COMMERCIAL
™
PATRIOT
LIGHT-DUTY
COMMERCIAL ELECTRIC WATER HEATERS
Low Lead Content
LISTED
Designed for use as recovery heaters for
light-duty hot water supply service.
™
Patriot
with tank capacities from 6 through 119
gallons. They can be installed for nonsimultaneous and single element operation
(maximum input up to 6 KW), or for
simultaneous dual-element operation
(maximum input up to 12 KW).
Zinc-Plated Copper Sheath
Heating Elements Standard
• Medium watt density design disperses
• Element options from 1.5 KW to 6
Standard Voltages for
Easy Installation
• 120V, 277V single-phase, and 208V,
• Easily converted to single-phase at ter-
• Single-element heater, single-phase only
Factory-Installed
Terminal Block
• Provides electrical service to heater and
Factory-Wired Controls
• Temperature control (adjustable from
PCE water heaters are available
element temperature over larger
surface contact area to minimize scale
buildup, maximize efficiency and prolong element life
KW (non-simultaneous or simultaneous operation), recoveries from 6 gph
to 49 gph at 100°F rise
240V and 480V unbalanced 3-phase
delta
minal block (except for 208V with
6000 watt elements
(see chart for dual-element options)
connects to block (excludes models 6-20)
110°F to 170°F on single-element;
120°F to 180°F on dual-element models)
• Manual reset high temperature cutoff
per element (dual-element models)
• Factory wired for non-simultaneous
operation; easily converted to simultaneous operation
Glasslined Tank with
Anode Rod
• Provides long-lasting protection against
corrosion
Maximum Hydrostatic Working
Pressure: 150 psi
Meets the standby loss
requirements of the U.S.
Department of Energy and
current edition of
ASHRAE/IESNA 90.1
Other Patriot™ PCE
Series Features
• CSA Certified and ASME rated T&P
relief valve is factory-installed
• Simplified, color-coded circuitry for
ease of service
• Bonderized undercoat on cabinet with
baked enamel finish
• Foam insulation
• Drain valve (not supplied for models 6-20)
• UL-approved field conversion program
• PCE models 6-20 are listed to UL
174 and PCE models 30-120 are listed to
UL 1453
Three-Year Limited Tank
Warranty
• Consult written warranty shipped with
water heater, or contact State for
complete information
For more information on State® contact:
State Water Heaters
500 Tennessee Waltz Parkway, Ashland City, TN 37015
800-365-0024 Toll-free USA
www.statewaterheaters.com
SCESS00106 Revised May 2012
Page 1 of 4 ©2012 State Water Heaters Company
PRODUCT SPECIFICATIONS
WATTAGE, RECOVERY AND ELECTRICAL CHARACTERISTICS
Wattage INPUT F
(Upper/Lower) KW C° 20C° 22.2C° 30C° 33.3C° 40C° 44.4C° 50C° 55.5C° 60C° 66.6C° 70C°
NON-SIMULATANEOUS OPERATION
/1500 GPH171511108 8 7 6655
/2000 GPH232015141110 9 8 8 7 6
/2500 GPH28251917141311 109 8 8
3000/3000 GPH34302320171514 12111010
4000/4000 GPH45413027232018 16151413
4500/4500 GPH51463430252320 18171514
5000/5000 GPH56513834282523 20191716
6000/6000 GPH68614541343027 24232019
SIMULATANEOUS OPERATION
3000/3000 GPH 68 61 45 41 34 30 27 24 23 20 19
4000/4000 GPH 90 81 60 54 45 41 36 32 30 27 26
4500/4500 GPH101916861514641 36343029
5000/5000 GPH 113 101 75 68 56 51 45 41 38 34 32
6000/6000 GPH 135 122 90 81 68 61 54 49 45 41 39
1.5 LPH 64 58 43 38 32 29 26 23 21 19 18
2.0 LPH 85 77 57 51 43 38 34 31 28 26 24
2.5 LPH 107 96 71 64 53 48 43 38 36 32 30
3.0 LPH 128 115 85 77 64 58 51 46 43 38 37
4.0 LPH 170 153 114 102 85 77 68 61 57 51 49
4.5 LPH 192 173 128 115 96 86 77 69 64 58 55
5.0 LPH 213 192 142 128 107 96 85 77 71 64 61
6.0 LPH 256 230 170 153 128 115 102 92 85 77 73
10 LPH 426 384 284 256 213 192 170 153 142 128 122
12 LPH 511 460 341 307 256 230 205 184 170 153 146
° 36F° 40F° 54F° 60F° 72F° 80F° 90F° 100F° 108F° 120F° 126F°
6 LPH 256 230 170 153 128 115 102 92 85 77 73
8 LPH 341 307 227 205 170 153 136 123 114 102 97
9 LPH 384 345 256 230 192 173 153 138 128 115 110
DETACIDNI ESIR ERUTAREPMET ta rH/sertiL dna rH/snollaG .S.UtnemelE
TANK CAPACITY, DIMENSIONS AND WEIGHTS
Models No. of Tank Capacity A B C D Shipping Weight.
Dimensions Elements US Gals. Litres inches mm inches mm inches mm inches mm Lbs. Kg.
PCE 6 1OMSA 1 6 23 15 1/2 394 14 1/4 362 11 279 - - 35 15.9
PCE 10 1OMSA 1 10 38 18 1/4 464 18 457 12 1/2 318 - - 54 24.5
PCE 17 OMSA 1 15 57 26 660 18 457 20 1/2 521 - - 58 26.3
PCE 20 1OMSA 1 20 76 22 1/4 565 21 3/4 552 15 3/8 391 - - 73 33.1
PCE 30 2OLSA 2 30 114 30 7/8 784 21 3/4 552 24 1/8 613 8 203 100 45.4
PCE 40 2OLSA 2 40 151 32 1/4 819 24 610 25 9/16 649 8 203 125 56.7
PCE 50 2OLSA 2 50 189 32 1/4 819 26 1/2 673 25 1/8 638 8 203 166 75.3
PCE 30 2ORTA 2 30 114 34 1/2 876 20 1/2 521 - - 8 203 98 44.5
PCE 40 2ORTA 2 40 151 45 1/8 1146 20 1/2 521 - - 8 203 113 51.3
PCE 52 2ORTA 2 50 189 54 7/8 1394 20 1/2 521 - - 8 203 131 59.4
PCE 66 2ORTA 2 66 250 60 3/4 1543 21 3/4 552 - - 8 203 176 79.8
PCE 82 2ORTA 2 80 303 59 3/8 1508 24 610 - - 8 203 211 95.7
PCE 120 2ORTA 2 119 450 62 7/16 1586 29 3/8 746 - - 8 203 326 147.9
Recovery capacities at 100° F rise equal: for non-simultaneous element operation = 4.1 gal. x KW of one element; for simultaneous element operation
= 4.1 gal. x 2/3 KW of both elements. For other rises multiply element KW as previously explained by 410 and divide by temperature rise. Full load current for single phase
= total watts : voltage.
Approx.
HEATING ELEMENT AVAILABILITY
INPUT
1500
2000
2500
3000
3500
4000
4500
5000
5500
6000
120V
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
WATTS
*Not available in PCE 10 10MSA, PCE 17 10MSA and PCE 30 20RTA.
**A6 non-simultaneous circuit only.
PCE 6 10MSA not available above 2500 W.
PCE 6 10MSA not available in 480V.
208V
YES
YES
YES
YES
NO
YES
YES
YES*
NO
YES**
240V
YES
YES
YES
YES
YES
YES
YES
YES*
ES
Y
YES
277V
YES
YES
YES
YES
NO
YES
YES
YES*
NO
YES
480V
NO
NO
YES
YES
NO
YES
YES
YES*
NO
YES
SCESS00106 Revised May 2012
Page 2 of 4 ©2012 State Water Heaters Company