34” DEEP COMBINATION CONVERTIBLE SERVICE ABOVE REFRIGERATED SELF-SERVICE CASE
PLEASE NOTE THE FOLLOWING:
1. YOUR SPECIFIC MODEL NUMBER IS ON THE SERIAL LABEL ON CASE REAR (NEAR MAIN
POWER SWITCH).
2. SEE “MODELS (AND THEIR RESPECTIVE CASE DIMENSIONS) LISTED IN THIS MANUAL”
SECTION FOR ADDITIONAL INFORMATION REGARDING SPECIFIC CASE DI MENSIONS OF
STANDARD MODELS AND
3. *[L] DENOTES DIFFERING CASE LENGTHS.
CDRs.
PN 54383
Note 1: HMBC2 and HMBC3 reflect an
undivided upper section.
Note 2
HMBC5 Case Shown Above
Structural Concepts Corporation · 888 E. Porter Road · Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 · www.structuralconcepts.com
TABLE OF CONTENTS ……………………………………………………………………………………...
MODELS LISTED IN MANUAL / DETERMINING THEIR RESPECTIVE CASE DIMENSIONS……..
OVERVIEW / NSF® TYPE / COMPLIANCE / WARNINGS / PRECAUTIONS …………………...…..
INSTALLATION: REMOVAL FROM SKID [LEVELERS vs. CASTERS] ...……...…….……………….
INSTALLATION: LOWER FRONT GRILLE and LOWER REAR PANEL REMOVAL/REPLACEMENT.
INSTALLATION: ELECTRICAL CONNECTIONS …………………………………………………………
INSTALLATION: POSITIONING AND ALIGNING UNITS / GLASS SHELVING ……………………...
INSTALLATION: SETUP / POWER CORDS / TEMPERATURE CONTROLLER ……….…………...
INSTALLATION, CONTINUED: REMOTE UNIT ELECTRICAL LEADS / REFRI GATION & DRAIN
MAINTENANCE FUNDAMENTALS: BRACKET RETAINERS / SHELVES / DRAIN / TXV VALVE…
MAINTENANCE FUNDAMENTALS: REFRIG. PACKAGE., TEMPERAT URE CONTROLLER,
CONDENSER PAN ACCESS [TO BE PERFORMED BY TRAINED SERVICE PROVIDERS ONLY]
MAINTENANCE FUNDAMENTALS: HONEYCOMB AIR DIFFUSERS / UPPER SECTION AIR
DUCT [SERVICE TO BE PERFORMED BY TRAINED SERVICE PROVIDERS ONLY].……………..
TROUBLESHOOTING [TO BE PERFORMED BY TRAINED SERVICE PROVIDERS ONLY] .…….
TROUBLESHOOTING - CONDENSING SYSTEM [TRAINED SERVICE PROVIDERS ONLY] ..…..
TROUBLESHOOTING - EVAPORATOR SYSTEM [TRAINED SERVICE PROVIDERS ONLY] ……
PREVENTIVE MAINTENANCE [TO BE PERFORMED BY TRAINED SERVICE PROVIDER] ….....
SERIAL LABEL INFORMATION & LOCATION ..……………………………………...…....…………..…
TEMPERATURE CONTROLLER - CAREL® ...…. ……………………..……..…………………...……..
TECHNICAL SERVICE CONTACT INFORMATION & WARRANTY INFORMATION ...……….….....
2
3
4-5
6
7
8
9
10
11
12
13
14
15
16
17-18
19
20-21
22
23
24
25
26
27-29
30
31
32-33
34
35-37
38
2
Page 3
MODELS LISTED IN THIS MANUAL / DETERMINING THEIR RESPECTIVE CASE DIMENSIONS
DETERMINING YOUR MODEL AND ITS CASE DIMENSIONS:
Note 1. Your model number can be found on serial label at rear of case (near main power switch).
Note 2. Dimensions of each model can be found at www.structuralconcepts.com. Simply enter
the case model number into the Product Number Search box. Click the product specification
link for complete dimensions.
Note 3. If your specific model is not found, contact technical service (phone number is listed at
Technical Service section in this manual) for dimensions.
Note 4. CDRs (Customer Design Requests) are listed with a 4-digit number. All CDR dimensions
are identical to standard model dimensions.
THIS OPERATING MANUAL ENCOMPASSES THE FOLLOWING MODELS (AND THEIR
RESPECTIVE CDRs):
Models: HMBC2
HMBC3
HMBC4
HMBC5
HMBC6
3
Page 4
OVERVIEW / NSF® TYPE / COMPLIANCE / WARNINGS / PRECAUTIONS - PAGE 1 of 2
OVERVIEW
These Structural Concepts Harmony® cases are
designed to merchandise packaged products at 41°F
[5 °C] or less product temperatures (unless custom
cases with wire rack shelving).
Cases should be installed and operated according to
this operating manual’s instructions to insure proper
performance. Improper use will void warranty.
NSF® TYPE
This unit is designed for the display of products in
ambient store conditions where temperatures and
humidity are maintained within a specific range.
For NSF® Type 1 Conditions (most cases): ambient
conditions are to be at 55% maximum humidity and
maximum temperatures of 75 °F [24 °C].
For NSF® Type 2 Conditions: ambient conditions are
This equipment MUST be installed in compliance with
all applicable NEC, federal, state and local
electrical and plumbing codes.
to be at 60% maximum humidity and maximum
temperatures of 80 °F [27 °C].
If unsure if unit is NSF® Type 1 or 2, see tag next to
serial label. See SERIAL LABEL LOCATION & INFORMATION LISTED / TECH INFO & SERVICE
section in this manual for sample serial labels).
COMPLIANCE
Performance issues when in violation of applicable
NEC, federal, state and local electrical and plumbing
codes are not covered by warranty.
See below compliance guideline.
WARNINGS
Following are important warnings to prevent injury or
death.
Please read carefully!
See next page for PRECAUTIONS.
COMPLIANCE
WARNING
ELECTRICAL
HAZARD
WARNING
KEEP
HANDS
CLEAR
WARNING
HOT
SURFACE
WARNING
Risk of electric shock. Disconnect power before servicing unit.
CAUTION! More than one source of electrical supply is
employed with units that have separate circuits.
Disconnect ALL ELECTRICAL SOURCES before servicing.
WARNING
Hazardous moving parts. Do not operate unit with covers removed.
Fan blades may be exposed when deck panel is removed.
Disconnect power before removing deck panel.
WARNING
Condenser Pan is Hot!
Disconnect and allow to cool
before cleaning or removing from case.
4
Page 5
OVERVIEW / NSF® TYPE / COMPLIANCE / WARNINGS / PRECAUTIONS - PAGE 2 of 2
PRECAUTIONS
Following are important precautions to prevent
damage to unit or merchandise.
CAUTION
Lamps have been treated to resist breakage
and must be replaced with similarly treated lamps.
Use the required GFCI (Ground Fault Circuit Interrupter)
when electrical code mandates such circuit breaker.
When GFCI is required, DO NOT use standard GFI receptacle.
CAUTION
Performance issues caused by adverse conditions are NOT covered
CAUTION! ADVERSE CONDITIONS / SPACING ISSUES
by warranty.
End panels must be tightly joined or kept at least 6-inches away
from any structure to prevent condensation.
Unit must be kept at least 15-feet from exterior doors, overhead
HVAC vents or any air curtain disruption to maintain proper
temperatures.
Unit must not be exposed to direct sunlight or any heat source
(ovens, fryers, etc.).
Tile floors, low ceilings or small rooms will increase noise level.
Whisper Cool compressor blanket or remote unit may resolve noise
level issues.
Keep at least 8-inch clearance above unit for air discharge
(self-contained units only).
Please read carefully!
See previous page for specifics on OVERVIEW, NSF
TYPE, COMPLIANCE and WARNINGS.
CAUTION
CAUTION
5
Page 6
INSTALLATION: REMOVAL FROM SKID [LEVELERS vs. CASTERS]
1. Remove Case From Skid (Levelers)
Remove shipping brace that may be
securing case to skid.
Support case to prevent tipping.
Caution! Levelers can be damaged if case
hits floor with heavy force!
Carefully slide unit to
rear of skid and tip
backward off skid.
Illustration may not
reflect every feature
or option of your
particular case.
Slide Skid Out
Case can be repositioned with pallet truck when
front lower panel is removed. Blocking may be
necessary to obtain adequate height.
2. Remove Case From Skid (Casters)
Remove shipping brackets that may be securing
casters to skid
Place ramp up against skid (to allow case to
smoothly slide off from skid).
Maintain support of case at all times or center
of gravity may cause case to fall.
Unlock Casters. Roll unit to rear of skid.
Roll down ramp
and off from skid.
Note: Illustrations
shown reflect a
general outline of
sample cases and do
not reflect features or
options of your
particular model.
Ramp
Support
while
rolling
case
down
ramp.
6
Page 7
INSTALLATION: LOWER FRONT GRILLE and LOWER REAR PANEL REMOVAL / REPLACEMENT
3. Removing Lower Front Grille
No screw removal is required to remove grille.
Front grille has retainer slots at each end of grille.
Case has retainer hooks at each end.
(2) Front Grille
Retainer Slots
(at Each End
of Grille)
Simply lift lower front grille up and off retainer
hooks (at each end of case).
Replace in same manner.
View below is shown is disassembled for
illustrative purposes only.
(2) Front Grille
Retainer Hooks
(at Each End of Case)
4. Removing Lower Rear Panel
No screw removal is required to remove panel.
Rear panel has retainer slots at each end of grille.
Case has retainer hooks at each end.
Simply lift lower rear panel up and off retainer
hooks (at each end of case).
Replace in same manner.
View below is shown is disassembled for
illustrative purposes only.
(2) Rear Panel
Retainer Slots
(at Each End
of Rear Panel)
7
(2) Lower Rear Panel
Retainer Hooks
(at Each End of Case)
Page 8
INSTALLATION, CONTINUED: ELECTRICAL CONNECTIONS
5. Electrical Connections
Ballast Box: Remove 4 screws from the thermostat/ballast cover. Remove screws holding ballast
cover to base.
Knockouts are located on side and rear of box for making electrical connections.
Note: Standard 120V or 220V (depending upon case chosen), single phase connections are
required for self contained refrigeration units and must be performed by a certified electrician.
Remove two (2) screws at
each end of cover to remove
thermostat/ballast cover.
Note: Illustrations shown
with rear grille removed for
View of case with
thermostat/ballast cover intact
illustrative purposes only.
Thermostat/Ballast Cover
Ballast Cover
Ballasts
View of case with
Base
thermostat/ballast cover removed
Enlarged view of thermostat/ballast area
8
Page 9
INSTALLATION, CONTINUED: POSITIONING AND ALIGNING UNITS / GLASS SHELVING
6. Position and Aligning Units
Position Units. Align multiple units carefully in areas
A & B shown at right.
7. Glass Shelving
A
Glass shelving will be packed separately.
Caution! Carefully remove from packaging.
Grasp firmly and carefully install.
Caution! Check that plastic edging is intact
before placing glass shelving onto brackets!
Plastic edging must NOT be removed from glass
shelves. Contact Structural Concepts for
replacement edging (see TECHNICAL SERVICE CONTACT INFORMATION section).
Check that glass shelving is in proper position
before placing product in case.
See illustration below.
B
Glass Shelves
(Typical)
9
Page 10
INSTALLATION, CONTINUED: SETUP / POWER CORDS / TEMPERATURE CONTROLLER
8. Merchandiser Setup: Self Contained
Units
Remove lower front grille; see
INSTALLATION: REMOVAL FROM SKID,
REMOVING LOWER FRONT GRILLE
section in this manual for instructions.
Insure that the Condenser Pan is installed
under the PVC condensate drain trap.
Insure that the Condenser Pan is plugged into
the receptacle inside base.
Return front grille to case.
See Drain, Hose and Bracket Placement
section in Operating Manual for details.
9.a. Self-contained refrigeration with
power cord
For your safety, equipment is furnished
with a properly grounded cord connector.
Do not attempt to defeat the grounded
connector.
Plug cord into a certified electrical outlet with
ground.
9.b. Self-Contained refrigeration without
power cord
Remove the rear lower grille required).
Note: The compressor/condenser assembly
can be slid out to facilitate maintenance.
Electrical leads are provided inside the base
exiting the ballast box.
Leads are labeled for identification.
9.c. Self-Contained Temperature
Controller
See below for location.
See Temperature Controller section for
To lock casters, press down on lever.
To unlock casters, pull lever up.
See illustration at right.
12. Cases With Levelers: Adjust Levelers
After case is in position, adjust case so it is level
and plumb (see illustration at right).
You may need to remove front and/or rear
Toe-Kick to access levelers.
Use adjustable wrench (and possibly a pry bar)
Adjustable
Wrench
to adjust leveler.
Do not use pry bar on toe-kick (it may buckle).
Do not use pry bar on end panel (it may chip).
Use pry bar ONLY on base frame to avoid
damaging case.
Pry Bar
Use a block to reach base frames with pry bar.
See illustrations at right.
Block
13. Raising the Curved Glass
To raise the curved glass, grab the lift handle
extrusion on the bottom edge of the front curved
glass and lift up.
Gas cylinders hold the glass open for hands free
access to the interior of the case.
14. Removing the Rear Doors
Move rear doors toward center of the case.
Individually lift each door up toward the top of the
case; pivot the bottom of the door out.
15. Electrical Wiring Diagram
Each case has its own wiring diagram folded
Front
Curved
Glass
Lift
Handle
Leveler
Toe-Kick
and in its own packet.
Wiring diagram placement may vary; it may
be placed near condenser fan cover, ballast
box, raceway cover, or other related location.
16. Ventilation and Clearance
Self-Contained refrigerated cases must
maintain airflow clearance of 6” (minimum) to
12” (recommended) at front and rear.
Restriction of air can void warranty.
See illustration at right.
Base
Frame
Rear
Doors
12
Check air grilles for obstructions.
Maintain airflow clearance of 6” (min.)
to 12” (recommended) at front & rear.
Page 13
INSTALLATION, CONTINUED: LIGHTS, TEMP. CONTROLLER, SATURATED SUCTION TE MP.
17. Main Power Switch
Turn main power switch on.
Case will power up and temperature controller will
begin operating.
18. Light Switch
Turn lights on. Light switch is at case rear. See
illustration at top-right for location.
All lights should come on at the same time. First
time lighting may require a short warm-up period.
Slightly dim / flickering of new bulbs is normal. If
lights do not turn on, check raceway plugs.
Lighting is wired in series so all lights must be
plugged in or receptacles capped for case
lights to be on. See illustrations at right.
19. Temperature Controller (All SelfContained Units and some Remote Units)
Check that compressor symbol light is on:
Compressor symbol (common in Carel®
temperature controllers) is shown at left.
After case has run for a few minutes, check that
temperature starts to drop.
If temperature controller does not begin cooling
(in a few minutes) see temperature controller
section in this operating manual for instructions.
Remote units (without temperature controller on
case): Verify that refrigeration requirements listed
on serial label (found on the case) are being met.
20. Saturated Suction Temperature (Remote
Units)
See serial label on case for suction temperature
requirements and BTU requirements.
See serial label on case for defrost schedule and
temperature termination parameters.
Light Switch
------- View from rear of case -------
Raceway Receptacle, Plug and Cap
Main Power
Switch
Raceway
Receptacle
Temperature
Controller
Cap
Plug
13
Sample Carel® Controller Face
Page 14
INSTALLATION, CONTINUED: FRONT GLASS ALIGNMENT & ADJUSTMENT
Front Glass Alignment & Adjustment via Levelers (For Curved and Flat Front Glass)
Proper alignment of the front glass is important to create and maintain a seal inside the case.
Improper alignment can cause air leaks compromising the environment inside the case and create
condensation.
Follow the five steps listed below to assure proper front glass alignment.
1. Side-to-Side Leveling: Place a level on top of
display case (parallel to the front glass). Raise or
lower either side of the case by rotating levelers to
center the level bubble.
2. Front-to-Back Leveling: Place a level on top of
case, perpendicular to front glass. Raise or lower
either side of case by rotating levelers to center the
level bubble. Double-check the side-to-side level.
—- Front Glass —-
Case with Curved
Front Glass
Case with Flat
Front Glass
END
PANEL
CURVED
FRONT
GLASS
3. If FRONT-LEFT CORNER
is too close to end panel (or
hitting it), adjust levelers at
the BACK LEFT CORNER
of case DOWNWARD.
CURVED
FRONT
GLASS
LIFT
5. Verification: After inserting shims (or adjusting levelers), open and shut
the front glass to confirm proper fit.
Verify (again) that front glass is properly aligned at left-hand and right-
hand side of the case.
If not, repeat the shimming procedure (or leveler adjustment) until the
front glass is properly aligned along both sides of the case.
END
PANEL
4. If FRONT-RIGHT CORNER
is too close to end panel (or
hitting it), adjust levelers at the
BACK RIGHT CORNER of
case DOWNWARD.
LIFT
14
Page 15
BAFFLES: AMBIENT VS. REFRIGERATED CONDITIONS
Baffles: Ambient vs. Refrigerated
Certain sections of the case can be either
ambient or refrigerated (depending upon type
of product being displayed).
A Dual-Purpose Baffle is provided to facilitate
desired condition. It is accessible through rear
doors.
The Baffle will prevent (or allow) refrigerated
air from circulating through the display area
and returning through the Air Return Grille.
1. For Ambient (Non-Refrigerated)
conditions, Baffle must be positioned to
block air flow. See photo #1 at top right.
Note
: Depending upon model, options and
features chosen, photos may not exactly
1
Photo of Baffle in Ambient (Non-Refrigerated) Position
reflect every aspect of your particular case.
2. To switch from Ambient to Refrigerated
condition, lift Baffle up and out of air
chamber. Rotate 90 degrees so arrows on
the tag point down and tag is to the rear of
the case. Lower Baffle, with slots facing
up, back down into the air chamber. See
photo #2 at mid-right.
3. For Refrigerated conditions, Baffle is
positioned to allow air to circulate through
display area and return through Air Return
Grille. See photo #3 at lower-right.
Note: To clean, remove Baffle from case,
2
brush out crumbs or residue from Baffle.
Wipe down with clean rag dipped in mild
soap and water solution.
Air Return Grille
Baffle
Tag
Tag
Air
Chamber
Photo of Baffle Removed From Chamber
Baffle
Air Return Grille
Baffle
3
Photo of Baffle in Refrigerated Position. Note: Airflow Direction
15
Page 16
OPTIONAL NIGHT AIR CURTAIN INSTALLATION & OPERATING INSTRUCTIONS
Night Air Curtain Installation & Operating Instructions
1. Use caution when handling Night Air Curtain.
2. Display case may come with Night Curtain already attached. If not, a retrofit kit
will be provided. If using the SCC-supplied retrofit kit, the Night Air Curtain
Support must first be attached to the existing Upper Front Duct Plate (see
illustration below). To attach, use the Night Air Curtain Support (as a template) by
placing it along the Front Duct Plate. Mark locations of existing Ø.20” hole onto
Upper Front Duct Plate. Drill clearance holes for #10 screws at these points.
3. Place Night Air Curtain Support into position and use the SCC-supplied screws to
attach it to the Upper Front Duct Plate (where pilot holes were just drilled).
4. Night Air Curtain Assembly may now b e placed on the Night Air Curtain Support.
Carefully positioned magnets will keep in place. Grasp the handle and pull
downward to desired location (see illustration below).
5. To return Night Air Curtain to its retracted position, grasp handle, lift up and away
from its magnetic attachment and carefully wind Night Air Curtain back into roll.
6. Caution!
Do not allow spring-loaded Night Air Curtain to freely snap back into roll.
Doing so can eventually destroy Night Air Curtain’s tension and retractability.
7. Note
: Due to ONLY the magnets keeping Night Air Curtain Assembly in place, it
may be removed at any time by firmly lifting up and off Night Air Curtain Support.
NOTE: THE
BELOW
ILLUSTRATION
MAY NOT
EXACTLY
REFLECT
EVERY
PARTICULAR
CASE’S
FEATURES
OR OPTIONS.
Acrylic
Sneeze
Guard)
M
O
u
S
n
e
Night Air Curtain
Support Existing
Hole (Typical)
N
i
a
g
g
h
n
t
e
A
t
i
s
r
t
s
i
d
e
e
z
e
G
Cu
T
o
r
A
V
e
r
u
a
r
t
a
t
t
i
n
a
c
t
h
i
c
A
a
l
l
o
Acr
d
S
u
n
g
y
l
i
c
p
p
o
r
t
Night Air
Curtain
Assembly
Night Air
Curtain
Support
Honeycomb
Upper Front
Duct Plate
16
Page 17
SECURITY GRID INSTRUCTIONS (OPTIONAL) - PAGE #1 of 2
Initial Positioning and Installation of Security Grid
1. Due to weight and size, Security Grid installment may require two (2) people.
2. After hoisting the Security Grid directly over Front Air Deflector, drop the (2)
Security Grid Positioning Rods into the Baffle Airflow Slots (see below).
3. After securely positioned in the Baffle Airflow Holes, carefully and slowly lean the
Security Grid back against the two Security Brackets.
4. The next page in this manual will show how to secure the top of the Security Grid
to the Security Brackets.
Enlarged View (Below)
Enlarged View (shown below)
shows Security Grid Positioning
Tab slid into Baffle Airflow Hole.
There is one Security Grid Position-
ing Tab on each Security Grid end.
Tabs must be securely positioned in
both Airflow Slots prior to locking
with Padlocks.
NOTE:
ILLUSTRATIONS
MAY NOT
EXACTLY
REFLECT EVERY
PARTICULAR
CASE’S
FEATURES
Front Air
Deflector
Baffle Airflow
Area
Security
Grid
Security Grid Positioning Rod
(Inserted in Baffle Airflow Hole)
17
17
Page 18
SECURITY GRID INSTRUCTIONS (OPTIONAL) - PAGE #2 of 2
Securing Security Grid Into Place and Locking
1. After leaning the Security Grid back against the two Security Brackets, slide the (two)
Padlocks through the Security Grid and the Security Brackets.
2. Securely lock the Padlocks (one Key fits both Padlocks).
Removing and Storing Security Grid and Locks
1. Due to weight and size, Security Grid removal requires two (2) people.
2. Unlock and remove Padlocks. Lean Security Grid forward. Lift upward and out of Baffle
Airflow Slots.
3. Store Security Grid, Padlocks and Keys in a secure location to prevent theft or damage.
Security Bracket
Enlarged View (At Left)
End Panel
Glass Lift
Enlarged View (at left) shows
Padlock through Security Grid
and Security Bracket.
There is one Security Bracket at
each end of Case.
Security
Grid
NOTE:
ILLUSTRATIONS
MAY NOT
EXACTLY
REFLECT EVERY
PARTICULAR
CASE’S
FEATURES
Padlock
Security Grid
18
Page 19
DRAIN, HOSE AND BRACKET PLACEMENT ILLUSTRATIONS
NOTE: BELOW ILLUSTRATIONS MAY
NOT EXACTLY REFLECT EVERY
PARTICULAR CASE’S FEATURES
Three Condenser Systems Are Illustrated Below:
Illustration #1: Hot Gas “CopeVap” Condenser
System. “Copevap” is built into Compressor Unit.
Illustration #2: Hot Gas Condenser System.
Illustration 3A/3B : Electrical Heat Rod Condenser
System. Note
: Separate Condenser Pan.
Warning! Regardless of Condenser, the Hose and
Drain Trap MUST BE secured and positioned over
Condenser Pan to prevent water seepage / spillage.
When sliding out Condenser Unit, be careful that
drain is not pulled from proper position.
Note: Drain
Bracket
positioned
directly over
Hose thru bracket
Reservoir
Drain Trap
“CopeVap”
Reservoir
Clamp
Clear PVC
Tube
2. Hot Gas Condenser System.
Hot gas serpentine coil is routed through a condensate
reservoir allowing water to be heated. This system
uses a wicking material (partially submersed) with
warm condenser air passing through it for evaporation.
Also incorporates an overflow reservoir with heating
element to ensure complete condensate removal.
This area of your unit
may widely vary (due to
display case options).
Sight Glass
Scroll
Compressor
Receiver
Elec. Box, Hot
Gas Condensate
Overflow
Fan
Shroud
Filter
Drier
1. Hot Gas “CopeVap” Evaporator System.
Use Hose Clamp
to Secure Hose
to Adapter
Clear PVC
Tube
Cond. Pan
Positioning
Bracket
3A. Front View of
Electrical Heat Rod Evaporator System
Drain
Trap
Condenser
Pan
Suction
Accumulator
Hot
Serpentine
Coil
Refrigeration
Assembly
Condenser Pan
Cond. Pan Positioning Bracket
3B. Isometric View of
Electrical Heat Rod Condenser System
Base
Wicking
Material
Compressor Pan
Shipment Screw
(1 at each side)
Drain
Trap
19
Page 20
CLEANING SCHEDULE: TO BE PERFORMED BY STORE PERSONNEL (PAGE 1 of 2)
AREA FREQ. INSTRUCTIONS
Exterior Daily
Daily
Daily
Weekly
Weekly
Weekly
All Glass / Mirrors: Clean side glass, front glass, glass shelves, and mirrors with
household or commercial glass cleaner. Clean out door track with moist cloth.
Rear Sliding Door Exterior Glass: Clean with household or commercial glass
cleaner.
End Panels, Front Panel, Toe-Kick, etc.: Wipe off all surfaces with warm water
and mild soap solution and non-abrasive cloth.
Wood, Laminate and Painted Surfaces: Clean with mild soap and water
solution and a soft cloth .
Acrylic Sneeze Guard: Clean with warm water, mild soap solution and soft
cloth; acrylic cleaning solutions are also available. Caution! Never use
ammonia-based cleaners on acrylic. Incorrect cleaning agents or abrasive
cleaning cloths cause surface to ‘cloud’ over time. See photo on next page.
Magnetic Air Filter and Condensing Coil: Clean condenser coil filter and
condenser coil fins. See corresponding photos a, b, c and d below.
a. Remove magnetic air filter. Remove dust, dirt, smoke and grease
stains by rinsing with hot water and multipurpose dish soap at sink.
b. Lift rear grille up and off (after removing screws).
c. Vacuum (or brush off) dust and dirt from condenser coil fins.
Warning! Do not use metallic objects to poke or insert into condenser
coil area!
d. Return rear grille and magnetic filter to case. Caution: Make certain
that magnetic filter completely covers all rear grille openings.
Monthly
Under Case Cleaning
case to remove all dust and dirt. Replace front toe-kick (or rear grille) when
complete.
a.
b.
: Remove front toe-kick (or rear grille). Vacuum under
c.
d.
20
Page 21
CLEANING SCHEDULE: TO BE PERFORMED BY STORE PERSONNEL (PAGE 2 of 2)
AREA FREQ. INSTRUCTIONS
Interior Weekly
Monthly
Monthly
Monthly
Monthly
Decks: Wipe off decks with moist cloth dipped in mild soap and water solution.
See photo below.
Tub and Drain: Keep clean and free of debris which could clog tub and drain.
To access drain area, remove the deck and fan shroud.
Vacuum tub under deck.
Direct the drain to a floor drain or a bucket.
Run hose into drain to flush out debris. Carefully hose out the tub.
Caution! Avoid splattering water over the case and surrounding areas!
Air Return Grille and Fan Shroud Area
: 1) Turn off power. 2) Remove decks
from case. 3) Clean with moist cloth.
Honeycomb Air Diffuser
: See MAINTENANCE FUNDAMENTALS: UPPER
SECTION AIR DUCT / HONEYCOMB AIR DIFFUSERS section in this manual
for cleaning instructions.
Air Duct - Upper Section
: See MAINTENANCE FUNDAMENTALS: UPPER
SECTION AIR DUCT / HONEYCOMB AIR DIFFUSERS section in this manual
for specifics.
Deck
Acrylic
Sneeze
Guard
21
Page 22
TROUBLESHOOTING [TO BE PERFORMED BY STORE PERSONNEL]
CONDITION TROUBLESHOOTING
Case Is Not Level
Case Not Lining Up
Water Is On The Floor
Fan Emits Excessive Noise
Case Lights Are Not
Working
Case is Not Holding Proper
Temperature
See ALIGNING CASE / FRAME SUPPORT RAIL SHIMMING /
ADJUSTING LEVELERS section in this manual for additional info.
See Installation Section for instructions on properly aligning case
(alongside other cases) and adjusting levelers (or rails).
Call service provider.
Call service provider.
Check that light switch is in the on position.
Check that ALL of the light cords and plugs are properly connected. See
MAINTENANCE: REAR SLIDING DOORS/LIGHT FIXTURES
[PERFORMED BY STORE PERSONNEL] section in manual.
If case lights still do not come on, call service provider.
If a large amount of warm product was added to the case, it will take
time for the temperature to adjust. Product must be pre-chilled before
placing in case.
Check that the case is not in the sun or near a heat or air-conditioning
vent. See OVERVIEW / NSF® TYPE / COMPLIANCE / WARNINGS / PRECAUTIONS section in this manual for specifics.
If case is located near front doors, temperature fluctuation can hinder
unit’s ability to maintain temperature.
Check that air filter and condenser coil has been cleaned. See
GENERAL CLEANING [TO BE PERFORMED BY STORE
PERSONNEL] section in this manual for specifics.
Check air return grilles (area at front of decking) for obstructions.
DO NOT set product on air grilles as this will prevent proper airflow!
If case still is not holding proper temperature, call service provider.
22
Page 23
MAINTENANCE: REAR SLIDING DOORS/LIGHT FIXTURES [PERFORMED BY ST ORE PERSONNEL]
Warning! Disconnect power before providing
maintenance and service to unit.
Caution: Lamps are treated to resist breakage and
must be replaced with similarly treated lamps.
Note: Warranty will be void if claims arise from
negligence, misuse of goods, extreme
environmental conditions or improper maintenance.
See Overview And Warnings section in manual.
Rear Sliding Doors
Note: Doors are not interchangeable. There is an inner
and outer door. Outer door must be removed first and
replaced last. See illustration at top-right.
The outer door is the right hand door (from the
service side or rear of case).
Move doors toward the center of the case.
Individually lift each door up toward the top of the
case; pivot the bottom of the door out.
Replace rear sliding doors in reverse order they
were removed.
Light Fixtures
Note: Depending upon model and options, light fixtures
can have either single or dual lamps.
Light fixtures are located on underside of shelf
assemblies and at the top inside of case. See
illustration at right for general locations.
Removal of lamps:
Rotate lamp (1/4-turn) to disengage (upper or lower)
pins/contacts from mounting sockets.
Remove bulb by applying even pressure from back
side at the bulb ends and pulling the remaining
contact from sockets.
See illustrations at mid and lower-right.
Installation of lamps:
Align pins with slot.
Insert pins into socket by rotating the bulb 1/4-turn
to secure either the (upper or lower) pin contacts
into the sockets.
To remove brackets, it may be necessary to remove
the nylon shipping bracket retainers.
Pliers will be required to accomplish this task.
See illustration at top-right for location of bracket
retainers.
Shelf Assembly Removal
Remove glass shelves
For lighted shelving, unplug the light cord.
Remove rear shelf support.
Remove shelf light cover from brackets.
Lift brackets up and out.
NOTE: SERVICE TO BE PERFORMED BY TRAINED
SERVICE PROVIDERS ONLY.
Drain and Expansion Valve Access
The drain and expansion valve are both accessible
from the front of the case.
Depending upon case, you may need to unplug fan
and remove fasteners from the access panel.
If no access panel to remove, the drain and expansion
valve (TXV) are directly below the decking and subdeck.
Rear Shelf Support
Gl
Bracket
Fan Plug
e
h
S
s
s
a
Shelf Light
Cover
f
l
TXV Access
Panel
Retainer
Locations
Lamp
Bracket
Shelf
Bracket
Evaporator
Fan
24
Page 25
MAINTENANCE FUNDAMENTALS: REFRIG. PKG., TEMP. CONTROLLER, EVAP. PAN ACCESS
Refrigeration Package Access
NOTE: SERVICE TO BE PERFORMED BY TRAINED
SERVICE PROVIDERS ONLY.
Air Filter
Magnetic strips attached to the filter adhere filter
to the rear grille.
See CLEANING SCHEDULE: TO BE
PERFORMED BY STORE PERSONNEL for
Air Filter
cleaning instructions.
See illustrations at top-right.
Rear Grille
Slide Out Refrigeration Package
Remove the rear grille. Grille may be slid upward
and out or
removal of screws may be required.
Temperature
Controller
Note: At initial slide-out, it may be necessary to
remove Compressor Pan Shipment Screws (see
illustration at right for location).
Refrigerant lines are flexible to facilitate rear access
maintenance.
Plastic glides are mounted at base to assist in sliding
the condenser out for access.
Service connections are at the left of compressor.
Slide condenser unit out 12 to 18 inches to access
high pressure service connection.
Evaporator
Pan
Refrigeration
Package Slide-Out
Condenser Pan Access / Removal
WARNING! Condenser Pan May Be Hot! Check
temperature of pan prior to handling.
Withdraw Condenser Pan from the right side behind
electrical box.
Unplug Condenser Pan from the electric outlet.
Empty Condenser Pan contents into suitable
container. Replace rear panel when completed.
Temperature Controller (Self-Contained Units Only)
Temperature Controller is located in the Ballast Box.
Temperature / Defrost control settings are
programmable from these locations.
Case Temperature Set Point is set at the factory, as
determined by case size & sensor probe location.
Temperature is controlled by thermostat.
Shipment
Screws
If a temperature setting change is required, follow
instructions regarding Temperature Control
Programming Steps in the technical information
section of this operating manual.
If service is required to the temperature control unit,
call Structural Concepts Corporation. Maintenance
should be performed by a certified technician.
The toll-free number is listed in the Technical
Service section of this manual.
See Temperature Controller section in this man-
ual.
NOTE: Spirit-filled thermometers located in the
refrigerated compartment are for monitoring warmest air temperature in accordance with NSF Std. 7.
25
Page 26
MAINTENANCE FUNDAMENTALS: UPPER SECTION AIR DUCT / HONEYCOMB AIR DIFFUSERS
NOTE: SERVICE TO BE PERFORMED BY TRAINED
SERVICE PROVIDERS ONLY.
Preventive maintenance should be performed every
90 days (unless conditions warrant a more frequent
replacement cycle).
Air Duct - Upper Section (see illustration at top-right)
Depending upon model, Upper Section Air Duct may
be removable for cleaning. If so, simply lift Air Duct
up and out of chamber to access area to clean.
If Upper Section Air Duct is not removable from case,
Honeycomb removal will allow access to area.
Clean with brush or vacuum with brush attachment.
Wipe down with moist cloth.
Honeycomb Air Diffuser Removal
A. Wedge non-metallic device of suitable strength (such
as a ballpoint pen) between honeycomb and end panel.
Caution
! Use care not to dislodge the heating wire (that
prevents condensation on the lamp assembly).
B. Apply pressure to collapse the honeycomb to allow it
to be pulled out of honeycomb retainer.
C. Pry downward and away from honeycomb retainer.
Clean honeycomb with warm water and soap solution.
Submerse if necessary. Use brush to dislodge stubborn
or sticky residue. Dry by using vacuum’s ‘blow mode’.
Honeycomb Air Diffuser Installation
D. Squeeze honeycomb into the honeycomb retainer.
E. Carefully slide honeycomb into place.
F. Adjust honeycomb so that it fits flat
against retainer.
It must not be wavy or out of position.
Air Diffuser
Air Duct
Upper
Section
Honeycomb Air Diffuser
A
B
F
D
C
E
26
Page 27
TROUBLESHOOTING [TO BE PERFORMED BY TRAINED SERVICE PROVIDERS ONLY] - PAGE 1 of 3
CONDITION TROUBLESHOOTING
Case Not Lining
Up
Water Is On The
Floor
See Installation Section for instructions on properly aligning case (alongside other
cases) and adjusting levelers.
Caution! Water on flooring can cause much damage! Until cause is determined (and
repaired), following these procedures:
Use wet-dry vacuum (or mop & bucket) to remove standing water.
Use ‘catch pans’ for water to drain into. Swap out regularly until case has
completely drained.
Note: See Drain, Hose and Bracket Placement Illustrations sheet in this manual for
views of different evaporator systems used in display cases.
Check that the drain trap is free of debris.
Check that the drain hose is correctly positioned over evaporator pan (or floor drain,
for remote units).
Check store conditions. To prevent condensation in NSF® Type 1 environments,
maximum conditions are to be 55% humidity / 75° Fahrenheit. For NSF® Type 2,
maximum conditions are to be 60% humidity / 80° Fahrenheit. See serial label (at
case rear near main power switch) for NSF® Type of your case.
Check evaporator pan float for proper operation (Heat Rod Evaporator System only).
Check that evaporator pan is properly plugged in or connected.
Caution! Evaporator pan may be malfunctioning (Electrical Heat Rod Evaporator
system). If so, water will overflow pan and seep onto flooring causing damage! Until
evaporator pan is functioning (or is replaced), following these procedures:
Use wet-dry vacuum (or mop & bucket) to remove standing water.
Use ‘catch pans’ for water to drain into. Swap out regularly until case has
completely drained.
Caution! Disruption of power can cause water to overflow pan and seep onto
flooring causing damage! Check that power to case is constant. Until power is
restored, following these procedures:
Use wet-dry vacuum (or mop & bucket) to remove standing water.
Use ‘catch pans’ for water to drainage. Swap out regularly until evaporation of
case is complete (or until power is restored).
When power to case is restored, evaporator pan should function properly and water
will no longer overflow onto flooring.
Caution! Wicking material may be dirty or worn and need replacement (Hot Gas
Evaporator system only).
Slide refrigeration system out from under unit.
After refrigeration system has been carefully slid out from under unit, replace
wicking material with new. If wicking material is not available, contact Structural
Concepts®. See toll-free number at last page of this operating manual.
27
Page 28
TROUBLESHOOTING [TO BE PERFORMED BY TRAINED SERVICE PROVIDERS ONLY] - PAGE 2 of 3
CONDITION TROUBLESHOOTING
Fan Emits Excessive
Noise
Fans Are Not Working
Check that the case is aligned, level and plumb.
Check evaporator fan for cleanliness.
Unplug/power off fan motors. Check motor shaft for bearing wear.
Check that fan motors are securely mounted in brackets.
Verify that fan blades are securely mounted to fan motor.
Check that nothing is preventing blade rotation.
Check that the fan shroud is properly secured.
Check that the MAIN power switch is on.
Check that fans are plugged in at the fan shroud.
Digital Control Display
Is Blank
System Not Operating
Check for foreign material obstructing fan performance.
Check that fan blades freely rotate within fan shrouds
Check that power is going to fans
Check that fan wiring is connected on terminal blocks.
Check that the MAIN power switch is on.
Check the circuit breaker box for tripped circuits.
Check that the utility power is on.
Check that the MAIN power switch is on.
Check the circuit breaker box for tripped circuits.
28
Page 29
TROUBLESHOOTING [TO BE PERFORMED BY TRAINED SERVICE PROVIDERS ONLY] - PAGE 3 of 3
CONDITION TROUBLESHOOTING
Case Lights Are Not
Working
Control Display Is
Flashing
Case Is Not Holding
Temperature
Check that light switch is in the on position.
Check that ALL of the light cords and plugs are properly connected. See
MAINTENANCE - LIGHT FIXTURES (LED LIGHT FIXTURES) section.
Service Technicians Only: Check voltage at LED drivers. If voltage is entering but
not exiting, LED driver may be faulty.
See your case’s serial label for your model’s specified settings. See SERIAL
LABEL LOCATION & INFORMATION LISTED / TECH INFO & SERVICE for label
location, etc.
If a large amount of warm product was added to the case, it will take time for the
temperature to adjust. Unit needs product to be pre-chilled.
Temperature changes during defrost mode but will return to normal. Fourth LED
will indicate defrost cycle in progress.
Check that case is not in sun or near a heat or air-conditioning vent. See
OVERVIEW AND WARNINGS section in manual for adverse conditions/spacing
issue parameters.
Condensing Unit Is
Not Operating
If case is located near front doors, temperature fluctuation can hinder unit’s ability
to maintain temperature. See OVERVIEW AND WARNINGS section in manual for
adverse conditions/spacing issue parameters.
Check that magnetic air filter (attached to rear grille) has been cleaned. See
GENERAL CLEANING [TO BE PERFORMED BY STORE PERSONNEL] section
in operating manual for instructions.
Check that condenser coil has been cleaned.
Check air return grilles for obstructions.
Check sight glass for flashing and/or low charge.
Check Set Point Temperature; it may be adjusted too high.
Check that the power is turned on.
Determine if temperature controller settings are properly set. See your case’s
serial label for your model’s specified settings. See SERIAL LABEL LOCATION
& INFORMATION LISTED / TECH INFO & SERVICE section in manual for label
location, etc.
29
Page 30
TROUBLESHOOTING - CONDENSING SYSTEM [TRAINED SERVICE PROVIDERS ONLY]
CONDITION TROUBLESHOOTING
Head Pressure Too High
Check that the Condensing Coil is not dirty or covered.
Check that Condensing Fans are working.
Check that the refrigeration system is not overcharged.
Check that case is free of non-condensables.
Check that the Liquid Line Drier Filter is not plugged.
Check Set Point temperature; it may be adjusted too high.
Head Pressure Too Low
Check System Operating temperatures.
Check that Store Ambient temperature isn’t above maximum
allowed. See Overview and Warnings Section.
Check that Refrigerant Charge isn’t too low.
Check that Suction Pressure isn’t too low.
Check to verify that Compressor Valves aren’t faulty.
30
Page 31
TROUBLESHOOTING - EVAPORATOR SYSTEM [TRAINED SERVICE PROVIDERS ONLY]
CONDITION TROUBLESHOOTING
Low Suction Pressure
High Suction Pressure
Check for low refrigerant.
Check that Expansion Valve isn’t restricted.
Check that Liquid Line or Filter isn’t restricted.
Check that Evaporator Motors are working.
Check for Superheat setting.
Check that the Thermostatic Element charge isn’t depleted.
Check that the Coil is not iced up.
Check that Refrigerant Charge isn’t too high.
Check that Compressor Valves aren’t faulty.
Check that there is no air seepage around Condensing Coil.
Check that the Cooling Load isn’t high.
Check that Superheat adjustment isn’t low.
Check TXV Bulb Installation
a. Poor thermal contact.
b. Warm location.
Check Compressor: Low capacity means it is undersized for its
application.
31
Page 32
PREVENTIVE MAINTENANCE [TO BE PERFORMED BY TRAINED SERVICE PROVIDER] - Page 1 of 2
PREVENTIVE
MAINTENANCE
Case Exterior Monthly Condensing Coil:
Quarterly Clean Sweep™ Condensing Coil: Disconnect power from case
FREQUENCY INSTRUCTIONS
Note: The vacuum ‘blow mode’ is to be used when cleaning the
condenser coil. Follow these steps:
a. Remove grille; use vacuum and brush to dislodge and remove
dust on and in coil
b. Place damp rags around condensing fan motor brackets to
collect airborne dust.
c. Using vacuum (in ‘blowing’ mode), blow air through condenser
coils and into fans. Make certain to blow entire surface of
condensing coils to assure that all entrenched dust is removed.
Caution! Coil fins are sharp. Handle with care!
d. Replace Rear Grille to case.
before cleaning Clean Sweep™ Condenser Coil!
Remove Rear Grille (by removing 4 screws).
Slide/Roll out condensing unit assembly.
Remove the four (4) screws holding the Clean Sweep™ rails
intact.
Remove the Clean Sweep™ rail.
Wash rails’ brushes in hot water and mild soap solution.
If brushes are worn, they must be replaced. Call Technical
Service Department to replace. Toll-Free number is listed at
end of manual.
Clean Condensing Coil: Use air pressure or industrial strength
vacuum; clean the dust and dirt that may collect on the Condenser Coil.
Caution! Coil fins are sharp. Handle with care!
Reattach Clean Sweep rail to condensing unit (4 screws).
Slide/Roll Condensing Unit Assembly back under case.
Replace Rear Grille to case (4 screws).
See photos below.
ng
i
s
n
de
n
Co
(4) Screws
--- Above photos are taken after rear grille has been removed from case ---
32
Coil
Rail
Brushes
Page 33
PREVENTIVE MAINTENANCE [TO BE PERFORMED BY TRAINED SERVICE PROVIDER] - Page 2 of 2
WARNING! TURN OFF CASE BEFORE PERFORMING PREVENTIVE MAINTENANCE!
PREVENTIVE
FREQUENCY INSTRUCTIONS
MAINTENANCE
Case Exterior Quarterly Condenser Pan: Caution! Disconnect from receptacle box.
Remove mounting screws from base.
Use de-scaling solution (such as CLR® that will prevent corro-
sion, lime and rust) to clean pan.
Rinse thoroughly; do not submerse in water.
Reattach pan to case with same mounting screws.
Reconnect power cord to receptacle box.
Quarterly Compressor Area: Caution! Be certain to disconnect power from
case before cleaning Compressor Area!
Slide/Roll compressor package out from under case.
Use moist cloth to wipe off dust & debris that collects on various
parts.
Slide/Roll compressor package back under case.
Quarterly
Under Case Cleaning: Once refrigeration package is clear of unit,
vacuum under case to remove all dust and dirt that may collect under case.
Case Interior Quarterly Tub, Coil, Drain, Fan Blades, Motors, Brackets:
Disconnect power from the case before cleaning the Tub, Coil, Fan,
Motor and Drain Area!
Remove Decking, Sub-Deck and Fan Shroud.
Use vacuum to clean Evaporator Coils.
Clean Tub, Coil and Drain with warm water, clean cloth, brush
and mild soap solution.
Remove any debris that may clog drain.
Clean Fan Blades, Motors and Brackets by wiping down with
moist cloth.
33
Page 34
SERIAL LABEL LOCATION & INFORMATION LISTED / TECH INFO & SERVICE
Serial Label Location & Information Listed / Technical Information & Service
Serial Label Location & Information Listed / Technical Information & Service
Serial labels are located near the electrical access on your case.
Serial labels are located near the electrical access on your case. Serial labels contain electrical, temperature & refrigeration information, as well as regulatory
Serial labels contain electrical, temperature & refrigeration information, as well as regulatory
standards to which the case conforms.
standards to which the case conforms.
For additional technical information and service, see the TECHNICAL SERVICE page in this
For additional technical information and service, see the TECHNICAL SERVICE page in this
manual for instructions on contacting Structural Concepts’ Technical Service Department.
manual for instructions on contacting Structural Concepts’ Technical Service Department.
See images below for samples of both refrigerated and non-refrigerated serial labels.
See images below for samples of both refrigerated and non-refrigerated serial labels.
S
S
S
A
A
M
M
P
P
L
L
A
M
E
E
P
L
ON
ON
E
L
L
Y
Y
O
N
L
Y
Y
Y
L
O
O
L
NL
O
NL
NL
Y
Y
Y
SA
MP
L
E
S
S
O
A
A
N
MP
MP
L
LE
LE
Y
SA
----- Sample Serial Label For Refrigerated Case -----
----- Sample Serial Label For Refrigerated Case -----
M
M
SA
SA
ON
ON
PLE
M
PLE
PLE
----- Sample Serial Label For Non-Refrigerated Case -----
----- Sample Serial Label For Non-Refrigerated Case -----
888 E. Porter Road · Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com
888 E. Porter Road · Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com
34
34
Page 35
Read And Save These Instructions - Page 1 of 3
Integrated Electronic
Microprocessor Controller
Programming The Instrument
To Modify The Setpoint
Press and hold the “SET” key for at least 1 second.
Set
Prg
mute
Set
▲
aux
def
▼
▲
aux
3. Quickly press and release the “SET” key again.
Set
To Modify Defrost, Differential or Other Parameters
Prg
mute
Set
▲
aux
Set
▲
aux
Set
Prg
mute
Warning! Save Your Parameter Settings!
1. To store the new parameter values, PRESS and HOLD the “Prg” key for at least 5 seconds.
2. All modifications made to parameters will be lost if you do NOT press a button within 60 seconds. Should
this “timeout” occur, normal operational settings (prior to modifications being made) will resume.
3. If the instrument is switched off before pressing the “Prg” key, all modifications to parameters will be lost.
def
▼
▲
aux
2. Use arrow keys ▲ ▼ on temperature
def
controller to increase (or decrease) the
▼
setpoint.
1. Press & hold “Prg” & “SET” keys together
Set
for five (5) seconds; display will flash “0”,
representing password prompt.
2. Confirm by pressing “SET” key.
3. Press ▲ or ▼ to reach the
def
category to be modified.
▼
4. Press “SET” to modify this selected parameter.
To Activate Manual Defrost
Press and hold the “def” key for at least 5 seconds.
5. Increase or decrease the value using
def
the ▲ or ▼ button respectively.
▼
6. Press the “SET” key to temporarily save the new
value and return to the display of the parameter.
7. Press & hold the “Prg” key for at least 5 seconds
to save changes. This action will also mute the
audible alarm (buzzer) & deactivate the alarm relay.
To Activate / Deactivate Auxiliary Output
Press and hold the “aux” key for 1 second.
How To Change Reading From
Prg
mute
Set
▲
aux
Set
▲
aux
Set
Fahrenheit (°F) To Celsius (°C)
1. Press and hold “Prg” and “SET” keys
together for at least 5 seconds; display will
Set
show “0”, representing password prompt.
2. Confirm by pressing “SET” key.
4. Press “SET” to modify this selected parameter.
3. Press ▲ or ▼ until reaching the
def
parameter “/ 5”.
▼
5. Press ▲ or ▼ to change value to desired
def
setting: “0” for Celsius (°C) or “1” for
▼
Fahrenheit (°F).
6. Press “SET” key to temporarily save the new
value and return to the display of the parameter.
7. Press & hold “Prg” key for at least 5 seconds to
Prg
save changes.
mute
convert to new scale. No conversion is required.
Prg
mute
▲
aux
key for at least 1 second.
Note! All values will automatically
To Reset Any Alarms With Manual
Reset
Press and hold the “Prg” and “aux”
Structural Concepts Corp., 888 E. Porter Rd · Muskegon, MI 49441
Ph: 231.798.8888 / Fax: 231-798-0393 / www.structuralconcepts.com
(Note: Standard Limited Warranty can be found at www.Structuralconcepts.com)
All sales by Structural Concepts Corporation (SCC) are subject to the following limited warranty. “Goods” refers to the product or products being sold by SCC.
Warranty Scope: Warranty is for equipment sold in the United States, Canada, Mexico and Puerto Rico. Equipment sold elsewhere may carry modified warranty.
Warranty; Remedies; Limitations. SCC warrants that if any Goods are found by an authorized representative of SCC not to be of good material or workmanship within one
year of the date of shipments SCC will, at its option after inspection by an authorized representative, replace any defective Good or pay the reasonable cost of replacement
for any such defective Goods, provided that written notice of the defect is given to SCC within 30 days of the appearance of such defect. If notice is not given within such
period, any claim for breach of warranty shall be conclusively deemed to have been waived and SCC shall not be liable under this warranty. If SCC is unable to repair or
replace the defective Goods, SCC shall issue a credit to the Purchaser for all or part of the purchase price, as SCC shall determine. The replacement or payment in the
manner described above shall be the sole and exclusive remedy of Purchaser for a breach of this warranty. If any Goods are defective or fail to conform to this warranty,
SCC will furnish instructions for their disposition. No Goods shall be returned to SCC without its prior consent.
SCC’s liability for any defect in the Goods shall not exceed the purchase price of the Goods. SCC SHALL HAVE NO LIABILITY TO PURCHASE FOR CONSEQUENTIAL
DAMAGES OF ANY KIND WHATSOEVER, INCLUDING, BUT NOT LIMITED TO, PERSONAL INJURY, PROPERTY DAMAGE, LOST PROFITS, OR OTHER ECONOMIC
INJURY DUE TO ANY DEFECT IN THE GOODS OR ANY BREACH OF SCC, SCC SHALL NOT BE LIABLE TO THE PURCHASER IN TORT FOR ANY NEGLIGENT DESIGN OR MANUFACTURE OF THE GOODS, OR FOR THE OMISSION OF ANY WARNING THEREFROM.
SCC shall have no obligation or liability under this warranty for claims arising from any other party’s (including Purchaser’s) negligence or misuse of the Goods or
environmental conditions. This warranty does not apply to any claim or damage arising for or cause by improper storage, handling, installation, maintenance, or from fire,
flood, accidents, structural defects, building settlement or movement, acts of God, or other causes beyond SCC’s control.
Except as expressly stated herein, SCC makes no warranty, express, implied, statutory or otherwise as to any parts or goods not manufactured by SCC. SCC shall warrant
such parts or Goods only (I) against such defects, (II) for such periods of time, and (III) with such remedies, as are expressly warranted by the manufacturer of such parts of
Goods. Notwithstanding the foregoing, any warranty with respect to such parts of Goods and any remedies available as a result of a breach thereof shall be subject to all of
the procedures, limitations, and exclusions set forth herein.
THE WARRANTIES HEREIN ARE IN LIEU OF ALL WARRANTIES, EXPRESS, IMPLIED, STATUTORY, OR OTHERWISE. IN PARTICULAR, SCC MAKES NO
WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
No representative, agent or dealer of SCC has authority to modify, expand, or extend this Warranty, to waive any of the limitations or exclusions, or to make any different or
additional warranties with respect to Goods.
Period of Limitations. No claim, suit or other proceeding may be brought by Purchaser for any breach of the foregoing warranty or this Agreement by SCC or in any way
arising out of this Agreement or relating to the Goods after one year from the date of the breach. In the interpretation of this limitation on action for a breach by SCC, it is
expressly agreed that there are no warranties of future performance of the goods that would extend that period of limitation herein contained for bringing an action.
Indemnifications. Purchaser agrees to indemnify, hold harmless, and defend SCC if so requested, from any and all liabilities, as defined herein, suffered, or incurred by SCC
as a result of, or in connection with, any act, omission, or use of the Goods by Purchaser, its employees or customers, or any breach of this Agreement by Purchaser.
Liabilities shall include all costs, claims, damages, judgments, and expenses (including reasonable attorney fees and costs).
Remedies of SCC. SCC’s rights and remedies shall be cumulative and may be exercised from time to time. In a proceeding or action relating to the breach of this Agreement
by Purchaser, Purchaser shall reimburse SCC for reasonable costs and attorney’s fees incurred by SCC. No waiver by SCC of any breach of Purchaser shall be effective
unless in writing nor operate as a waiver of any other breach of the same term thereafter. SCC shall not lose any right because it has not exercised it in the past.
Applicable Law. This Agreement is made in Michigan and shall be governed by and interpreted according to Michigan law. Any lawsuit arising out of this Agreement or the
Goods may be handled by a federal or state court whose district includes Muskegon County, Michigan, and Purchaser consents that such court shall have personal
jurisdiction over Purchaser.
Miscellaneous. If any provision of this Agreement is found to be invalid or unenforceable under any law, the provision shall be ineffective to that extent and for the duration of
the illegality, but the remaining provisions shall be unaffected. Purchaser shall not assign any of its rights nor delegate any of this obligations under this Agreement without
prior written of SCC. This Agreement shall be binding upon and inure to the benefit of SCC and Purchaser and each of their legal representatives, successors and assigns.
SCC warrants its products to be free of defects in materials and workmanship under normal use and service for a period of one (1) year from the date of delivery.
This warranty is extended only to the original purchaser for use of the Goods. It does not cover normal wear parts such as plastic tongs, tong holders, tong cables, bag
holders, or acrylic dividers.
General Conditions. All service labor and/or parts charges are subject to approval by SCC. Contact the Customer Service Department in writing or call 231-798-8888.
All claims must contain the following information: (1) model & serial code number of equipment; (2) the date and place of installation; (3) the name and address of the agency
which performed the installation; (4) the date of the equipment failure; and (5) a complete description of the equipment failure and all circumstances relating to that failure.
Once the claim has been determined to be a true warranty claim by SCC’s Customer Service Department, the following procedure will be taken: (1) replacement parts will be
sent at no charge from SCC on a freight prepaid basis; (2) reimbursement for service labor will be paid if the following conditions have been met— (a) prior approval of service agency was awarded from the Customer Service Department; and (b) an itemized statement of all labor charges incurred is received by the Customer Service Department. The cost of the service labor reimbursement will be based on straight time rates and reasonable time for the repair of the defect.
If problems occur with any compressor, notify SCC’s Customer Service Department immediately. Any attempt to repair or alter the unit without prior consent from the
Customer Service Department will render any warranty claim null and void. This warranty and protection plan does not apply to any condensing unit or any part thereof which
has been subject to accident, negligence, misuse, or abuse, or which has not been operated in accordance with the manufacturer’s recommendations or if the serial number
of the unit has been altered, defaced, or removed.
Limit of Liability. The limit of liability of SCC toward the exchange cost of the original condensing unit, F.O.B. SCC, Norton Shores, MI, of each motor-compressor assembly
replaced during the warranty shall not exceed manufacturer's current established wholesaler’s exchange price and in no case shall the labor of removing or replacing the
motor-compressor or parts thereof be the responsibility of SCC.
38
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.