Super Systems 3L User Manual

Operations Manual Series 3L
Series 3L Limit Alarm
OPERATIONS MANUAL
P/N 31334
Super Systems Inc.
7205 Edington Drive
Cincinnati, OH 45249
Ph : 513-772-0060, 800-666-4330
Fax: 513-772-9466
www.supersystems.com
Series 3L Process Indicators and Alarm Units
Operations Manual Series 3L
2
Contents
1. Installation and Basic Operation ............................................................................................ 4
1.1 Unpacking Your Indicator ...................................................................................................................... 4
1.2 Dimensions Front Views ....................................................................................................................... 4
1.3 Dimensions – Side Views ....................................................................................................................... 4
1.4 Step 1: Installation ................................................................................................................................. 5
1.4.1 Panel Mounting the Indicator ....................................................................................................................................... 5
1.4.2 Panel Cut-out Sizes ..................................................................................................................................................... 5
1.4.3 Recommended Minimum Spacing of Indicators........................................................................................................... 5
1.4.4 To Remove the Indicator from its Sleeve ..................................................................................................................... 5
1.5 Step 2: Wiring ......................................................................................................................................... 6
1.6 Terminal Layout Series 3L Indicators ................................................................................................... 6
1.7 Wire Sizes ................................................................................................................................................ 7
1.8 Sensor Input (Measuring Input) ............................................................................................................. 7
1.9 Outputs .................................................................................................................................................... 7
1.9.1 Output 1 & Output 3 ..................................................................................................................................................... 7
1.9.2 AA Relay Form C (FM Approved) ................................................................................................................................ 7
1.9.3 Transmitter Supply ....................................................................................................................................................... 7
1.9.4 Digital Inputs A and B ................................................................................................................................................... 8
1.10 Indicator Power Supply .......................................................................................................................... 8
1.11 Digital Communications (Optional) ....................................................................................................... 8
2. Safety and EMC Information ................................................................................................... 9
2.1 Installation Safety Requirements .......................................................................................................... 9
3. Switch On .................................................................................................................................. 11
3.1 New Indicator .......................................................................................................................................... 11
3.1.1 To Re-Enter Quick Code Mode .................................................................................................................................. 13
3.2 Pre-Configured Indicator or Subsequent Starts ................................................................................... 13
3.3 Front panel layout ................................................................................................................................... 13
3.3.1 Alarm Indication ......................................................................................................................................................... 14
3.3.2 Out of Range Indication ............................................................................................................................................. 14
3.3.3 Sensor Break Indication ............................................................................................................................................. 14
3.4 Operator Parameters in Level 1 ............................................................................................................. 14
4. Operator Level 2 ....................................................................................................................... 15
4.1 To Enter Level 2 ...................................................................................................................................... 15
4.1.1 To Return to Level 1 ................................................................................................................................................... 15
4.2 Level 2 Parameters ................................................................................................................................. 15
4.3 FM and Alarm Units ................................................................................................................................ 17
4.4 Recipes .................................................................................................................................................... 17
5. Access to Further Parameters ................................................................................................ 18
5.1 Level 3 ...................................................................................................................................................... 18
5.2 Configuration Level ................................................................................................................................ 18
5.2.1 To Select Access Level 3 or Configuration Level ...................................................................................................... 19
5.3 Parameter lists ........................................................................................................................................ 20
5.3.1 To Choose Parameter List Headers........................................................................................................................... 20
5.3.2 To Locate a Parameter .............................................................................................................................................. 20
5.3.3 How Parameters are Displayed ................................................................................................................................. 20
5.3.4 To Change a Parameter Value .................................................................................................................................. 20
5.3.5 To Return to the HOME Display ................................................................................................................................. 20
5.3.6 Time Out .................................................................................................................................................................... 20
5.4 Navigation Diagram ................................................................................................................................ 21
5.5 Access Parameters ................................................................................................................................. 22
6. Process Input ............................................................................................................................ 23
6.1 Process Input Parameters ...................................................................................................................... 23
6.1.1 Input Types and Ranges ............................................................................................................................................ 24
6.1.2 Units ........................................................................................................................................................................... 24
6.1.3 PV Offset .................................................................................................................................................................... 25
6.1.4 PV Input Scaling ......................................................................................................................................................... 25
7. Input/Output Channels ............................................................................................................. 26
7.1 Output Channel 1 (OP-1) – Series 3L Indicators .................................................................................. 26
7.1.1 Sense ......................................................................................................................................................................... 27
7.1.2 Source ........................................................................................................................................................................ 27
7.1.3 Power Fail .................................................................................................................................................................. 27
7.1.4 Example: To Configure OP-1 Relay to Operate on Alarms 1 and 2:- ....................................................................... 27
7.2 Output Channel 3 (OP-3) – Series 3L Indicators .................................................................................. 28
7.2.1 Sense ......................................................................................................................................................................... 29
Operations Manual Series 3L
3
7.2.2 Source ......................................................................................................................................................................... 29
7.2.3 Power Fail ................................................................................................................................................................... 29
7.2.4 Example: To Configure OP-3 Relay to Operate on Alarms 1 and 2:- ........................................................................ 29
7.3 AA Relay Channel (AA) (Output 4 FM Relay) ........................................................................................ 30
8. Digital Inputs ............................................................................................................................. 31
8.1 Digital Input Parameters ........................................................................................................................ 31
9. Alarms ........................................................................................................................................ 32
9.1 Types of Alarm ........................................................................................................................................ 32
9.1.1 Alarm Relay Output..................................................................................................................................................... 33
9.1.2 Alarm Indication .......................................................................................................................................................... 33
9.1.3 To Acknowledge An Alarm ......................................................................................................................................... 33
9.2 Behavior of Alar ms After a Pow er C ycle .............................................................................................. 34
9.2.1 Example 1 ................................................................................................................................................................... 34
9.2.2 Example 2 ................................................................................................................................................................... 34
9.2.3 Example 3 ................................................................................................................................................................... 34
9.3 Alarm Parameters ................................................................................................................................... 35
9.3.1 Example: To Configure Alarm 1 ................................................................................................................................. 36
9.4 Diagnostic Alarms .................................................................................................................................. 37
10. Recipe ........................................................................................................................................ 38
11. Digital Communications .......................................................................................................... 39
11.1 Digital Communications Wiring ............................................................................................................. 39
11.1.1 EIA 485 .................................................................................................................................................................. 39
11.2 Digital Commu nications Parameters .................................................................................................... 40
11.2.1 Broadcast Communications ................................................................................................................................... 41
11.2.2 Broadcast Master Communications ....................................................................................................................... 41
11.2.3 Wiring Connections ................................................................................................................................................ 41
11.3 Example: To Set Up Instrument Address ............................................................................................. 42
11.4 DATA ENCODING ................................................................................................................................... 42
11.5 Parameter Modbus Addresses .............................................................................................................. 43
12. Calibration ................................................................................................................................. 46
12.1 To Check Input Calibration .................................................................................................................... 46
12.1.1 Precautions ............................................................................................................................................................ 46
12.1.2 To Check mV Input Calibration .............................................................................................................................. 46
12.1.3 To Check Thermocouple Input Calibration ............................................................................................................ 46
12.1.4 To Check RTD Input Calibration ............................................................................................................................ 47
12.2 Offsets ..................................................................................................................................................... 47
12.2.1 Five Point Offset .................................................................................................................................................... 47
12.3 Input Calibration ..................................................................................................................................... 48
12.3.1 To Calibrate mV Range ......................................................................................................................................... 48
12.3.2 To Calibrate Thermocouple Ranges ...................................................................................................................... 48
12.3.3 To Calibrate RTD Ranges...................................................................................................................................... 49
12.4 Calibration P ar ameters .......................................................................................................................... 50
13. TECHNICAL SPECIFICATION .................................................................................................. 51
14. Parameter Index ........................................................................................................................ 53
15. Revision History ....................................................................................................................... 54
Operations Manual Series 3L
4

1. Installation and Basic Operation

Thank you for choosing this Series 3L Process Indicator.
This unit comes in a single 1/4DIN size with three relay outputs.
Relay outputs can be configured for al ar m and events. 2-wire Modbus digital communications are available in this unit.
The indicator may have been ordered to a hardware code only or pre-configured using an opt ional ‘Quick Start’ code. The label fitted to the side of the sleeve shows the ordering code of the indicator. If the Quick Code shows ***** the indicator will need to be configured when it is first switched o n.

1.1 Unpacking Your Indicator

The following items are included in the box:
Indicator mounted in its sleeve
Two panel retaining clips
AN IP65 sealing gasket mounted on the sleeve
Component packet containing a s nubber for each
relay output and a 2.49resistor for current inputs (see section 2)

1.2 Dimensions Front Views

1.3 Dimensions – Side Views

Series 3L Indicators
5

1.4 Step 1: Installation

10mm (0.4 inch)
This indicator is intended for permanent installation, for indoor use only, and enclosed in an elect r i c al panel
Select a location which is subject to minimum vibrations, the ambient temperatur e is within 0 and
C (32 - 131oF) and humidity 5 to 95% RH non
55 condensing.
The indicator can be mounted on a panel up to 15mm thick
To ensure IP65 and NEMA 4 front sealing a gainst dust and water, mount on a non-textured surface.
Please read the safety information in section 2 before proceeding.

1.4.1 Panel Mounting the Indicator

1. Prepare a cut-out in the mo unting panel to the size shown. If a number of instruments are t o be mounted in the same panel, observe the minimum spacing shown.
2. Fit the IP65 sealing gasket behind the front bezel of the indicator.
3. Insert the indicator through the cut-out.
4. Spring the panel retaining clips into place. Secure the indicator in position by holdin g i t level and pushing both retaining clips forward.
5. Peel off the protective cover from the display

1.4.2 Panel Cut-out Sizes

1.4.3 Recommended Minimum Spacing of Indicators

Applies to all Model sizes
38mm (1.5 inch)
(Not to scale)

1.4.4 To Remove the Indicator from its Sl eeve

The indicator can be unplugged from its sleeve by easing the latching ears outwards and pulling it forward out of the sleeve. When plugging it back i nto its sleeve, ensure that the latching ears click back into place to maintain the IP65 sealing.
Operations Manual Series 3L
6

1.5 Step 2: Wiring

!
1A
1B
LB
LC
3A
3B
3C
3D
L
N
AA
AB
AC
HD
HE
HF
CT
C
LA
VI
V+
V-
Series 3L
+ 24V _
COM
A(+)
B(-)
Output 1 (OP1)
Digital Input B
Output 3 (OP3)
24V Transmitter Supply
Line Supply
100 to 230Vac ±15% 48 to 62 Hz
+
-
AA Relay (OP4) FM RElay
Digital Communications EIA 485
Digital Input A
2.49
+
-
+
-
100K
806
+
-
10V Input
T/C Pt100 mA mV Vots
Sensor Input
Key to Symbols used in the wiring diagrams
Relay Output
Contact Input

1.6 Terminal Layout Series 3L Indicators

Ensure that you have the correct supply for your indicator. Check order code of the indicator supplied
Series 3L Indicators
7

1.7 Wire Sizes

100K
+
V+
+
-
3C
VI
V+
2.49
-
V+
OP4
AA
OP1
OP3
1A
3A
The screw terminals accept wire siz es from 0.5 to 1.5 mm (16 to 22AWG). Hinged covers prevent hands or metal making accidental contac t with live wires. The rear terminal screws should be tight ened to 0.4Nm (3.5 in-lbs).

1.8 Sensor Input (Measuring Input)

Do not run input wires with power cables
When shielded cable is used, it should be
grounded at one point only
Any external components (such as zener barriers)
connected between sensor and input terminals may cause errors in measurement due to excessive and/or un-balanced line r esistance, or leakage currents.
Not isolated from the logic outputs & digital inputs
Thermocouple Input
+
Positive
V-
-
Negative
Use the correct compensating cable, preferably
shielded.
It is not recommended to connect two or more
instruments to one thermocouple.
RTD Input
V+
V-
The resistance of the three wires mus t be the
PRT PRT Lead compensation
same. The line resistance may cause err ors if it exceeds 22Ω.
Linear mA, or mV Inputs
+
V-
Positive Negative
For a mA input, connect the 2.49 bur den resistor
supplied between the V+ and V- ter m i nals as shown. For mV, omit this resistor.
Linear Voltage Inputs
An external potential
0-10V
V-
806
Input
-
Sensor break alarm does not operate if this adaptor is fitted.
divider is required for the Series 3L

1.9 Outputs

The indicators are supplied as standard with two changeover relay outputs as follows:.

1.9.1 Output 1 & Output 3

Relay (Form A)
1B
3B
Isolated output 300Vac CATII
Contact rating:: 2A 264Vac resis tive
Output functions: Alarm/Event
* General Notes about Relays and Inductive Loads
High voltage transients may occur when switching inductive loads such as some contact ors or solenoid valves. Through the internal contact s , these transients may introduce disturbances which could affect the performance of the instrument.
For this type of load it is recommended that a ‘snubber’ be connected across the normally open contact of the relay switching the load. The snub ber recommended consists of a series connected resistor/capacitor (typically 15nF/100). A snubber will also prolong the life of the relay contacts.
A snubber should also be connected acr oss the output terminal of a triac output to prevent f alse triggering under line transient conditions.
WARNING
When the relay contact is open, or it is connected to a high impedance load, it passes a current (typically 0.6mA at 110Vac and 1.2mA at 230Vac). You must ensure that this current will not hold on low power electrical loads. If the load is of this type, the snubber should not be connected.

1.9.2 AA Rela y Form C (FM Approved)

o Isolated output 300Vac CATII o Software configurable: 0-20mA or 4-
20mA plus 0-5V, 0-10V, 1-5V and 2-
AB
AC

1.9.3 Transmitter Supply

A fixed 24Vdc supply is available to power an external transducer
Isolated output 300Vac CATII
3D
10V.
o Max load resistance: 500 o Calibr ation accuracy: +(<0.25% of
reading + <50µA
Operations Manual Series 3L
8

1.9.4 Digital Inputs A and B

Dig In A
LA
Dig In B
LB
* EIA232/ EIA485 2-
Com
Twisted pairs
Tx Rx Com
Rx Tx Com
Screen
RxB/
RxA/
*
HD Common
Line
L
C
LC
Not isolated from the sensor input
Switching: 12Vdc at 40mA max
Contact open > 500Ω. Contact closed < 200Ω
Input functions: Please refer to the l ist in the quick
codes.

1.10 Indicator Power Supply

1. Before connecting the indicator to the power line, make sure that the line voltage corresponds to the description on the identification label.
2. Use copper conductors only.
3. The power supply input is not fuse pr otected. This should be provided externally.
4. For 24V, the polarity is not important.
N
High voltage supply: 100 to 230Vac, +15%,
Recommended external fuse ratings are as
Neutral
48 to 62 Hz
follows:
For 100 - 230Vac, fuse type: T rated 2A 250V.

1.11 Digital Communications (Optional)

Digital communications uses the Modbus protocol. The interface is EIA485 (2-wire).
Isolated 300Vac CATII.
EIA 485 Connections
TxB
220 termination
resistor
TxA
wire communications converter eg Type KD485
220 termination resistor on last instrument in the line
Daisy Chain to further instruments
HE Rx HF Tx
Series 3L Indicators
9

2. Safety and EMC Information

!
Caution (refer to accompanying documents)
This indicator is intended for industrial temperature and process applications when it will m eet the requirements of the European Direct ives on Safety and EMC. Use in other applications, or failure to observe the installation instructions of this handbook, may impair safety or EMC. The installer must ensure the safety and EMC of any particular installation.
Safety
This indicator complies with the E uropean Low Voltage Directive 2006/95/EC, by the application of the safety standard EN 61010.
Electromagnetic compatibility
This indicator conforms with the es s ential protection requirements of the EMC Directive 2004/108/EC by the application of a Technical Constr uction File. This instrument satisfies the general requirements of the industrial environment defined in EN 61326. For more information on product compliance, refer to the Technical Construction File.
GENERAL
The information contained in this manual is subject to change without notice. While every effor t has been made to ensure the accuracy of the information, your supplier shall not be held liable f or errors contained herein.
Unpacking and storage
The packaging should contain an inst rument mounted in its sleeve, two mounting brackets for panel installation and an Installation & Operating guide. Certain ranges are supplied with an input adapter.
If on receipt, the packaging or the instrument is damaged, do not install the product but c ontact your supplier. If the instrument is to be stor ed before use, protect from humidity and dust in an ambient temperature range of -10OC to +70OC.
Service and repair
This indicator has no user serviceable parts. Contact your supplier for repair.
Caution: Charged capacitors
Before removing an instrument f rom its sleeve, disconnect the supply and wait at least two minutes to allow capacitors to discharge. I t may be convenient to partially withdraw the instrument from the sleeve, then pause before completing the removal. In any case, avoid touching the exposed elect r oni c s of an instrument when withdrawing it from the sleeve.
Failure to observe these precautions m ay cause damage to components of the instrume nt or some discomfort to the user.
Electrostatic discharge precautions
When the indicator is removed from it s sleeve, some of the exposed electronic components are vulnerable to damage by electrostatic discharge from someone handling the indicator. To avoid this, before handling the unplugged indicator, disch ar ge yourself to a ground.
Cleaning
Do not use water or water based products to clean labels, or they will become illegible. Isopropyl alcohol may be used to clean labels. A mild soap solution may be used to clean other exterior surfaces of the product.

2.1 Installation Safety Requirements

Safety Symbols
Various symbols may be used on the in dicator. They have the following meaning:
Equipment protected throughout by DOUBLE INSULATION
Helpful hints
Personnel
Installation must only be carried out by suitably qualified personnel in accordance with the instructions in this handbook.
Enclosure of Live Parts
To prevent hands or metal tools from touc hi ng parts that may be electrically live, the indicator must be enclosed in an enclosure.
Caution: Live sensors
The indicator is designed to operate if the temperature sensor is connected directly to an el ec trical heating element. However, you must ensure that service personnel do not touch connections t o these inputs while they are live. With a live sensor, al l cables, connectors and switches for connec ting the sensor must be mains rated for use in 230Vac +15% CATII.
Wiring
It is important to connect the indicator in accordance with the wiring data given in this guide. Take particular care not to connect AC supplies to the low voltage sensor input or other low level inputs and outputs. Only use copper conductors for conn ec tions (except thermocouple inputs) and ensure that the wiring of installations comply with all local wiring regulations. For example, in the USA, use NEC Class 1 wi ring methods. In the UK, use the latest vers ion of the IEE wiring regulations (BS7671).
Power Isolation
The installation must include a power isolating switch or circuit breaker. This device should be in close proximity to the indicator, within easy reach of the operator and marked as the disconnecting device for the instrument.
Overcurrent protection
The power supply to the system should be f used appropriately to protect the cabli ng to the units.
Operations Manual Series 3L
10
Voltage rating
The maximum continuous voltage applied between any of the following terminals must not exceed 230Vac:
relay output to logic, dc or sensor connections;
any connection to ground.
The indicator must not be wired to a three phase supply with an unearthed star connec tion. Under fault conditions, such a supply could ri s e above 240Vac with respect to ground, and the produc t would not be safe.
Conductive pollution
Electrically conductive pollut ion must be excluded from the cabinet in which the indicator is mount ed. For example, carbon dust is a form of elect rically conductive pollution. To secure a suitable atmosphere in conditions of conductive pollution, fit an air filter to the air intake of the cabinet. Where con densation is likely—for example, at low temperatures—include a thermostatically controlled heater in the cabinet.
This product has been designed to conform to BSEN61010 installation category II, pollution degree 2. These are defined as follows:
Installation Category II (CAT II)
For equipment on nominal 230V supply, the maximum rated impulse voltage is 2500V.
Pollution Degree 2
Normally only non-conductive pollution occurs. Occasionally, however, a temporary conductivity caused by condensation shall be expected.
Grounding of the temperature sensor shield
In some installations, it is common practice to replace the temperature sensor while the indicator is still powered up. Under these conditions, as additional protection against electric shoc k, we recommend that the shield of the temperature sensor be grounded. Do not rely on grounding through the f ramework of the machine.
Over-temperature protection
When designing any control system, it is essential to consider what will happen if any part of the system should fail. In temperature control applications, the primary danger is that the heating will remain constantly on. Apart from spoiling the product, this could damage any process machinery being controlled, or even cause a fire.
Reasons why the heating might remain c onstantly on include:
the temperature sensor becoming detac hed from
the process
thermocouple wiring becoming short circuit
the controller failing with its heating output
constantly on
an external valve or contactor sticking in the
heating condition
the controller setpoint being set too high.
Where damage or injury is possible, we recommend fitting a separate over-temperature protection unit, with an independent temperature sensor , which will isolate the heating circuit.
This indicator can be used in addition t o a controller as an over-temperature device. It is recommended that the relay used to indicate the alarm condition should be set to high alarm configured with sensor break and inverse ‘Inv’ operation so that it relax es to the alarm condition when power is removed.
Installation requirements for EMC
To ensure compliance with the Europea n E MC directive certain installation precautions are necessary as follows:
When using relay outputs it may be necessary to fit a filter suitable for suppressing the emissions. The filter requirements will depend on the type of load.
If the unit is used in table top equipment which is plugged into a standard power socket, then it is likely that compliance to the commerc i al and light industrial emissions standard i s required. In this case to meet the conducted emissions requirement, a suitable mains filter should be installed.
Routing of wires
To minimize the pick-up of electrical noise, the low voltage DC connections and the sensor input wiring should be routed away from high-current power cables. Where it is impractical to do this, us e s hi elded cables with the shield grounded at both ends. In general, keep cable lengths to a minimum.
Series 3L Indicators
11

3. Switch On

!
K C H C 0
o
(1)
(1)
(1)
(1) Up to 2 decimal places on Series 3L

3.1 New Indicator

If the indicator is new and has not previously been configured, or following a ‘Cold Start’ (section 5.5), it will start up showing the ‘Quick Configuration’ codes. This is a built in tool which enables you to configure the input type and range, the output functions, and the display format.
Incorrect configuration can result in damage to the process and/or personal injury and must be carried out by a competent person authorized to do so. It is the responsibility of the person commissioning the instrument to ensure the configuration is correct.
The quick code consists of two ‘SETS’ of five characters.
The upper section of the display shows the set selected. The lower section sho ws the fi v e digits which make up the set.
Adjust these as follows:
SET 1
Input Type Thermocouple
B Type B J Type J K Type K L Type L N Type N R Type R S Type S T Type T C Custom C RTD P Pt100 Linear (all units) M 0-80mV 2 0-20mA 4 4-20mA
Display units
Temperature
X None 1 nnnn.n C F oF 3 nn.nnn K K 4 n.nnnn P %
Decimal point
0 nnnnn
C 2 nnn.nn
(1)
1. Press any button. The first charac ter will change
to a flashing ‘-‘.
2. Press
or
to change the flashing character
to the required code shown in the quick c ode tables –see next page. Note: An
x indicates that
the option is not fitted.
3. Press to scroll to the next ch aracter.
You cannot scroll to the next character until the
current character is configured.
To return to the first character press
4. When all five characters have been conf i gured the
display will change to rng.hi followed by rng.lo which allows range high and low limits to be set.
5. The next press of will select Set 2. Adjust
each character as described for Set 1.
6. When the last character has been entered press
again; the display will show . Continue
to press if you wish to repeat the above quick
or
codes or press satisfied with the quick codes. The indicator will then automatically go to the operator level
Not Applicable
(1)
X Not applicable
Set 1 is followed Set this for the maximum with RNG.HI display range required Then Set this for the minimum RNG.Lo display range required
Set 2 follows these parameters
to if you are
Home display
N PV only A First Alarm SP only 1 PV + Alarm SP 2 PV + Alarm SP
See next page
.
(Read only)
Operations Manual Series 3L
12
Series 3L Indicators
13

3.1.1 To Re-Enter Quick Code Mode

If you need to re-enter the ‘Quick Configuration’ m ode this can always be done as follows:
1. Power down the indicator.

3.3 Front panel layout

2. Hold
button down and power up the indicat or again. Keep the button pressed until you are requested to enter a passcode.
3. Enter a passcode using the
or
buttons. In a new indicator the passcode defau l ts to 4. If an incorrect passcode is entered, you must repeat the whole procedure.
Parameters may also be configured using a
deeper level of access as described in subsequent chapters of this manual. If this has been done and the Quick Code Mode is re-entered as descri bed above, then the quick codes are shown with full stops (e.g. G.S.2.G.A.) to indicate that the conf iguration has been changed.

3.2 Pre-Configured Indicator or Subsequent Starts

A brief start up sequence consists of a self test in which all elements of the display are illuminated and the software version number is shown.
The indicator will briefly displa y the quick codes during start up and then proceed to Operator Level 1.
You will see the display shown below. It is called the HOME display.
If the Quick Codes do not appear during start up,
this means that the indicator has been configured in a deeper level of access, as stated opposite. The quick codes may then not be valid and are therefore not shown.
Beacons
ALM Alarm active (Red) OP1 Lit when output 1 is ON OP3 Lit when output 3 is ON OP4 Lit when output 4 (AA relay) is ON REM Communications active
Operator Buttons:
From any display - press to return to the HOME
display. Press to select a new parameter. Hold down to
continuously scroll through parameters.
Press to change or decrease a value.
Press to change or increase a value.
Message Center
A scrolling message may appear in this section. For example, if a high alarm is configured to operate output 1, and a low alarm is configured to operate output 4, the scrolling messages ‘ALARM 1 HIGH’ and ‘ALARM 4 LOW’ are shown together with the beac ons ‘ALM’, ‘OP1’ and ‘OP4’. ‘ALM’ flashes if the alarm has not been acknowledged.
If the input sensor is broken ‘S.brappear s in the top display and the scrolling message ‘INPUT SENSOR BROKEN’ appears in the message center.
Operations Manual Series 3L
14

3.3.1 Alarm Indication

Parameter
Scrolling
Description
Availability
HIGH
PEAK HIGH
This is the highest reading
LOW
PEAK LOW
This is the lowest reading
or since it was reset
SETPOINT
SETPOINT
ALARM 3 SETPOINT
A4 (----)
ALARM 4 SETPOINT
Up to three alarms can be configured. If any alarm occurs, the red ALM beacon will flas h. A scrolling text message will describe the source of the alarm (for example, ALARM 1 HIGH). Any output attached to the alarm will operate.
Press
and (Ack) together to acknowledge the alarm
If the alarm is still present, the ALM beacon will light continuously.
By default alarms are configured as non-latching, de­energized in alarm. If you require lat ched alarms, please refer to the engineering handbook.

3.3.2 Out of Range Indication

If the input is too high, HHHHH will be displayed. If the input is too low, LLLLL will be displayed.

3.3.3 Sensor Break Indication

An alarm condition (S.br) is indicated if the sensor or the wiring between sensor and indicator becomes open circuit.
For a PRT input, sensor break is indicated if any one of the three wires is broken.
For mA input, sensor break will not be detected due to the load resistor connected across the input terminals.
For Volts input, sensor break may not be detected due to the potential divider network connec ted across the input terminals.

3.4 Operator Parameters in Level 1

Operator level 1 is designed for day to day operation of the indicator, and access to these parameters is not protected by a pass code.
Press
to step through the list of parameters. The
mnemonic of the parameter is sho wn in t he lower display. After five seconds, a scrolling text description of the parameter appears.
The value of the parameter is shown in the u pper display. In level 1 the value is read onl y.
The parameters that appear depend upon the functions configured. They are:
Mnemonic
A1 (----) ALARM 1
A2 (----) ALARM 2
A3 (----)
text and
that the indicator has recorded since switch on or since it was reset
that the indicator has recorded since switch on
(----) shows the type of alarm configured. For example: HI, LO, ROC. This parameter sets the alarm thresholds.
Series 3L Indicators
15

4. Operator Level 2

Level 2 provides access to additional parameters. It is protected by a security code.

4.1 To Enter Level 2

1. From any display press and hold
2. After a few seconds the display will show:-
3. Release
.
(If no button is pressed for 45 seconds the display returns to the HOME display)
4. Press
or
to
choose Lev 2 (Level 2)
5. After 2 seconds the
dis play will show:-
6. Press pass code. Default = ‘2’
or
to enter the
7. If an incorrect code is entered the indicator reverts to Level 1.

4.1.1 To Return to Level 1

1. Press and hold
.

4.2 Level 2 Parameters

As in Level 1, press to step throu gh the list of parameters. in the message center. After five seconds, a scrolling text description of the parameter appears.
The value of the parameter is shown in the upper display. Press
If no key is pressed for 30 seconds, the indicator returns to the HOME display.
Backscroll is achieved when you are in this list by pressing
To return to the HOME display at any time, press The following table shows a list of parameters
available in Level 2.
The mnemonic of the parameter is shown
or
to adjust this value.
while holding down .
.
2. Press
to select LEv 1
The indicator will return to the level 1 HOME display. Note: A pass code is not required when goi ng from a higher level to a lower level.
Operations Manual Series 3L
16
Mnemonic Scrolling Display and description Range
has recorded since switch on or since it was reset
Read only has recorded since switch on or since it was reset
A1 (----)
ALARM 1 SETPOINT
(----) shows the type of alarm configured. For example
A2 (----)
ALARM 2 SETPOINT
ALARM 3 SETPOINT
A4 (----)
ALARM 4 SETPOINT
ADDR
ADDRESS Digital communications address for the instrument (if digital communications fitted)
1 to 254
HOME
HOME DISPLAY This configures the parameter which
Process variable
PV + Alarm SP
PV + Alarm SP read only
number
O
O
O
PRST
PEAK RESET Select On to reset the HIGH and LOW peak values. The display automatically returns to OFF
OFF ON
HIGH PEAK HIGH This is the highest reading that the indicator
LOW
PEAK LOW This is the lowest reading that the indicator
Read only
HIGH, LOW,
A3 (----)
will be displayed in the HOME display in normal operation
ALm pv.aL p.a.ro
PV
ID CUSTOMER ID Customized instrument identification
0 to 9999
UNITS DISPLAY UNITS The display units are shown in the top right hand
corner of the display in normal operation. Units available are:-
O
C
none
C
No units displayed
O
F
Perc
F
Percentage
Press
at any time to return immediately to the HOME screen at the top of the list.
Hold down to continuously scroll through the above list
Alarm setpoint
k
Kelvin
Series 3L Indicators
17

4.3 FM and Alarm Units

!
Series 3L indicators supplied to Function code FM are FM approved.
Series 3L indicators supplied to Function code DN are approved to EN14597.
The instrument label is marked accordingly. In these instruments, the alarm operating the AA relay
output is set to inverted and latching. This function cannot be altered.
When the instrument is configured using the Quick Start codes (section 3.1), Alarm 1 is used to operate both Outputs 1 and 4 (AA relay). The Quick Start configuration for the AA relay will enable and configure Alarm 4 but Alarm 4 will not be used to operate Output
4.
If Quick Start is used to configure Alarm 1 as a high alarm and Alarm 4 as a low alarm, then the resulting configuration will be t hat the high alarm 1 is used to drive both outputs 1 and 4. The low alarm 4 will not be connected to any output.
Further details on latching and blocking alarms can be found in section 9.1.

4.4 Recipes

Not Applicable to this Instrument
Loading...
+ 37 hidden pages