State PR6 75 XODS User Manual

Instruction Manual
NOT FOR USE IN MANUF ACTURED (MOBILE) HOMES
GAMA certification applies to all residential gas water heaters with capacities of 20 to 100 gallons with input rating of 75,000 BTU/Hr. or less.
For Your Safety
AN ODORANT IS ADDED TO THE GAS USED
BY THIS WA TER HEATER.
ALL TECHNICAL AND W ARRANTY QUESTIONS: SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WA TER HEA TER WAS PURCHASED. IF YOU ARE UNSUCCESSFUL, PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLA TE ON THE WA TER HEA TER.
KEEP THIS MANUAL IN THE POCKET ON HEA TER FOR FUTURE REFERENCE
PRINTED 1005 183774-001
WHENEVER MAINTENANCE ADJUSTMENT OR SERVICE IS REQUIRED.
1
SAFE INSTALLATION, USE AND SERVICE
Your safety and the safety of others is extremely important in the installation, use and servicing of this water heater.
Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and others of a potential injury hazard. Read and obey all safety messages and instructions throughout this manual. It is very important that the meaning of each safety message is understood by you and others who install, use or service this water heater.
All safety messages will generally tell you about the type of hazard, what can happen if you do not follow the safety message and how to avoid the risk of injury.
IMPORTANT DEFINITIONS
Qualified Installer: A qualified installer must have ability equivalent to a licensed tradesman in the fields of plumbing, air supply , venting and gas supply, including a thorough understanding of the requirements of the National Fuel Gas Code as it relates to the installation of gas fired water heaters. The qualified installer must also be familiar with the design features and use of flammable vapor ignition resistant water heaters, and have a thorough understanding of this instruction manual.
Service Agency: A service agency also must have ability equivalent to a licensed tradesman in the fields of plumbing, air supply , venting and gas supply, including a thorough understanding of the requirements of the National Fuel Gas Code as it relates to the installation of gas fired water heaters. The service agency must also have a thorough understanding of this instruction manual, and be able to perform repairs strictly in accordance with the service guidelines provided by the manufacturer.
Gas Supplier: The Natural Gas or Propane Utility or service who supplies gas for utilization by the gas burning
appliances within this application. The gas supplier typically has responsibility for the inspection and code approval of gas piping up to and including the Natural Gas meter or Propane storage tank of a building. Many gas suppliers also offer service and inspection of appliances within the building.
Piezo-Electric Spark Gas Ignition System: A combination of a piezo-electric spark generator , high voltage lead(s) and
a spark electrode(s) designed to ignite pilot burner gas at an appliance burner .
2
GENERAL SAFETY
3
TABLE OF CONTENTS
SAFE INSTALLA TION, USE AND SERVICE...............................2
GENERAL SAFETY ..................................................................3
T ABLE OF CONTENTS .............................................................. 4
INTRODUCTION ........................................................................4
Preparing for the New Installation...................................4
TYPICAL INST ALLA TION ...................................................... 5-6
LOCA TING THE NEW WA TER HEA TER..................................... 7
Facts to Consider About Location ............................... 7-8
Venting Clearances..........................................................8
Optional Wire Grill ............................................................9
Flue Extensions ................................................................ 9
Vertical Height (Extension Kit).......................................10
Horizontal (Extension Kit) .............................................. 10
Vent Inst allations .......................................................11-24
INST ALLING THE NEW WA TER HEATER ................................ 25
Water Piping ...................................................................25
T emperature-Pressure Relief V alve............................... 26
Filling the Water Heater............... .......... .......... .......... .....27
Gas Piping ................................................................ 27-28
Sediment Traps .............................................................. 28
Installation Checklist.......................................................29
LIGHTING & OPERA TING LABEL ............................................ 30
TEMPERA TURE REGULATION ................................................ 31
FOR YOUR INFORMATION .....................................................31
Start Up Conditions ........................................................ 31
Condensate ....................................................................32
Smoke/Odor....................................................................32
Thermal Expansion......................................................... 32
Strange Sounds..............................................................32
OPERATIONAL CONDITIONS..................................................32
Smelly Water .................................................................. 32
“Air” in Hot Water Faucets.............................................32
High T emperature Shut Of f System ............................... 32
PERIODIC MAINTENANCE ....................................................... 33
Venting System Inspection ............................................ 33
Burner Inspection...........................................................33
Burner Cleaning..............................................................33
Housekeeping ................................................................34
Anode Rod Inspection.................................................... 34
T emperature-Pressure Relief V alve Operation.............. 34
Draining ..........................................................................34
Drain Valve Washer Replacement................................. 35
LEAKAGE CHECKPOINTS ......................................................35
REPAIR P ARTS ....................................................................... 36
TROUBLESHOOTING .............................................................. 40
NOTES .............................................................................. 41-43
WARRANTY ..................................................................... Insert
INTRODUCTION
Thank Yo u for purchasing this water heater. Properly installed and
maintained, it should give you years of trouble free service. Abbreviations Found In This Instruction Manual:
• CSA - Canadian Standards Association
• ANSI - American National Standards Institute
• NFPA - National Fire Protection Association
• ASME - American Society of Mechanical Engineers
• GAMA - Gas Appliance Manufacturer’s Association
This gas-fired water heater is design certified by CSA INTERNA TIONAL under American National S tandard/CSA Standard for Gas W ater Heaters ANSI Z21.10.1 • CSA 4.1 (current edition).
This gas-fired water heater is equipped with a piezo-electric spark device used for pilot burner ignition, and complies with the St andard for Manually-Operated Piezo-Electric Spark Gas Ignition Systems and Components, ANSI Z21.77 • CGA 6.23.
PREPARING FOR THE INSTALLATION
1. Read the “General Safety” section, page 3 of this manual first and then the entire manual carefully. If you don’t follow the safety rules, the water heater will not operate properly . It could cause DEA TH, SERIOUS BODIL Y INJURY AND/OR PROPERTY DAMAGE.
This manual contains instructions for the installation, operation, and maintenance of the gas-fired water heater. It also contains warnings throughout the manual that you must read and be aware of. All warnings and all instructions are essential to the proper operation of the water heater and your safety . Since we cannot put everything on the first few pages, READ THE ENTIRE MANUAL BEFORE
A TTEMPTING TO INST ALL OR OPERA TE THE WATER HEA TER.
2. The installation must conform with these instructions and the local code authority having jurisdiction. In the absence of local codes, installations shall comply with the National Fuel Gas Code ANSI Z223.1/NFPA 54. This publication is available from the Canadian Standards Association, 8501 East Pleasant V alley Rd., Cleveland Ohio 44131, or The National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269.
3. If after reading this manual you have any questions or do not understand any portion of the instructions, call the local gas utility or the manufacturer whose name appears on the rating plate.
4. Carefully plan the place where you are going to put the water heater. Correct combustion, vent action and vent pipe installation are very important in preventing death from possible carbon monoxide poisoning and fires, see Figures 1 and 2.
Examine the location to ensure the water heater complies with the “Locating the New Water Heater” section in this manual.
5. For California installation this water heater must be braced, anchored or strapped to avoid falling or moving during an earthquake. See instructions for correct installation procedures. Instructions may be obtained from California Office of the St ate Architect, 400 P Street, Sacramento, CA 95814.
6. Massachusetts Code requires this water heater to be installed in accordance with Massachusetts 248-CMR 2.00: St ate Plumbing Code and 248-CMR 5.00.
7. Complies with SCAQMD rule #1121 and districts having equivalent NOx requirements.
4
TYPICAL INSTALLATION
GET TO KNOW YOUR WATER HEATER - GAS MODELS
A Vent Assembly B Flue Outlet C Anode D Hot Water Outlet
E Outlet
F Insulation G Gas Supply H Manual Gas Shut-off Valve
* INSTALL IN ACCORDANCE
WITH LOCAL CODES.
*DRIP LEG AS REQUIRED
BY LOCAL CODES.
I Ground Joint Union J Drip Leg (Sediment Trap) K Inner Door L Outer Doors w ith Gaskets
M Union
N Inlet Water Shut-off Valve
O Cold Water Inlet
P Inlet Dip Tube Q Temperature-Pressure Relief Valve R Rating Plate S Flue Baffle T Thermostat U Drain Valve
V Pilot and Main Burner
W Flue
X Drain Pan Y Piezo Ignitor Z Thermostat Shield (optional)
(V) PILOT & MAIN BURNER
(T) THERMOSTA T
*ALL PIPING MATERIALS TO BE
SUPPLIED BY CUSTOMERS.
FIGURE 1.
5
TYPICAL INSTALLATION
MIXING VALVE USAGE
This appliance has been design certified as complying with Am erican N ational Standard/CS A Standard for water heat ers and is considered suitable for:
Water (Potable) Heating: All models are “considered suitable for water (potable) heating.”
Water (Potable) Heating and Space Heating: Certain models are “considered suitable for water (potable) heating and space heating.” Refer to the model and rating plate of the water heater.
FIGURE 2.
HOT WATER CAN SCALD:
Water heaters are intended to produce hot water. Water heated to a temperature which will satisfy space heating, clothes washing, dish washing, and other sanitizing needs can scald and permanently injure you upon contact. Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, the infirm or physically/ mentally handicapped. If anyone using hot water in your home fits into one of these groups or if there is a local code or state law requiring a certain temperature water at the hot water tap, then you must take special precautions. In addition to using the lowest possible temperature setting that satisfies your hot water needs, a means such as a *Mixing Valve shall be used at the hot water taps used by these people or at the water heater. Mixing valves are available at plumbing supply or hardware stores. Consult a Qualified Installer or Service Agency. Follow mixing valve manufacturer ’s instructions for installation of the valves. Before changing the factory setting on the thermostat, read the “Temperature Regulation” section in this manual, see Figures 109 and 110.
6
LOCATING THE NEW WATER HEATER
FACTS TO CONSIDER ABOUT THE LOCA TION
Carefully choose an indoor location for the new water heater, because the placement is a very important consideration for the safety of the occupants in the building and for the most economical use of the appliance. This water heater is not for use in manufactured
(mobile) homes or outdoor installation.
Whether replacing an old water heater or putting the water heater in a new location, the following critical points must be observed:
1. The location selected should be indoors, as close as practical to the outside wall through which the water heater vent is going to be installed, and as centralized with the water piping system as possible. The water heater, as all water heaters, will eventually leak. Do not install without adequate drainage provisions where water flow will cause damage.
2. Selected location must provide adequate clearances for servicing and proper operation of the water heater.
Installation of the water heater must be accomplished in such a manner that if the tank or any connections should leak, the flow will not cause damage to the structure. For this reason, it is not advisable to install the water heater in an attic or upper floor. When such locations cannot be avoided, a suitable drain pan should be installed under the water heater. Drain pans are available at your local hardware store. Such a drain pan must have a minimum length and width of at least 2 inches (5.1 cm) greater that the water heater dimensions and must be piped to an adequate drain. Drain pan depth must allow for access to the outer doors for servicing the pilot and burner.
INSTALLA TIONS IN AREAS WHERE FLAMMABLE LIQUIDS (VAPORS) ARE LIKELY TO BE PRESENT OR STORED (GARAGES, STORAGE AND UTILITY AREAS, ETC.): Flammable liquids (such as gasoline, solvent s, propane [LP or butane, etc.] and other substances such as adhesives, etc.) emit flammable vapors which can be ignited by a gas water heater’s pilot light or main burner. The resulting flashback and fire can cause death or serious burns to anyone in the area, as well as property damage. If installation in such areas is your only option, then the installation must be accomplished in a way that the pilot flame and main burner flame are elevated from the floor at least 18 inches (45.7 cm). While this may reduce the chances of flammable vapors, from a floor spill being ignited, gasoline and other flammable substances should never be stored or used in the same room or area containing a gas water heater or other open flame or spark producing appliance. NOTE: Flammable vapors may be drawn by air currents from other areas of the structure to the appliance.
Water heater life depends upon water quality, water pressure and the environment in which the water heater is installed. Water heaters are sometimes installed in locations where leakage may result in property damage, even with the use of a drain pan piped to a drain. However, unanticipated damage can be reduced or prevented by a leak detector or water shut-off device used in conjunction with a piped drain pan. These devices are available from some plumbing supply wholesalers and retailers, and detect and react to leakage in various ways:
• Sensors mounted in the drain pan that trigger an alarm or turn off the
incoming water to the water heater when leakage is detected.
• Sensors mounted in the drain pan that turn off the water supply to
the entire home when water is detected in the drain pan.
• Water supply shut-off devices that activate based on the water
pressure differential between the cold water and hot water pipes connected to the water heater.
• Devices that will turn off the gas supply to a gas water heater while
at the same time shutting off its water supply .
7
Also, the water heater must be located and/or protected so it is not subject to physical damage by a moving vehicle.
This water heater must not be installed directly on carpeting. Carpeting mu st be protected by metal or wood panel beneath the appliance extending beyond the full width and depth of the appliance by at least 3 inches (7.62 cm) in any direction, or if the appliance is installed in an alcove or closet, the entire floor must be co ve r ed by the panel. Failure to heed this warning may result in a fire hazard.
Minimum clearances between the water heater and combustible and noncombustible construction are 0 inch at the sides, 0 inches from back, 4”(10.2 cm) from front of jacket to closet door and 3”(7 .6 cm ) from top of jacket to combustible and noncombustible material. Minimum vent clearance: 0 inches.
No vent damper , whether it is operated thermally or otherwise, is to be installed on this direct vent water heater. Alteration of any p art of the factory-furnished vent assembly could result in improper operation due to restriction of flue gases and may cause carbon monoxide poisoning.
Venting Clearances
When determining the installation location for a direct vent water heater , snow accumulation and drifting should be considered in areas where applicable. See Figures 4 through 8 and items below.
• 18” minimum in all directions from any obstruction that may interfere.
• 18” minimum from the ground and 12 “ from ceiling overhangs.
• The direct vent terminal shall terminate at least 3 feet above any forced air inlet located within 10 feet. See Figure 5.
• 9” minimum horizontally from or above any door, window or gravity air inlet into the building (50,000 BtuH input or less.)
FIGURE 3.
NOTE: Provide 24 inches (61 cm) front clearance for servicing and
a adequate clearance between the jacket top and ceiling for servicing the flue area.
Combustion Air and Ventilation
• 12” minimum horizontally from or above any door, window or gravity air inlet into the building (over 50,000 BtuH input).
• 12” minimum below any door, window or gravity air inlet into the building (50,000 BtuH input or less).
• 18” minimum below any door, window or gravity air inlet into the building (over 50,000 BtuH input).
• 18” minimum from other gravity or natural appliance outlet vents when directly above or 135° to either side of center line. See Figure 6.
• 36” minimum from any outlet vents when directly below or 45° to either side of center line. See Figure 7.
• 36” minimum in all directions from any other forced air appliance outlet vent. See Figure 7.
• The location selection must provide clearances for servicing and proper operation of the water heater. See Figure 8.
• Vent termination must not be within 4 feet of any items such as gas meters, gas valves or other gas regulating equipment.
Unless specified at time of ordering, a standard extension
kit (No. 9000687) is individually packaged and shipped with the water heater.
FIGURE 4.
8
FIGURE 5.
Some local codes may require a vent cap cover. Figure 9 shows the optional wire vent cap protector available from the water heater manufacturer.
A wire mesh chain link fence (see Figure 9) may be used instead of the factory cover. Care should be t aken to maintain adequate ventilation around the vent cap. If a chain link fence is installed, it must not be used as a storage area for items that may block proper ventilation.
FIGURE 9.
Flue Extensions
There are three optional extension kits available. Any combination of the three kits can be chosen; however, only one kit can be used vertically and/or horizontally, see Figures 10 & 11.
Unless otherwise specified at the time of ordering, a standard exten­sion kit (9000687) is individually packaged and shipped within the water heater carton.
FIGURE 10.
FIGURE 8.
Optional Wire Grill
When the water heater vent cap is low enough to be touched accidentally , or is accessible to small children, installation of a protective vent cover is recommended. See Figure 9.
9
V ertical Height (Extension Kit)
It is simple to determine which kit is needed for vertical height. T ake the total height (to the top of the flue) required and comparing that to “F dimension” in the chart #1, it can be determined which kit needs to be used vertically.
BTU’s DIMENSION “F” (IN CENTIMETERS)
*Gal. in 1000’s 9000687 9001246 9001247 9001248 Cap. Nat/L.P STD. MIN. MAX. MIN. MAX. MIN. MAX.
40 36/36 162 183 196 196 224 224 279 50 38/38 183 205 218 219 247 247 302 40 40/40 162 183 196 196 224 224 279 50 48/44 193 214 228 228 256 256 312 75 55 NAT. 194 21 5 2 2 7 227 255 255 311
*Check the model and rating plate attached to the water heater for specific model number and other detailed information.
Horizontal (Extension Kit)
T o determine the horizontal length and extension kit needed, simply plug the dimensions “D” and “G” into the equation below. The answer “E” should then be located in Chart #2. The size range in which “E” dimension falls indicates the kit that should be used horizontally to obtain the desired length.
“D” = The wall thickness “G” = The distance wanted between the edge of the water heater
and the inside edge of the wall
“E” = The distance the extension kit must be able to extend
The Equation: D + G = E
FIGURE 11.
FIGURE 12.
CHART #1 .
BTU’s DIMENSION “F” (IN INCHES)
*Gal. in 1000’s 9000687 9001246 9001247 9001248
Cap. Nat/L.P STD. MIN. MAX. MIN. MAX. MIN. MAX.
40 36/36 63 3/4 72 77 77 88 88 110 50 38/38 72 80 3/4 86 86 1/4 97 1/4 97 1/4 1 18 3/4 40 40/40 63 3/4 72 77 77 88 88 110 50 48/44 76 84 1/4 89 3/4 89 3/4 100 3/4 100 3/4 122 3/4 75 55 NAT. 76 1/4 84 1/2 89 1/2 89 1/2 100 1/2 100 1/2 122 1/2
FIGURE 13 .
CHART #2.
DIMENSION “E” (IN INCHES)
40-50 GAL. 75 GAL.
VENT KITS MIN MAX MIN MAX
9000687-Std. 3 1/2 10 7/8 7 3/8 9001246 10 15 1/2 7 3/8 12 7/8 9001247 15 1/2 26 1/2 12 7/8 23 7/8 9001248 26 1/2 48 23 7/8 45 3/8
DIMENSION “E” (I N CENTIMETERS )
40-50 GAL. 75 GAL.
VENT KITS MIN MAX MIN MAX
9000687-Std. 8.9 cm 25.4 cm 2.2 cm 18.7 cm 9001246 25.4 cm 29.4 cm 18.7 cm 32.7 cm 9001247 39.4 cm 67.3 cm 32.7 cm 60.6 cm
9001248 67.3 cm 121.9 cm 60.6 cm 115.3 cm
BTU’s DIMENSION “A, B, C” (INCHES/CENTIMETERS)
*Gal. in 1000’s Cap. Nat.
40 36/36 48 3/4” 124 cm 41 3/4” 106 cm 21” 53 cm 50 38/38 57 1/2” 146 cm 50 1/2” 128 cm 21” 53 cm 40 40/40 48 3/4” 124 cm 41 3/4” 106 cm 21” 53 cm 50 48/44 61” 155 cm 54” 137 cm 21” 53 cm 75 55 NAT. 63” 160 cm 54 3/4” 139 cm 26 1/4” 67 cm
10
ABC
ALL INST ALLA TIONS
Standard Vent Kit - Installation #1
For ease of assembly the installation of the various kit combinations has been broken into individual sections. The two steps below are common to all installations. Once these have been performed, you need only to refer to the type installation that pertains to you.
Installation Using Vent Kit s:
1. St andard Vent Kit 9000687 ............................................. Page 1 1
2. Optional Vertical V ent Kit................................................. Page 14
with Standard V ent Kit
3. Optional Horizontal Vent Kit............................................. Page 17
4. Optional Horizontal.......................................................... Page 19
and Vertical V ent Kits
Cutting The Opening Through The Outside Wall
After thoroughly reading the “Locating the New Water Heater” section of this manual and you have chosen a suitable water heater installation site, use Chart #1 to determine dimensions for the wall opening.
Cut a 6 1/4” (159 mm) diameter hole completely through the outside wall.
The opening through the wall should be cut at this time. If this has not been done, refer to “Cutting The Opening Through The Outside Wall ” section.
1. Lock the elbow to the straight 3” (76 mm) flue pipe. Set this assembly in place on the end of the water heater’s flue collar.
FIGURE 14.
Water Heater Attitude
There is a certain amount of variance with regard to the direction the water heater faces.
Standing in front of the water heater (gas control facing you), set the 3” (76 mm) diameter elbow (slotted end) on the flue. This will give you a better understanding of the relation of the vent assembly to the opening in the wall and more importantly any possibility of interference of venting and water piping.
The direction of the water heater can now be made. Also consider the gas control valve to insure installation, lighting and maintenance accessibility are retained.
NOTE: Supplementary installation instructions are applicable only if this direct vent water heater is provided with the alternate brown porcelain-enameled vent cap and the 6” (152 mm) vent wall assembly show below, See pages 22 thru 24.
FIGURE 15.
2. Mark the flue collar at the slots in the elbow . Using a #22 drill bit, drill holes into the flue collar at the two slots and secure the elbow to the flue collar using the screws provided.
NOTE: Make sure elbow is properly aligned to opening in the outside wall.
FIGURE 16 .
3. Using the tube of sealant supplied, run an ample amount around the oval flare of the jacket.
11
FIGURE 17.
4. First remove the 3” (76 mm) horizontal extension from the elbow. Start­ing with the long end (with four securing holes), place the 6” (152 mm) diameter vent elbow over the 3” (76 mm) diameter elbow . Bend the round end “oval” to fit the flared oval end of the jacket top.
FIGURE 18.
5. Making sure the 6” (152 mm) diameter elbow is centered around the 3” (76 mm) diameter flue, secure the 6” (152 mm) diameter vent pipe using four sheet metal screws at the connection of the jacket top.
FIGURE 21.
8. Slide the vent collar (to be installed later) over the 6” (152 mm) vent elbow.
FIGURE 22.
9. Place the water heater at the opening in the wall, at the predetermined clearance.
FIGURE 19 .
6. The standard vent kit includes a 6” (152 mm) diameter extension pipe which is used when “E” dimension is over 6 1/2” ( 165 mm).
FIGURE 23.
10. Move outdoors with all the remaining vent parts. Using the tube of sealant supplied, run an ample amount on the inside surface of the collar assembly that will contact the exterior wall and also fill the bead on the end of the 6” ((152 mm) diameter vent collar.
FIGURE 20.
7. If “E” dimension is less than 6 1/2” (165 mm) move to next step. If “E” dimension is over 6 1/2” (165 mm), assemble the 6” (152 mm)
diameter extension pipe (crimped end) to the 6” (152 mm) diameter vent elbow and secure using two sheet metal screws. Apply an ample amount of sealant around the joint to ensure a good seal.
FIGURE 24.
12
11. Inst all the vent collar assembly through the wall, connecting it to the extension and/or elbow (depending on which one was used).
FIGURE 25.
12. We have supplied four wood screws to temporarily attach the collar
to the exterior wall of the building. However , other types of screws may have to be substituted depending on the material used in the construction of the exterior wall.
15. The vent cap has four holes around the outer edge. Remove the four screws used to temporarily attach the collar to the exterior wall. Then secure the vent cap assembly with the vent collar assembly to the exterior wall using the same four screws.
NOTE: Screws are supplied: However, substitution may be necessary depending on the exterior wall material.
FIGURE 26.
13. Insert the 3” (76 mm) diameter flue extension pipe into the vent collar assembly (flared & notched end first) and lock (turn clockwise to lock studs to slots) the flue extension pipe to the flue elbow .
14. Connect the vent cap by sliding its end over the 3” (76 mm) diameter extension pipe and O-ring.
NOTE: T o facilitate ease of assembly of the vent cap to the 3” (76 mm ) pipe, a soap solution can be applied to the O-ring gasket.
FIGURE28.
16. Go back indoors to a ttach inside collar to the inside wall. Place the collar against the wall. Secure to wall by using four long sheet metal screws.
NOTE: Screws are supplied: However, substitution may be necessary depending on the interior wall material.
FIGURE 29.
17. Using the tube of sealant supplied, run an ample amount of sealant
around the edge of the vent pipe where it is inserted through the inside collar to seal air drafts from wall.
FIGURE 27.
FIGURE 30.
13
Optional Vertical Vent Kit with Standard Horizontal V ent Kit - Installation #2
Any Optional Vent Kit
2. Set the vertical 3” (76 mm) diameter telescoping flue section in place on the flue collar. Using a # 22 drill bit, drill two holes (180° apart) and secure the vertical assembly to the flue collar.
FIGURE 33.
*Each part is stamped with a part number.
The opening through the wall should be cut at this time. If this has not been done, refer to “Cutting The Opening Through The Out side Wall,” on page 1 1.
1. First it must be determined how far the vertical 3” (76 mm) diameter telescoping flue sections are set and locked together using the two screws supplied.
FIGURE 31 .
Use chart #3, drawing and simple equation below, to find the length of expansion of the telescoping flue sections. Because of manufacturing tolerances, place the telescoping extension on the water heater and adjust the height (“X” Dimension) and mark the point. Once the length has been determined, lock the two sections together by drilling two holes (180° apart) in the pipe and securing with the screws supplied.
3. Slide the 6” (152 mm) vent telescoping section apart to reveal the beads. Using the caulking supplied, fill the beads.
FIGURE34.
4. Apply an ample amount of sealant around the oval flare of the jacket.
FIGURE 35.
5. Place the 6” (152 mm) vent section over the 3” (76 mm) flue section. Subtract 3/4” (19 mm) from the predetermined “X” dimension. This determines the length of the 6” (152 mm) vent extension. Slide the 6” (152 mm) vent extension apart to this dimension and secure with the two screws supplied.
FIGURE 32.
CHART #3 *GAL CAP . *BTU’s in 1000’ s - NAT./L.P . A
40 36/36 48 3/4” 124 cm 50 38/38 57 1/2” 146 cm 40 40/40 48 3/4” 124 cm 50 48/4 4 61” 155 cm 75 55 NAT . 63” 160 cm
*Check the model and rating plate attached to the water heater for specific model number and other detailed information.
FIGURE 36.
6. Form the round end of the 6” (152 mm) vent extension to the top of the jacket and secure with four sheet metal screws.
FIGURE 37.
14
7. Place the 3” (76 mm) elbow on the flue extension.
NOTE: Make sure elbow is properly aligned to opening in the outside wall.
Mark the 3” (76 mm) diameter end of the flue extension at the slots in the elbow. Using a #22 drill bit, drill holes into the flue extension at the two slots and secure the elbow to the flue extension using the screws provided.
10. If “E” dimension is less than 6 1/2” (165 m m) move to next step. If “E” dimension is over 6 1/2” (165 mm), assemble the 6” (152 mm) diameter extension pipe to the 6” (152 mm) diameter vent elbow and secure using two sheet metal screws. Using the tube of sealant supplied, run an ample amount around the joint to insure a good seal.
FIGURE 41.
FIGURE 38.
8. Be sure the 6” ( 1 52 mm) diameter elbow is centered around the 3” (76 mm) diameter flue. Secure the 6” (152 mm) diameter vent pipe using two sheet metal screws at the cnnection of the elbow and 6” (152 mm) vertical extension.
FIGURE 39.
9. The standard vent kit includes a 6” (152 mm) diameter extension pipe which is used when dimension “E” (refer to Chart 2) is over 6 1/2” (165 mm).
11. Slide the vent collar (to be installed later ) over the 6” ( 152 mm) vent elbow.
FIGURE 42.
12. Move the water heater into position at the vent opening.
FIGURE 40.
FIGURE43.
13. T ake the remaining vent parts outside to complete the inst allation. Using the tube of sealant supplied, apply an ample amount of sealant to the inside surface of the collar assembly that will contact the exterior wall. Also, apply sealant to the bead around the outside edge at the end of the 6” ( 152 mm) diameter vent collar.
FIGURE 44.
15
14. Install the vent collar assembly through the wall, connecting it to the extension and/or elbow depending on which one was used.
FIGURE 45.
15. Four wood screws are supplied to temporarily attach the collar to the exterior wall of the building. However, other types of screws may have to be substituted depending on the construction material of the exterior wall.
18. The vent cap has four holes around the outer edge. Remove the four screws used to temporarily attach the collar to the exterior wall. Then secure the vent cap to the exterior wall using the same four screws.
NOTE: Screws are supplied. However, substitution may be necessary depending on the exterior wall material.
FIGURE 49.
FIGURE46.
16. Insert the 3” (76 mm) diameter flue extension pipe into the vent collar assembly (flared and notched end first) and rotate clockwise to lock the studs to the slots in the extension pipe.
FIGURE 47.
17. Connect the vent cap by sliding it’s end over the 3” (7.6 cm) diam­eter extension pipe an O-ring.
NOTE: to facilitate ease of assembly of the vent cap to the 3” (7.6 cm) pipe a soap solution can be applied to the O-ring gasket.
19. Go back in do or s to att ach ins id e collar to the inside wall. Place the collar against the wall. Secure to wall by using four long sheet metal screws.
NOTE: Screws are supplied. However, substitution may be necessary depending on the exterior wall material.
FIGURE 50.
20. Using the tube of sealant supplied, apply an ample amount of sealant around the edge of the vent pipe where it is inserted through the inside collar. This will seal air draft from the walls.
FIGURE 48.
FIGURE 51.
16
Optional Horizontal V ent Kit - Installation #3
If the vent hole has not been cut, refer to “Cutting The Opening Through The Outside W all.” See page 11.
1. Lock the elbow to the straight 3” (76 mm) flue pipe. Set this assembly in place on the end of the water heater’s flue collar.
FIGURE 54.
4. First remove the 3” (7.6 cm) horizontal extension from the elbow. Starting with the long end, which has four mounting holes, place the 6” (152 mm) diameter vent elbow over the 3” (76 mm) elbow. Bend the round end to fit the flared oval end of the jacket top.
FIGURE 55.
FIGURE 52.
2. Mark the flue collar at the slots in the elbow. Using a # 22 drill bit, drill holes into the collar at the two slots and secure the elbow to the collar with the screws provided.
NOTE: make sure elbow is properly aligned to the opening in the outside wall.
5 . Be sure the 6” (152 mm ) diam eter e lbow is cen tered aro und the
3” (76 mm ) diameter flue. Secure the vent pipe with four sheet metal screws at the connection at the jacket top.
FIGURE 56.
NOTE: the standard kit includes a 3” (76 mm) flue extension and a 6” (152 mm) elbow extension. These parts will not be used with the horizontal kit.
6. Slide the vent collar (to be installed later) over the 6” (152 mm) vent elbow.
FIGURE 53.
3. Using the tube of sealant supplied run an ample amount around the oval flare of the jacket.
FIGURE 57.
17
7. Place the waterheater at the opening in the wall at the predetermined clearance.
FIGURE 58.
8. Slide the 6” (152 mm) telescoping vent section apart to expose the
beads. Use the supplied tube of sealant and fill the exposed beads.
11. Insert the vent collar assembly through the wall opening, connect­ing to the 6” (1 52 mm) telescoping extension. Remember, the vent extension has not been connected so it may be necessary to go back outdoors and push it back up into the wall opening for a tight fit to the collar.
FIGURE 62.
12. Four wood screws were supplied to temporarily attach the collar to the exterior wall of the building. However, you may have to substi­tute other types of screws depending on the construction material of the exterior wall.
FIGURE 59.
9. Insert the 6” (152 mm) telescoping vent section into the opening in the wall.
FIGURE 60.
10. The remaining vent parts will be installed from the outside. Apply ample
amount of sealant to the inside surface of the collar assembly that will contact the exterior wall. Also, apply sealant to the bead around the outside edge at the end of the 6” (152 mm) diameter vent collar .
FIGURE 63.
13. Insert the vent cap into the vent collar assembly .
FIGURE 64.
14. The vent cap has four holes around the outer edge. Remove the four screws used to temporarily attach the collar to the exterior wall. Then secure the vent cap assembly with the vent collar assembly to the exterior wall using the same screws.
Note: Screws are supplied; however, substitution may be necessary depending on the exterior wall material.
FIGURE 61.
FIGURE 65.
15. The remainder of the installation will be indoors to complete the
assembly process.
18
16. Collapse the 6” flue extension assembly as shown below. Install the O-ring end of the 3” (7.6 cm) extension approximately 1 1/4” (3.2 cm) into the end of the vent cap. If necessary, apply a soap solution to the O-ring to ease the assembly. Rot ate the 3” extension clockwise until the other end is locked to the studs on the elbow.
FIGURE 66.
17. Using a # 22 drill bit, drill holes 180° apart at the connection point of the two 3” (7.6 cm) flue extensions. Secure with the two screws provided.
20. Secure the 6” (15.2 cm) vent extension to the vent elbow with the two provided screws spacing them 180° apart.
FIGURE 70.
Optional Vertical and Horizontal Vent Kit ­Installation #4
FIGURE 67.
18. Expand the 6” (15.2 cm) telescoping extension to connect at the vent elbow.
FIGURE 68.
19. Push the vent collar from the elbow against the wall and secure with the four provided screws.
FIGURE 69.
If the vent hole has not been cut, refer to section, “Cutting The Opening Through The Outside Wall.” See page 11.
1. First determine how far the vertical 3” (7.6 cm) diameter telescoping flue sections are to be set and locked together with two screws supplied.
FIGURE 71.
Use the Chart #4, and figure 72 to determine the length of expansion of the telescoping flue sections. Because of manufacturing tolerances, put the telescoping extension on the water heater, adjust the height (dimen­sion “X”) and mark the point. Once the length has been determined, lock the two sections together by drilling two holes (180° apart) in the pipe and secure with the supplied screws.
19
CHART #4.
5. Place the 6” (15.2 cm) vent section over the 3” (7.6 cm) flue section. Subtract 3/4” ( 1.9 cm) from the predetermined “X” dimension. This determines the length of the 6” (15.2 cm) vent extension. Slide the 6” (15.2 cm) vent extension apart to this dimension and secure with the two screws supplied.
FIGURE 72.
*GAL CAP *BTU’s in 1000’s - NA T . /L.P. A
40 36/36 48 3/4” 124 cm 50 38/38 57 1/2” 146 cm 40 40/40 48 3/4” 124 cm 50 48/44 61” 155 cm 75 55 NAT . 63” 160 cm
*Check the model and rating plate attached to the water heater for specific model number and other detailed information.
2. Set the vertical 3” (7. 6 c m ) diameter telescoping flue s ect io n i n place on the flue collar . Using a #22 drill bit, drill two holes ( 180° apart) and secure the vertical assembly to the flue collar with the two supplied screws.
FIGURE 73.
3. Slide the 6” (15.2 cm) vent telescoping section apart to reveal the beads. Fill the beads using the supplied caulking.
FIGURE 76.
6. Form the round end of the 6” (15.2 cm) vent extension to the top of the jacket and secure with four sheet metal screws.
FIGURE 77 .
7. Place the 3” (7.6 cm) elbow on the flue extension. Align the elbow to the hole previously made in the outside wall. Using the slots in the elbow, mark the 3” (7.6 cm) diameter end of the flue extension. Using a #22 drill bit, drill two holes into the flue extension and secure with the two provided sheet metal screws.
FIGURE 74.
4. Apply an ample amount of sealant around the oval flare of the jacket.
FIGURE 75.
FIGURE 78.
NOTE: the standard kit includes a 3” (7.6 cm) flue extension and a 6” (15.2 cm) elbow extension. These parts will not be used with the horizontal kit.
20
8. Be sure the 6” (15.2 cm) diameter elbow is centered around the 3” (7.6 cm) diameter flue, secure using two sheet metal screws at the connection of the elbow and the 6” (1 5.2 cm) vertical extension.
FIGURE 79.
9. Slide the vent collar ( to be installed later) over the 6” (15.2 cm ) vent elbow.
11. Slide the 6” (15.2 cm) telescoping vent section apart to expose the beads. Use the supplied tube of caulking and fill the exposed beads.
FIGURE 82.
12. Insert the 6” (15.2 cm) telescoping vent section into the wall.
FIGURE 80.
10. Move the water heater into position at the vent opening.
FIGURE 83.
13. The remaining vent parts will be installed from the outside. Apply
ample amount of sealant to the inside surface of the collar assembly that will contact the exterior wall. Also, apply sealant to the bead around the outside edge at the end of the 6” (15.2 cm) diameter vent collar.
FIGURE 84.
14. Install the vent collar assembly through the wall, connecting to the
6” (15.2 cm) telescoping extension. R emember, the extension is not connected and may be necessary to return indoors to push the extension back against the interior wall for a tight fit to the collar.
FIGURE 81.
FIGURE 85.
21
15. Four wood screws were supplied to temporarily attach the collar to the exterior wall of the building. However, you may have to substitute other types of screws depending on the construction material of the
exterior wall.
FIGURE 86.
20. Using a #22 drill bit, drill holes 180° apart at the connection point of the two 3” (76 mm) flue extensions. Secure with the two screws provided.
16. Insert the vent cap into the vent collar assembly.
FIGURE 87.
17. The vent cap has four holes around the outer edge. Remove the four screws used to temporarily attach the collar to the exterior wall. Then secure the vent cap assembly with the vent collar assembly to the exterior wall using the same screws.
Note: Screws are supplied; however, substitution may be necessary depending on the exterior wall material.
FIGURE 88.
FIGURE 90.
21. Expand the 6” (152 mm) telescoping extension pipes to connect at the vent elbow.
FIGURE 91.
22. Push the vent collar from the elbow against the wall and secure with the four provided screws.
18. The remainder of the installation will be conducted indoors to complete the assembly process.
19. Collapse the 6” extension assembly as shown below. Inst all the O-
ring end of the 3” (7.6 cm) extension approximately 1 1/4” (3.2 cm) into the end of the vent cap. If necessary , apply a soap solution to the O-ring to ease the assembly. Rotate the extension clockwise until the other end is locked to the studs on the elbow.
FIGURE 89.
FIGURE 92.
23. Secure the 6” (152 mm) vent extension to the vent elbow with the two provided screws spacing them 180° apart.
FIGURE 93.
Optional Vent Cap - Porcelain-Enameled
These supplementary installation instructions are applicable only if this direct vent water heater is provided with the alternate brown
22
porcelain-enameled ven t cap assembly and the 6” ( 15 .2 cm) vent
wall assembly shown by Figure 94.
FIGURE 94.
The water heater model designation on the rating plate will have a suffix “P” to indicate this alternate vent cap assembly.
The alternate installation instructions below will replace the itemized instructions in the manual as follows: Items 11 thru 15 on page 13 and items 14 thru 18 on page 16.
1. Making sure the arrow points “UP”, install the vent collar assembly through the wall, connecting it to the extension and/or elbow depending on which one was used.
16. Insert the 3” (7.6 cm) diameter flue extension pipe into the vent collar assembly (flared and notched end first). Lock the flue extension pipe to the flue elbow by rotating clockwise to lock studs to slots.
FIGURE 97.
4. Connect the vent cap by sliding it over the 3” (7.6 cm) diameter
extension pipe and O-ring.
NOTE: for ease of assembly of the vent cap to the 3” (7.6 cm) pipe a
soap solution can be applied to the O-ring gasket.
FIGURE 95.
2. Three wood screws are supplied to attach the collar to the exterior wall of the building. However, other types of screws may have to be substituted depending on the construction of the exterior wall.
NOTE: alternate screws used must not have a head larger than 3/8” (.95 cm).
The three screws must be placed at every other hole (120° apart) to secure the vent collar assembly to the outside wall.
FIGURE 98.
5. The vent cap has six holes around the outer edge. The three larger ones are to fit over the three screws securing the vent collar assem­bly to the exterior wall. The three smaller ones will now be used to attach the vent cap assembly .
NOTE: screws are supplied. However, substitution may be necessary depending on the exterior wall material.
FIGURE 96.
FIGURE 99.
23
The following alternate illustrated instructions will replace the itemized instructions in the manual as follows: Items 11 through 14 on page 18 and Items 14 through 17 on pages 21 and 22.
1. Making sure the arrow points “up”, install the vent collar assembly through the wall, connecting it to the 6” (15.2 cm) telescoping extension. Remember, the extension is not connected, and it may be necessary to return indoors to push the extension back against the interior wall for a tight fit to the collar.
FIGURE 100.
2. Three wood screws are supplied to attach the collar to the exterior
wall of the building. However, other types of screws may be substituted
depending on the construction of the exterior wall. NO TE: alternate screws used must not have heads larger than 3/8” (.9 5 cm). The three screws must be placed at every other hole 120° apart to
secure the vent collar assembly to the outside wall.
3. Insert the vent cap in the vent collar assembly.
FIGURE 102.
4.The vent cap has six holes around its outer edge. The three larger ones are to fit over the three screws securing the vent collar assembly to the exterior wall. The three smaller ones will now be used to attach the vent cap assembly.
NOTE: screws are supplied. However , substitution may be necessary , depending on the exterior wall material.
FIGURE 101.
FIGURE 103.
24
INSTALLING THE NEW WATER HEATER
WATER PIPING
HOTTER WA TER CAN SCALD: Water heaters are intended to produce hot water. Water heated to a temperature which will satisfy space heating, clothes washing, dish washing, cleaning and other sanitizing needs can scald and permanently injure you upon contact. Some people are more likely to be permanently injured by hot water than others. These include the elderly , children, the infirm, or physically/mentally handicapped. If anyone using hot water in your home fits into one of these groups or if there is a local code or state law requiring a certain temperature water at the hot water tap, then you must take special precautions. In addition to using the lowest possible temperature setting that satisfies your hot water needs, a means such as a *mixing valve, shall be used at the hot water taps used by these people or at the water heater, see Figure. V alves for reducing point of use temperature by mixing cold and hot water are also available. Consult a Qualified Installer or Service Agency. Follow manufacturer’s instructions for installation of the valves. Before changing the factory setting on the thermostat, read the “T emperature Regulation” section in this manual.
As water is heated, it expands (thermal expansion) and closed systems do not allow for the expansion of heated water.
The water within the water heater tank expands as it is heated and increases the pressure of the water system. If the relieving point of the water heater’s temperature-pressure relief valve is reached, the valve will relieve the excess pressure. The temperature-pressure relief
valve is not intended for the constant relief of thermal expansion. This is an unacceptable condition and must be corrected.
It is recommended that any devices installed which could create a closed system have a by-pass and/or the system have an expansion tank to relieve the pressure built by thermal expansion in the water system. Expansion tanks are available for ordering through a local plumbing contractor. Contact the local water supplier and/or a service agency for assistance in controlling these situations.
NOTE: To protect against untimely corrosion of hot and cold water fittings, it is strongly recommended that di-electric unions or couplings be installed on this water heater when connected to copper pipe.
This water heater shall not be connected to any heating systems or component(s) used with a non-potable water heating appliance.
All piping components connected to this unit for space heating applications shall be suitable for use with potable water.
T oxic chemicals, such as those used for boiler treatment shall not be introduced into this system.
When the system requires water for space heating at temperatures higher than required for domestic water purposes, a tempering valve must be installed. Please refer to Figure 2 for suggested piping arrangement.
Water supply systems may, because of such events as high line pressure, frequent cut-offs, the effects of water hammer among others, have installed devices such as pressure reducing valves, check valves, back flow preventers, etc. to control these types of problems. When these devices are not equipped with an internal by-pass, and no other measures are taken, the devices cause the water system to be closed.
FIGURE 104.
25
Figure 104 shows the typical attachment of the water piping to the water heater. The water heater is equipped with 3/4 inch NPT water connections.
NOTE: If using copper tubing, solder tubing to an adapter before attaching the adapter to the cold water inlet connection. Do not solder the cold water supply line directly to the cold water inlet. It will harm the dip tube and damage the tank.
T & P Valve and Pipe Insulation
Remove insulation for T & P valve and pipe connections from carton.
FIGURE 105.
The valve must be marked with a maximum set pressure not to exceed the marked hydrostatic working pressure of the water heater (150 psi = 1,035 kPa) and a discharge capacity not less than the water heater input rate as shown on the model rating plate.
For safe operation of the water heater, the relief valve must not be removed from its designated opening nor plugged.
The temperature-pressure relief valve must be installed directly into the fitting of the water heater designed for the relief valve. Position the valve downward and provide tubing so that any discharge will exit only within 6 inches (153 mm) above, or at any distance below the structural floor. Be cert ain that no contact is made with any live electrical part. The discharge opening must not be blocked or reduced in size under any circumstances. Excessive length, over 30 feet (9.14 m), or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve, see Figure 106.
No valve or other obstruction is to be placed between the relief valve and the tank. Do not connect tubing directly to discharge drain unless a 6 inch air gap is provided. T o prevent bodily injury, hazard to life , or property damage, the relief valve must be allowed to discharge water in quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage.
Fit pipe insulation over the incoming cold water line and the hot water line. Make sure that the insulation is against the top cover of the heater. Fit T & P valve insulation over valve. Make sure that the insulation does not interfere with the lever of the T & P valve.
Secure all insulation using tape.
TEMPERA TURE-PRESSURE RELIEF VALVE
The Discharge Pipe:
•Shall not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions.
•Shall not be plugged or blocked.
•Shall be of material listed for hot water distribution.
• Shall be installed so as to allow complete drainage of both the temperature-pressure relief valve, and the discharge pipe.
•Shall terminate at an adequate drain.
•Shall not have any valve between the relief valve and tank.
This heater is provided with a properly certified combination temperature - pressure relief valve by the manufacturer.
The valve is certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment of materials as meeting the requirements for Relief V alves and Automatic Gas Shut-off Devices for Hot Water Supply Systems, ANSI Z21.22 • CSA 4.4, and the code requirements of ASME.
If replaced, the valve must meet the requirements of local codes, but not less than a combination temperature and pressure relief valve certified as indicated in the above paragraph.
The temperature-pressure relief valve must be manually operated at least once a year. Caution should be t aken to ensure that (1) no one is in front of or around the outlet of the temperature-pressure relief valve discharge line, and (2) the water manually discharged will not cause any bodily injury or property damage because the water may be extremely hot.
26
If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater, follow the draining instructions, and replace the temperature-pressure relief valve with a new one.
GAS PIPING
Make sure the gas supplied is the same type listed on the model rating plate. The inlet gas pressure must not exceed 14 inch water column (2.6 kPa) for natural and propane gas (L.P.). The minimum inlet gas pressure shown on the rating plate is that which will permit firing at rated input.
If the gas control valve is subjected to pressures exceeding 1/2 pound per square inch (3.5 kPa), the damage to the gas control valve could result in a fire or explosion from leaking gas.
FIGURE 106.
FILLING THE WATER HEA TER
Never use this water heater unless it is completely full of water. To prevent damage to the tank, the tank must be filled with water. W ater must flow from the hot water faucet before turning “ON” gas to the water heater.
To fill the water heater with water:
1. Close the water heater drain valve by turning the handle to the right (clockwise). The drain valve is on the lower front of the water heater.
If the main gas line Shut-off serving all gas appliances is used, also turn “off” the gas at each appliance. Leave all gas appliances shut “off” until the water heater installation is complete.
A gas line of suf ficient size must be run to the water heater. Consult the current edition of National Fuel Gas Code ANSI Z223.1/NFP A 54 and your gas supplier concerning pipe size.
There must be:
• A readily accessible manual shut off valve in the gas supply line serving the water heater , and
• A drip leg (sediment trap) ahead of the gas control valve to help prevent dirt and foreign materials from entering the gas control valve.
• A flexible gas connector or a ground joint union between the shut off valve and control valve to permit servicing of the unit.
Be sure to check all the gas piping for leaks before lighting the water heater. Use a soapy water solution, not a match or open flame. Rinse off soapy solution and wipe dry.
2. Open the cold water supply valve to the water heater.
NOTE: The cold water supply valve must be left open when the water heater is in use.
3. T o insure complete filling of the tank, allow air to exit by opening the nearest hot water faucet. Allow water to run until a constant flow is obtained. This will let air out of the water heater and the piping.
4. Check all water piping and connections for leaks. Repair as needed.
27
When installed at elevations above 2,000 feet (610 meters), input rating should be reduced at the rate of 4 percent for each 1,000 feet (305 meters) above sea level which requires replacement of the burner orifice in accordance with National Fuel Gas Code ANSI Z223.1/ NFPA 54. Contact your local gas supplier for further information.
Failure to replace the standard orifice with a high altitude orifice when installed could result in improper and inefficient operation of the appliance, producing carbon monoxide gas in excess of safe limits, which could result in serious injury or death. Contact your gas supplier for any specific changes which may be required in your area.
Use pipe joint compound or teflon tape marked as being resistant to the action of petroleum [Propane (L.P.)] gases.
The appliance and its gas connection must be leak tested before placing the appliance in operation.
GAS PIPING WITH ALL BLACK IRON PIPE TO GAS CONTROL
FIGURE 108.
SEDIMENT TRAPS
The appliance and its individual Shut-off valve shall be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 pound per square inch (3.5 kPa). It shall be isolated from the gas supply piping system by closing its individual manual Shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 pound per square inch (3.5 kPa).
Conn ecting the gas piping to the gas control valve of the water heater can be accomplished by either of the two methods shown in Figures 107 and 108.
GAS PIPING WITH FLEXIBLE CONNECTOR
FIGURE 107.
A sediment trap shall be installed as close to the inlet of the water heater as practical at the time of water heater installation. The sediment trap shall be either a tee fitting with a capped nipple in the bottom outlet or other device recognized as an effective sediment trap. If a tee fitting is used, it shall be installed in conformance with one of the methods of installation shown in Figures 1 07 a nd 10 8 .
Contaminants in the gas lines may cause improper operation of the gas control valve that may result in fire or explosion. Before attaching the gas line be sure that all gas pipe is clean on the inside. T o trap any dirt or foreign material in the gas supply line, a drip leg (sometimes called a sediment trap) must be incorporated in the piping. The drip leg must be readily accessible. Install in accordance with the “Gas Piping” section. Refer to the current edition of the National Fuel Gas Code, ANSI Z223.1/NFP A 54.
28
INSTALLING THE NEW WATER HEATER (cont’d.)
INSTALLATION CHECKLIST
BEFORE LIGHTING THE PILOT:
1. Check the gas line for leaks.
a. Use a soapy water solution. DO NOT test for gas leaks using
a match or open flame. b. Brush the soapy water solution on all gas pipes, joints and fittings. c. Check for bubbling soap. This means you have a leak. Turn
“OFF” gas and make the necessary repairs. d. Recheck for leaks. e. Rinse off soapy solution and wipe dry .
2. Is this new temperature-pressure relief valve properly installed and piped to an adequate drain? See “T emperature-Pressure Relief V alve” section.
3. Are the cold and hot water lines connected to the water heater correctly? See “Water Piping” instructions in the “Installing the New Water Heater” section.
4. Is the water heater completely filled with water? See “Filing the Water Heater” instructions in the “Installing the New Water Heater” section.
5. Will a water leak damage anything? See the “Locating the New Water Heater” section.
6. Is there proper clearance between the water heater and anything that might catch fire? See the “Locating the New Water Heater” section.
7. Do you have adequate ventilation so that the water heater will operate properly? See “Combustion Air and V entilation” in the “Locating the New Water Heater” section.
8. Is the vent piping properly secured? See “Venting” instructions in the “Installing the New Water Heater section.
9. Is there proper clearance between the vent pipe and anything that might catch fire? See “Venting” instructions in the “Installing the New Water Heater” section.
10. Is the vent pipe properly sloped and does the vent terminate outdoors? See “Venting” instructions in the “Installing the New W ater Heater” section.
1 1. Do you need to call your gas company to check the gas pipe and its
hookup?
29
30
TEMPERATURE REGULATION
NOTE: A water temperature range of 120°F-140°F (49°C-60°C) is recommended by most dishwasher manufacturers.
The thermostat of this water heater has been factory set at its lowest position (PILOT LIGHTING). It is adjustable and must be reset to the desired temperature setting to reduce the risk of scald injury. The mark
) indicative of approximately 120°F (49°C) is preferred starting
( point. Some States have a requirement for a lower setting.
HOT WA TER CAN SCALD: W ater heaters are intended to produce hot water. Water heated to a temperature that will satisfy space heating, clothes washing, dish washing, and other sanitizing needs can scald and permanently injure you upon contact. Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, the infirm, or physically/ment ally handicapped. If anyone using hot water in your home fits into one of these groups or if there is a local code or state law requiring a specific hot water temperature at the tap, then you must take special precautions. Never allow small children to use a hot water tap, or to draw their own bath water. Never leave a child or handicapped person unattended in a bathtub or shower.
It is recommended that lower water temperatures be used to avoid the risk of scalding. It is further recommended, in all cases, that the water temperature be set for the lowest temperature that satisfies your hot water needs. This will also provide the most energy efficient operation of the water heater.
Figure 110 shows the approximate water temperatures produced at various thermostat settings. Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the thermostat setting by up to 30°F (17°C). If you experience this type of use you should consider using lower temperature settings to reduce scald hazards.
Turn the water temperature dial clockwise ( temperature, or counterclockwise ( temperature.
Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the appliance.
FIGURE 109.
) to decrease the
) to increase the
V alves for reducing the point-of-use temperature by mixing cold and hot water are available. See Figure 2. Also available are inexpensive devices that attach to faucets to limit hot water temperatures. Contact a licensed plumber or the local plumbing authority .
FOR YOUR INFORMATION
ST ART UP CONDITIONS
CONDENSA TE
Whenever the water heater is filled with cold water, some condensate will form while the burner is on. A water heater may appear to be leaking when in fact the water is condensation. This usually happens when:
a. A new water heater is filled with cold water for the first time. b. Burning gas produces water vapor in water heaters, particularly
high efficiency models where flue temperatures are lower.
c. Large amounts of hot water are used in a short time and the
refill water in the tank is very cold.
FIGURE 110.
Moisture from the products of combustion condense on the cooler tank surfaces and form drops of water which may fall onto the burner or other hot surfaces to produce a “sizzling” or “frying” noise.
Excessive condensation can cause pilot outage due to water running down the flue tube onto the main burner and putting out the pilot. Because of the suddenness and amount of water, condensation water may be diagnosed as a “tank leak”. After the water in the tank warms up (about 1-2 hours), the condition should disappear.
Do not assume the water heater is leaking until there has been enough time for the water in the tank to warm up.
An undersized water heater will cause more condensation. The water heater must be sized properly to meet the family’s demands for hot water including dishwashers, washing machines and shower heads.
31
Excessive condensation may be noticed during the winter and early spring months when incoming water temperatures are at their lowest.
Good venting is essential for a gas fired water heater to operate properly as well as to carry away products of combustion and water vapor.
will cause a reaction between this rod and the water. The most common complaint associated with the anode rod is one of a “rotten egg smell” in the hot water. This odor is derived from hydrogen sulfide gas dissolved in the water. The smell is the result of four factors which must all be present for the odor to develop:
SMOKE / ODOR
It is not uncommon to experience a small amount of smoke and odor during the initial start-up. This is due to burning off of oil from metal parts, and will disappear in a short while.
THERMAL EXP ANSION
Water supply systems may, because of such events as high line pressure, frequent cut-offs, the effects of water hammer among others, have installed devices such as pressure reducing valves, check valves, back flow preventers, etc. to control these types of problems. When these devices are not equipped with an internal by-pass, and no other measures are taken, the devices cause the water system to be closed. As water is heated, it expands (thermal expansion) and closed systems do not allow for the expansion of heated water.
a. A concentration of sulfate in the supply water. b. Little or no dissolved oxygen in the water. c. A sulfate reducing bacteria which has accumulated within the water
heater (this harmless bacteria is nontoxic to humans).
d. An excess of active hydrogen in the tank. This is caused by the
corrosion protective action of the anode.
Smelly water may be eliminated or reduced in some water heater models by replacing the anode(s) with one of less active material, and then chlorinating the water heater tank and all hot water lines. Contact the local water heater supplier or service agency for further information concerning an Anode Replacement Kit and this chlorination treatment.
If the smelly water persists after the anode replacement and chlorination treatment, we can only suggest that chlorination or aeration of the water supply be considered to eliminate the water problem.
Do not remove the anode leaving the tank unprotected. By doing so, all warranty on the water heater tank is voided.
“AIR” IN HOT WA TER F AUCETS
The water within the water heater tank expands as it is heated and increases the pressure of the water system. If the relieving point of the water heater’s temperature-pressure relief valve is reached, the valve will relieve the excess pressure. The temperature-pressure relief
valve is not intended for the constant relief of thermal expansion. This is an unacceptable condition and must be corrected.
It is recommended that any devices installed which could create a closed system have a by-pass and/or the system have an expansion tank or device to relieve the pressure built by thermal expansion in the water system. Expansion tanks are available for ordering through a local plumbing contractor. Contact the local water heater supplier or service agency for assistance in controlling these situations.
STRANGE SOUNDS
Possible noises due to expansion and contraction of some metal parts during periods of heat-up and cool-down do not necessarily represent harmful or dangerous conditions.
Condensation causes sizzling and popping within the burner area during heating and cooling periods and should be considered normal. See “Condensation” in this section.
OPERA TIONAL CONDITIONS
SMELL Y WA TER
In each water heater there is installed at least one anode rod (see parts sections) for corrosion protection of the tank. Certain water conditions
HYDROGEN GAS: Hydrogen gas can be produced in a hot water system that has not been used for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable and explosive. T o prevent the possibility of injury under these conditions, we recommend the hot water faucet, located farthest away, be opened for several minutes before any electrical appliances which are connected to the hot water system are used (such as a dishwasher or washing machine). If hydrogen gas is present, there will probably be an unusual sound similar to air escaping through the pipe as the hot water faucet is opened. There must be no smoking or open flame near the faucet at the time it is open.
HIGH WA TER TEMPERA TURE SHUT OFF SYSTEM
This water heater is equipped with an automatic gas Shut-off system. This system works when high water temperatures are present. Turn “OFF” the entire gas supply to the water heater . The high temperature Shut-off is built into the gas control valve. It is non-resettable. If the high temperature Shut-off activates, the gas control valve must be replaced. Contact your gas supplier or service agency .
32
PERIODIC MAINTENANCE
VENTING SYSTEM INSPECTION
At least once a year a visual inspection should be made of the venting system. Y ou should look for:
1. Obstructions which could cause improper venting. The combustion and ventilation air flow must not be obstructed.
2. Damage or deterioration which could cause improper venting or leakage of combustion products.
3. Rusted flakes around top of water heater.
Be sure the vent piping is properly connected to prevent escape of dangerous flue gasses which could cause deadly asphyxiation.
Y ou should check for sooting. Soot is not normal and will impair proper combustion.
Soot build-up indicates a problem that requires correction before further use. Turn “OFF” gas to water heater and leave off until repairs are made, because failure to correct the cause of the sooting can result in a fire causing death, serious injury, or property damage.
FIGURE 11 1.
BURNER CLEANING
In the event your burner needs cleaning, follow these instructions: If inspection of the burner shows that cleaning is required, turn the gas
control knob clockwise (
NOTE: The knob cannot be turned from “PILOT” to “OFF” unless knob is depressed slightly. DO NOT FORCE.
Loose deposits on or around the burner can be removed by carefully using the hose of a vacuum cleaner inserted through the access doors of the water heater. If the burner needs to be removed for additional cleaning, call the local gas utility to remove and clean the burner and correct the problem that required the burner to be cleaned.
) to the “OFF” position, depressing slightly.
Obstructions and deteriorated vent systems may present serious health risk or asphyxiation.
Chemical vapor corrosion of the flue and vent system may occur if air for combustion contains certain chemical vapors. Spray can propellants, cleaning solvents, refrigerator and air conditioner refrigerants, swimming pool chemicals, calcium and sodium chloride, waxes, bleach and process chemicals are typical compounds which are potentially corrosive.
If after inspection of the vent system you found sooting or deterioration, something is wrong. Call the local gas utility to correct the problem and clean or replace the flue and venting before resuming operation of the water heater.
BURNER INSPECTION
Flood damage to a water heater may not be readily visible or immediately detectable. However , over a period of time a flooded water heater will create dangerous conditions which can cause DEATH, SERIOUS BODIL Y INJURY , OR PROPERTY DAMAGE. Contact a qualified installer or service agency to replace a flooded water heater. Do not attempt to repair the unit! It must be replaced!
At least once a year a visual inspection should be made of the main burner and pilot burner, see Figure 1 1 1.
L.P . GAS CONTROL VAL VE & BURNER ASSEMBL Y
Propane (L.P .) gas control valve and burner assembly replacement in­formation.
For Propane (L.P.) Gas Models Only: Your water heater is equipped with a Propane (L.P.) gas control valve and a main burner assembly with left hand threads for the following fittings and their connections.
The connection between the manifold and the gas control valve (A to
B) are left hand threads.
The connection between the main burner orifice and the manifold (C to
D) are left hand threads.
For ordering these replacement parts, please refer to the “Repair Parts” section of this manual.
FIGURE 112.
33
HOUSEKEEPING
Vacuum around base of water heater for dust, dirt, and lint on a regular basis.
The temperature-pressure relief valve must be manually operated at least once a year .
FIGURE 113.
When checking the temperature-pressure relief va lve operation, make sure that (1 ) no one is in front of or around the outlet of the tem perature­pressure relief valve discharge line, and (2) that the water discharge will not cause any property damage, as the water may be extremely hot, see Figure 1 13.
INST ALLED IN SUITABLE AREA: To insure sufficient ventilation and combustion air supply , proper clearances from the water heater must be maintained. See “Locating the New Water Heater” section. Combustible materials such as clothing, cleaning materials, or flammable liquids, etc. must not be placed against or adjacent to the water heater which can cause a fire.
ANODE ROD INSPECTION
The anode rod is used to protect the tank from corrosion. Most hot water tanks are equipped with an anode rod. The submerged rod sacrifices itself to protect the tank. Instead of corroding the tank, water ions attack and eat away the anode rod. This does not affect the water’s taste or color. The rod must be maintained to keep the tank in operating condition.
Anode deterioration depends on water conductivity, not necessarily water condition. A corroded or pitted anode rod indicates high water conductivity and should be checked and/or replaced more often than an anode rod that appears to be intact. Replacement of a depleted anode rod can extend the life of your water heater. Inspection should be conducted by a qualified technician, and at a minimum should be checked annually after the warranty period.
TEMPERA TURE-PRESSURE RELIEF VAL VE OPERATION
If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater, follow the draining instructions, and replace the temperature-pressure relief valve with a new one.
If the temperature-pressure relief valve on the appliance weeps or discharges periodically , this may be due to thermal expansion. Y ou may have a check valve installed in the water line or a water meter with a check valve. Consult your local water supplier or service agency for further information. Do not plug the temperature-pressure relief valve.
DRAINING
The water heater should be drained if being shut down during freezing temperatures. Also periodic draining and cleaning of sediment from the tank may be necessary .
1. Turn the gas control knob to the “OFF” position.
2. CLOSE the cold water inlet valve to the water heater.
3. OPEN a nearby hot water faucet and leave open to allow for draining.
4. Connect a hose to the drain valve and terminate to an adequate drain.
5. OPEN the water heater drain valve to allow for tank draining.
NOTE: If the water heater is going to be shut down and drained for an extended period, the drain valve should be left open with hose connected allowing water to terminate to an adequate drain.
6. CLOSE the drain valve.
7. Follow instructions in the “Filling The Water Heater” section.
8. Follow the lighting instructions on the label, see page 29 under “Lighting Instructions” to restart the water heater .
34
DRAIN VAL VE WASHER REPLACEMENT
(See Figure 114)
1. Turn “OFF” gas supply to water heater .
2. Follow “Draining” instructions.
8. Follow the lighting instructions in the “Lighting” section to restart the water heater.
3. Turning counterclockwise ( screw handle.
4. Remove the washer and put the new one in place.
5. Screw the handle and cap assembly back into the drain valve and retighten using a wrench. DO NOT OVER TIGHTEN.
6. Follow instructions in the “Filling The Water Heater” section.
7. Check for leaks.
), remove the hex cap below the
LEAKAGE CHECKPOINTS
FIGURE 114.
Read this manual first. Then before checking the water heater make sure the gas supply has been turned “OFF”, and never turn the gas “ON” before the tank is completely full of water.
Never use this water heater unless it is completely filled with water. To prevent damage to the tank, the tank must be filled with water. W ater must flow from the hot water faucet before turning “ON” gas to the water heater.
A. Water at the draft hood is water vapor which has condensed out of
the combustion products. This is caused by a problem in the vent. Contact the gas utility .
B. *Condensation may be seen on pipes in humid weather or pipe
connections may be leaking.
C . *The anode rod fitting may be leaking.
D . Small amounts of water from temperature-pressure relief valve may
be due to thermal expansion or high water pressure in your area.
E. *The temperature-press ure r elief valv e m ay be leaking at th e tank fitting .
F . Water from a drain valve may be due to the valve being slightly opened.
G . *The drain valve may be leaking at the tank fitting.
H . Combustion products contain water vapor which can condense on
the cooler surfaces of the tank. Droplets form and drip onto the burner or run on the floor. This is common at the time of start-up after installation and when incoming water is cold.
I. Water in the water heater bottom or on the floor may be from
condensation, loose connections, or the relief valve. DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken.
Leakage from other appliances, water lines, or ground seepage should also be checked.
* To check where threaded portion enters tank, insert cotton swab
between jacket opening and fitting. If cotton is wet, follow “Draining” instructions in the “Periodic Maintenance” section and then remove fitting. Put pipe dope or teflon tape on the threads and replace. Then follow “Filling the Water Heater” instructions in the “Installing the New Water Heater” section.
35
REPAIR PARTS LIST
36
REPAIR PARTS LIST (cont’d.)
P ARTS GAL. CAP. 40 5 0 40 50 75
KEY # DESCRIPTION BTU’ s in 1000’s NAT/L.P. 36/36 38/38 40/40 48/44 55 NA T .
1. Access Door Clips (Pkg. 2) 9000694 9000694 9000694 9000694 9000694
2. Right Access Door w/Gasket 9000695 9000695 9000695 9000695 9000695
3. Left Access Door w/Gasket 9000696 9000696 9000696 9000696 9000696
4. Burner Orifice (Nat.) 9005165 9005170 9001700 9005171 9001701 (Drill Size) #36 #35 #33 1/8 #30
4. Burner Orifice (Nat.) Hi-Altitude 9005928 9001886 9005165 9001700 9005172 (Drill Size) #39 #37 #36 #33 #31
4. Burner Orifice (L.P.) LHT 9004005 9004005 9002134 9002130 — (Drill Size) #51 #51 #50 #49
4. Burner Orifice (L.P.) Hi-Altitude/LHT 9002129 9002129 9004005 9002134 — (Drill Size) #5 2 #5 2 # 51 #50
5. Thermocouple 9000876 9000876 9000876 9000876 9002002
6. Gas Control Valve (Nat.) 9000249 9000249 9000249 9000249 9000249
6. Gas Control Valve Propane (L.P.) 9002123 9002123 9002123 9002123 9002123
7. Gas Manifold (Nat.) 9002413 9002413 9002413 9002413 9003046
7. Gas Manifold (L.P .) 9002415 9002415 9002415 9002415
8. Pilot Tubing w/Fittings 9000278 9000278 9000278 9000278 9000278
9. Burner (Nat.) 900241 1 9002411 9002411 9002411 9003040
9. Burner Propane (L.P .) 9002411 9002411 9002411 9000349
10. Inner Door 9000281 9000281 9000281 9000281 9000281
11. Pilot (Nat.) w/electrode 9003084 9003084 9003084 9003084 9003084
11. Pilot Propane (L.P.) w/electrode 9003085 9003085 9003085 9003085
12. Drain V alve 9000058 9000058 9000058 9000058 9001588
13. Jacket Clips (Pkg. 8) 9001305 9001305 9001305 9001305 9001305
14. Secondary Anode w/Nipple* 9000705 9000705 9000705 9000705 9000705
15. T emperature-Pressure Relief V alve 9000728 9000728 9000728 9000728 9000728
16. Anode Rod 9000707 9000279 9000707 9000279 9000734
17. Nipple 9000399 9000399 9000399 9000399 9002298
18. Flue Baffle (Nat.) 9000709 9002836 9002837 9001288 9002297
18. Flue Baffle (L.P .) 9000709 9000806 9001287 9001288
19. Flue Adaptor 9001289 9001290 9001290
20. Adaptor Gasket 9001291 9001292 9001292
21. Adaptor Plate w/Gasket 9001293 9001294 9001294 St andard Kit No. 9000687
22. O-Ring Gasket 9000710 9000710 9000710 9000710 9000710
23. 3” I.D. x 9.5” Flue Extension Pipe with 900071 1 9000711 9000711 9000711 900071 1 Gaskets
24. Rope Gasket 9000712 9000712 9000712 9000712 9000712
25. 3” I.D. x 5 1/2” V ent Extension Pipe 9000713 9000713 9000713 9000713 9000713 Kit A VK-1 No. 9001246
26. 3” I.D. x 7 7/8” Flue Extension Pipe with 9001280 9001280 9001280 9001280 9001280 Gaskets
27. 6” I.D. x 8 1/8” V ent Pipe 9001277 9001277 9001277 9001277 9001277
28. 6” O.D. x 8 1/8” V ent Extension Pipe 9001274 9001274 9001274 9001274 9001274
29. 3” O.D. x 8 3/8” Flue Pipe 9001283 9001283 9001283 9001283 9001283
30. Rope Gasket 9000712 9000712 9000712 9000712 9000712
31. O-Ring Gasket 9000710 9000710 9000710 9000710 9000710
37
REPAIR PARTS LIST
38
REPAIR PARTS LIST (cont’d.)
P ARTS GAL. CAP . 40 50 40 50 75
KEY # DESCRIPTION BTU’s in 1000’ s NAT/L.P. 36/36 38/38 40/40 48/44 55 NA T .
Kit A VK-2 No. 9001247
32. 3” I.D. x 13 7/8” Flue Extension Pipe with 9001281 9001281 9001281 9001281 9001281
Gaskets
33. 6” O.D. x 13 5/8” V ent Extension Pipe 9001275 9001275 9001275 9001275 9001275
34. 3” O.D. x 13 3/8” Flue Pipe 9001284 9001284 9001284 9001284 9001284
35. 6” I.D. x 13 5/8” V ent Pipe 9001278 9001278 9001278 9001278 9001278
36. Rope Gasket 9000712 9000712 9000712 9000712 9000712
37. O-Ring Gasket 9000710 9000710 9000710 9000710 9000710
Kit A VK-3 No. 9001248
38. 3” I.D. x 24 3/8” Flue Extension Pipe with 9001282 9001282 9001282 9001282 9001282
Gaskets
39. 6” O.D. x 24 3/8” V ent Extension Pipe 9001276 9001276 9001276 9001276 9001276
40. 3” O.D. x 24 3/8” Flue Pipe 9001285 9001285 9001285 9001285 9001285
41. 6” I.D. x 24 3/8” V ent Pipe 9001279 9001279 9001279 9001279 9001279
42. Rope Gasket 9000712 9000712 9000712 9000712 9000712
43. O-Ring Gasket 9000710 9000710 9000710 9000710 9000710
44. 3” Flue Elbow 9000718 9000718 9000718 9000718 9000718
45. Rope Gasket 9000712 9000712 9000712 9000712 9000712
46. 6” V ent Elbow 9000719 9000719 9000719 9000719 9000719
47. Inside Wall Collar 9003168 9003168 9003168 9003168 9003168
48. 6” Vent Wall Assembly 9003166 9003166 9003166 9003166 9003166
49. Vent Cap Assembly 9003165 9003165 9003165 9003165 9003165
50. 24” Diameter Drain Pan w/Side Drain 9002769 9002769 9002769 9002769
51. 28” Diameter Drain Pan w/Side Drain 9001608
52. 24” Base St and 9001422 9001422 9001422 9001422
53. Wire Grill Protector 9000915 9000915 9000915 9000915 9000915
54. Dip Tube *9002365 9001595 *9002365 *9002361 *9001598
55. 6” Vent Wall Assembly 9000724 9000724 9000724 9000724 9000724
56. Brown-Porcelain Vent Cap Assembly 9000725 9000725 9000725 9000725 9000725
57. Piezo Ignitor w/Bracket 9003410 9003410 9003410 9003410 9003410
*NOTE: Some models are factory equipped with a special dip tube to retard a build-up of mineral deposits precipitating from the water supply over time. This is not illustrated and is not a replaceable part.
Now that you have purchased this water heater, should a need ever exist for repair parts or service, simply contact the company it was purchased from or direct from the manufacturer listed on the rating plate on the water heater .
Be sure to provide all pertinent facts when you call or visit.
Selling prices will be furnished on request or parts will be shipped at prevailing prices and you will be billed accordingly .
The model number of your water heater will be found on the rating plate located above the gas control valve. WHEN ORDERING REPAIR PARTS, AL WA YS GIVE THE FOLLOWING INFORMA TION:
MODEL NUMBER TYPE GAS SERIAL NUMBER PAR T DESCRIPTION
THIS IS A REP AIR PARTS LIST, NOT A PACKING LIST.
39
TROUBLESHOOTING GUIDELINES
These guidelines should be utilized by a qualified service agent.
Problem Cause Solution
Improperly sealed, hot or cold supply connection, Tighten threaded connections.
WA TER LEAKS
LEAKING T&P VALVE
SMELL Y ODORS
PILOT WILL NOT LIGHT of ignitor wire.
BURNER WILL NOT Thermocouple malfunction. Replace pilot assembly.
STAY LIT Defective Gas Control. Replace Gas Control.
PILOT OUTAGE Thermocouple tip is not in contact with pilot flame. Insert thermocouple correctly.
NOT ENOUGH Low gas pressure. Contact your gas supplier.
HOT WA TER Incoming water is unusually cold. Allow more time for heater to re-heat.
WA TER T OO HOT Thermostat set too high. Refer to TEMPERA TURE REGULATION.
WA TER HEA TER SOUNDS Condensation dripping on burner. Refer to CONDENSA TE above.
SIZZLING - RUMBLING Sediment or calcium in bottom of heater tank. Clean sediment from tank. Refer to DRAINING
SOOTING Improper combustion. No adjustment available. Contact a service agency
VENT GAS ODORS Improperly installed vent piping. Contact a service agency to determine cause.
relief valve, drain valve, or thermostat threads. Leakage from other appliances or water lines. Inspect other appliances near water heater. Condensation of flue products. Refer to CONDENSA TE. Thermal expansion in closed water system. Install thermal expansion tank (DO NOT plug T&P valve). Improperly seated valve. Check relief valve for proper operation
(DO NOT plug T&P valve).
High sulfate or mineral content in water supply. Drain and flush heater thoroughly, then refill.
Bacteria in water supply. Chlorinate or aerate water supply. Gas control knob not positioned correctly. Refer to LIGHTING INSTRUCTIONS. Main gas supply off. Turn on main gas Shut-off valve. Igniter tip more than 1/8" from pilot hood. Adjust ignitor tip. Melted insulation on ignitor wire or shorting Contact a service agency to determine cause.
Wire disconnected from spark ignitor. Reconnect wire connector to spark ignitor. Broken electrode or electrical wire. Replace pilot assembly. Piezo Ignitor generator fails to operate or Replace Piezo Ignitor generator. malfunctions.
Dirty pilot burner. Clean pilot assembly.
Thermocouple malfunction. Replace pilot assembly. Defective Gas Control. Replace Gas Control. Heater not lit or thermostat not on. Refer to LIGHTING INSTRUCTIONS. Thermostat set too low. Refer to TEMPERATURE REGULA TION. Heater undersized. Reduce hot water use.
Leaking hot water pipes or fixtures. Have plumber check and repair leaks. High temperature limit switch activated. Contact a service agency to
determine cause.
instructions in Maintenance section of manual.
to determine cause.
Lack of supply air.
Downdraft Poor combustion.
40
NOTES:
41
NOTES:
42
NOTES:
43
44
Loading...