TECHNICAL SERVICE CONTACT INFORMATION & WARRANTY INFORMATION ..….....
3
4
5-7
8
9
10
11
12
13
14
15
16
17
18
19
20
21-23
24
25
2
OVERVIEW AND WARNINGS
OVERVIEW
These cases should be installed and operated according to the following instructions to insure
proper performance.
This unit is designed for the display of products in ambient store conditions where
temperatures and humidity are maintained at a maximum of 75° F and 55% relative humidity.
WARNING
ELECTRICAL
HAZARD
WARNING
ELECTRICAL
HAZARD
WARNING
KEEP HANDS
CLEAR
WARNING
Risk of Electric Shock.
Disconnect Power Before Servicing Unit
WARNING
More Than One Source of Electrical Supply.
Disconnect All Sources Before Servicing.
Employed with units that have separate circuits.
WARNING
Hazardous Moving Parts.
Do Not Operate unit with covers removed.
Fan blades may be exposed when deck panel is removed. Disconnect
power before removing deck panel.
3
FORK LIFT INSTRUCTIONS
1. Remove From Skid By Placing Fork Lift At Case Rear
Illustration below shows proper location for forks to be placed to remove case from skid.
Forks MUST slide between casters (see illustration below). Be careful to NOT hit casters.
Forks MUST NOT hit P-Trap (see illustration below).
An approximate 31” space is available for forks to go between casters.
Forks MUST be positioned under Rear-Left and Rear-Right U-Channels for proper support.
Placement of forks at any other locations can cause case to be damaged.
Caution! Due to case length, provide support on both case ends to prevent tipping!
Labels: “Use
Fork Lift In
This Area
Only!
Support
Case To
Prevent
Tipping
31”
Support
Case To
Prevent
Tipping
Rear-Left
U-Channel
Rear-Right
U-Channel
P-Trap
4
INSTALLATION INSTRUCTIONS
2. Position and Level Units
After removal from skid, roll case to
location desired.
Using 13/16” wrench, adjust feet until
they reach the floor.
Adjust each foot (six total on case) until
all casters are slightly raised off the floor
and case is level and plumb.
Note: For proper case leveling, this
procedure may need to be performed
several times on each foot.
See illustrations at right.
4. Electrical Connection
Note: Standard single phase connections
required, and must be performed by a certified electrician.
Two 220-Volt electrical circuits with leads
are provided.
Remove screws from 4X4 box provided
for field hook up.
3. Remote Evaporator Connections
A 220-Volt electrical stub up connection is
provided on the rear side at either the top
or base of case (per customer request).
Refrigeration stub up connections are pro-
vided on the rear side at either the top or
base of case per customer request.
Caster
5
Adjustable
Foot (Six Total
on Case)
INSTALLATION INSTRUCTIONS, CONTINUED
5. Electrical Specifications
See Technical Information Sheet
6. Field Wiring Hookup
See Illustration below. Note: Self-Contained Unit shown below.
Whether Remote or Self-Contained unit, Field Wiring Box is in same location.
Field Wiring Box to
Refrigeration Fans, Lights,
Compressor,
Ballasts & CPC® Controller
Field Wiring
Box to
Evaporator
Pan & Pump
Note: CPC® Controller Box
shown with cover removed for
illustrative purposes only.
6
INSTALLATION INSTRUCTIONS, CONTINUED
7. Skirt Specifics
Skirt is held in place with brackets
Brackets are placed along lower skirt and attaches to top of case.
One bracket is to be placed in each of the four (4) corners of skirt.
Whether Remote or Self-Contained, skirt location and positioning is the same.
7
START-UP AND OPERATION
Merchandiser Start-Up
Turn on main power circuit breaker. Coil fans
(and in self-contained units, compressor motor) will turn on.
Check to see that coil fans are all functioning
properly. To do so, the following steps must
be taken:
1. Remove the Square Buckets for access to coil
fans. See illustration #1.
2. Remove Intake Panels by removing screws
(approx. 7 screws per panel). See illustration
#2.
3. Access Coil Fans and/or Coil. See illustration
#3.
Check to see if air is discharging properly.
Caution! While fans are rotating, be
careful not to put hands or fingers near
fan blades. Serious injury can occur.
When main power circuit breaker is turned on,
all of the lights should come on at the same
time. First time lighting may require short
warm up period for bulbs. Slightly dim or a
flickering of new bulbs is normal.
Case temperature is set at the factory, as
determined by the case size.
Square
Buckets
Illustration #1: View of Case with
Square Buckets In Case
Case
Front
Intake
Panel
Illustration #2: View of Case with
Square Buckets removed from Case
Right
Side
Intake
Panel
View of Coil
Fans after
removal of
Buckets &
Intake Panel
Illustration #3: View of Case with Square Buckets
and Intake Panel removed from Case
8
Loading...
+ 17 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.