IN-LINE MIXED FLOW DUCT FANS ULTRA-QUIET
TD-SILENT Series
TD-SILENT - MODELS 160 TO 1000
(Models 350,
500, 800 and 1000)
Low profile “Mixed-flow” fans with soundabsorbent insulation. Extremely quiet. Certified of Approval Noise Abatement Society (TD-350, TD-500, TD-800 and TD-1000 models).
Manufactured in plastic material, with a specifically designed internal skin to direct the sound waves at the right angle for them to be captured by the sound-absorbent material (1). Fitted with rubber gaskets on the inlet and outlet to absorb vibrations, a body that can be dismantled. Connection box can be rotated 360º, to facilitate easy connection of the power cable.
Motors
Speed controlable 230V-50Hz motor, of two speed or 3-speed motors (depending on the models). IP44.
Motors are class B, with ball bearings and safety thermal overload protection.
(1)Except the TD-160 SILENT, that is fitted with the special floating motor system patented by S&P.
Additional information
The models offer solutions to ventilation problems, especially in places where people work and low sound level is required.
TD-SILENT-T models
TD-SILENT versions fitted with a run-on- timer adjustable within 1 and 30 minutes and onespeed or 3-speed motors (depending on the model) not suitable for speed control.
TD-SILENT - MODELS 1300 AND 2000
Low profile “Mixed-flow” fans with soundabsorbent insulation. Extremely quiet. Certified of Approval Noise Abatement Society (TD-2000 model). Constructed from sheet steel with epoxy polyester paint, acoustic insulation (MO) glass fibre, within outer shell.
Aerodynamic inlet to improve airflow and reduce sound. Detachable fan unit without demounting duct connections. IP44. External terminal box IP55. Removeable fan body with 3 speed motor, single phase 230V-50/60Hz speed controlable, Class F, external rotor aluminium motor with capacitor and thermal protection.
Additional information
The models offer solutions to ventilation problems, especially in places where people work and low sound level is required.
(Model 2000)
706 |
In-Line duct fans TD-SILENT |
www.solerpalau.com |
|
|
|
IN-LINE MIXED FLOW DUCT FANS ULTRA-QUIET
TD-SILENT Series
MODELS 250 TO 1000
Low profile
The low profile of the TD-SILENT fans makes them the most effective solution for installations where space is very limited, especially in ceiling voids.
1
2
Low noise level
Sound waves produced inside the TD, are directed through the perforated inner skin 1 and absorbed by the layer of sound absorbent material 2
Easymaintenance
Removable motor-body assembly to easy cleaning and repairing without touching the ducts. Support plastic brackets simplify the operation.
MODELS WITH RUN-ON-TIMER
Models TD-SILENT-T (from models 250 to 1000) are fitted with an adjustable timer between 1 and 30 minutes and are supplied with a one-speed or 3-speed motors (depending on the model)
not suitable for speed control.
Easy to mount
Connection box rotated 360º
Connection box can be rotated 360º, to facilitate easy connection of the power cable.
Support bracket
Support bracket for installing on a wall or ceiling, incorporating twinmaterial support brackets for the motor section that absorbs vibration.
Rubber seals
Bi-material inlet and outlet incorporating a rubber seal to facilitate installation and absorb vibrations.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Loosen and open clamps on both sides. |
Remove the fan body. |
|
Remove the terminal |
Connect electrical |
Remount the fan |
|||||||
|
|
|
|
|
|
box lid. |
supply. |
body by tightening |
||||
|
|
|
|
|
|
|
|
|
the clamps. |
|
|
|
|
|
|
|
|
|
|
||||||
www.solerpalau.com |
|
|
|
|
In-Line duct fans TD-SILENT |
707 |
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
IN-LINE MIXED FLOW DUCT FANS ULTRA-QUIET
TD-SILENT Series
MODEL 160
SILENT-ELASTIC-BLOCKS
Model TD-160/100N SILENT offer very low noise level, with a motor mounted on silentelasticblocks which absorb the vibrations.
MODELS 1300 AND 2000
Low profile - compact
Low profile fans TD-1300/250 SILENT and TD-2000/315 SILENT are ideal for installations where space is very limited, especially in ceiling voids.
1
4
2
3
Easy maintenance
Detachable fan unit for maintenance, or cleaning, without demounting duct connections.
Low noise level
1Acoustic insulation (A2-s1, d0) glass fibre.
2Outer shell.
3Aerodynamic inlet to improve air flow and reduce sound.
4Attenuating perforated skin.
Support bracket |
IP55 REMOTE terminal box |
Suitable for wall or ceiling |
Easy installation and |
mounting. Fixing brackets |
connection. |
to the motor-body included. |
|
708 |
In-Line duct fans TD-SILENT |
www.solerpalau.com |
|
|
|
IN-LINE MIXED FLOW DUCT FANS ULTRA-QUIET
TD-SILENT Series
TECHNICAL CHARACTERISTICS
TD-SILENT |
Speed |
Maximum |
Maximum |
Maximum |
Sound |
Min-Max |
Weight |
Duct |
3-speed |
Speed con- |
Wiring |
|
|
(r.p.m.) |
absorbed |
absorbed |
airflow |
pressure |
air |
(kg) |
diameter |
switch |
troller |
diagram** |
|
|
|
power |
current |
(m3/h) |
level* |
temperature |
|
(mm) |
|
|
(nº) |
|
|
|
(W) |
(A) |
|
(dB(A)) |
(°C) |
|
|
|
|
|
|
TD-160/100 N SILENT |
2400 |
29 |
0,17 |
180 |
24 |
-20/+40 |
1,4 |
100 |
COM-2 |
RMB-1,5 |
9, 10 |
|
2200 |
18 |
0,11 |
150 |
22 |
REGUL-2 |
REB-1 |
||||||
|
|
|
|
|
||||||||
TD-250/100 SILENT |
2210 |
27 |
0,12 |
250 |
25 |
-20/+40 |
5,4 |
100 |
COM-2 |
RMB-1,5 |
9, 10 |
|
1680 |
21 |
0,1 |
200 |
20 |
REGUL-2 |
REB-1 |
||||||
|
|
|
|
|
||||||||
TD-350/125 SILENT |
2100 |
27 |
0,12 |
330 |
23 |
-20/+40 |
5 |
125 |
COM-2 |
RMB-1,5 |
9, 10 |
|
1650 |
21 |
0,1 |
260 |
18 |
REGUL-2 |
REB-1 |
||||||
|
|
|
|
|
||||||||
TD-500/150-160 |
2480 |
59 |
0,26 |
550 |
27 |
|
|
|
COM-3 |
RMB-1,5 |
|
|
2060 |
50 |
0,22 |
450 |
22 |
-20/+60 |
6 |
150/160 |
9, 10 |
||||
SILENT 3V |
INTER 4P |
REB-1 |
||||||||||
1610 |
45 |
0,2 |
350 |
17 |
|
|
|
|
||||
|
|
|
|
|
|
|
||||||
TD-800/200 |
2170 |
102 |
0,5 |
910 |
28 |
|
|
|
COM-3 |
RMB-1,5 |
|
|
1870 |
92 |
0,47 |
780 |
24 |
-20/+60 |
8,7 |
200 |
9, 10 |
||||
SILENT 3V |
INTER 4P |
REB-1 |
||||||||||
1660 |
90 |
0,46 |
690 |
22 |
|
|
|
|
||||
|
|
|
|
|
|
|
||||||
TD-1000/200 |
2450 |
130 |
0,55 |
1.040 |
29 |
|
|
|
COM-3 |
RMB-1,5 |
|
|
2210 |
127 |
0,55 |
910 |
27 |
-20/+60 |
8,7 |
200 |
9, 10 |
||||
SILENT 3V |
INTER 4P |
REB-1 |
||||||||||
1920 |
122 |
0,53 |
790 |
24 |
|
|
|
|
||||
|
|
|
|
|
|
|
||||||
TD-1300/250 |
2530 |
204 |
0,85 |
1.320 |
36 |
|
|
|
COM-3 |
RMB-1,5 |
|
|
2230 |
163 |
0,68 |
1.160 |
33 |
-20/+60 |
20 |
250 |
12, 13 |
||||
SILENT 3V |
INTER 4P |
REB-1 |
||||||||||
2030 |
144 |
0,6 |
1.040 |
31 |
|
|
|
|
||||
|
|
|
|
|
|
|
||||||
TD-2000/315 |
2670 |
293 |
1,25 |
1.770 |
39 |
|
|
|
COM-3 |
RMB-1,5 |
|
|
2490 |
232 |
0,97 |
1.610 |
38 |
-40/+60 |
25 |
315 |
12, 13 |
||||
SILENT 3V |
INTER 4P |
REB-2,5 |
||||||||||
2240 |
190 |
0,78 |
1.480 |
36 |
|
|
|
|
||||
|
|
|
|
|
|
|
*Sound pressure level radiated at 3 m at free air conditions with rigid ducts at the inlet and at the outlet.
**See section of Wiring Diagrams.
TD-SILENT |
Speed |
Maximum |
Maximum |
Maximum |
Sound |
Min-Max |
Weight |
Duct |
|
(r.p.m.) |
absorbed |
absorbed |
airflow |
pressure |
air |
(kg) |
diameter |
|
|
power |
current |
(m3/h) |
level* |
temperature |
|
(mm) |
|
|
(W) |
(A) |
|
(dB(A)) |
(°C) |
|
|
TD-160/100 NT SILENT |
2400 |
29 |
0,17 |
180 |
24 |
-20/+40 |
1,4 |
100 |
TD-250/100 SILENT T |
2140 |
28 |
0,12 |
250 |
25 |
-20/+40 |
5,4 |
100 |
TD-350/125 SILENT T |
2050 |
26 |
0,11 |
330 |
23 |
-20/+40 |
5 |
125 |
|
2590 |
53 |
0,21 |
560 |
27 |
|
|
|
TD-500/150-160 SILENT T 3V** |
2150 |
44 |
0,19 |
470 |
22 |
-20/+60 |
6 |
150 |
|
1820 |
41 |
0,18 |
390 |
17 |
|
|
|
|
2170 |
102 |
0,5 |
910 |
28 |
|
|
|
TD-800/200 SILENT T 3V** |
1870 |
92 |
0,47 |
780 |
24 |
-20/+60 |
8,7 |
200 |
|
1660 |
90 |
0,46 |
690 |
22 |
|
|
|
|
2450 |
130 |
0,55 |
1.040 |
29 |
|
|
|
TD-1000/200 SILENT T 3V** |
2210 |
127 |
0,55 |
910 |
27 |
-20/+60 |
8,7 |
200 |
|
1920 |
122 |
0,53 |
790 |
24 |
|
|
|
*Radiated sound pressure level measured at 3 m, in free field conditions, with rigid ducts at the inlet and outlet.
**Temporisation only on high speed.
www.solerpalau.com |
In-Line duct fans TD-SILENT |
709 |