Structural Concepts FSC663R Installation Manual

Page 1
READ AND SAVE THESE INSTRUCTIONS
INSTALLATION &
OPERATING MANUAL
SCC P/N
20-30109
888 E. Porter Road · Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com
I:\Oper Manual\Oasis\FSC463R Ref Grab-N-Go 20-30109.pub
Merchandiser Shown With Product
For Illustrative Purposes Only
Rev B Date: 12.23.2013
Page 2
TABLE OF CONTENTS
OVERVIEW / TYPE / COMPLIANCE / WARNINGS / PRECAUTIONS / WIRING DIAGRAM ..............
REMOVAL OF CASE FROM SKID / POSITIONING UNIT ..…………..………………………………….. ADJUSTING LEVELERS ………………………………………………...………………………………...…. FIELD WIRING BOX / ACCESS / PANEL REMOVAL / MAIN POWER SWITCH / TEMP. CONTROL CEILING ORIGINATED ELECTRICAL & REFRIGERATION LINES / KNOCKOUT REMOVAL /
SEALING ………………………………………………………………………………………………. MODEL FSC463R PLAN-O-GRAM (LOAD LEVEL GUIDELINES) ..……………………………………. DIGITAL THERMOMETERS / SECURITY COVER INSTALLATION & REMOVAL …………..…..…... POWER-UP CHECK (EVAPORATOR FAN AREA) ...…………………………………………………….. MAINTENANCE FUNDAMENTALS: NON-ADJUSTABLE SHELF / BR ACKET ASSEMBLY ...…….
MAINTENANCE FUNDAMENTALS, CONTINUED: LED LIGHT FIXTURES / REMOVAL / REPLACEMENT ………………………………………………………………………………...……..
REFRIGERATION FUNDAMENTALS: UNDERSIDE LAYOUT (BOTH SELF-CONTAINED & REMOTE) ………………………………………………………………………………………………. REFRIGERATION FUNDAMENTALS: SELF-CONTAINED UNIT ILLUSTRATED PARTS BREAKDOWN ………………………………………………………………………………………….
GENERAL CLEANING (TO BE PERFORMED BY STORE PERSONNEL) - EXTERIOR / INTERIOR GENERAL CLEANING (TO BE PERFORMED BY TRAINED SERVICE PROVIDERS ONLY) …..….
TROUBLESHOOTING (TO BE PERFORMED BY STORE PERSONNEL UNLESS STATED OTHERWISE) ………………………………………………………………………………………….. TROUBLESHOOTING (TO BE PERFORMED BY TRAINED SERVICE PROVIDERS ONLY) ………. TROUBLESHOOTING (BY TRAINED SERVICE PROVIDERS ONLY) - CONDENSING SYSTEM TROUBLESHOOTING (BY TRAINED SERVICE PROVIDERS ONLY) - EVAPORATOR SYSTEM
PREVENTIVE MAINTENANCE (TO BE PERFORMED BY TRAINED SERVICE PROVIDERS) ……. PREVENTIVE MAINTENANCE: HONEYCOMB AIR DIFFUSERS (TO BE PERFORMED BY TRAINED SERVICE PROVIDERS ONLY) .………………………………………………………...
SERIAL LABEL LOCATION & INFORMATION LISTED / TECH INFO & SERVICE………………......
CAREL® CONTROLLER - PROGRAMMING THE INSTRUMENT….……………………...….…….......
CAREL® CONTROLLER - USER INTERFACE, SUMMARY TABLES OF ALARMS & SIGNALS …. CAREL® CONTROLLER - Summary Table of Operating Parameters (After Programming Key) .
TECHNICAL SERVICE CONTACT INFORMATION & WARRANTY INFORMATION ..…………….....
3-4
5 6 7
8
9 10 11 12 13
14 15 16
17
18
19-20
21 22
23 24 25 26
27 28
29
2
Page 3
OVERVIEW / TYPE / COMPLIANCE / WARNINGS / PRECAUTIONS / WIRING DIAGRAM - PAGE 1 of 2
OVERVIEW
 These Structural Concepts merchandisers are
designed to merchandise packaged products at 41 °F (5 °C) or less product temperatures.
 Cases should be installed and operated according to
this operating manual’s instructions to ensure proper performance.
 Improper use will void warranty.
TYPE 1 vs. TYPE 2 CONDITIONS
This unit is designed for the display of products in ambient store conditions where temperatures and humidity are maintained within a specific range.
 Self-Contained cases are designed for Type 1
conditions: Ambient conditions at 55% maximum humidity and maximum temperatures of 75 °F (24 °C).
 Remote cases are designed for Type 2 conditions:
Ambient conditions at 60% maximum humidity and maximum temperatures of 80 °F (27 °C).
This equipment MUST be installed in compliance with
all applicable NEC, federal, state and local
electrical and plumbing codes.
 If unsure if your case is designed for Type 1 or Type 2
conditions, see identifier label on your case. Location may vary.
COMPLIANCE
 Performance issues when in violation of applicable
NEC, federal, state and local electrical and plumbing codes are not covered by warranty.
 See below compliance guideline.
WARNINGS
 This sheet contains important warnings to prevent
injury or death.
 Please read carefully!
PRECAUTIONS, MAINTENANCE & WIRING DIAGRAM INFORMATION
 See next page for PRECAUTIONS, MAINTENANCE
and WIRING DIAGRAM information.
COMPLIANCE
WARNING
ELECTRICAL
HAZARD
WARNING
KEEP
HANDS
WARNING
Risk of electric shock. Disconnect power before servicing unit.
CAUTION! More than one source of electrical supply is
employed with units that have separate circuits.
Disconnect ALL ELECTRICAL SOURCES before servicing.
WARNING
Hazardous moving parts. Do not operate unit with covers removed.
Fan blades may be exposed when deck panel is removed.
Disconnect power before removing deck panel.
WARNING! POWER CORD AND PLUG MAINTENANCE
Risk of electric shock. If cord or plug becomes damaged,
replace only with cord and plug of same type.
3
Page 4
OVERVIEW / TYPE / COMPLIANCE / WARNINGS / PRECAUTIONS / WIRING DIAGRAM - PAGE 2 of 2
PRECAUTIONS
 This sheet contains important precautions to prevent
damage to unit or merchandise.
 Please read carefully!  See previous page for specifics on OVERVIEW,
CONDITION TYPE, COMPLIANCE and WARNINGS.
CAUTION! LED LAMP REPLACEMENT GUIDELINES
CAUTION
LED lamps reflect specific size, shape and overall design.
Any replacements must meet factory specifications.
CAUTION! GFCI BREAKER USE REQUIREMENT
If N.E.C. (National Electric Code) or your local code
requires GFCI (Ground Fault Circuit Interrupter) protection,
you MUST use a GFCI breaker in lieu of a GFCI receptacle.
CAUTION
 Performance issues caused by adverse conditions are NOT warranted.  End panels must be tightly joined or kept at least 6-inches away from
CAUTION! ADVERSE CONDITIONS / SPACING ISSUES
any structure to prevent condensation.
 Unit must be kept at least 15-feet from exterior doors, overhead HVAC
vents or any air curtain disruption to maintain proper temperatures.
 Unit must not be exposed to direct sunlight or any heat source
(ovens, fryers, etc.).
 Tile floors/low ceilings/small rooms increase noise level. Whisper Cool
compressor blanket or remote unit may resolve noise level issues.
 Keep at least 8-inch clearance above unit for air discharge
(self-contained units only).
WIRING DIAGRAM
 Each case has its own wiring diagram folded and in
its own packet.
 Wiring diagram placement may vary; it may be
placed near ballast box, field wiring box, raceway cover, or other related location.
CAUTION! WATER ON FLOOR CAN CAUSE EXTENSIVE DAMAGE
Before powering up unit:
 Check that drain lines flow directly to floor drain.  Units with optional Clean Sweep™ MUST be properly connected.
4
Page 5
REMOVAL OF CASE FROM SKID / POSITIONING UNIT
1. Remove Unit From Skid
For your safety, the equipment is furnished with a properly grounded cord connector. Do not attempt to defeat the grounded connector.
 Caution! Remove BOTH lower panels from case
before removing from skid to prevent buckling.
 Illustrations below show case being removed
from skid.
 Place case in proper location.  Plug cord into certified electrical outlet with
ground.
2. Positioning Unit
 Place unit into desired location before leveling.  See next page for specifics about leveling.
Slide Skid Out From Under Case
5
Page 6
ADJUSTING LEVELERS
Adjust Levelers
 After case is in position, adjust case so it is level
and plumb.
 You may need to remove front and/or rear
toe-kick to access levelers.
Pry Bar
 Use adjustable wrench (and/or a pry bar) to adjust
leveler.
 Do not use Pry Bar on Toe-Kick as it will buckle.  Do not use Pry Bar on End Panel. It may chip.  Use Pry Bar ONLY on Base Frame to avoid
damaging case.
6
Page 7
FIELD WIRING BOX / ACCESS / PANEL REMOVAL / MAIN POWER SWITCH / TEMP. CONTROL
If main power switch is not turned on, lights will
1. Field Wiring Box / Access
 Warning! Turn power off and/or disconnect
power before providing maintenance and service to unit.
 Assembly/disassembly/servicing to be
performed by licensed electrical contractor.
 Panel must be removed to access field wiring box
and main power switch.
 See illustration below.
2. Panel Removal

not turn on NOR will refrigeration components operate.
 See illustration below.
4. Temperature Control
 Illustration below shows location of temperature
controller (after removal of front panel).
 See Carel Temperature Controller information
in this manual for specifics on settings.
 To remove panel (and access field wiring box), lift
panel up and off case hooks by grasping firmly and pulling up and outward. See illustration at top-right.

3. Main Power Switch
 For self-contained cases, the main power switch
controls power to entire case.
Slots For Attaching
To Case Hooks
Field Wiring /
Ballast Box
Removable Front Panel
Main Power
Switch
Self-Contained Merchandiser
(Partially Disassembled)
Thermostat Controller &
Main Power Switch
7
Page 8
CEILING ORIGINATED ELECTRICAL & REFRIGERATION LINES / KNOCKOUT REMOVAL / SEALING
1. Merchandiser Versatility
 Structural Concepts cases can accompany
either floor or ceiling-originated electrical and/or refrigeration lines.
 This page shows how ceiling-originated lines
are routed into case.
2. Ceiling Routed Electrical/Refrigeration. Lines
 A center pass-through protective plate is
mounted at top of case over two (2) PVC center pass-throughs.
 If electrical/refrigeration lines are ceiling-
originated, remove plate knockouts.
 Electrical and/or refrigeration lines may then be
dropped through PVC center pass-throughs.
Center Pass-Through Protective Plate Mounted on Merchandiser
 Caution! If ceiling-originated lines are used,
you MUST seal both upper and lower PVC center pass-throughs (at entrance points) with expandable foam sealant to prevent condensation in case.
3. Plate Removal
 Note: Though not required, protective plate can be
removed from merchandiser via four (4) screws.
4. Case Underside
 See REFRIGERATION FUNDAMENTALS:
UNDERSIDE LAYOUT (BOTH SELF­CONTAINED & REMOTE) section in this manual
for location of center pass-throughs at underside of case.
Caution! If ceiling originated lines are
used, you MUST seal both upper and
lower PVC center pass-throughs (at
entrance points) with expandable
foam sealant to prevent
condensation in case.
Center Pass-Through
Protective Plate Shown After
Removal of Knock-Outs
8
Page 9
MODEL FSC463R PLAN-O-GRAM (LOAD LEVEL GUIDELINES)
Model FSC463R Plan-O-Gram (Load Level Guidelines)
SCC P/N 20-30299
> Note: Any changes to this document must also be made to Operating Manual P/N 20-30299
CAUTION! TO MAINTAIN SAFE PRODUCT TEMPERATURES AND AIRFLOW CAREFULLY FOLLOW THESE GUIDELINES:
 DO NOT STACK PRODUCT NEARER THAN 1” TO UNDERSIDE OF PLENUM  DO NOT STACK PRODUCT NEARER THAN 1” TO UNDERSIDE OF SHELVES  DO NOT ALLOW PRODUCT TO HANG OVER FRONT OF SHELVES  DO NOT STACK PRODUCT ON DECKS HIGHER THAN UNDERSIDE OF SHELF  DO NOT ALLOW PRODUCT ON DECKS TO HANG OVER PRODUCT STOP
ACCEPTABLE
PRODUCT PLACEMENT
1” Min.
1” Min.
1” Min.
1” Min.
Acrylic Air
Deflector
Product
Stop
UNACCEPTABLE
PRODUCT PLACEMENT
Do Not Stack Product
Nearer Than 1” To
Underside of Plenum
ct
u
d
o
r
P
ct
u
d
o
r
P
ct
u
d
o
r
P
ct
u
d
o
r
P
Do Not Stack Product
Nearer Than 1” To
Underside of Shelves
Do Not Allow Product
To Hang Over Front
of Shelves
Do Not Stack Product On
Decks Higher Than The
Underside Of Lower Shelf
Do Not Allow Product
On Decks To Hang Over Product Stop
P
P
P
r
P
ct
u
d
o
r
ct
u
d
o
r
ct
u
d
o
r
ct
u
d
o
--- SIDE VIEW ---
NOTE: ANY
REVISIONS TO THIS
DOCUMENT MUST
ALSO BE MADE TO
SCC P/N 20-30299
--- SIDE VIEW ---
9
Page 10
DIGITAL THERMOMETERS / SECURITY COVER INSTALLATION & REMOVAL
1. Digital Thermometers
Digital thermometers are located on rear plenum at upper area of case.
 Digital thermometers are on BOTH side of case.  See enlarged illustration at lower-left.
2. Security Cover Installation (Optional)
A. Place security cover inside lower retainer
bracket. See illustration of random unit with
lower retainer bracket at below-right. B. Lean security cover against header at top of unit. C. With key inserted in the lock, rotate the locking
mechanism’s “flat bar” into the bracket with slot at
center of case. See illustration at top-right and
mid-right.
3. Security Cover Removal (Optional)
A. With key inserted in the lock, rotate the locking
mechanism’s “flat bar” out of the bracket with slot
(as shown in top-right illustration).
Digital Thermometer
Header
B. Lean security cover away from header at top of
unit.
C. Holding security cover handles (or grasping sides
of security cover, if no handles), lift security cover up and away from header. See illustration below-right
Locking
Mechanism With
“Flat Bar” To
Lock Into Slot
Bracket With Slot For Latch
Sample View of
Lower Retainer
Bracket (Rotated
For Illustrative
Purposes Only)
Key & Locking Mechanism
Security
Cover
10
Page 11
POWER-UP CHECK (EVAPORATOR FAN AREA)
Power-Up Check (Evaporator Fan Area) On Both Sides of Merchandiser
After power has been supplied, evaporator coil fans will be operational.
 To verify fans are operational, lift up deck pans; check to see that the coil fans are functioning properly.  See illustration below (partially disassembled for illustrative purposes only).
Illustration Shown May Not
Exactly Reflect Every
Feature or Option of Your
Particular Case
Lines Route
Evaporator Coil
Fans
TXV Drain Refrigeration
11
Page 12
MAINTENANCE FUNDAMENTALS: NON-ADJUSTABLE SHELF / BR ACKET ASSEMBLY
1. Airflow/Temperature Requirements
 This merchandiser is tested in the factory to
maintain airflow and temperatures in a very
narrow range.
 The positioning of each shelf/bracket assemblies
in its specific slot is crucial to maintaining this
factory set temperature and airflow.
2. Shelf / Bracket Assembly
 Shelf/bracket assemblies ARE NOT to be
adjusted or moved from their factory determined
slots.
 Item 3 below provides an exception to this
guideline.
3. Shelf / Bracket Assembly Removal
 Cleaning can usually be accomplished
WITHOUT the removal of the shelf/bracket assembly.
 Should stubborn stains or residue require removal
of shelf/bracket assembly however, see
GENERAL CLEANING (TO BE PERFORMED BY STORE PERSONNEL) - EXTERIOR / INTERIOR section in this manual for specifics.
12
Page 13
MAINTENANCE FUNDAMENTALS, CONTINUED: LED LIGHT FIXTURES / REMOVAL / R EPLACEMENT
1. LED Light Switch
 LED light switch to entire case is always located
in upper section of the case.
 See illustration below.
2. LED Light Fixtures
 Light fixtures are located in upper section of the
case (in front of honeycomb) and under
shelving.
3. LED Light Fixture Removal and Replacement
 This case is provided with mini-LED lights which
will rarely require change-out.
 To remove LED light fixture, disconnect the
existing LED light from its brackets. Replace.
 Note: LED Plug must be connected in a specific
manner or they will not work.
 Oval form of plug must connect to oval form of
LED light. See illustrations at top-right.
o
O
FF
2
O
N
13
Page 14
REFRIGERATION FUNDAMENTALS: UNDERSIDE LAYOUT (BOTH SELF-CONTAINED & REMOTE)
Self-Contained & Remote Refrigeration Line Access, Connections & Servicing To Be Accomplished By Licensed Contractors Only
 Partially-disassembled illustration below shows location of refrigeration lines for self-contained operation.  Two (2) drains accessible from top of unit by lifting up decking.  See POWER-UP CHECK (EVAPORATOR FAN AREA) section in this manual for under decking drain
illustration.
Electrical
Case Rear
Drain
Center Pass-Through
(Covered)
Drain Line (To Position Over Condensate Pan)
Box
Drain Line (To Position Over Condensate
Pan or Route To Floor Drain)
14
Case Front Drain
Refrigeration
Lines
Page 15
REFRIGERATION FUNDAMENTALS: SELF-CONTAINED UNIT ILLUSTRATED PARTS BREAKDOWN
Self-Contained Merchandiser’s Condensate Unit Illustrated Parts Breakdown
 Assembly/disassembly and servicing to be performed by licensed refrigeration contractor.
Refrigeration
U-Tubes
Condenser Coil Fan,
Fan Housing & Motor
Condenser Coil Housing
Electrical
Starter Unit
Pan
Sight Glass
Refrigeration
Lines
Filter Dryer
15
Compressor
Page 16
GENERAL CLEANING (TO BE PERFORMED BY STORE PERSONNEL) - EXTERIOR / INTERIOR
FREQ. AREA / INSTRUCTIONS
Daily Deck/Rear Plenums: Clean with a warm soap and water solution. For stubborn stains and
residue, TURN MAIN POWER SWITCH OFF. Remove deck and clean with soap and water solution or submersed in hot, soapy water solution. Rinse thoroughly. Dry. Return to case. Turn main power switch back on.
Daily Glass Surfaces (Sides): Clean with household or commercial glass cleaner.
Weekly Shelving/Bracket Assemblies
 Wipe off shelf/bracket assemblies with moist cloth.  Brackets and shelving CAN BE removed for more thorough cleaning. Caution! Removal
of shelving/bracket assemblies should ONLY be performed when stubborn stains or residue CANNOT be removed with shelving/bracket assemblies remaining on case.
 To remove shelf/bracket assembly, simply lift upward and out.  Caution: As LED lighting is attached to underside of shelving, you must disconnect LED
wire from its connectors. Due to the electrical components, DO NOT submerse shelving/ bracket assemblies while cleaning.
 Clean with mild soap and water solution and a non-abrasive soft cloth. For stubborn
stains use a nylon brush. DO NOT use abrasive cleaners or Brillo® pads, as these can destroy the shelf/bracket finish.
 Caution! After removing and cleaning shelving/bracket assemblies YOU MUST return
them to THE SAME EXACT slots they were in prior to their removal.
 Reconnect connectors into LED plugs after shelving/bracket assemblies are in place.
Weekly Side Panels All Around (and Upper Fascia): Clean with mild soap and water solution and a
non-abrasive soft cloth.
Weekly Acrylic Air Deflectors: Clean with warm water, mild soap solution and soft cloth; acrylic
cleaning solutions are also available. Caution! Never use ammonia-based cleaners on acrylic. Incorrect cleaning agents or abrasive cleaning cloths cause surface to ‘cloud’ over time.
Weekly Condenser Coil: Vacuum or brush grille condenser coil at case front. Use metal or fiber
brush to remove dust and dirt that can collect on condenser coils. Be careful not to damage the fins on the coil. See REFRIGERATION FUNDAMENTALS: CONDENSATE PACKAGE ACCESS section in this manual for instructions on side panel removal.
Monthly Under Case Cleaning : Remove front (or rear) panels. Vacuum under case to remove all dust
and dirt. Replace front (or rear) panels when complete.
16
Page 17
GENERAL CLEANING (TO BE PERFORMED BY TRAINED SERVICE PROVIDERS ONLY)
AREA TO CLEAN FREQUENCY INSTRUCTIONS
Case Interior Monthly Evaporator Fan Shroud Area (Under Decking): Caution! Due to
rotating fans in area, turn off case and disconnect plug from wall outlet before beginning fan shroud (and surrounding tub area) cleaning! 1) Turn off power. 2) Remove deck from case. 3)
Clean fan shroud area (and surrounding tub area) with moist cloth.
Quarterly Tub & Drain: Caution! Due to rotating fans in area, turn off case
and disconnect plug from wall outlet before beginning tub & drain cleaning! Vacuum tub under decks. Clean with soap and water
solution. Wipe dry with clean cloth. Keep drain free of debris to prevent clogging.
17
Page 18
TROUBLESHOOTING (TO BE PERFORMED BY STORE PERSONNEL UNLESS STATED OTHERWISE)
CONDITION TROUBLESHOOTING
Water Is On The Floor
Fans Emit Excessive Noise No Case Lights Are
Working
One (or Several) Case Lights are Not Working
Floor drain units: Check that drain (at underside of case) is properly routed to floor drain.
Call service provider. Call service provider. Check that light switch is in the on position.
Check that ALL of the light cords and plugs are properly connected. See
MAINTENANCE FUNDAMENTALS - SHELF & BRACKET ASSEMBLY REMOVAL / LIGHT FIXTURES section in this manual for specifics.
Authorized Service Contractors Only
: Check circuit breaker box for
tripped circuit.
If case lights still do not come on, call service provider.
Check that ALL of the light cords and plugs are properly connected. This includes the following items:
 Oval form of plug must connect to oval form of LED light.  The power end of cord is to connect at the “red dot” marker at the end
of the LED lamp.
 See MAINTENANCE FUNDAMENTALS - SHELF & BRACKET
ASSEMBLY REMOVAL / LIGHT FIXTURES section in this manual for
more specifics including illustrations.
Case is Not Holding Proper Temperature
If case light still do not come on, call service provider.
If a large amount of warm product was added to the case, it will take time for the temperature to adjust. Product must be pre-chilled before placing in case.
Check that the case is not in the sun or near a heat or air-conditioning vent. See OVERVIEW / TYPE / COMPLIANCE / WARNINGS / PRECAUTIONS / WIRING DIAGRAM section in this manual for specifics.
If case is located near front doors, temperature fluctuation can hinder unit’s ability to maintain temperature. See OVERVIEW / TYPE /
COMPLIANCE / WARNINGS / PRECAUTIONS / WIRING DIAGRAM
section in this manual for specifics. Check air return grilles (area at front of decking) for obstructions.
DO NOT set product on air grilles as this will prevent proper airflow! If case still is not holding proper temperature, call service provider.
18
Page 19
TROUBLESHOOTING (TO BE PERFORMED BY TRAINED SERVICE PROVIDERS ONLY)
CONDITION TROUBLESHOOTING
Water Is On The Floor
Fans Emit Excessive Noise
Check that the drain trap is free of debris. Check that the drain hose is correctly positioned over floor drain. Remote units condensate pump: Check that unit is operating properly. Check store conditions.
 For Type 1 Conditions (most cases): ambient conditions are to be at 55%
max. humidity / 75°F.
 For Type 2 Conditions: ambient conditions are to be at 60% maximum
humidity / 80°F.
Check that the case is aligned, level and plumb.
Check evaporator fan for cleanliness. Unplug/power off fan motors. Check motor shaft for bearing wear. Check that fan motors are securely mounted in brackets. Verify that fan blades are securely mounted to fan motor. Check that nothing is preventing blade rotation.
Fans Are Not Working
Digital Control Display
Check that the fan shroud is properly secured. Check that the MAIN power switch is on. Check that fans are plugged in at the fan shroud. Check for foreign material obstructing fan performance. Check that fan blades freely rotate within fan shrouds Check that power is going to fans Check that fan wiring is connected on terminal blocks. Check that the MAIN power switch is on.
Is Blank.
System Not Operating
Check the circuit breaker box for tripped circuits. Check that the utility power is on. Check that the MAIN power switch is on. Check the circuit breaker box for tripped circuits.
19
Page 20
TROUBLESHOOTING (TO BE PERFORMED BY TRAINED SERVICE PROVIDERS ONLY), CONTINUED
CONDITION TROUBLESHOOTING
No Case Lights Are Working
One (or Several) Case Lights are Not Working
Follow previous page’s System Not Operating instructions.
Check voltage at LED driver. If voltage is entering but not exiting, LED driver may be faulty.
Check connection at front of case (from circuit breaker) for voltage.
Check connection at case rear (from field wiring box) for voltage.
If no case light STILL do not come on, call SCC Technical Service phone number (listed on last page of this operating manual).
Follow previous page’s System Not Operating instructions.
Control Display Is Flashing
Case Is Not Holding Temperature
If case light still do not come on, call SCC Technical Service phone number (listed on last page of this operating manual).
See your case’s serial label for your model’s specified settings. See SERIAL LABEL LOCATION & INFORMATION LISTED / TECH INFO & SERVICE
for label location, etc.
If a large amount of warm product was added to the case, it will take time for the temperature to adjust. Unit needs product to be pre-chilled.
Temperature changes during defrost mode but will return to normal. Fourth LED (on temperature controller) will indicate defrost cycle in progress.
Check that case is not in sun or near a heat or air-conditioning vent.
If case is located near front doors, temperature fluctuation can hinder unit’s ability to maintain temperature.
Check air grilles for obstructions.
20
Page 21
TROUBLESHOOTING (BY TRAINED SERVICE PROVIDERS ONLY) - CONDENSING SYSTEM
CONDITION TROUBLESHOOTING
Head Pressure Too High
Check that the Condensing Coil is not dirty or covered.
Check that Condensing Fans are working.
Check that refrigerant is not overcharged.
Check to verify that a non-condensable is not in the system.
Check that Liquid Line Drier is not plugged.
Check that there are no close-offs around Condensing Coil.
Check Set Point Temp.; it may be adjusted too high.
Head Pressure Too Low
Check System Operating Temperatures.
Check that Store Ambient Temperature isn’t above maximum allowed. See Overview and Warnings Section.
Check that Refrigerant Charge isn’t too low.
Check that Suction Pressure isn’t too low.
Check to verify that Compressor Valves aren’t bad.
21
Page 22
TROUBLESHOOTING (BY TRAINED SERVICE PROVIDERS ONLY) - EVAPORATOR SYSTEM
CONDITION TROUBLESHOOTING
Low Suction Pressure
Check that the Refrigerant doesn’t have a low charge.
Check that Expansion Valve (TXV Valve) isn’t restricted.
Check that Liquid Line or Filter isn’t restricted.
Check that Evaporator Motors are working.
Check that High Superheat doesn’t need adjusting.
Check that the Thermostatic Element charge isn’t depleted.
Check that there is air no seepage of air around Condensing Coil.
Check that the Coil is not iced up.
High Suction Pressure
Check that Refrigerant Charge isn’t too high.
Check that Compressor Valves aren’t bad.
Check that the Cooling Load isn’t high.
Check that Superheat Adjustment isn’t low.
Check TXV Bulb Installation a. Poor thermal contact. b. Warm location.
Check Compressor: Low capacity means it is undersized for its application.
22
Page 23
PREVENTIVE MAINTENANCE (TO BE PERFORMED BY TRAINED SERVICE PROVIDERS ONLY)
WARNING! TURN OFF CASE BEFORE PERFORMING PREVENTIVE MAINTENANCE!
PREVENTIVE
FREQ. INSTRUCTIONS
MAINTENANCE
Case Exterior Quarterly Condensing Coil:
 Remove side panel (by lifting up and off).  Use air pressure or industrial strength vacuum; clean dust and dirt that
may collect on the Condenser Coil. Take care to NOT allow dust to become airborne. Use wet rags to cover area where dust will flow when air pressure is applied.
 Caution! Coil fins are sharp. Handle with care!  Replace front panel to case.
Quarterly Refrigeration Package/Compressor Area: Caution! Be certain to
disconnect power from case before cleaning refrigeration package!
 Warning! Evaporator Pan Is HOT! Disconnect power from case and
allow to cool before cleaning evaporator pan!
 Slide/Roll compressor package out from under case.  See REFRIGERATION FUNDAMENTALS section for in-depth
instructions on accessing the evaporator pan.
 Use a scrub-brush and a de-scaling solution such as CLR® (to prevent
corrosion, lime and rust). Follow instructions as to proper dilution, safety precautions and scrubbing method.
 After thoroughly cleaning pan with scrub-brush and solution, rinse
thoroughly with clean water (in spray bottle) and wipe dry with sponge or paper towel.
 Use moist cloth to wipe off dust & debris that collects on various parts
(fans, sight glass, overflow pan, etc.).
 Slide refrigeration assembly back under case.  Replace front panel and lower grille via hooks (no screws required).
Quarterly
Under Case Cleaning: Once refrigeration package is clear of unit, vacuum under case to remove all dust and dirt that may collect under case.
Case Interior Quarterly Tub, Coil, Drain, Evaporator Fan Blades, Motors, Brackets:
Disconnect power from the case before cleaning the Tub, Coil, Fan, Motor and Drain Area!
 Remove Decking, Sub-Deck and Fan Shroud.  Use vacuum to clean Evaporator Coils.  Clean Tub, Coil and Drain with warm water, clean cloth, brush and mild
soap solution.
 Remove any debris that may clog drain.  Clean Fan Blades, Motors and Brackets by wiping down with moist
cloth.
Quarterly
Honeycomb: Check honeycomb air diffuser to determine whether it is
dirty. If dirty, remove from case. See MAINTENANCE FUNDAMENTALS
- HONEYCOMB AIR DIFFUSERS (SERVICE TECHNICIANS ONLY)
section of this manual (next page) for cleaning specifics.
23
Page 24
PREVENTIVE MAINTENANCE: HONEYCOMB AIR DIFFUSERS (TRAINED SERVICE PROVIDERS ONLY)
Preventive maintenance should be performed every 30 days unless conditions warrant a more frequent replacement cycle.
1. Honeycomb Air Diffuser Removal
A. Wedge non-metallic device of suitable strength (such as a ballpoint pen) between honeycomb and end panel. Caution (that prevents condensation on the lamp assembly). B. Apply pressure to collapse the honeycomb to allow it to be pulled out of honeycomb retainer. C. Pry downward and away from honeycomb retainer.
Clean honeycomb with warm water and soap
! Use care not to dislodge the heating wire
Honeycomb Air Diffuser
At Each Side of Merchandiser
solution. Submerse if necessary. Use brush to dislodge stubborn or sticky residue. Dry by using vacuum’s ‘blow mode’.
2. Honeycomb Air Diffuser Installation
D. Squeeze honeycomb into the honeycomb retainer. E. Carefully slide honeycomb into place. F. Adjust honeycomb so that it fits flat retainer. It must not be wavy or out of position.
against
Note: For honeycomb air diffusers in other locations, these same general instructions apply.
A
F
B
D
C
E
24
Page 25
SERIAL LABEL LOCATION & INFORMATION LISTED / TECHNICAL INFO & SERVICE
Serial Label Location & Information Listed / Technical Information & Service
 Serial labels are located near the electrical access on your case.  Serial labels contain electrical, temperature & refrigeration information, as well as regulatory
standards to which the case conforms.
 For additional technical information and service, see the TECHNICAL SERVICE page in this
manual for instructions on contacting Structural Concepts’ Technical Service Department.
 See images below for samples of both refrigerated and non-refrigerated serial labels.
Y
S
A
SA
M
P
L
MPLE
E
N
O
ON
L
L
Y
O
Y
L
NL
LY
Y
A
S
----- Sample Serial Label For Refrigerated Case -----
S
A
MP
SA
S
LE
AM
M
O
LE
P
M
ON
P
LE ON
PLE
Y
L
N
----- Sample Serial Label For Non-Refrigerated Case -----
25
Page 26
Read And Save These Instructions - Page 1 of 3
Integrated Electronic
Microprocessor Controller
Programming The Instrument
To Modify The Setpoint
1. Press and hold the “SET” key for at least 1 second.
Set
Prg
mute
Set
aux
def
aux
3. Quickly press and release the “SET” key again.
Set
To Modify Defrost, Differential, Other Parameters
Prg
mute
2. Confirm by pressing “SET” key.
Set
aux
4. Press “SET” to modify this selected parameter.
Set
aux
Set
7. Press & hold the “Prg” key for at least 5 seconds
Prg
to save changes. This action will also mute the
mute
audible alarm (buzzer) & deactivate the alarm relay.
2. Use arrow keys ▲ ▼ on temperature
def
controller to increase (or decrease) the
setpoint.
1. Press & hold “Prg” & “SET” keys together for five (5) seconds; display will flash “0”,
Set
representing password prompt.
3. Press or to reach the
def
category to be modified.
5. Increase or decrease the value using
def
the or button respectively.
6. Press the “SET” key to temporarily save the new value and return to the display of the parameter.
Prg
mute
Set
aux
Set
aux
Set
Prg
mute
Warning! Save Your Parameter Settings!
1. To store the new parameter values, PRESS and HOLD the “Prg” key for at least 5 seconds.
2. All modifications made to parameters will be lost if you do NOT press a button within 60 seconds. Should this “timeout” occur, normal operational settings (prior to modifications being made) will resume.
3. If the instrument is switched off before pressing the “Prg” key, all modifications to parameters will be lost.
How To Change Reading From Fahrenheit (°F) To Celsius (°C)
1. Press and hold “Prg” and “SET” keys
Set
together for at least 5 seconds; display
2. Confirm by pressing “SET” key.
4. Press “SET” to modify this selected parameter.
6. Press “SET” key to temporarily save the new value and return to the display of the parameter.
will show “0” (password prompt).
def
3. Press or until reaching the parameter “/ 5”.
5. Press or to change value to
def
desired setting: “0” for Celsius (°C) or
“1” for Fahrenheit (°F).
7. Press & hold “Prg” key for at least 5 seconds to save changes.
will automatically convert to new scale. No conversion is required.
Note! All values
To Activate Manual Defrost
def
Press and hold “def” key for at least 5 seconds.
To Activate / Deactivate Auxiliary Output
Press and hold the “aux” key for 1 second.
aux
26
Prg
mute
To Reset Any Alarms With Manual
Reset
aux
Press and hold the “Prg” and “aux”
key for at least 1 second.
Oper Manuals - PUB\Templates\Carel Controller\Carel Controller IR33.pub
This data derived from Carel Material: ir33 +030220441 - rel. 2.0 - 01.05.2006
Page 27
Read And Save These Instructions - Page 2 of 3
Integrated Electronic
Microprocessor Controller
User Interface - Display
Summary Table of Alarm and Signals: Display, Buzzer and Relay
reset alarms w/manual reset / reset HACCP alarms / reset temp. monitoring
27
Page 28
Read And Save These Instructions - Page 3 of 3
Integrated Electronic
Microprocessor Controller
Summary Table of Operating Parameters
CODE PARAMETER UOM* TYPE MINIMUM MAXIMUM DEFAULT
/5
Select Celsius (°C) or Fahrenheit (°F)
flag C 0 1
/c1 Calibration of probe 1 °C/°F C -20 20
/c2 Calibration of probe 2 °C/°F C -20 20
St Temperature set point °C/°F F r2 r1
rd Control delta °C/°F F 20 0.1
dl Interval between defrosts hours F 0 250
dt1 End defrost temperature, evaporator °C/°F F -50 200
dP1 Maximum defrost duration, evaporator min F 1 250
d6 Display on hold during defrost - C 0 2
For Case
Specific
Defaults
See Serial
Label
Located
Near
Electrical
Access
On Your
Case.
For
Additional
Technical
Information
Call Structural Concepts Technical
Service
Dept. at
1(800)
433.9489
dd Dripping time after defrost min F 0 15
d/1 Display of defrost probe 1 °C/°F F - -
* Unit Of Measure
28
Page 29
SCC TECHNICAL SERVICE CONTACT INFORMATION & WARRANTY INFORMATION
STRUCTURAL CONCEPTS CORPORATION TECHNICAL SERVICE
PHONE NUMBER: 1.800.433.9489 or For Your Master Service Agent See
WWW.STRUCTURALCONCEPTS.COM/Contact/Master_Service_Agents.asp
LIMITED WARRANTY
All sales by Structural Concepts Corporation (SCC) are subject to the following limited warranty. “Goods” refers to the product or products being sold by SCC.
Warranty Scope: Warranty is for equipment sold in the United States, Canada, Mexico and Puerto Rico. Equipment sold elsewhere may carry modified warranty. Warranty; Remedies; Limitations. SCC warrants that if any Goods are found by an authorized representative of SCC not to be of good material or workmanship within one
year of the date of shipments SCC will, at its option after inspection by an authorized representative, replace any defective Good or pay the reasonable cost of replacement for any such defective Goods, provided that written notice of the defect is given to SCC within 30 days of the appearance of such defect. If notice is not given within such period, any claim for breach of warranty shall be conclusively deemed to have been waived and SCC shall not be liable under this warranty. If SCC is unable to repair or replace the defective Goods, SCC shall issue a credit to the Purchaser for all or part of the purchase price, as SCC shall determine. The replacement or payment in the manner described above shall be the sole and exclusive remedy of Purchaser for a breach of this warranty. If any Goods are defective or fail to conform to this warranty, SCC will furnish instructions for their disposition. No Goods shall be returned to SCC without its prior consent.
SCC’s liability for any defect in the Goods shall not exceed the purchase price of the Goods. SCC SHALL HAVE NO LIABILITY TO PURCHASE FOR CONSEQUENTIAL DAMAGES OF ANY KIND WHATSOEVER, INCLUDING, BUT NOT LIMITED TO, PERSONAL INJURY, PROPERTY DAMAGE, LOST PROFITS, OR OTHER ECONOMIC INJURY DUE TO ANY DEFECT IN THE GOODS OR ANY BREACH OF SCC, SCC SHALL NOT BE LIABLE TO THE PURCHASER IN TORT FOR ANY NEGLIGENT DESIGN OR MANUFACTURE OF THE GOODS, OR FOR THE OMISSION OF ANY WARNING THEREFROM.
SCC shall have no obligation or liability under this warranty for claims arising from any other party’s (including Purchaser’s) negligence or misuse of the Goods or environmental conditions. This warranty does not apply to any claim or damage arising for or cause by improper storage, handling, installation, maintenance, or from fire, flood, accidents, structural defects, building settlement or movement, acts of God, or other causes beyond SCC’s control.
Except as expressly stated herein, SCC makes no warranty, express, implied, statutory or otherwise as to any parts or goods not manufactured by SCC. SCC shall warrant such parts or Goods only (I) against such defects, (II) for such periods of time, and (III) with such remedies, as are expressly warranted by the manufacturer of such parts of Goods. Notwithstanding the foregoing, any warranty with respect to such parts of Goods and any remedies available as a result of a breach thereof shall be subject to all of the procedures, limitations, and exclusions set forth herein.
THE WARRANTIES HEREIN ARE IN LIEU OF ALL WARRANTIES, EXPRESS, IMPLIED, STATUTORY, OR OTHERWISE. IN PARTICULAR, SCC MAKES NO WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
No representative, agent or dealer of SCC has authority to modify, expand, or extend this Warranty, to waive any of the limitations or exclusions, or to make any different or additional warranties with respect to Goods.
Period of Limitations. No claim, suit or other proceeding may be brought by Purchaser for any breach of the foregoing warranty or this Agreement by SCC or in any way arising out of this Agreement or relating to the Goods after one year from the date of the breach. In the interpretation of this limitation on action for a breach by SCC, it is expressly agreed that there are no warranties of future performance of the goods that would extend that period of limitation herein contained for bringing an action.
Indemnifications. Purchaser agrees to indemnify, hold harmless, and defend SCC if so requested, from any and all liabilities, as defined herein, suffered, or incurred by SCC as a result of, or in connection with, any act, omission, or use of the Goods by Purchaser, its employees or customers, or any breach of this Agreement by Purchaser. Liabilities shall include all costs, claims, damages, judgments, and expenses (including reasonable attorney fees and costs).
Remedies of SCC. SCC’s rights and remedies shall be cumulative and may be exercised from time to time. In a proceeding or action relating to the breach of this Agreement by Purchaser, Purchaser shall reimburse SCC for reasonable costs and attorney’s fees incurred by SCC. No waiver by SCC of any breach of Purchaser shall be effective unless in writing nor operate as a waiver of any other breach of the same term thereafter. SCC shall not lose any right because it has not exercised it in the past.
Applicable Law. This Agreement is made in Michigan and shall be governed by and interpreted according to Michigan law. Any lawsuit arising out of this Agreement or the Goods may be handled by a federal or state court whose district includes Muskegon County, Michigan, and Purchaser consents that such court shall have personal jurisdiction over Purchaser.
Miscellaneous. If any provision of this Agreement is found to be invalid or unenforceable under any law, the provision shall be ineffective to that extent and for the duration of the illegality, but the remaining provisions shall be unaffected. Purchaser shall not assign any of its rights nor delegate any of this obligations under this Agreement without prior written of SCC. This Agreement shall be binding upon and inure to the benefit of SCC and Purchaser and each of their legal representatives, successors and assigns.
SCC warrants its products to be free of defects in materials and workmanship under normal use and service for a period of one (1) year from the date of delivery. This warranty is extended only to the original purchaser for use of the Goods. It does not cover normal wear parts such as plastic tongs, tong holders, tong cables, bag holders,
or acrylic dividers. General Conditions. All service labor and/or parts charges are subject to approval by SCC. Contact the Customer Service Department in writing or call 231-798-8888. All claims must contain the following information: (1) model & serial code number of equipment; (2) the date and place of installation; (3) the name and address of the agency
which performed the installation; (4) the date of the equipment failure; and (5) a complete description of the equipment failure and all circumstances relating to that failure. Once the claim has been determined to be a true warranty claim by SCC’s Customer Service Department, the following procedure will be taken: (1) replacement parts will be sent
at no charge from SCC on a freight prepaid basis; (2) reimbursement for service labor will be paid if the following conditions have been met - (a) prior approval of service agency was awarded from the Customer Service Department; and (b) an itemized statement of all labor charges incurred is received by the Customer Service Department. The cost of the service labor reimbursement will be based on straight time rates and reasonable time for the repair of the defect.
If problems occur with any compressor, notify SCC’s Customer Service Department immediately. Any attempt to repair or alter the unit without prior consent from the Customer Service Department will render any warranty claim null and void. This warranty and protection plan does not apply to any condensing unit or any part thereof which has been subject to accident, negligence, misuse, or abuse, or which has not been operated in accordance with the manufacturer’s recommendations or if the serial number of the unit has been altered, defaced, or removed.
Limit of Liability. The limit of liability of SCC toward the exchange cost of the original condensing unit, F.O.B. SCC, Norton Shores, MI, of each motor-compressor assembly replaced during the warranty shall not exceed manufacturer's current established wholesaler’s exchange price and in no case shall the labor of removing or replacing the motor-compressor or parts thereof be the responsibility of SCC.
29
Loading...