STIEBEL ELTRON FEK Operating And Installation Instructions

Page 1
26_03_01_0106
270783
FEK
Control module Operating and installation instructions
Page 2
1. Operating instructions 2
for users and contractors
1.1 Equipment description 2
1.2 Equipment overview 2
1.3 Important information 2
1.4 Operation 3
1.5 Settings 3
2. Installation instructions 12
for contractors
2.1 Standard delivery 12
2.2 General 12
2.3 Installation 12
2.4 Specification 13
2.5 Commissioning 13
2
Page 3
1 Operating instructions for users and contractors
1.1 Equipment description
The FEK control module only works in conjunction with the weather-compensated WPMi control unit. It enables the convenient entry and display of system parameters, e.g. outside temperature, relative humidity and heating circuit parameters (e.g. heating times and required room temperature) for the heating system from the user’s living room. This allows the constant monitoring and optimising of the heating system, both in heating and in cooling mode. In addition, hooking up a room temperature enables the correction of the weather­compensated WPMi control unit.
1.2 Equipment overview
1.2.1 With closed control flap and standard display
Relative humidity
Heating times
Time
Room temperature
Day
1.2.2 With the control flap open and with all indicator elements on display
2
1
1 Programming indicator 2 + key 3 PRG key 4 - key 5 Reset
1.3 Important information
3 4
The control module must only be installed and maintained by qualified contractors.
5
C26_21_01_0011
1 2
1 Away key 2 Operating mode key 3 Help key 4 Rotary selector for changing the set
room temperature ± 5 K
3 4
1.4 Operation
The operation is split over three control levels. Control levels and contractors alike. Control level 3 is only designed for qualified contractors:
Control level 1
This enables the adjustment of operating modes, such as standby mode, programmed
C26_21_01_0010
operation, constant day or setback mode (for this, see section 1.5.1).
Control level 2
This enables parameters, such as room temperature, heating programs, etc. to be adjusted (for this, see section 1.5.5).
1 and 2 are accessible to users
(control flap closed)
(control flap open)
3
Page 4
Control level 3 (for contractors only) This level is protected by a code and should only be used by contractors. At this level, heat pump and system-specific details are determined (for this, see section 2.5).
1.5 Adjustments (control level 1)
With the flap closed, the display shows the operating mode, time and day, as well as the current room temperature and relative humidity.
1.5.1 Operating mode key
Vital facts in brief
Settings
All adjustments follow the same pattern:
Opening the control flap toggles the FEK to control level 2. The display shows the parameter “room temp.”. Pressing enables you to adjust the parameter you want to change. Press to change the value of the parameter. You can change the currently displayed value with indicator is illuminated. Press again, the indicator then extinguishes and the new set value has been saved. You can modify further values for this parameter by pressing
or , if the red indicator has not been extinguished after saving. The programming step can only be terminated when the red indicator has extinguished.
Terminating programming
You can terminate the programming process after entering and saving the required parameter changes by closing the control flap. However, if you want to make further changes, press one of the keys until the display shows BACK, then press will return you to the previous level. Closing the control flap with illuminated indicator returns the FEK into its original position. The modified value will then not be saved.
or , when the red
. This
When connecting a FEK, only the operating modes for the pre-selected heating circuit are adopted by the WPMi.
You can select the required operating mode by pressing this key several times with the flap closed. The selected operating mode is indicated by a symbol in the display. It becomes effective if the setting was not changed for five seconds.
Standby mode
Frost protection for the heating operation is active. The standby symbol flashes, when the heat pump manager is in standby mode, and the operating mode cannot be adjusted. Application: During holidays.
Automatic mode Heating according to time switch program.
Changeover between day temperature and setback temperature. With this operating mode, an additional symbol (sun or moon) indicates in the display, whether the heating circuit is currently in day or in setback mode.
Constant day mode
The heating circuit is held at constant day temperature.
Application: In low energy houses without
setback mode.
Constant setback mode
The heating circuit is held at constant setback temperature.
Application: During weekends away.
4
Page 5
1.5.2 Away key
This key activates the eco mode (away). Press twice: The heating circuit switches to setback mode for one hour. The selected heating interruption is briefly displayed in hours. Press this key several times: the heating circuit switches for the respective number of hours to setback mode. If no key is then pressed for approx. three seconds, the display returns to the standard display and the active heating interruption is displayed by the flashing moon symbol. You can scan the selected heating interruption by pressing the “Away” key once at any time. Pressing the operating mode key deactivates the “Away” period and the moon symbol will extinguish.
1.5.3 Help key
Pressing this key allows you to scan
sensor temperatures of the heat pump or heat pump system, such as outside temperature, actual DHW temperature, actual return temperature, actual room temperature and
the relative humidity.
After you press this key, the first display is the outside temperature. Continuing to press displays, in sequence, the actual DHW temperature, the actual return temperature, the maximum and minimum room temperatures and the maximum and minimum relative humidity. The standard display returns after five seconds. The MIN/MAX values for room temperature and relative humidity are constantly updated and stored. If you hold down the key for four seconds, the top of the display shows DELETE VALUES. All MIN/MAX values will then be deleted.
Any fault in the heat pump causes an arrow above the help key and the attention symbol to flash. Pressing the help key displays that fault. Three seconds later, the fault display extinguishes and the standard display returns again.
1.5.4 Room temperature
You can adjust the room temperature by +/- 5K with the rotary selector. This set value adjustment applies to the then current heating time, not to the setback time.
Display (including all elements)
1 2 3
10
11
4
5
6
12 13 14915 16
7 8
1 Heating times for central heating and DHW (black) 2 12-digit plain text display 3 Mixer mode 4 Heating mode 5
DHW mode 6 Cooling mode 7 Compressor runs 8 Booster in operation
Stage 1, 2 or 3 9 Fault message (flashing) 10 ‘BUS connection to the
WPMi established 11 WPMI in away mode 12 Standby mode 13 Automatic mode 14 Constant day mode 15 Constant setback mode 16 Day
C26_21_01_0012
5
Page 6
1.5.5 Overview of system parameter (control level 2)
Select the required parameter with the rotary selector. For adjustments to parameters, turn to page 6.
With the Room temp. parameter you can adjust the set
ROOM T
room temperature of the heating circuit for the day and
setback mode.
TEMPERATURES
HTG PROG
HTG CURVE
CONTRACTOR
The Temperatures parameter enables you to scan the sensor temperatures of the heat pump or heat pump
system, comparing the actual with the set temperatures,
the relative humidity, etc.
In the Heating program parameter, you can adjust the heating program.
In the Heating curve parameter, you can adjust the heating curve. The room temperature will only remain
constant, irrespective of the outside temperature, if the correct heating curve has been selected for the relevant type of building. Selecting the correct heating curve is therefore vitally important.
commissioning, you need to not only determine
During the settings of control level 2, but also the system-specific parameters. These parameters are adjusted at control level 3 by your heating contractor, access to which is protected by code.
.
6
Page 7
Adjustments at control level 2 for users and contractors
The heating curve, room temperature
and heating program parameters are not shown at the WPMi heat pump manager, if the FEK is pre-selected for a specific heating circuit.
Room temperature
With the Room temp. parameters you can adjust the set room temperature for the day and setback mode. Changing these parameters results in a parallel offset of the heating curve.
Open the control flap
ROOM T
SET DAY
SET HIGHT
SET HIGHT
ROOM T
BACK
Temperatures
SET DAY
SET DAY
SET HIGHT
The Temperatures parameter enables you to scan the following sensor temperatures of the heat pump or heat pump system, comparing the actual with the set temperatures,
relative humidity, etc.
Outside temperatureActual room temperatureSet room temperature Relative humidity Actual DHW temperature Set DHW temperature Actual heat pump return temperature System frost protection temperature
Note
No display, if the corresponding temperature sensor is not connected.
.
the
7
Page 8
Open the control flap
TEMPERATURES
OUTDOOR TEMP
BACK
At all other times, the heat pump operates in setback mode. You will already have selected the corresponding set values for day and setback mode under the Room temp. parameter.
Example:
Your heating system should operate daily from Monday to Friday at two different times, i.e. from 05:30 h until 08:30 h and from 14:00 h until 22:00 h. For the weekend, your heating system should provide heat from 08:30 h until 21:00 h.
Open the control flap
HTG PROG
MON-FRI
TEMPERATURES
Heating program
Under this parameter you have the option of setting up a heating program, i.e: – for every day of the week (Mo, ..., Su
Monday to Friday (Mo - Fr) – Saturday and Sunday (Sa - Su) – the whole week (Mo - Su)
You can adjust three switching time pairs (I, II, III) for each of these options.This determines when and how often the heat pump system should heat in day mode.
8
)
ON
OFF
ON
Page 9
OFF
ON
SAT - SUN
ON
OFF
Heating curve
The Heating curve parameter allows you to select a heating curve for heating circuit 1 or
2. Selecting the correct heating curve is vitally important. Note: Your contractor will have set up a building and system-specific optimum heating curve for the heating circuit. It relates to the heat pump return temperature for heating circuit 1 and to the mixer flow temperature for heating circuit 2.
When adjusting the heating curve, the calculated set return or flow temperature, which is subject to the outside temperature and the set room temperature, will be shown at the top of the display.
Relative to +20 °C Outside temperature
Relative to 0 °C Outside temperature
Relative to -20 °C Outside temperature
ON
ON
BACK
Relative to +20 °C Outside temperature
Relative to 0 °C Outside temperature
Relative to -20 °C Outside temperature
26_21_01_0013
9
Page 10
Open the control flap
1,5
2
1,2 1
0,6 0,4 0,2
2,5
3
2018161412
10
8
6
4
2
0
-2-4-6
-8
-10
-12
-14
-16
-18
-20
100
80
60
40
20
Außentemperatur [°C]
Heizkreis 2 WP-Vorlauftemperatur [°C]
Heizkreis 1 WP-Rücklauftemperatur [°C]
0,8
HTG CURVE
BACK
Heating curve diagram
One heating curve respectively can be adjusted for heating circuit 1 and heating circuit 2. At the factory, heating curve 0.6 is set up for heating circuit 1 and heating curve 0.2 for heating circuit 2. These heating curves relate to a set room temperature of 20 °C.
Heating circuit 1, HP return temperature [°C]
Heating circuit 2, HP flow temperature [°C]
10
Outside temperature [°C]
26_03_01_0077
Page 11
2018161412
10
8
6
4
2
0
-2
-4
-6
-8
-10
-12
-14
-16
-18
-20
Außentemperatur [°C]
70
60
50
40
30
20
Tag-Betrieb
Absenk-Betrieb
Rücklauf- / Vorlauftemperatur [°C]
Adjustment of programmed changeover between day/setback mode
2018161412
10
8
6
4
2
0
-2
-4
-6
-8
-10
-12
-14
-16
-18
-20
Außentemperatur [°C]
Rücklauf- / Vorlauftemperatur [°C]
70
60
50
40
30
20
geänderte Heizkurve
The figure shows a standard heating curve with a slope of 0.8, relative to a set room temperature for day mode of 20 °C. The lower curve represents the setback curve. For this, a set room temperature for setback mode of 15 °C is used, in other words the heating curve is subjected to a parallel offset.
Day operation
Setback operation
HP return temp. / flow temp. [°C]
Matching a heating curve to actual conditions
Example: During spring and autumn, the return or flow temperature of a heating system is too low at an outside temperature between 5 and 15 °C, but is OK at outside temperatures of ≤ 0 °C. This problem can be remedied by a parallel offset and a simultaneous reduction of the heating curve. Prior to this adjustment, heating curve 1.0 was adjusted, relative to a set room temperature of 20 °C. The dotted line indicates the modified heating curve at 0.83 and a modified set room temperature at 23.2 °C.
HP return temp. / flow temp. [°C]
Modified heating curve
Outside temperature [°C]
26_03_01_0078
Outside temperature [°C]
26_03_01_0079
11
Page 12
2 Installation instructions for contractors
2.1 Standard delivery
FEK Part no: 22 01 93
Dimensions: 147 x 97 x 33 (mm)
2.2 General information
The FEK is vitally important for area cooling, e.g. underfloor heating systems, area heating etc. Apart from the room temperature, it also determines the relative humidity to prevent condensation.
2.3 Installation
The correct function of the control module can only be assured if the following are observed:
Fitting on an internal wall (not in a recess)No cover through curtains or similarExternal heat influence is prevented
(e.g. sun, heating system, TV set)
– Prevention of direct draughts
(next to windows and doors)
For fitting, remove the top part of the casing by levering a screwdriver above the opening in the bottom part.
Secure the bottom part on the wall and connect the BUS cable.
A Fixing holes B Cable entry (knock-out) C Terminals
Position the top part of the casing centrally at the upper edge, hook into place and then pivot down onto the base, using only
26_21_01_0018
light pressure, and push home.
26_21_01_0017
12
26_21_01_0016
Page 13
2.4 Specification
Supply voltage 12 V DC ± 15 %
Power consumption
EN 60529 IP 40
EN 60730 Protection class II
Clock backup > 10 hours
Permiss. ambient temp. during operation
Permiss. ambient temp. during storage
Room temperature sensor resistance Tolerance in Ohm Temperature tolerance
~ 25 mA
0 to 50 °C
- 20 to 60 °C
Test resistance NTC 5 k ± 1 % at 25 °C ± 0.2 K at 25 °C
2.5 FEK commissioning
Only approved contractors may commission this control module and instruct the owner in its use.
Not only the adjustments at control level 2 but also the system-specific parameters must be determined as part of commissioning the FEK. These parameters are adjusted at control level 3, access to which is protected by code. To reach this point, press “Contractor” parameter, then press . Check all parameters in sequence,
Note: Not all adjustments take immediate effect. Some adjustments only become effective in certain situations or after a delay.
Code 1 0 0 0
Enter the correct four-digit code to change parameters at control level 3. The factory-set code is 1 0 0 0. After pressing (indicator illuminates), by pressing Pressing again confirms the value, then the second digit of the code begins to flash.
you can adjust the first digit.
, until you reach the
Pressing enables the adjustment of the second digit of the code, etc. The display shows CODE OK when all four digits have been entered correctly. This enables access to control level 3. Closing and re-opening the flap requires that the code is entered again. Checking settings does not require the code to be entered.
Language
Press and select the required language with . Then confirm your selection by pressing
.
Contrast
Press
SELECT REM CON
You can predetermine with parameter selection, to which heating circuit the remote control applies. As standard, HC1 is pre-selected. Accordingly, the parameters room temp., heating curve and heating program for heating circuit 1 are not displayed at the WPMi.
and adjust the contrast with
or .
FE
13
Page 14
FE Correction
This parameter enables the calibration of the actual room temperature.
Room influence for FEK
Standard setting 5; adjustable from ----via “0 to 20” dashes (----) in the display: When the FEK control module is connected, the room temperature sensor only serves to capture and display the actual room temperature; it has no influence on the actual control. With any setting, you can adjust the set room temperature for the heating circuit at the FEK control module by ±5 K. This set value adjustment applies for the then current heating time, not for the setback time. At the same time, setting “0 to 20” serves to control the room temperature-dependent night setback. This means, the heating circuit pump is switched OFF at the point of changeover from the heating into the setback phase. It remains OFF, until the actual room temperature first drops below the set room temperature. Afterwards the system regulates in weather­compensated mode. If you want the room temperature to be taken into account, set the room temperature sensor influence to > 0. The room sensor influence has the same effect as the outside temperature sensor has on the return temperature. Only this effect is 1 to 20 times greater than the set factor.
Room temperature-dependent return temperature with weather compensation
With this type of control, a control cascade is formed from weather-compensated and room temperature-dependent return temperature control. In other words, the weather­compensated return temperature control pre-selects the return temperature, which is corrected by the overlaid return temperature control in accordance with the following formula:
Because a substantial proportion of control is already taken care of by the weather­compensated control, the room temperature sensor influence K can be set lower than with a purely room temperature control ( figure on page 15 indicates the control method with the set factor K = 10 (room influence) and a heating curve S = 1.2.
Room temperature control with weather­compensation
This type of control offers two substantial benefits: Incorrectly set heating curves are corrected by the room temperature sensor influence K, whilst the smaller factor K provides more stable control.
However, observe the following for all control units with room temperature sensor influence: – The room temperature sensor must capture
the room temperature accurately.
– Open doors and windows severely
influence the control result.
– All radiator valves in the lead room must
always be fully open.
– The temperature inside the lead room is
decisive for the entire heating circuit. Set the room temperature sensor influence to > 0, if you want the room temperature to be taken into account.
LCD test
Pressing once initiates a LCD test. All display elements are displayed in sequence.
FEK software
Display of the current software issue.
K = 20). The
∆ϑR = (ϑ
14
Rset
− ϑ
Ractual
) * S * K
Page 15
20
30
40
20
50
60
70
80
90
Vorlauftemperatur [°C]
15 16 1917 18 21 22 23 24 25
Raumtemperatur [°C]
0
10
20
30
40
0
50
60
70
80
90
Vorlauftemperatur [°C]
20
-20
Außentemperatur [°C]
0
10
15
10
5
-5
-10
-15
Heizkurve
S = 1,2

= S K (
- )
witterungsabhängiger Vorlaufsollwert bei
A
= -10°C
witterungsabhängiger Vorlaufsollwert bei
A
= 0°C
witterungsabhängiger Vorlaufsollwert bei
A
= 10°C
Raumfühlereinfluss bei K = 10 und S = 1,2
und Regelabweichung +/- 2 K
R
R soll R ist
26_03_01_0098
S = 1.2
Heating curve
Outside temp. [°C]
Flow temp. [°C]
Weather-compensated set flow temperature ϑ = 0 °C
Weather-compensated set flow temperature ϑ = -10 °C
Weather-compensated set flow temperature ϑ = 10 °C
Room temp. [°C]
and control deviation ± 2 K
Room influence at K = 10 and S = 1.2
ϑRoom = S * K * (ϑSet Room - ϑSet Room )
Room influence
Flow temp. [°C]
15
Page 16
www.stiebel-eltron.com
Stiebel Eltron International GmbH
Dr.-Stiebel-Str. 37603 Holzminden Telefon 0 55 31/702
-0
Fax
055 31/702 - 479 E-Mail info@stiebel-eltron.com Internet www.stiebel-eltron.com
Austria
Stiebel Eltron Ges.m.b.H. Eferdinger Str. 73 A-4600 Wels 072 42-47367-0 Fax 07242-47367-42 E-Mail info@stiebel-eltron.at Internet www.stiebel-eltron.at
Belgique
Stiebel Eltron S.p.r.l./ b.v.b.a. Rue Mitoyenne 897 B-4840 Welkenraedt 087-88 1465 Fax 087-881597 E-Mail info@stiebel-eltron.be Internet www.stiebel-eltron.be
 
Stiebel Eltron spol. s r.o. K Háju
o
m 946 C�Z-15500 Praha 5-Stodulky 235 512 122 / 6111 Fax 251 116 111 E-Mail info@stiebel-eltron.cz Internet www.stiebel-eltron.cz
France
Stiebel Eltron SAS 7-9, rue des Selliers BP 85107 F-57073 Metz-Cédex 3 03-87-74 3888 Fax 03-87-746826 E-Mail info@stiebel-eltron.fr Internet www.stiebel-eltron.fr
Great Britain
Exclusive Distributor: Applied Energy Products Ltd. Morley Way GB-Peterborough PE2 9JJ 08709 000420 Fax 01733-319610 E-Mail sales@applied-energy.com Internet www.applied-energy.com
Magyarország
Stiebel Eltron Kft. Pacsirtamezo´´ u. 41 H-1036 Budapest 012 50-6055 Fax 013 68-8097 E-Mail info@stiebel-eltron.hu Internet www.stiebel-eltron.hu
Nederland
Stiebel Eltron Nederland B.V. Daviottenweg 36 Postbus 2020 NL-5202 CA‘s-Her togenbosch 073-6 2300 00 Fax 073-6 231141 E-Mail stiebel@stiebel-eltron.nl Internet www.stiebel-eltron.nl
Polska
Stiebel Eltron sp.z. o.o ul. Instalatorów 9 PL-02-237 Warszawa 022-8 4648 20 Fax 022-8 466703 E-Mail stiebel@stiebel-eltron.com.pl Internet www.stiebel-eltron.com.pl
Sverige
Stiebel Eltron AB Friggagatan 5 SE-641 37 Katrineholm 0150-487900 Fax 0150-487901 E-Mail info@stiebel-eltron.se Internet www.stiebel-eltron.se
Switzerland
Stiebel Eltron AG Netzibodenstr. 23 c CH-4133 Pratteln 061-8 169333 Fax 061-8 169344 E-Mail info@stiebel-eltron.ch Internet www.stiebel-eltron.com
Thailand
Stiebel Eltron Asia Ltd. 469 Moo 2, Tambol Klong-Jik Amphur Bangpa-In Ayutthaya 13160 035-220088 Fax 035-221188 E-Mail stiebel@loxinfo.co.th Internet www.stiebeleltronasia.com
USA
Stiebel Eltron Inc. 17 West Street West Hatfield MA 01088 04 13-247-3380 Fax 0413-247-3369 E-Mail info@stiebel-eltron-usa.com Internet www.stiebel-eltron-usa.com
Irrtum und technische Änderungenvorbehalten · Subject to errors
and technical changes! · Sous réserve d‘erreurs et de modifications
techniques!
· Onder voorbehoud vanvergissingen en technische
wijzigingen! · Salvo error o modificación técnica! · Rätt till misstag och tekniska ändringar förbehålls! · Excepto erro ou alteração técnica ·
      · Omyly a
technické změny jsou vyhrazeny!
·    
  
· Возможность неточностей и
технических изменений не исключается
CAP 270783/34075/1/8043 · HD · Subject to modifications. · 6.6701.394-00
Loading...