Super Systems 31095, 31097 Instruction Manual

45.80
50
3
Table of contents
TANDARD DISPLAY.......................................................................................page 57
Control Alarms
Retransmission
OP1
OP2
OP3
OP4
OP5
OP6
(option)
Operating mode
2 OP5 OP1 OP2 OP3 OP4 OP6
3 OP1 OP2 OP3 OP4 OP5 OP6
4 OP1 OP5 OP2 OP3 OP4 OP6
5 OP5 OP2 OP1 OP3 OP4 OP6
1 OP1 OP2 OP3 OP4 OP5 OP6
6 OP5 OP6 OP1 OP2 OP3 OP4
7
Valve
OP1 OP2 OP3 OP4 OP5 OP6
PV/SP/MV
Fuzzy tuning
with automatic selection
One shot Auto tuning
One shot Natural Frequency
(opt.)
Single action
Double action
5
1 - Introduction
0
0X5 A B C D 3 0
3
5
5
1
5
0
2ndSSR drive/analog output (OP6)
4
Options D
None
0
8
7
Front panel
IP65 protection
EN 650529 (IEC 529)
Panel
surface
7
2 - Installation
65 mm min
2.56 in min
45
+0.6
mm
1.78
+0.023
in
92
+0.8
mm
3.62
+0.031
in
113 mm min
4.45 in min
B
Use filter
Warm up
Use forced air ventilation
Use 24Vac supply version
Suggestions
9
2 - Installation
1
2
2.3.4 INSTRUMENT REMOVAL
B
1 Push and 2 Pull to remove the instrument.
Electrostatic discharges can damage the instrument.
Before removing the instrument the operator must discharge himself to ground.
1M
2
1
1
Terminals
Rear
terminal
cover
Cable size 1 mm
2
[2]
5.7 mm
0.22 in
B
35 screw terminals M3
Option terminals
Holding screw 0.5 Nm
Phillips screwdriver PH1
Flat blade screwdriver
0.8 x 4 mm
Pin connector q 1.4 mm - 0.055 in max.
Ø
Fork-shape AMP 165004 Ø 5.5 mm - 0.21 in
L
Stripped wire L 5.5 mm - 0.21 in
28
27
30
29
26
25
19
31
20
32
33
34
23
35
24
36
16
15
18
17
14
13
21
A B
11
3 - Electrical Connections
B
A = Supply B = Outputs C = Analog inputs D = Analog output E = Digital input
Serial Comm.s
B
Notes:
1] Ensure that the power supply voltage is
the same as that on the instrument label.
2] Switch ON the power supply only after
all electrical connections have been completed.
3] In accordance with electrical safety reg-
ulations, there must be an easly identifi­able and accessable power disconnect.
4] The instrument is PTC protected.
In case of failure, return the instrument to the manufacturer for repair.
5] To protect internal circuits use:
- 2 A
~ T fuse for Relay outputs (220 Vac)
- 4 A~ T fuse for Relay outputs (110 Vac)
- 1 A~ T fuse for Triac outputs
6] Relay contacts are protected with varis-
tors.
In case of 24 Vac inductive loads, use model A51-065-30D7 varistors (on request).
13
3 - Electrical Connections
B
Wire resistance 150max.
Only for two wires system, put a jumper between ter­minals 11 and 12.
Use wires of the same length and 1.5 mm
2
size.
Maximum line resis­tance 20 /line.
10
11
12
A
B
A
R2
R1
10
11
12
A
b
B
11
12
15
3 - Electrical Connections
B
3
7
6
TTL o.c.
Isolated contact
Com.
IL 3
IL 2
C2
C3
5
NPN o.c.
IL 1
C1
B
OP6
OP6
OP6
OP6
OP6
OP6
17
3 - Electrical Connections
B
B
B
Fuse
Coil of the cool load contactor
32
33
OP2
[1]
Cool load
Static Relay
8
9
OP5
8
9
OP5
Cool load
mA mV,V
Notes for pages 17 - 18 - 19 OP1 - OP2 Relay output
• SPST Relay N.O., 2A/250 Vac
(4A/120Vac)
for resistive load,
• Fuse 2A ac T at 250V, 4A ac T at 110V.
OP1 - OP2 Triac output
• N.O. contact for resistive load of up to 1A/250 Vac max.
• Fuse 1A ac T
Isolated digital outputs OP5-OP6
• 0…24Vdc, ±20%, 30 mA max.
Isolated analog outputs OP5-OP6
• 0/4…20mA, 750/ 15V max. 0/1…5V, 0…10V, 500/ 20mA max.
[1] Varistor for inductive load 24Vac only
19
3 - Electrical Connections
3.3.6-G MOTOR POSITIONER OUTPUT
RELAY (TRIAC) / RELAY (TRIAC)
Valve drive PID without potentiometer 3 pole output with N.O. contacts (raise, lower, stop)
OP1
33
32
31
OP2
V~
Lower
Raise
M
~
3.3.9 SERIAL COMMUNICATIONS
(OPTION) [2]
B
• Galvanic isolation 500Vac/1 min; Compliance to the EIA RS485 standard for Modbus/Jbus;
• Termination setting dip switches.
C
SLAVE
13
14
15
1234
SLAVE
B
21
3 - Electrical Connections
33
Description according to
PROFIBUS specifications
Receive data/transmission data plus
Receive data/transmission data negative
VP (VP)
Data transmission potential (ground to 5V)
Supply voltage of the termi­nating resistance-P, (P5V)
SP operating Setpoint
(Local/Remote or Stored)
% Control output
or Program status (see page 64)
Control output LEDs (red)
å OP1/OP4 ON - ç OP2/OP4 OFF
Run/stop Timer or a program
Entry key for selection and value setting confirmation
Setpoint setting
Menu access
8888____ 8888----
PV control input in engineering units
Over range Under range
23
4 - Operation
Parameter value
Value modification
Unit
°f
Unit
none
Unit
ph
Engineering Units Celsius
Degree Fahrenheit
Degree Celsius
Degree Fahrenheit
no units defined
Ph
25
4 - Operation
33
OK
EHit
Conf
ConfConf
tiMe
Conf
(see page 30... 33)
(see page 34)
NOYES
Back to the operator mode
Enter the configuration
password
Must be equal to the
value
of the parameter
C.Pas (see page.50)
from -999...9999
(33 default from factory)
Alarms
Timer
configuration
Exit the
Configuration
Hertz
ph Hz
PInp.
32…1112°F
Engineering units
-58.0…122.0°F
-99.9…572.0°F
-328…1112°F
-328…752°F
32…2912°F
32…2912°F
32…2192°F 32…1112°F
Value Description
éUnit
Tab. 2 Engineering units
none
None
rh
°C
Degree centigrade
°f
Degree Fahrenheit
Rh
MA
mA
MU
mV
U
Volt
Ph
bar
bar
psI
PSI
Frequency (option)
32…3272°F 32…2192°F
32…1112°F
32…3632°F 32…3632°F
éInP.
32…2012°F
Notes:
[1]
NiChroSil-NiSil thermocouple.
[2] Ni-Mo thermocouple. [3] Factory default for the
custom range is: type K (32... 2448°F).
27
4 - Operation
Tab. 4 Rem. Setpoint
Value Description
0=5
0…5 Volt
1=5
1…5 Volt
0=20
0…20 mA
Tab. 3
4=20
4…20 mA
Setpoint type
0=10
reM.t
Remote - trim
0…10 Volt
érs.In
loc.t
Local - trim
l=r
Local/remote only
reM
Remote only
loc
Local only
Value Description
éS.P.ty
rt. 2
énone
O.rt.2
é4=20
rt.L2
é 0
rt.H2
é9999
WITH OPTIONAL OP6 ANALOG
OUTPUT NOT USED AS COOL CON-
TROL OUTPUT
1
st
retransmitted
output selection
none/ P.U./S.P.
1stretransmission output
see table 8
1
st
retransmission
low range
whole range
1
st
retransmission
high range
whole range
2
nd
retransmitted
output selection
none/P.U/S.P./M.U.
2ndretransmission output
see table 8
2
nd
retransmission
low range
whole range
2
nd
retransmission
high range
whole range
29
4 - Operation
Retransmitted signal
none/P.U./S.P
/M.U.
Output range
0=5 /1=5 /0=10 0=20 / 4=20
Retransmission low range
Retransmission high range
Example:
• T/C S: range 0…1600°C;
• Output range, 4…20 mA;
• Retransmitted signal PV on 800…1200°C range.
#rt.H1 #rt.H2
20
4
800 1200 1600
#retr = 4=20 #rt.H = P.U. #rt.L1 = 800 #rt.H1 =1200
mA
°C
With rt.lI greater than
rt.H1 it is possible to obtain
a reverse scale.
bloc
éno
Ltch
éno
A1.Ou
éOP1
AL. 1
éOFF
donb
éno
AL1 alarm type
see table 11
AL1 addressing
OP1 / OP2 [1]
OP3 / OP4
AL1 latching
no / yeS
AL1 start-up disabling
no / yeS
Disables AL1 if a sen­sor break occurs
no / yeS
NOT AVAILABLE
OF
AL. 1 = OFF
31
4 - Operation
AL4 alarm type
see table 11
AL4 addressing
OP1 / OP2 [1]
OP3 / OP4
AL4 latching
no / yeS
AL4 start-up disabling
no / yeS
Disables AL4 if a sen­sor break occurs
no / yeS
Band
éAl 4
Description
Tab. 11 Alarm type
éAl 1
Value
Off
Not used or used by the program (AL3/AL4)
fs.H
Active High
Absolute
fs.l
Active Low
deU.H
Active High
Deviation
deU.l
Active Low
bno
Active Out
bni
Active In
lba
Loop break alarm (AL1 only)
éAl 3
éAl 2
tiMe
Alarm 3 active when Timer ON
Active high
é-fsH
On
Off
High rangeLow range
Active high
On
Off
+ range- range
é-deH
On
Off
SP
Alarm threshold
full scale
hyd hyu
SP SP
[B] ALARM ACKNOWLEDGE
FUNCTION
The alarm, once occurred, is presented on the display until acknowledged. The acknowledge operation consists in pressing any key.
After this operation, the alarm leaves the alarm state only when the alarm condition is no longer present.
Ltch
Yes
mA
°C
OP1
275.0
A / M
1 2 3
Ilba
4
33
4 - Operation
LOOP BREAK ALARM (LBA)
When the controller connection to the sensor is discontinued or other faults are detected in the control loop, AL1 alarm becomes active after a predefined time of
1... 9999 s from the detection of the failure (see page 37). When a sensor failure occours, the LBA interventrion is immedi­ate. The alarm state ceases when the fault condition is no longer present.
eIn case of ON-OFF control, the
LBA alarm is not active.
#donb = no
#donb = yes
Menu
AL
Menu
time
(see pages 37)
Operator mode
(see page 41)
Alarm menu
Time
menu
A
The parameter setting procedure has a timeout. If no keys are pressed for, at least, 30 seconds, the controller switches back, auto­matically, to the operator mode.
35
4 - Operation
Menu
Conf
Menu
AccS
(see page 54)
Access
menu
(see page 25)
Configuration
menu
menu
SL. u
SL. d
éOFF
éOFF
S.P. H
éH.réange
S.P. L
éL.réange
Ratio Setpoint
-9.99…99.99
Remote Setpoint bias
full scale
Setpoint low limit
full scale
Setpoint high limit
full scale
Slope up
0ff/1…9999 digit/
[1]
Slop down
0ff/1…9999
digit/..
0ff/1…9999
digit/ [1]
37
4 - Operation
Timer Action
Timer OP function
std/eHpd
standard/extended Standard: tdop = 0 OP3 is set to 1 at timer lauch and reset 0 on time elapsing. Extended: tdop = 1 OP3 is set to 1 at time elapsing and set to 0 by reset command.
P.I.D enable yes/no
Yes:
PID is enabled when time function is enabled.
Extended:
PID is disabled and output is maintained at zero.
#Pid
#tdop
[1] OP3
status
Value
On
4
Off
5
On
6
Off
7
C - Counting start time = timer launch
time, end in control mode.
The time counting starts when the timer is launched. The control action is not affected by the Timer function.
tdop = 1
tdop = 0
#tiMe
Timer launch
SP
Process variable PV
Output OP [2]
#t.Mod = 4
OP3
Reset
OP3
OP = 0
39
4 - Operation
F - Control action with stand-by Setpoint
during the counting time.
The time counting starts when the timer is launched and the control action use the Stand-by Setpoint. At the end, the control action use the working Setpoint.
tdop = 1
tdop = 0
#tiMe
Timer launch
#s.p. 2
#t.Mod =7
SP
Process variable PV
Output OP [2]
OP3
Reset
OP3
OP = 0
41
4 - Operation
Alarm 3 hysteresis asymmetric upper
0…5% Span in engineering units
Alarm 3 hysteresis asymmetric lower
0…5% Span in engineering units
Alarm 3 delay
OFF/1...9999
Alarm 4 hysteresis asymmetric upper
0…5% Span in engineering units
Alarm 4 hysteresis asymmetric lower
0…5% Span in engineering units
Alarm 4 delay
OFF/1...9999
Type and value Mode
No. and
Param.
Absolute
full scale
Active high
-fs.H
Active low
-fs.l
Deviation
full scale
Active high
-de.H
Active low
-de.l
Band
full scale
L.B.A.
1…9999 s
Active high
-lba
Timer
ON on timer signal
Alarm 3 active on timer signal
-ton
[1] A code, specifying the No. and the
alarm type that has been config­ured (see page 31), is displayed. At this point, the user must enter the threshold value, according to the following table.
Active out
-bno
Active in
-bni
OK
t.d. C
é 12:0
t.i. C
é 60
P.b. C
é 5:0
Proportional band Cool channel
0.5…999.9%c.s.
Cool Integral time
0ff/1
9999 s
Cool Derivative time
0ff/0.1
999.9 s
NO
YES
43
4 - Operation
Menu
InP
T.SaM
é 0:11
In.Sh
é 0
t.FiL
éOFF
Filter time constant
(user enabled/disabled)
Off/0.2…99.9 seconds
Measure bias
-60…60 digit
Sampling time
0.1…10.0 seconds
Input menu
Op.rC
é Off
OP.C.H
t.c. C
é 10:0
é100:0
d.bnd
é 0:5
Motor travel time
15…600 seconds
Minimum output step
0.1…5.0%
Dead band
0.0…5.0%
Cool cycle time
(time proportional only)
0.2…100.0 s
Cool control output high limit
(PID only)
0.0…100.0%
Cool output rate limit
(user enabled/disabled)
0ff/0.01…99.99%s
Heat / Cool
Algorithm
45
4 - Operation
Target Setpoint = 350°C
t = 10
#
sL. u = 10
digit/minute
1st stored Setpoint 2nd stored Setpoint 3th stored Setpoint
Values of the three Setpoints, that are activated by mean of logic inputs, communication parameters, and keyboard. The Setpoint active is indicated by the ú, ù or û green LED.
See page 56 for further explana­tion.
Remote Setpoint Slope enable
To enable or disable slopes when the remote Setpoint is active.
#rs.sl
#S.P. 3
#S.P. 2
#S.P. 1
47
4 - Operation
bias = 20 ratio = 0.1
ratio = –0.1
Range
600
100
20
Remote
Setpoint span
bias = 100
a b
a´ b´
HR
´ ) b (a´ )
PV = Process Variable LR = PV low limit HR = PV high limit SR = Remote Setpoint a (a´) = SR starting point b (b´) = SR ending point
Asymmetric upper alarm
hysteresis Asymmetric lower alarm hysteresis
Alarm delay
Delay time for alarm activation.
OFF: alarm activated immediately
1...9999 seconds: alarm acti­vated only if the condition per­sists for the set time
#tF1
=
#hy-u
49
4 - Operation
Manual reset
Error
Dead Band
4.5.4 TUNING MENU (not shown for ON-OFF main control output)
See page also 57
Two tuning method are provided:
• Initial one shoot Fuzzy-Tuning
• Continuous, self learning
Adaptive Tuning
The Fuzzy-Tuning automatically
determines the best PID term with behaviour respect to the process.
The controller provides 2 types of “one shot” tuning algorithms, that automatically are selected according to the process con­ditions when the tune operation is started.
STEP response
SP
End of the tuning
operating and
setting of the new
calculated terms
Start of autotune
operation
Setpoint change
PV variable
Control output
4.5.5 INPUT MENU
Input filter
Time constant, in seconds, of the RC input filter on the PV input. When this parameter is
Off the filter is bypassed.
Measure Bias
This value is added to the mea­sured PV input value. Its effect is to shift the whole PV scale of its value (±60 digits).
Sampling Time
Sampling time, in seconds, of the instrument. This parameter is normally used when control­ling slow process, increasing the sampling time from 0.1... 10 s.
#t.SaM
#In.sh
0
PV
63.2%
Filter time
Time
#t.fil
51
4 - Operation
Soft start
time
Travel
time
Minimum
step
#Op.r
Time
Speed in %/s
Heat/Cool deadband
This parameter specifies the width of the deadband between the Cool and the Heat outputs.
#d.bnd
#OpC.H
#
Op.H.
0
100%
100%
0
SP
d.bnd
P.b. / CP.b.
eat / Cool Algorithm
Heat Cool
100%
Cool output
Heat output
Heat
53
4 - Operation
Ac.le
C.pas
Oper
EHec
C.pas
33
Access to all the levels [1]
Execute the following operations
A/M enable
yes/nO
Operator level Access
Change the Configuration password
Enter the Configuration password
pot.H
EHec
C.pot
pot.l
O
255
55
4 - Operation
Calibrate the potentiometer
(if present)
The valve goes to low scale
The valve goes to full scale
Download the data to Memory chip
When the indication
(the valve) is stopped,
confirm the calibra-
tion value using
$ or %
The parameters in the access level
fast are recalled on the
front panel through the pro­cedure of fast parameter access illustrated in par. 5.2
page 57. The maximum num­ber of fast parameters is 10.
At the end of the parameter list of the selected group, the controller exits from the Edit access level.
Therefore, the Edit level must be selected for each group of parameters
The access level of groups and parameters is activated through:
Ac.le
Oper
Access level operator
Confirm
57
5 - Displays
Operator mode Automatic mode
One shot tune start
no/yes
Alarm 3 threshold
(high absolute alarm)
full scale
Stored Setpoint selection
none/s.LOC/ s.s.p.I/s.s.p.2/ s.s.p.3
5.2 FAST VIEW
(fast access to the parameters)
With this procedure, up to 10 parameters, selected through the fast view (see par 4.6 page
56) are displayed and can be modified by the operator without requiring the standard parameter setting procedure. Press
$% in order to
modify the parameters. The value is entered by pressing è key.
On left side, please find a sample list of parameters on Fast view menu.
6.3 SERIAL
COMMUNICATIONS
see the manual on this topic
59
6 - Commands
275.0
274.8
63
275.0
274.8
35
275.0
274.8
63
A
Operator mode
(automatic)
The bumpless action is present switching between AUTO, MAN and vice versa.
AUTO AUTO
SP = PV
OPMAN=OPAUTO
SP (PV)
O
Y
0
0
MAN
Op.r
SP
change OP
100% Setpoint SP
with
100% output OP
OPAUTO=OPMAN
PV
OP
AIn case of power failure, the
AUTO/MAN status and the output value remain stored in the controller memory.
s.sel
s.sel
S.LOC
s.sel
s.s.p.1
s.s.p.3
The selected Setpoint
becomes operating
pressing the
è key.
The three
ú ù û
leds flag the Setpoint
operating.
tune
tune
no
tune
yes
no
61
6 - Commands
Confirm
yes
to start
Confirm
no
to stop
The command start/stop is executed pressing the
è key.
When the controller is
calculating the PID
parameters, the green
Ä led is ON.
Fuzzy Tune
start-up
After the execution of the tuning, the calculated values are automatically presented in the PID menu.
Notes
With the keypad locked the commands from digital inputs and serial communications are still operating
The value of PV is “frozen” at the time the digital input goes to the close state
The permanent closure forces the chosen stored value. Setpoint modification is not possible. The impulsive closure, selects the stored value. Setpoint modification is allowed. If more than one digital input is selecting a Setpoint, the last to be activated is the operating one (see page 43)
When the input is in the on state, the Setpoint is changed in steps
With ON command the output is equal to the forced value (see page 28)
The blocking function is activated on closing the com­mand from digital inputs
63
8 - Technical Specifications
- the type and functionality of the alarms
- control parameter values
- access levels
Between 100…240Vac the error is minimal
Max. wire Res: 20max. (3 wires) Input drift: 0.1°C/10° T
env
<0.1°C/10Wire Res.
Line: 150max. Input drift: <2µV/°C. T
env.
<5µV/10Wire Res.
Input drift: <0.1%/20°C T
env.
<5µV/10Wire Res.
Bias in engineering units and ± range Ratio: -9.99… +99.99 Local + Remote Setpoint
OP2
OP3
Relay
OP4
Relay
OP5
Analog/Digital
OP6
Analog/Digital
OP2
OP3
Relay
OP4
Relay
OP6
Analog/Digital
OP3
Relay
OP4
Relay
OP5
Analog/Digital
OP6
Analog/Digital
OP2
OP3
Relay
OP4
Relay
OP6
Analog/Digital
OP3
Relay
OP4
Relay
OP6
Analog/Digital
OP2
OP3
Relay
OP4
Relay
OP3
Relay
OP4
Relay
OP5
Analog/Digital
OP6
Analog/Digital
Feedback valve position
65
8 - Technical Specifications
Single action PID algorithm
OFF = O
Double action PID algorithm (Heat / Cool)
OFF = O
Valve drive PID algorithm Raise/Stop/Lower
OFF = O
OFF = O
0/4... 20mA, 750/15V max.
67
8 - Technical Specifications
Power consumption 5W max.
Factory default parameters
FACTORY DEFAULT PARAMETERS
Parameter Parameter Name Default value User settings Notes
S.SEL
Setpoint selection NONE
SP.1
1st stored Setpoint 0
SP.2
2nd stored Setpoint 0
S.P.L
Setpoint low limit PV.LO
S.P.H
Setpoint high limit PV.HI
Sl.u
Setpoint ramp up OFF
Sl.d
Setpoint ramp down OFF
rtio
Ratio remote Setpoint 1.00
biaS
Remote Setpoint Bias 0
1
AL1 alarm threshold 0
SSI.fm Page 68 Friday, December 12, 2008 5:04 PM
Factory default parameters
tFl1
AL1 delay 1
Hy.2u
AL2 alarm hysteresis Up 1
Hy.2d
AL2 alarm hysteresis Down 1
tFl2
AL2 delay 1
Hy.3u
AL3 alarm hysteresis Up 1
Hy.3d
AL3 alarm hysteresis Down 1
tFl3
AL3 delay 1
Hy.4u
AL4 alarm hysteresis Up 1
Hy.4d
AL4 alarm hysteresis Down 1
tFl4
AL4 delay 1
t.Mod
Timer Operating Mode 0
t.act
Timer Action 4
t.dOP
Timer OP Function 1
Parameter Parameter Name Default value User settings Notes
SSI.fm Page 69 Friday, December 12, 2008 5:04 PM
Factory default parameters
t.i.
Integral time 60
t.d.
Derivative time 12.0
d.Err
Error Dead Band OFF
O.C.
Overshoot Control 0.8
O.C.r.b.
Overshoot Control relative band 1.0
MreS
Manual Reset 50
P.b. C
Cool proportional band 3.0
t.i. C
Cool integral time 60
t.d. C
Cool derivative time 12.0
tune
Start/Stop One shot tuning (0=Stop 1=Run) NO
AdPt
Start/Stop Adaptive tuning (0=Stop 1=Run) NO
t.Fil
Input filter 2.0
In.Sh
Input shift OFF
Parameter Parameter Name Default value User settings Notes
SSI.fm Page 70 Friday, December 12, 2008 5:04 PM
Factory default parameters
OP.r
Control output maximum speed OFF
St.OP
Soft start output high value OFF
St.tM
Soft start time 10
M.t
Output minimum step Servomotor 60
M.hy
Output minimum step Servomotor 0.5
d.bnd
Heat/Cool Dead band 0.5
tc.C
Cool cycle time 5.0
OP.C.H
Cool output maximum value 100.0
OP.rC
Cool output maximum speed OFF
Add.S
Communication SLAVE address 247
dr.S
SLAVE Baud rate 9600
Pro.S
SLAVE Communication protocol MBUS
Par.y
Parity NONE
Parameter Parameter Name Default value User settings Notes
SSI.fm Page 71 Friday, December 12, 2008 5:04 PM
Factory default parameters
A.PAS
Access password 11
In
Input type selection 0 - 10
Unit
Engineering units NONE
SC.dd
Number of decimals (0... 3) 0
SC.lo
Low range 0
SC.Hi
High range 9999
Sqr
Square root (0 = OFF, 1 = ON) NO
Char
Linear input characterization NO
S.P.ty
Setpoint type LOC
S.P.tr
Stored Setpoint tracking NO
S.P.T
Time units and Setpoint slope P.SEC
.In
Remote Setpoint input 4 - 20
Parameter Parameter Name Default value User settings Notes
SSI.fm Page 72 Friday, December 12, 2008 5:04 PM
73
Warranty
Logic
mA mV
mA
SPDT Relay
Triac
SPST Relay
Output
Setpoint slopes inhibition
PV hold
Run, Hold, Reset and program selection
Auto/Manual
Digital input connected functions
Loading...