State PCE 52 2ORTA Installation Manual

MODELS PCE 6-120 GALLONS
COMMERCIAL ELECTRIC WATER HEATERS
Installation Electrical Wiring Diagrams Replacement Parts
Operation Maintenance Leakage Checkpoints Limited Warranty
500 Tennessee Waltz Parkway, Ashland City, TN 37015
www.statewaterheaters.com
TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY.
PLEASE READ THOROUGHLY BEFORE INSTALLING AND USING THIS APPLIANCE.
PLACE THESE INSTRUCTIONS ADJACENT TO HEATER AND NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE.
Printed 0707 195202-003
1
ROUGH-IN DIMENSIONS
* NO SIDE OUTLET AVAILABLE
ROUGH-IN DIMENSIONS
Models No. of Tank Capacity A B C D Shipping Weight.
Dimensions Elements US Gals. Litres inches mm inches mm inches mm inches mm Lbs. Kg.
PCE 6 1OMSA 1 6 23 15 1/2 394 14 1/4 362 11 279 - - 35 15.9
PCE 10 1OMSA 1 10 38 18 1/4 464 18 457 12 1/2 318 - - 54 24.5
PCE 17 OMSA 1 15 57 26 660 18 457 20 1/2 521 - - 58 26.3
PCE 20 1OMSA 1 20 76 22 1/4 565 21 3/4 552 15 3/8 391 - - 73 33.1
PCE 30 2OLSA 2 30 114 30 7/8 784 21 3/4 552 24 1/8 613 8 203 100 45.4 PCE 40 2OLSA 2 40 151 32 1/4 819 24 610 25 9/16 649 8 203 125 56.7 PCE 50 2OLSA 2 50 189 32 1/4 819 26 1/2 673 25 1/8 638 8 203 166 75.3 PCE 30 2ORTA 2 30 114 34 1/2 876 20 1/2 521 - - 8 203 98 44.5 PCE 40 2ORTA 2 40 151 45 1/8 1146 20 1/2 521 - - 8 203 113 51.3 PCE 52 2ORTA 2 50 189 54 7/8 1394 20 1/2 521 - - 8 203 131 59.4 PCE 66 2ORTA 2 66 250 60 3/4 1543 21 3/4 552 - - 8 203 176 79.8 PCE 82 2ORTA 2 80 303 59 3/8 1508 24 610 - - 8 203 211 95.7
PCE 120 2ORTA 2 119 450 62 7/16 1586 29 3/8 746 - - 8 203 326 147.9
RECOVERY CAPACITIES
Element U.S. Gallons/Hr and Litres/Hr at TEMPERATURE RISE INDICATED Wattage INPUT 36F° 40F° 54F° 60F° 72F° 80F° 90F° 100F° 108F° 120F° 126F° (Upper/Lower) KW 20C° 22.2C° 30C° 33.3C° 40C° 44.4C° 50C° 55.5C° 60C° 66.6C° 70C°
NON-SIMULATANEOUS OPERATION
/1500 GPH171511108 8 7 6655
/2000 GPH2320151411109 8876
/2500 GPH 28 25 19 17 14 13 11 10 9 8 8
3000/3000 GPH 34 30 23 20 17 15 14 12 11 10 10
4000/4000 GPH 45 41 30 27 23 20 18 16 15 14 13
4500/4500 GPH 51 46 34 30 25 23 20 18 17 15 14
5000/5000 GPH 56 51 38 34 28 25 23 20 19 17 16
6000/6000 GPH 68 61 45 41 34 30 27 24 23 20 19
SIMULATANEOUS OPERATION
3000/3000 GPH 68 61 45 41 34 30 27 24 23 20 19
4000/4000 GPH 90 81 60 54 45 41 36 32 30 27 26
4500/4500 GPH 101 91 68 61 51 46 41 36 34 30 29
5000/5000 GPH 113 101 75 68 56 51 45 41 38 34 32
6000/6000 GPH 135 122 90 81 68 61 54 49 45 41 39
1.5 LPH 64 58 43 38 32 29 26 23 21 19 18
2.0 LPH 85 77 57 51 43 38 34 31 28 26 24
2.5 LPH 107 96 71 64 53 48 43 38 36 32 30
3.0LPH12811585 77 64 58 51 46433837
4.0 LPH 170 153 114 102 85 77 68 61 57 51 49
4.5 LPH 192 173 128 115 96 86 77 69 64 58 55
5.0 LPH 213 192 142 128 107 96 85 77 71 64 61
6.0 LPH 256 230 170 153 128 115 102 92 85 77 73
6 LPH 256 230 170 153 128 115 102 92 85 77 73
8 LPH 341 307 227 205 170 153 136 123 114 102 97
9 LPH 384 345 256 230 192 173 153 138 128 115 110
10 LPH 426 384 284 256 213 192 170 153 142 128 122
12 LPH 511 460 341 307 256 230 205 184 170 153 146
FOR PCE 6 MODELS
Approx.
Recovery capacities at 100° F rise equal: for non-simultaneous element operation = 4.1 gal. x KW of one element; for simultaneous element operation = 4.1 gal. x 2/3 KW of both elements. For other rises multiply element KW as previously explained by 410 and divide by temperature rise. Full load current for single phase = total watts : voltage.
2
FOREWORD
Thank you for buying this energy efficient water heater from State. We appreciate your confidence in our products. Detailed installation diagrams are in this manual. These diagrams will serve to provide the installer with a reference for the materials and method of piping suggested. IT IS NECESSARY THAT ALL WATER PIPING AND THE ELECTRICAL WIRING BE INSTALLED AND CONNECTED AS SHOWN IN THE DIAGRAMS.
In addition to these instructions, the water heater must be installed in accordance with local codes and the authority having jurisdiction.
GENERAL SAFETY INSTRUCTIONS
BE SURE TO TURN OFF POWER WHEN WORKING ON OR NEAR THE ELECTRICAL SYSTEM OF THE HEATER. NEVER TOUCH ELECTRICAL COMPONENTS WITH WET HANDS OR WHEN STANDING IN WATER. WHEN REPLACING FUSES ALWAYS USE THE CORRECT SIZE FOR THE CIRCUIT.
The principal components of the heater are identified on page
6. The model and rating plate on page 5 interprets certain markings into useful information. Both of these references should be used to identify the heater, its components and optional equipment.
reduce the risk of injury under these conditions, it is recommended that the hot water faucet be opened for several minutes at a nearby kitchen sink before using any electrical appliance connected to the hot water system. If hydrogen is present, there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow. THERE SHOULD BE NO SMOKING OR OPEN
FLAME NEAR THE FAUCET AT THE TIME IT IS OPENED.
CAUTION
AN ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF ELECTRIC SHOCK OR POSSIBLE ELECTROCUTION. THE GROUND SCREW AT THE JUNCTION BOX IS FOR BONDING THE HEATER TO A GROUNDED SERVICE ENTRANCE CONDUCTOR, A GROUNDED SERVICE ENTRANCE RACEWAY, OR AN EARTH GROUNDING ELECTRODE CONDUCTOR.
WARNING
FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN SERIOUS PERSONAL INJURY OR DEATH.
REQUIRED ABILITY
INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIELD INVOLVED. PLUMBING AND ELECTRICAL WORK ARE REQUIRED.
WARNING
FOR CALIFORNIA INSTALLATION THIS WATER HEATER MUST BE BRACED, ANCHORED, OR STRAPPED TO AVOID FALLING OR MOVING DURING AN EARTHQUAKE. SEE INSTRUCTIONS FOR CORRECT INSTALLATION AND PROCEDURES. INSTRUCTIONS MAY BE OBTAINED FROM YOUR LOCAL DEALER, WHOLESALER, PUBLIC UTILITIES OR CALIFORNIA’S OFFICE OF STATE ARCHITECT, 400 P STREET, SACRAMENTO, CALIFORNIA 95814.
INSULATION BLANKETS
Insulation blankets available to the general public for external use on electric water heaters are not approved for use on your State water heater. The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank water heaters. Your State water heater meets or exceeds the National Appliance Energy Act standards with respect to insulation and standby loss requirements, making an insulation blanket unnecessary.
Should you choose to apply an insulation blanket to this heater, you should follow these instructions (See page 5 for identification of components mentioned below). Failure to follow these instructions can result in fire, serious personal injury or death.
• Do not cover the temperature & pressure relief valve.
• Do not cover the instruction manual. Keep it on the side of the water heater or nearby for future reference.
• Do obtain new labels from State Water Heaters for placement on the blanket directly over the existing labels.
WARNING
EXTENDED NON-USE PERIODS
HYDROGEN GAS CAN BE PRODUCED IN A HOT WATER SYSTEM SERVED BY THIS HEATER THAT HAS NOT BEEN USED FOR A LONG PERIOD OF TIME (GENERALLY TWO WEEKS OR MORE).
HYDROGEN GAS IS EXTREMELY FLAMMABLE. To
CAUTION
GENERAL
The installation must conform to these instructions, the local code authority having jurisdiction, and the requirements of the power company. In the absence of code requirements follow the current edition of NFPA-70, The National Electrical Code which may be ordered from: National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269.
LOCATION
The water heater should be located as close as possible to/or centralized to the water piping system. The water heater should be located in an area not subject to freezing temperatures.
The heater should be located in an area where leakage of the tank or connections will not result in damage to the area adjacent to the heater or to lower floors of the structure.
When such locations cannot be avoided, a suitable drain pan should be installed under the heater.
Such pans should be at least two inches deep, have a minimum length and width of at least two inches greater than the diameter of the heater and should be piped to an adequate drain.
Drain pans suitable for these heaters are available from your distributor or State Water Heaters, 500 Tennessee Waltz Parkway, Ashland City, TN 37015.
Water heater life depends upon water quality, water pressure and the environment in which the water heater is installed. Water heaters are sometimes installed in locations where leakage may result in property damage, even with the use of a drain pan piped to a drain. However, unanticipated damage can be reduced or prevented by a leak detector or water shut-off device used in conjunction with a piped drain pan. These devices are available from some plumbing supply wholesalers and retailers, and detect and react to leakage in various ways:
• Sensors mounted in the drain pan that trigger an alarm or turn off the incoming water to the water heater when leakage is detected.
3
• Sensors mounted in the drain pan that turn off the water supply to the entire home when water is detected in the drain pan.
• Water supply shut-off devices that activate based on the water pressure differential between the cold water and how water pipes connected to the water heater.
• Devices that will turn off the gas supply to a gas water heater while at the same time shutting off its water supply.
CLEARANCES
CALCULATING
AMPERAGE/OVERCURRENT PROTECTION
The heaters come from the factory in two configurations:
1. Two wire C-2 circuit for single element heater equipped with a high limit control, single phase power input.
2. Four wire A-8 circuit for dual element heater equipped with two high limit controls, single phase or three phase power input.
A minimum clearance of 4” must be allowed for access to replaceable parts such as thermostats, drain valve and relief valve.
Adequate clearance for servicing this appliance should be considered before installation, such as changing the anodes, etc.
FLOOD WARNING
IF THE HEATER BECOMES IMMERSED IN WATER UP TO OR ABOVE THE LEVEL OF THE BOTTOM OF THE ELEMENT DOORS, THE HEATER SHOULD BE EXAMINED BY A COMPETENT SERVICE PERSON BEFORE IT IS PLACED IN OPERATION.
CHEMICAL VAPOR CORROSION
Water heater corrosion and component failure can be caused by the heating and breakdown of airborne chemical vapors. Spray can propellants, cleaning solvents, refrigerator and air conditioning refrigerants, swimming pool chemicals, calcium and sodium chloride, waxes, and process chemicals are typical compounds which are potentially corrosive. These materials are corrosive at very low concentration levels with little or no odor to reveal their presence. Products of this sort should not be stored near the heater.
ELECTRICAL (GENERAL)
Check the heater model and rating plate information against the characteristics of the branch circuit electrical supply. DO NOT
CONNECT THE HEATER TO AN IMPROPER SOURCE OF ELECTRICITY. Contact the heater supplier for conversion
information if necessary.
The heater with dual elements is factory wired for connection to a three wire, three-phase delta branch circuit, non-simultaneous operation. In addition a ground conductor is required.
Element connection is for non-simultaneous operation. This means only one element at a time operates. The wiring diagram, on page 5, shows the heater may be field converted to simultaneous element operation by moving the red wire on “J” terminal to L1. It is then possible for both elements to operate at once as determined by the thermostats. Regardless of element connection the heater operates in an “unbalanced” fashion.
The heater may be field converted to single-phase operation by moving the wire on L3 of the terminal block to L2. L3 is not used, see page 5.
The heater, now in single-phase non-simultaneous operation, may be field-converted to single phase simultaneous operation by moving the red wire on terminal “J” to L1, see page 5.
This is an example of calculating heater amperage for both types of element operation. From this, the branch circuit conductor and overcurrent protection sizing can be established.
The example is of a three-phase 240 volt unit with two, 6 kw elements. The notations are for units field converted to single-phase. Check the heater model and rating plate for actual specifications and substitute those values in the following.
Non-simultaneous: Simultaneous: (as factory wired) (Field conversion)
Voltage applied to the heater should not vary more than +5% to -10% of the model and rating plate marking for satisfactory operation.
DO NOT ENERGIZE THE BRANCH CIRCUIT FOR ANY REASON BEFORE THE HEATER TANK IS FILLED WITH WATER.
SO WILL CAUSE THE HEATING ELEMENTS TO BURN OUT.
The factory wiring is attached to a terminal block within the external junction box unit. The branch circuit is connected to the terminal block within this junction box. The water heater should be connected to a separate, grounded, branch circuit with overcurrent protection and disconnect switch. The water heater should be grounded in accordance with national and local codes.
DOING
BRANCH CIRCUIT
The branch circuit wire size should be established through reference to the current edition of NFPA-70, the National Electrical Code or other locally approved source in conjunction with the heater amperage rating. For convenience, portions of the wire size tables from the Code are reproduced here. The branch circuit should be sized at 125 percent of the heater rating and further increase wire size as necessary to compensate for voltage drop in long runs.
3000 : 240 = 12.5 amps* 3000 : 240 = 12.5 amps*
12.5 x 1.73 = 21.6 amps
*NOTE: as a single-phase *NOTE: as a single-phase non-simultaneous unit. simultaneous unit the
total is:
12.5 x 2 = 25 amps
The rating of the overcurrent protection should be computed on the basis of 125 percent of the total connected load amperage. Where the standard ratings and settings do not correspond with this computation, the next higher standard rating or setting should be selected.
Portion of Table 310-16 (NFPA-70) follows: Allowable Ampacities of Insulated Copper Conductors. Not more than three conductors in Raceway or Cable or Direct Burial (Based on Ambient Temperature of 30° C, 86° F).
These ampacities relate only to conductors described in Table 310-13 in Code.
For ambient temperatures over 30° C (86° F), see Correction Factors, Note 13 in Code.
4
Size Temperature Rating of Conductor See Table 310-13 in Code
AMG 60° C 75° C
MCM (140° F) (167° F)
TYPES: TYPES:
RUW RH, RHW, RUH,
(14-2), (14-2), THW
T, TW, THWN, XHHW,
UF USE 18 - - - - - ­16 - - - - - ­14 15 15 12 20 20 10 30 30
840 45 655 65 470 85 3 80 100
Size Temperature Rating of Conductor
See Table 310-13 in Code AMG 60° C 75° C MCM (140° F) (167° F)
TYPES: TYPES:
RUW RH, RHW, RUH, (12-2), (12-2), THW T, TW, THWN, XHHW,
UF USE 12 15 15 10 25 25
830 40 640 50 455 65 365 75 275 90 1 85 100
Portion of Table 310-18 follows:
Allowable Ampacities of Insulated Aluminum and Copper -Clad Aluminum Conductors.
Not more than three conductors in Raceway or Cable or Direct Burial (Based on Ambient Temperature of 30° C, 86° F. These ampacities relate only to conductors described in Table 310-13 in Code.
For ambient temperatures over 30° C (86° F), see Correction Factors, Note 13 in Code.
WIRING DIAGRAMS
A-8 CIRCUIT FOR DUAL ELEMENT HEATER
C-2 CIRCUIT
FOR SINGLE
ELEMENT HEATERS
EQUIPPED WITH HIGH
LIMIT CONTROL
FACTORY WIRED
---------- FIELD WIRINGWHITE FOR 120V
AND 277V
5