SPX Cooling Technologies 03-11A User Manual

Page 1
Cofimco Fan – Adjustable Hub
/
/
User Manual 03-11A
Page 2
Fan Components
102
101
V11
X14
W29
101
103
102
VBA
Figure 1—Typical Fan Assembly
X12
200
103
W29
Order No. _______________________________________
Trial Pitch Angle _________________________________
Final Pitch Angle _________________________________
Speed-rpm _____________________________________
Contract hp _____________________________________
2
Page 3
Note
Fan Assembly Instructions
The following instructions apply to installations having straight bores or tapered output shafts without split taper bushings.
It is convenient to preassemble the fan prior to installation on the driving shaft.
1—Select a large open area corresponding to the fan diameter.
2—Position the fan hub in the center of the work area with the center spool 101 oriented as shown in Figure 1.
3—Secure blade retention sleeves 104 to the blade 200 using
3
machine bolt V11 and locking nut X12. Tighten 40 ft·lb
.
ƒ
8" nut X12 to
4—Position the blade clamp blocks 103 around the blade shank so that the blade 200 droops slightly downward when the blade clamp hardware is tight.
TRAILING EDGE
Figure 2
LEADING EDGE
5—Position the blade clamps and blade between the hub plates
5
102 to align bolt holes. Loosely install
8" bolts VBA, flat washers
W29 and self locking nuts X14 to secure blades. Finger tighten all
5
8" nuts.
6—On fans where the blades overlap at the hub be sure to have the leading edge under the trailing edge of the forward blade. Refer to Figure 2.
7—Pull the blades radially outward until the blade retention sleeve bears against the back side of the blade clamp.
3
Page 4
8—Repeat steps 3 through 7 for all blades.
9—Progressively tighten all blade clamp nuts X14 until the blades are barely able to move when twisting the blade.
Figure 3
RETENTION SLEEVE
TIGHTEN BLADE CLAMP BOLTS TO 100 FT·LB LUBRICATED
TIGHTEN RETENTION SLEEVE NUT TO 40 FT·LB
10- Measure the final fan diameter. By using a different hole in the blade retention sleeves the fan diameter can be altered for the ap-
1
propriate fit within the cylinder. blade tips and the fan cylinder is recommended.
2" minimum clearance between all
Fan Installation Instructions
1—Be sure motor is locked out.
2—Clean the hub bore and driving shaft extension for the full length of the key.
3—Insert the key in the keyway. The top of the key must be below the top of the shaft by not more than fit across the width and must never be altered.
4—After cleaning, apply a coat of anti-seize compound to the en­gagement portion of the shaft.
5—Raise the fan assembly above the shaft and slowly lower the hub onto the shaft with the keyways aligned. Make certain the key does not slide down during installation.
6—Install the Hub Retention Cap Screw with Lock Washer. Torque hub retention cap screw to 40 ft·lb
4
1
8" (3 mm) . The key is a tight
(54 N·m).
ƒ
Page 5
Note
Adjusting Fan Blade Pitch
The trial pitch is the calculated setting for design conditions (water rate , heat load, air density, and brake horsepower). The trial pitch is provided by SPX (see page 2).
1–Select a position on the fan circumference and rotate each blade to this common location when setting or checking blade pitch. Sup­port the blade tip to maintain a common rotation plane while setting
3
the fan pitch. The pitch is set by placing a protractor on top of a parallel sided straight edge that extends across blade width as shown in Figure 4.
2–Be sure all blades are positioned correctly on hub, then set the pitch. Blades should be within ± the desired setting is obtained, progressively tighten the hardware according to Table 5. Recheck the pitch angle. If required, loosen the hex nuts and reset the pitch as necessary until the proper pitch angle is obtained.
16" (5 mm) inboard of the blade tip
1
4° of the desired pitch angle. After
Figure 4
Table 5
Bolt
Diameter
3
8"
5
8"
Torque Wrench Setting
ft·lb
100
ƒ
40
N·m
55
136
5
Page 6
Fan Maintenance
Preventative maintenance will prolong useful life and assure contin­ued trouble-free operation. After the first week and subsequently at six month intervals:
• Torque all hardware to specications referenced in this manual.
• Visually inspect the fan for airborne debris damage, contact with
fan cylinder segments, and corrosive attack. Correct any situations determined detrimental to fan operation.
• Remove any accumulated scale or dirt.
• Clear blade drain holes at fan tip.
Service
Proper identification of your fan is necessary to insure you receive correct replacement parts. The Marley cooling tower serial number can be used to determine the fan and any components installed and maintained as original equipment on a Marley cooling tower. Please provide the Marley sales representative the necessary information when ordering replacement fans or components.
Blades can be replaced without rebalancing the entire fan.
If rebalancing is desired, contact the Marley sales representative in your area.
6
Page 7
Motor Load
The corrected horsepower should be close to but not exceed the contract horsepower specified by SPX. Determine corrected horse­power using the following equation.
Actual volts and amperage must be obtained with the fan running and the specified rate of water flowing over the tower after the motor and Geareducer have reached operating temperature (approximately 30 minutes of operation).
Note
HP
C
VOLTS
AMPS
DENSITY
A
A
HP
= Corrected Horsepower
= Actual Volts
= Actual Amperage
= Actual Air Density
A
VOLTSA × AMPSA × DENSITY
=
C
VOLTSN × AMPSN × DENSITYA
VOLTS
AMPS
HP
N
DENSITY
D
× HP
N
= Nameplate Volts
N
= Nameplate Amperage
N
= Nameplate Horsepower
= Design Air Density
D
Measurements taken on motors operating with Variable Fre­quency Drive controls may read up to 15% high from errors in measuring the approximated sine wave. Instruments capable of measuring a squared off wave form accurately should be used for measuring power in this situation.
Do not exceed 30 sec/hour total motor starting time as motor may overheat.
7
Page 8
7401 WEST 129 STREET | OVERLAND PARK, KANSAS 66213 UNITED STATES | 913 664 7400 | spxcooling@spx.com | spxcooling.com
In the interest of technological progress, all products are subject to design and/or material change without notice.
©2008 SPX Cooling Technologies, Inc. | Printed in USA
Manual 03-11A
Loading...