown if the alarm is
configured.
xxx = alarm type as follows:
HI = High alarm
LO = Low alarm
d.HI = Deviatio n high
d.LO = Deviation low
d.HI = Deviatio n high
rrc = Rising ra te of change
(unit s/minute)
Frc = Falling rate of chan ge
(unit s/minute)
is configured
6. Press
or
to enter the
pass code. Default = ‘2’
•If an incorrect code is entered the controller reverts to
Level 1.
5.2 To Return to Level 1
1. Press and hold
2. Press
to select LEv 1
The controller will return to the level 1 HOME display.
Note: A security code is not required when going from a
higher level to a lower level.
5.3 Level 2 Parameters
Press
mnemonic of the parameter is shown in the lower display.
After five seconds a scrolling text description of the
parameter appears.
The value of the parameter is shown in the upper display.
Press
for 30 seconds the controller returns to the HOME display
Backscroll is achieved when you are in this list by pressing
The following table shows a list of parameters available in
Level 2.
to step through the list of parameters. The
or
to adjust this value. If no key is pressed
while holding down .
5. Operator Level 2
Level 2 provides access to additional parameters. Access to
these is protected by a security code.
5.1 To Enter Level 2
1. From any display press and hold
2. After a few seconds the display will
show
3. Release
.
(If no button is pressed for about 45 seconds the display
returns to the HOME display)
21
.
Operations Manual Series 3
Mnemonic Scrolling Display and description Range
WKG.SP
WORKING SETPOINT is the active setpoint value and appears when the controller is
SP.HI to SP.LO
in Manual mode. It may be derived from SP1 o r SP2, or, if t he cont roller is ramp ing
(see SP.RAT), it is the current ramp value.
WRK.OP WORKING OUTPUT is the output from the controller expressed as a percentage of
full output. It ap pears when the controller is in Auto mode.
For a time proportioning output, 50% = relay or logic output on or off for equal
lengths of time.
For On/Off control: OFF = <1%. ON = >1 %
Read only value
0 to 100% for heatin g
0 to –100% for cooling
-100 (max c ooling) to 100% (max
heating
T.STAT FEATURE UNAVAILABLE Reset rES
Running run
Hold hoLd
End Timed out
UNITS DISPLAY UNITS Temperature display units. ‘Percentage’ is provided for linear
input s
O
C Degrees C
O
F Degrees F
O
k Degrees K
nonE
PErc
None
Percentage
SP.HI SETPOINT HIGH High set point limit applied to SP1 and SP2. Alterable between range limits
SP.LO SETPOINT LOW Low setpoint limit applied to SP1 and SP2
By default the remote setpoint is scaled between SP.HI and SP.LO. Two further parameters (REM.HI and REM.LO) are
available in access level 3 to limit the Remote SP range if req uired.
SP1 SETPOINT 1 allows control setpoint 1 value to be adjusted Alterable: SP.HI to SP.LO
SP2 SETPOINT 2 allows cont rol setpoint 2 value to be adjusted
Alterable: SP.HI to SP.LO
SP.RAT SETPOINT RATE LIMIT Rate of change of setpoint value. OFF to 3000 display units per
minute
The next section applies to the Timer only.
TM.CFG FEATURE UNAVAILABLEnone None
Dwel
DeLy
sfst
Dwell
Delayed switch on
Soft start
TM.RES FEATURE UNAVAILABLEHour
min
THRES FEATURE UNAVAILABLE
OFF or 1 to 3000
END.T FEATURE UNAVAILABLEOFF
Dwel
SP2
Hours
Minutes
Control OP goes to zero
Control continues at SP1
Go to SP2
SS.PWR FEATURE UNAVAILABLE-100 to 100%
SS.SP FEATURE UNAVAILABLE
DWELL FEATURE UNAVAILABLE
T.REMN FEATURE UNAVAILABLE
Between SP.HI and SP.LO
0:00 to 9 9.59 hh :mm: or mm:ss
0:00 to 99.59 hh:mm: or mm:ss
The following parameters are available when the timer is configured as a programmer.
SERVO FEATURE UNAVAILABLESP
PV
SP.rb
PV.rb
Setpoint
Process variable
Ramp back to SP
Ramp back to PV
TSP.1 TARGET SETPOINT 1. To set the target value for the first setpoint
RMP.1 FEAT URE UNAVAILABLEOFF, 0:01 to 3000 units per min or
hour as set by
TM.RES
22
Series 3 Operations Manual
!
Mnemonic Scrolling Display and description Range
DWEL.1 FEATURE UNAVAILABLE OFF, 0:01 to 99:59 hh:mm or
The above three parameters are repeated for the next three program segments, i.e. TSP.2 (3 & 4), RMP.2 (3 & 4), DWEL.2 (3 & 4)
This section applies to Alarms only If an alarm is not configured the parameters do not appear
A1.--- - to A4.-
--
A.TUNE AUTOTUNE automatically sets the control parameters to match the process
PB PROPORTIONAL BAND sets an output which is proportional to the size of the error
TI INTEGRAL TIME removes steady state control offsets by ramping the output up or
TD DERIVATIVE TIME determines how strongly the controller will reac t to the rate of
MR MANUAL RESET applies to a PD on ly controller i.e. the integral term is turned off.
R2G RELATIVE COOL GAIN adjusts the cooling proportional band relative to the heating
HYST.H HEATING HYSTERESIS Sets the difference in temperature units between heating
HYST.C COOLING HYSTERESIS Sets the difference in temperature units between cooling
D.BAND CHANNEL 2 DEADBAND adjusts a zone between heating and cooling outputs when
OP.HI OUTPUT HIGH limits the maximum heating power applied to the process or a
1. (2, 3 or 4)
PLS.
LD.AMP LOAD CURRENT is the measured load current when the power demand is on CT Range
LK.AMP LEAK CURRENT is the measured leakage current when the power demand is off.
LD.ALM LOAD CURRENT THRESHOLD Sets a low alarm on the load current measured by
LK.ALM LEAK CURRENT THRESHOLD sets a high alarm on the leakage current measured by
HC.ALM OVERCURRENT THRESHOLD Sets a high alarm on the load current measured by
ADDR ADDRESS - communications address of the controller. 1 to 254
HOME HOME DISPLAY Defines the parameter which appears in the lower section of the STDStandard
ALARM 1 (2, 3 or 4) SETPOINT sets the threshold value at which an alarm occurs.
Up to four alarms are available and are only shown if configured.
The last three characters in the mnemonic specify the alarm type:
Lo Full Scale Low Hi Full Scale High
dHi Deviation H igh dLo Deviation Low Bnd Deviation Band
rrc Rising rate of
change
This section applies to control the parameters. A further description of theses parameters is given in section 11
characteristics.
signal. Units may be % or display units.
down in proportion to the amplitude and duration of the error signal.
change in the process value. It is used to prevent overshoot and undershoot and to
restore the PV rapidly if there is a sudden change in demand.
Set this to a value of power output (from +100% heat, to -100% cool which removes
any steady state error between SP and PV.
proportional band. Particularly necessary if the rate of heating and rate of cooling are
very different. (Heat/Cool only)
turning off and turning on when ON’OFF control is used. Only appears if channel 1(heating) control action is On/Off
turning off and turning on when ON/OFF control is used. Only appears if channel 2 (cooling) control action is On/Off
neither output is on. Off = no deadband. 100 = heating and cooling off.
Only appears if On/Off control configured.
minimum cooling output.
OUTPUT 1 (2, 3 or 4) MINIMUM PULSE TIME Sets the minimum on an d off time for
the control output.
Ensure this parameter is set to a value that is suitable for the output
switching device in use. For example, if a logic output is used to switch a small
relay, set the value to 5.0 seconds or greater to prevent damage to the device due
to rapid switching.
This section applies to current transformer input only. The CT option is not available on the Series 3.
the CT. Used to detect partial load failure.
the CT.
the CT
Frc Falling rate of
change
mm:ss as set by
SP.HI to SP.LO
1 to 9999 units/minute
Off
On
1 to 9999 display units
Default 20
Off to 9999 seconds
Default 36 0
Off to 9999 seconds
Default 60 for PID control
Default 0 for VP control
-100 to 100%
Default 0
0.1 to 10. 0
Default 1. 0
0.1 to 200.0 d isplay units
0.2 D efault 1.0
0.1 to 200.0 d isplay units
Default 1. 0
OFF or 0.1 to 100.0% of the
cooling proportional band
+100% to OP.LO
Relay outputs 0.1 to 150.0 seconds
– default 5.0.
Logic outputs Auto to 150.0 -
Default
CT Range
CT Range
CT Range
CT Range
1 to 25 4
TM.RES
Disable
Enable
Auto = 55ms
23
Operations Manual Series 3
Mnemonic Scrolling Display and description Range
HOME display .
ID CUSTOMER ID Sets a number from 0 to 9999 used as a custom defined identification
number for th e contro ller.
REC.NO FE ATURE UNAVAILABLEnone or 1 to 5 or
STORE FEATURE UNAVAILABLEnone or 1 to 5
OP Output power
Tr Time remaining
ELAP Time elapsed
AL First alarm setpoint
CT Load c urrent
CLr Clear (blank)
TMr Combined setpoint and
time display
0 to 9999
FaiL if no recipe set stored
done when stored
Press
at any time to return immediately to the HOME screen at the top of the list.
Hold down to continuously scroll through the above list
24
Series 3 Operations Manual
6. Access to Further Parameters
Parameters are available under different levels of security
and are defined as Level 1 (Lev1), Level 2 (Lev2), Level 3
(Lev 3) and Configuration (Conf).
Level 1 has no passcode since it contains a minimal set of
parameters generally sufficient to run the process on a daily
basis.
Level 2 allows access to parameters which may used in
commissioning a controller or settings between different
products or batches.
Level 1 and Level 2 operation has been described in the
previous sections.
Level 3 and Configuration level parameters are also
available as follows:
6.1.1 Level 3
Level 3 makes all operating parameters available and
alterable (if not read only). It is typically used when
commissioning a controller.
Examples of parameters available in Level 3 are:
Range limits, setting alarm levels, communications
address.
The instrument will continue to control when in Levels 1, 2
or 3.
6.1.2 Configuration Level
This level makes available all parameters including the
operation parameters so that there is no need to switch
between configuration and operation levels during
commissioning. It is designed for those who may wish to
change the fundamental characteristics of the instrument
to match the process.
Examples of parameters available in Configuration level
are:
Configuration level gives access to a wide range of
parameters which match the controller to the process.
Incorrect configuration could result in damage to the
process being controlled and/or personal injury. It is the
responsibility of the person commissioning the process
to ensure that the configuration is correct.
In configuration level the controller is not controlling the
process or providing alarm indication. Do not select
configuration level on a live process.
Operating
Level
Level 1
Level 2
Level 3
Conf
Home
List
Full
Operator
Yes
Yes
Configuration Control
Yes
No
25
Operations Manual Series 3
6.1.3 To Select Access Level 3 or Configuration Level
Lev 3
goto
0
CODE
3
code
Conf
goto
0
CODE
4
code
Conf
Conf
goto
Lev1
goto
controller will then go through its start up sequence, starting in the
Do This The Displa y You Shoul d See Additional Notes
1. F rom any display press and hold
for more than 5 seconds
2. Press
passcode for L evel 3
or
to ent er the
3. W hen the LEV3GOTO view is shown,
as in paragraph 1 above, press
select ‘Conf’
4. Press
passcode for Configurat ion level
or
to ent er the
to
To Select Level 3
To Select Configuration level
The display will pass from the current operating level, for ex ample,
Lev 1 to Lev 3 as the button is held down.
(If no button is then pressed for about 50 seconds the display
returns to the HOME display)
The default code is 3 :
If an in correct code is entered the display revert s to ‘goto’.
The cont roller is now in t he level 3 will then revert to the HOME
display
Note:
the code for level 3
The default co de is 4:
If an in correct code is entered the display revert s to ‘goto’.
The cont roller is now in Configurat ion level will now show Conf
mus t be pressed quickly before t he controller requ ests
To Retur n to a Lower Level
5. Press and hold
seconds
6. Press
eg LEV 1
for more t han 3
to s elect the required level
A special case exists if a security code has been
configured as ‘0’. If this has been done it is not necessary to
enter a code and the controller will enter the chosen level
immediately.
When the controller is in configuration level the
ACCESS list header can be selected from any view by
holding down the
Then press
button for more than 3 seconds.
again to select ‘ACCES’
The choices are:
LEV 1 L evel 1
LEV 2 L evel 2
LEV 3 L evel 3
ConF Configuratio n
It is not necess ary to enter a code when going f rom a higher level
to a low er level.
Alternatively, press
then press
The display will t hen flash ‘ConF’ for a few seconds and the
level select ed.
Do not power down w hile Conf is flashing. If a power down does
occur an error message w ill appear – see ‘Diagnostic Alarms’
and scroll to the Acces list header,
to s elect the required level.
26
Series 3 Operations Manual
6.2 Parameter lists
Parameters are organised in lists. The top of the list shows
the list header only. The name of the list header describes
the generic function of the parameters within the list. For
example, the list header ‘ALARM’ contains parameters
which enable you to set up alarm conditions.
6.2.1 To Choose Parameter List Headers
Press
this key is pressed.
The name of the list header appears in the lower display,
followed, after a few seconds, by a scrolling longer
description of the name.
The following example shows how to select the first two list
headers.
6.2.2 To Locate a Parameter
Choose the appropriate list, then press . Each parameter
in the list is selected in turn each time this button is
pressed. The following example shows how to select the
first two parameters in the ALARM List. All parameters in
all lists follow the same procedure.
. Each list header is selected in turn every time
Scrolling parameter name
Configu ration IO- 1 LIST
PROCESS
INPUT LIST
Keep pres sing to select further lis t headers
The list is continuous
Alarm List Header
Parameter ‘Value’. In this case set to
Full Scale High Alarm
Parameter mnemonic ‘a1.typ’
followed by a scrolling message
‘alarm1 type’
Parameter ‘Value’. In this case an
’numerical’ value, set to ‘112’
Parameter mnemonic ‘a1.HI’ followed
by a scrolling message ‘alarm 1 setpoint’
Press
to jump back to the list
header
6.2.3 How Parameters are Displayed
As shown above. whenever a parameter is selected it is
displayed as a mnemonic, of four or five characters, for
example ‘A1.TYP’.
After a few seconds this display is replaced by a scrolling
banner which gives a more detailed description of the
parameter. In this example ‘A1.TYP’ = ‘alarm 1 type’. The
scrolling banner is only shown once after the parameter is
first accessed.
The name of the list header is also displayed in this way.
The upper part of the display shows the value of the
parameter.
The lower part shows its mnemonic followed by the
scrolling name of the parameter
6.2.4 To Change a Parameter Value
With the parameter selected, press
value, press
to decrease the value. If either key is held
down the analogue value changes at an increasing rate.
The new value is entered after the key is released and is
indicated by the display blinking. The exception to this is
output ‘Power’ when in manual. In this case the value is
entered continuously.
The upper display shows the parameter value the lower
display shows the parameter name.
to increase the
6.2.5 To Return to the HOME Display
Press
On release of the keys the display returns to the HOME list.
The current operating level remains unchanged.
+
.
6.2.6 Time Out
A time out applies to the ‘Go To’ and ‘Control Mode’
parameters. If no key presses are detected within a period
of 5 seconds the display will revert back to the HOME list.
Press and hold to scroll parameters forward through
the list. With depressed, press
backward.
to scroll parameters
27
Operations Manual Series 3
6.3 Navigation Diagram
The diagram below shows the all list headings available in configuration level for Series 3 controllers.
The parameters in a list are shown in tables in the following sections of this manual together with explanations of their meanings
and possible use.
Paramet ers see
For Series 3 controllers additional lists are available, for example Output 3 and Digital Input B
Configu ration
Level 2
Paramet ers
Section 5.3
Access
Paramet ers see
Section 6.4
PROCESS
INPUT
Calibration
Section 16
LIST
Sensor Input
Paramet ers see
Section 8
Commu nications
Paramet ers see
IO1 LIST Output 2 List AA Relay List Logic Input a
Output 1 or
Input 1
Paramet ers see
Section 9
Paramet ers see
Section 15
Paramet ers see
Recipe
Section 14
Output 2
Section 9
AA Relay
(Output 4)
Paramet ers see
Section 9
Timer
Paramet ers see
Section 13
Digital Input
Paramet ers see
Section 9
Alarm
Paramet ers see
Section 12
List
Cont rol List Recipe List Comms List Timer List Alarms List Setpoint List Calibration List Access List
Control
Paramet ers see
Section 11
current
transformer List
CT Input
Paramet ers
Not Supported
Setpoint
Paramet ers see
Section 10
28
Loading...
+ 64 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.