SMA SB 3300TL User Manual

Page 1
PV Inverter
SUNNY BOY 3300TL HC
Installation Guide
SB3300TLHC-IEN094121 | IME-SB33TLHC | Version 2.1
EN
Page 2
Page 3
SMA Solar Technology AG Table of Contents
Table of Contents
1.1 Validity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Additional Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4 Symbols Used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1 Appropriate Usage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2 Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.1 Identifying the Sunny Boy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.2 External dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4 Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.1 Selecting the Mounting Location. . . . . . . . . . . . . . . . . . . . . . . . 10
4.2 Mounting the Sunny Boy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5 Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.1 Overview Connection Area . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.1.1 View from Below. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.1.2 View from Inside . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.2 Low Voltage Grid (AC). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.2.1 Connection of the AC Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.3 PV Generator Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.3.1 PV string (DC) connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
5.4 Setting the Display Language . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.5 The Communications Interface . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.5.1 Connection RS485, Radio Piggy-Back . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.5.2 Jumper Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Installation Guide SB3300TLHC-IEN094121 3
Page 4
Table of Contents SMA Solar Technology AG
6 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6.1 Display Message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
6.2 Blink Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
7 Sunny Boy Opening and Closing . . . . . . . . . . . . . . . . . . . 29
7.1 Opening the Sunny Boy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
7.2 Closing the Sunny Boy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
8 Maintenance and Cleaning. . . . . . . . . . . . . . . . . . . . . . . . 31
8.1 Cleaning the Cooling Fins. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
8.2 Check the Electronic Solar Switch for wear . . . . . . . . . . . . . . . 31
9 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
9.1 The red LED is continuously lit. . . . . . . . . . . . . . . . . . . . . . . . . . 32
9.1.1 Checking the PV Generator for Ground Fault. . . . . . . . . . . . . . . . . . . . . . . . 32
9.1.2 Checking the Function of the Varistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
10 Decommissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
10.1 Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
10.2 Packaging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
10.3 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
10.4 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
11 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
12 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
13 Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4 SB3300TLHC-IEN094121 Installation Guide
Page 5
SMA Solar Technology AG Notes on this Manual

1 Notes on this Manual

This manual describes the mounting, installation, commissioning and servicing of the SMA inverters of the type Sunny Boy 3300TL HC (SB 3300TL HC). Store this manual where it will be accessible at all times.

1.1 Validity

This manual is valid for the Sunny Boy 3300TL HC.

1.2 Target group

This manual is intended for the electrician.

1.3 Additional Information

You will find further information on special topics such as designing a line circuit breaker or the description of the operating parameters in the download area at www.SMA.de/en.
Refer to the user manual for detailed information on troubleshooting and operating the Sunny Boy.
Installation Guide SB3300TLHC-IEN094121 5
Page 6
Notes on this Manual SMA Solar Technology AG

1.4 Symbols Used

The following types of safety instructions and general information appear in this document as described below:
DANGER!
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING!
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION!
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE!
NOTICE indicates a situation that can result in property damage if not avoided.
Information
Information provides tips that are valuable for the optimal installation and operation of your product.
6 SB3300TLHC-IEN094121 Installation Guide
Page 7
SMA Solar Technology AG Safety

2 Safety

2.1 Appropriate Usage

The Sunny Boy is a PV inverter that converts the DC current of solar cells to AC current and feeds it into the public grid.
Principle of a PV system with this Sunny Boy
The Sunny Boy may only be operated with PV generators (modules and cabling) of protection class II. Do not connect any sources of energy other than PV modules to the Sunny Boy.
PV modules with large capacities relative to ground, such as thin-film modules with cells on a metallic substrate, are only to be implemented if their coupling capacity is below 50 nF/kWp.
During grid feeding, a leakage current whose magnitude depends on the manner in which the modules are installed and on the weather (rain, snow) flows from the cells to ground. This operational leakage current is not to exceed a value of 50 mA.
When designing the PV system, ensure that the values comply with the permitted operating range of all components at all times. The free design program "Sunny Design" (www.SMA.de/en/SunnyDesign) will assist you. The manufacturer of the PV modules must have approved the modules for use with this Sunny Boy unit. You must also ensure that all measures recommended by the module manufacturer for long-term maintenance of the module properties are taken (see also Technical Information "Module Technology", in the download area of www.SMA.de/en).
Do not use the Sunny Boy for purposes other than those described here. Alternative uses, modifications to the Sunny Boy or the installation of components not expressly recommended or sold by the manufacturer void the warranty claims and operation permission.
Installation Guide SB3300TLHC-IEN094121 7
Page 8
Safety SMA Solar Technology AG

2.2 Safety Instructions

DANGER!
Danger to life due to high voltages.
• All work on the Sunny Boy must only be carried out by a qualified personnel.
CAUTION!
Danger of burn injuries due to hot housing parts!
• Do not touch the housing of the Sunny Boy during operation.
NOTICE!
Foreign objects or water entering the Sunny Boy can damage the device!
Once the Electronic Solar Switch has been pulled out, the Sunny Boy only provides protection degree IP21. The Sunny Boy is then no longer protected against water and contamination with dirt!
In order that the protection level IP65 is also provided during a temporary decommissioning, proceed as follows:
• Unplug all DC plug connectors and seal them with the protecting caps provided.
• Attach the Electronic Solar Switch again.
Grounding the PV generator
Comply with the local requirem ents for groundi ng the module s an d the PV generator. SMA reccomends to electrically bond the module frames, the racks and all metal surfaces and ground these in order to have optimal protection of the system and personnel.
8 SB3300TLHC-IEN094121 Installation Guide
Page 9
SMA Solar Technology AG Overview

3 Overview

3.1 Identifying the Sunny Boy

You can identify the Sunny Boy using the type label. The type label can be found on the right side of the housing and contains information about the serial number, the device type as well as technical data.

3.2 External dimensions

225 mm
470 mm
490 mm
Installation Guide SB3300TLHC-IEN094121 9
Page 10
Mounting SMA Solar Technology AG

4 Mounting

4.1 Selecting the Mounting Location

DANGER!
Danger to life due to fire or explosion!
Despite careful construction, a fire can occur with electrical devices.
• Do not mount the Sunny Boy on flammable construction materials.
• Do not mount the Sunny Boy near highly flammable materials.
• Do not install the Sunny Boy in potentially explosive areas!
CAUTION!
Danger of burn injuries due to hot housing parts!
The temperature of individual parts of the housing, in particular the temperature of the heatsink and the components inside the Sunny Boy can reach more than 60 °C. Touching could result in burns!
Weight
CAUTION!
Risk of injury due to the heavy weight of the Sunny Boy!
The Sunny Boy weighs more than 28 kg.
• Consider the weight of the Sunny Boy when choosing the location and method of installation.
Ambient Conditions
• The mounting location and mounting method must be suitable for the weight and dimensions.
• Mount on a solid surface.
• The installation location must be accessible at all times (do not mount in inaccessible places).
• The Sunny Boy must be easy to remove from the mounting location at any time.
• The Sunny Boy must not be in operation in ambient temperatures outside the range of -25 °C and +60 °C. For optimal operation, the ambient temperature should not exceed +40 °C.
• Do not expose the Sunny Boy to direct sunlight, so as to avoid power reduction due to excessive heating.
10 SB3300TLHC-IEN094121 Installation Guide
Page 11
SMA Solar Technology AG Mounting
• In a living area, do not mount the unit on plasterboard walls (or similar) in order to avoid audible vibrations.
The Sunny Boy can make noises when in use which can be regarded as a nuisance when installed in a living area.
• Vertical installation or tilted backwards by max. 45°.
• Install at eye level to allow operating modes to be read at all times.
• Never install the device with a forward tilt.
• Do not install horizontally.
Safety Clearances
Observe the following safety clearances to walls, other devices or other objects in order to guarantee sufficient heat dissipation and enough space for removing the Electronic Solar Switch:
Direction Minimum Clearance
Sides 20 cm
Top 20 cm
Bottom 50 cm
Front 5 cm
Installation Guide SB3300TLHC-IEN094121 11
Page 12
Mounting SMA Solar Technology AG

4.2 Mounting the Sunny Boy

To make the job easier, we recommend you use the supplied wall bracket to mount the Sunny Boy. For vertical installation on solid concrete or block walls, for example, you can fit the bracket using 8 mm x 50 mm hexagon bolts to DIN 571 standard, stainless steel type, and with wall plugs type SX10.
When selecting the mounting materials, be sure to take into account the weight of the Sunny Boy (28 kg).
If you do not want to use the supplied wall bracket as a template, observe the dimensions shown in the illustration below. The procedure for mounting the inverter using the wall bracket is described on the following pages.
95 mm
395 mm
105 mm
130 mm
260 mm
300 mm
12 SB3300TLHC-IEN094121 Installation Guide
Page 13
SMA Solar Technology AG Mounting
1. Mount the wall bracket (1). In order to mark the positions for the drill holes, you can use the wall bracket as a drilling template.
2. Now han g the Su nny Boy onto the wall brac ket (2) using its upper mounting plate so that it cannot be moved sideways.
3. Fix the Sunny Boy onto its bracket by screwing the supplied M6x10 bolt into the central threaded hole at the bottom of the bracket (3).
4. Make sure that the Sunny Boy is positioned securely on the bracket.
Installation Guide SB3300TLHC-IEN094121 13
Page 14
Electrical Connection SMA Solar Technology AG

5 Electrical Connection

5.1 Overview Connection Area

NOTICE!
Electrostatic discharges can damage the Sunny Boy!
Internal components of the Sunny Boy can be irreparably damaged by electrostatic discharge.
• Ground yourself before you touch a component.
The complete wiring for a Sunny Boy is shown schematically in the following figure:
Opening for optional
communication
String 1
14 SB3300TLHC-IEN094121 Installation Guide
String 2
AC connection, max. 10 mm²
Page 15
SMA Solar Technology AG Electrical Connection

5.1.1 View from Below

Electronic Solar Switch (ESS)
socket
Plug and socket
connector for connection
of the solar modules
AC plug for the mains
supply connection
Cable openings for optional
communication via RS485 or
radio (PG16)
Installation Guide SB3300TLHC-IEN094121 15
Page 16
Electrical Connection SMA Solar Technology AG

5.1.2 View from Inside

The following diagram gives a schematic overview of the various components and connection points inside the Sunny Boy with the cover removed:
Object Description A Socket for communication (RS485, radio), section 5.5”The Communications Interface”
(page23)
B Sunny Display C PE (protective earth) connecting cable for cover D Operating status LEDs E Connection terminals (AC), chapter 5.2.1”Connection of the AC Output” (page18) F Tab for grounding the cable shield with RS485 communication G Socket for the PLC power module (required for mains grid communication) H Electronic Solar Switch (ESS) socket I PV input plugs (DC), section 5.3.1”PV string (DC) connection” (page20) J Varistors, section 9.1”The red LED is continuously lit” (page32) K Jumper slot for communication L Communication connector
16 SB3300TLHC-IEN094121 Installation Guide
Page 17
SMA Solar Technology AG Electrical Connection

5.2 Low Voltage Grid (AC)

Load Disconnection Unit
The maximal permissible rating is located in the technical data (page 36).
DANGER!
Danger to life due to fire!
When a generator (Sunny Boy) and a consumer are connected to the same line circuit breaker, the protective function of the line circuit breaker is no longer guaranteed. The current from the Sunny Boy and the grid can add up to overcurrent which is not detected by the line circuit breaker.
• Never connect loads between the Sunny Boy and the line circuit breaker without protection.
• Always install separate fuses for loads.
The relevant technical regulations and the special instructions of the local grid operator must be followed.
The connection terminals of the Sunny Boy are suitable for wire cross-sections of up to 10 mm². The external diameter of the cable must be between 9mm and 17mm.
The connection is made with three wires (L, N, PE).
Examples for the rating of a line circuit breaker can be found in the Technical Information "line circuit breaker" in the download area of www.SMA.de/en.
The Sunny Boy is equipped with an integrated universal current sensitive leakage-current monitoring unit. The Sunny Boy can automatically differ between real fault currents and "normal" capacitive leakage currents.
The Sunny Boy does not generate any extraordinary leakage curre nts in normal operation. In certain operating states (e.g. during self-test of the protective equipment), leakage currents may occur which can trigger a "normal" 30 mA RCD or FI circuit breaker.
A 30 mA RCD or FI circuit breaker must not be installed.
In the event that an RCD or FI circuit breaker is necessary or mandatory, you must use a circuit breaker with a tripping characteristic of 100 mA or more.
Installation Guide SB3300TLHC-IEN094121 17
Page 18
Electrical Connection SMA Solar Technology AG

5.2.1 Connection of the AC Output

Connection requirements of the grid operator
Always observe the connection requirements of your grid operator!
To connect the AC cable, proceed as follows:
1. Check the grid voltage. Complying with DIN VDE 0126-1-1, the Sunny Boy will not be fully operational if the grid voltage is constantly higher than 253 V. In this case, contact the local grid operator for assistance. The inverter can temporarily feed power into the grid with a maximum output voltage of 260 V. However, the 10-minute average must not exceed 253 V.
2. Isolate the grid connection (switch the line circuit br eak er t o it s "Off" po sit ion ), m ake sure it c ann ot b e switched back on, and test to make sure no voltage is present.
3. Remove the screws that secure the enclosure of the Su nny Boy and c are fully re mov e th e co ver. Rem ove the PE connection from the cover.
Off!
4. Connect the mains cable as shown in the figure. Use the supplied cable opening.
"L" and "N" must not be swapped.
5. Connect the protective earth (PE) of the power line to the upper screw terminal with the earth sign.
6. Reconnect the PE connection to the housing cover with these.
7. Fix the housing cover of the Sunny Boy and tighten the four screws evenly.
18 SB3300TLHC-IEN094121 Installation Guide
Page 19
SMA Solar Technology AG Electrical Connection
Correct operation of your Sunny Boy requires, among other things, the connection of the PE conductor to the equipotential bonding of the building. Please check the prescribed PE connection from the Sunny Boy case to protective earth when commissioning the device!
DANGER!
Danger to life due to high voltages.
• Do not switch the line circuit breaker on yet! The Sunny Boy may only be connected to the AC grid once the PV strings are connected and the device is securely closed.

5.3 PV Generator Requirements

The Sunny Boy is designed to be connected to up to two strings having a homogenous structure (modules of the same type, identical orientation, tilt and number).
Sunny Design will assist you in the system design and checking of the string size for a given type of inverter. Further information on Sunny Design is available at www.SMA.de/en.
The unit has four DC plug connectors (two for each string) for connecting the PV generators. The connecting cables from the PV generators must also be fitted with this type of plug connector. The SMA order codes for the various connectors are as follows [see also section 12”Accessories” (page39)]:
• Multi-Contact 3 mm: "SWR-MC"
• Multi-Contact 4 mm: "MC-SET"
•Tyco: "TYCO-SET"
Limit values for DC input
Max. voltage 750 V (DC)
Max. input current 11 A (DC)
Installation Guide SB3300TLHC-IEN094121 19
Page 20
Electrical Connection SMA Solar Technology AG

5.3.1 PV string (DC) connection

DANGER!
Danger to life due to high voltages on the Sunny Boy!
• Before connecting the PV generator, ensure that the line circuit breaker is switched off.
Use of Adaptors
Adaptors (branch connectors) are not to be visible or freely accessible in the immediate surrounding of the Sunny Boy, in order that the DC circuit is not disrupted as a result.
• Always disconnect the current flow first via the Electronic Solar Switch.
Procedure for DC connection
1. Remove the Electronic Solar Switch on the underside of the Sunny Boy.
NOTICE!
Excessive voltages can destroy the measuring device!
• Only use measuring devices with a DC input voltage range up to at least 800 V.
2. Check that the PV generator connectors have the right polarity and do not exceed the maximum string voltage of 750 V (DC). See also section
5.1”Overview Connection Area” (page14).
20 SB3300TLHC-IEN094121 Installation Guide
Page 21
SMA Solar Technology AG Electrical Connection
NOTICE!
Exceeding the maximum input voltage can destroy the Sunny Boy!
If the voltage of the PV modules exceeds the maximum input voltage of the Sunny Boy, it can be destroyed by the overvoltage. All warranty claims become void.
• Do not connect strings to the Sunny Boy with open circuit voltage greater than the maximum input voltage of the Sunny Boy.
• Check the system design.
3. Check the strings for ground faults, as described in section 9.1.1”Checking the PV Generator for Ground Fault” (page32).
DANGER!
Risk of lethal electric shock!
• Do not connect any strings in which you have detected a ground fault!
• Firstly, clear the ground fault in the PV generator.
4. Connect up the faultless PV generator strings to the inverter.
5. Close the unused DC input sockets with the caps included in the delivery.
6. Reinsert the Electronic Solar Switch in the socket on the underside of the Sunny Boy.
Installation Guide SB3300TLHC-IEN094121 21
Page 22
Electrical Connection SMA Solar Technology AG
NOTICE!
Manipulating the connector in the handle can damage the Electronic Solar Switch!
The connector within the handle must remain movable in order to ensure proper contact. Tightening the screw voids all warranty claims and creates a fire risk.
•Do not tighten the connector screw in the Electronic Solar Switch handle.
NOTICE!
The Electronic Solar Switch can be damaged if it is inserted incorrectly!
The Electronic Solar Switch can be damaged by high voltage if it has not been attached properly.
• Press the handle firmly into place on the socket of the Electronic Solar Switch until it audibly locks into place.
• Check that the handle is securely in place.

5.4 Setting the Display Language

The display language of the display is set with the switches underneath the display assemblies inside the Sunny Boy.
You can change the language setting of the display as follows:
1. Open the Sunny Boy as described in section 7.1”Opening the Sunny Boy” (page29).
2. Set the switch combination of the required language. See Table.
Language Switch S2 Switch S1
German B B English B A French A B Spanish A A
3. Close the Sunny Boy as described in section 7.2”Closing the Sunny Boy” (page30).
22 SB3300TLHC-IEN094121 Installation Guide
Page 23
SMA Solar Technology AG Electrical Connection

5.5 The Communications Interface

The communication interface is used to communicate with SMA communication devices (e.g. Sunny Boy Control, Sunny WebBox) or a PC with appropriate software (e.g. Sunny Data Control). Depending on the selected communication interface, up to 2500 inverters can be interconnected. Detailed information on this topic can be found in the communication device manual, the software or on the Internet at www.SMA.de/en.
For the installation of the communication interfaces there are the following possibilities:
• RS485, Funk Piggy-Back (see section 5.5.1”Connection RS485, Radio Piggy-Back” (page24))
The detailed wiring diagram for each communication interface can be found in the communication device manual. This wiring diagram includes the following information:
• Details on the required cable type
• Which of the inverter's connections are used
• Whether jumpers need to be mounted, and if so, which jumpers
• Whether the PE needs to be connected to the cable shield
The next pages will describe the following:
• The housing feed-throughs for the communication interface
• The permitted cable route in the Sunny Boy
• The location of the PE connector
• The location of the screw terminals for connecting the communication wires
• The location of the jumper slots
• The location of the interface port
• The location of the interface port for the PLC power module and the Powerline modem
Installation Guide SB3300TLHC-IEN094121 23
Page 24
Electrical Connection SMA Solar Technology AG

5.5.1 Connection RS485, Radio Piggy-Back

This section describes the installation of the Piggy-Backs for the different Sunny Boy communication systems: RS485 interface and Radio Piggy-Back. You can take the relevant SMA order numbers fro m the section 12”Accessories” (page39).
NOTICE!
Electrostatic discharges can damage the Sunny Boy and the communication interface!
Electrostatic discharges are an acute danger to the Sunny Boy and to the communication interface.
• Ground yourself by touching PE before removing the communication interface from the packaging, and before touching any components within the Sunny Boy.
Read the communication device manual before beginning installation work. Further wiring details can be found there.
1. Open the Sunny Boy as described in section 7.1”Opening the Sunny Boy” (page29).
2. Guide the PG screw fitting over the communication cable.
3. Th rea d th e ca ble thro ugh one of t he cable ope nings (A ) on the Sun ny B oy. Use one or tw o ca ble openings, depending on the ty pe of cable u sed. Use th e right -hand housing feed-through for the Radio Piggy-Back.
4. Screw the PG screw fitting onto the Sunny Boy.
5. Sheathe the cable inside the Sunny Boy using the silicone tube provided. The silicone tube is imperative for safety reasons. The interface may not be commissioned without this silicone tube (with the exception of the Radio Piggy-Back).
6. Lay the cable in area (B) as shown in the figure to the right.
7. Ground the cable shield at the PE connector (C) if the connection plan of the communication device indicates this as necessary.
8. Connect the communication wires to the screw terminal strip (D) as described in the connection plan of the communication device. Note down the connector color coding for the respective pin numbers. Connecting the receiver incorrectly can damage the devices.
– Pin 2 color: – Pin 3 color: – Pin 5 color: – Pin 7 color:
9. Connect the jumpers (E) if the connection plan of the communication device indicates this as necessary. The table in section 5.5.2”Jumper Functions” (page25) provides an overview of the jumper functions.
24 SB3300TLHC-IEN094121 Installation Guide
Page 25
SMA Solar Technology AG Electrical Connection
10. Plug the communication interface to the left of the board (F).
11. Close the Sunny Boy as described in section 7.2”Closing the Sunny Boy” (page30).
F
E
D
CAB
A Enclosure openings in the base of the Sunny Boy.
B Cable route (gray surface)
C PE connector
D Screw terminals for connection of the communication wires
E Jumper slots
F Interface port

5.5.2 Jumper Functions

Jumper A Jumper B Jumper C
RS485 Termination Bias 1 Bias 2
Radio Piggy-Back - - -
A detailed description of the jumper functiosn can be found in the communication device documentation.
Installation Guide SB3300TLHC-IEN094121 25
Page 26
Commissioning SMA Solar Technology AG

6 Commissioning

Check the following requirements before commissioning:
• The cover is securely screwed on.
• The AC (power) cable is connected correctly.
• The DC cables (PV-Strings) are fully connected.
• The unused DC plug connectors on the underside of the housing are sealed with protecting caps.
• The Electronic Solar Switch (ESS) is correctly attached.
• The line circuit breaker is correctly rated.
Commissioning Procedure
1. Switch the line circuit breaker to the "On" position. On
2. Now look at the LED display and consult the table
on the following page to check whether the Sunny Boy is in a fault-free and expedient operating mode. If this is the case, commissioning was successfully completed.
Operation (green)
Ground fault (red) Disturbance (yellow)
26 SB3300TLHC-IEN094121 Installation Guide
Page 27
SMA Solar Technology AG Commissioning

6.1 Display Message

Feeding Operation
After fault-free grid connection of the Sunny Boy, it takes app roximately one minute until the following display messages are shown alternately. The display messages shown before only have the purpose of indicating the initialization of the Sunny Boy and the process of controlling whether the power supply requirements are fulfilled.
• Initially, the energy generated on the respective day and the current operating mode are displayed.
• After 5 seconds or by tapping on the enclosure lid, the current feed-in output and the output voltage are displayed.
• After a further 5 seconds, or when you tap again, the current input voltage and the input power are displayed.
• After a further 5 seconds, or when you tap again, the total energy produced and the time the Sunny Boy has been connected to the grid are displayed.
• Then the cycle begins again.
Disturbance
• In case of a failure, the message "Disturbance" will be indicated in the status bar.
• The exact failure message follows.
• For example, if the grid fault message shown here is displayed immediately after connection, it may be due to the fact that the AC wire is not correctly connected or the circuit breaker is not switched on yet.
• If the disturbance was caused by a measured value that does not correspond to the standard, the value measured at the time of the disturbance is displayed. If another measurement is possible, the present value is displayed in the second line.
Pac 903W Vac 230V
Vpv 520V Ppv 1325W
Installation Guide SB3300TLHC-IEN094121 27
Page 28
Commissioning SMA Solar Technology AG
PV Overvoltage
NOTICE!
Excessive DC input voltage can destroy the Sunny Boy!
If the bottom yellow LED flashes four times at intervals of on e secon d, the grid voltag e and t he PV gen era tor mus t be imm edi ate ly d isc onn ecte d from the Sunny Boy! There is a danger of damage to the inverter resulting from excessive DC input voltage!
Check the string voltages again to make sure they are wit hin th e limits stated in section 5.1”Overview Connection Area” (page14). If the input voltage is too high, contact the planner / installer of the PV generator for assistance.
If des pit e ch ecking th e st rin g vo lta ges the L ED s ign al o ccu rs a gain when the PV generator is connected to the Sunny Boy, disconnect the PV generator from the Sunny Boy again and contact SMA Solar Technology (see section 13”Contact” (page40)).

6.2 Blink Codes

Green Red Yellow Status
Glows continuously Is not glowing Is not glowing OK (feeding operation)
Glows continuously Is not glowing Disturbance
Glows continuously OK (initialization)
Flashes quickly
(3 x per second)
Flashes slowly
(1 x per second)
Briefly goes out
(approx. 1x per
second)
Is not glowing Is not glowing Is not glowing OK (night shutdown)
Is not glowing Is not glowing OK (Stop)
Glows continuously Is not glowing Disturbance
Is not glowing Is not glowing OK (waiting, grid monitoring)
Glows continuously Is not glowing Disturbance
Is not glowing Is not glowing OK (derating)
Glows continuously Is not glowing Disturbance
glowing/blinking Disturbance
Glows continuously Is not glowing Disturbance
glowing/blinking Disturbance
You will find a detailed description of the failure messages and their causes as well as the meaning of the blink codes in the the Sunny Boy user manual included in delivery.
28 SB3300TLHC-IEN094121 Installation Guide
Page 29
SMA Solar Technology AG Sunny Boy Opening and Closing

7 Sunny Boy Opening and Closing

NOTICE!
Electrostatic discharges can damage the Sunny Boy!
Internal components of the Sunny Boy can be irreparably damaged by electrostatic discharge.
• Ground yourself before you touch a component.

7.1 Opening the Sunny Boy

DANGER!
Danger to life due to high voltages.
• Before opening the Sunny Boy, switch the line circuit breaker off and make sure that it cannot be switched back on.
1. Remove the Electronic Solar Switch.
2. Disconnect the PV generator from the Sunny Boy.
DANGER!
Danger to life due to unsafe disconnection from the PV generator!
A secure separation from the PV generator is only guaranteed after pulling off the Electronic Solar Switch and all DC connectors.
• Remove all DC plug connectors to completely disconnect the PV generator from the Sunny Boy.
3. Check whether all LEDs and the display have gone out.
DANGER!
Danger to life due to high voltages.
• Wait 15 minutes for the capacitors to discharge.
4. Remove the four screws from the housing cover and pull the cover forward smoothly. Remove the PE connection from the cover by loosening the locking device of the PE connection on the cover.
5. Verify the absence of voltage with respect to ground at the AC clamp with an appropriate meter. If there is a voltage present, check the installation!
Installation Guide SB3300TLHC-IEN094121 29
Page 30
Sunny Boy Opening and Closing SMA Solar Technology AG

7.2 Closing the Sunny Boy

1. Reconnect the protective earth (PE) to the housing cover.
2. Now secure the lid to the Sunny Boy by tightening the four screws evenly. The screws must be tightened with approximately 4 Nm torque in order to guarantee the sealing of the housing.
3. Connect the PV generator. Ensure the assignment of the strings is correct.
4. Check the Electronic Solar Switch for wear, as described in section 8.2”Check the Electronic Solar Switch for wear” (page31).
5. Reinsert the Electronic Solar Switch in the socket on the underside of the Sunny Boy.
NOTICE!
Manipulating the connector in the handle can damage the Electronic Solar Switch!
The connector within the handle must remain movable in order to ensure proper contact. Tightening the screw voids all warranty claims and creates a fire risk.
•Do not tighten the connector screw in the Electronic Solar Switch handle.
NOTICE!
The Electronic Solar Switch can be damaged if it is inserted incorrectly!
The Electronic Solar Switch can be damaged by high voltage if it has not been attached properly.
• Press the handle firmly into place on the socket of the Electronic Solar Switch until it audibly locks into place.
• Check that the handle is securely in place.
6. Switch the line circuit breaker to the "On" position.
7. Now check whether the LED display on the Sunny Boy indicates that the device is functioning correctly.
30 SB3300TLHC-IEN094121 Installation Guide
Operation (green) Ground fault (red) Disturbance (yellow)
Page 31
SMA Solar Technology AG Maintenance and Cleaning

8 Maintenance and Cleaning

Check the correct operation of the Sunny Boy at regular intervals. Impurities such as dust or airborne blossoms can cause heat concentration that can lead to yield
losses. Also check the Sunny Boy and the cables for visible external damage. Undertake repairs if necessary.

8.1 Cleaning the Cooling Fins

The heat dissipation of the product can be restricted by unclean cooling fins.
• Clean the cooling fins with a suitable, soft brush.

8.2 Check the Electronic Solar Switch for wear

To check the Electronic Solar Switch for wear, proceed as follows:
1. Remove the Electronic Solar Switch.
2. Check whether metal tongues inside the connector have a brown discoloration or are burned off.
Metal tongues
☑ If all metal tongues are in acceptable condition (as illustrated above), the Electronic Solar
Switch can continue to be used.
☑ If at least one of the metal tongues has a brown discoloration or is completely burned off
(as illustrated below), proper functioning of the Electronic Solar Switch is no longer guaranteed.
worn-out metal tongues
3. Replace the defective Electronic Solar Switch, before you re-commission the Sunny Boy. You can purchase replacements from SMA Solar Technology (see section 12”Accessories” (page39)).
Installation Guide SB3300TLHC-IEN094121 31
Page 32
Troubleshooting SMA Solar Technology AG

9 Troubleshooting

The Sunny Boy is a complex high-technology device. As a result, the possibilities for fixing faults on site are limited to just a few items. Do not attempt to carry out repairs other than those described here. Use the SMA Solar Technology 24-hour replacement service and repair service instead.

9.1 The red LED is continuously lit

If the red LED of the status display is continuously on during operation, there is either a ground fault in the PV generator or at least one of the varistors for the overvoltage protection is defective.

9.1.1 Checking the PV Generator for Ground Fault

1. Disconnect the Sunny Boy from both the DC and AC connections, as described in section
7.1”Opening the Sunny Boy” (page29).
2. Measure the voltages between the plus and minus pole of a string against the ground potential. If voltage is found, there is a ground fault in the corresponding string.
DANGER!
Risk of lethal electric shock!
In case of a ground fault, the PV generator may carry high voltages.
• Do not touch the frame of the PV generator.
• Wait until no voltage can be measured.
• Do not connect strings with ground faults to the Sunny Boy.
The approximate position of the ground fault can be determined from the ratio of the measured voltages between plus against ground potential and minus against ground potential.
Example:
V = 40 V
1
20 V 20 V 20 V 20 V 20 V
V = 60 V
2
The ground fault is between the second and third module in this case.
32 SB3300TLHC-IEN094121 Installation Guide
Page 33
SMA Solar Technology AG Troubleshooting
3. Repeat step 2 for each string.
4. The table illustrated below shows the various results and corresponding measures.
Result Measure
You have found a ground fault. • The installer of the PV generator must remedy the
ground fault in the affected string before you may reconnect the string to the Sunny Boy.
• Do not reconnect the faulty string.
• Close the Sunny Boy and operate as described in section 7.2”Closing the Sunny Boy” (page30).
You have found no ground fault. It is likely that one of the thermally monitored varistors is
defective.
• Check the varistors as described in section
9.1.2”Checking the Function of the Varistors” (page33).

9.1.2 Checking the Function of the Varistors

Varistors are wearing parts. Their functioning becomes restricted through aging or due to repeated responses as a result of overvoltages. It is therefore possible that one of the thermallly monitored varistors has lost its protective functioning, and thus the red LED is permanently lit.
Position of varistors
The position of the varistors are to be determined with the help of the diagram below. Observe the following allocation of the terminals:
• Terminal A: outer terminal (varistor connection with crimp)
• Terminal B: middle terminal
• Terminal C: outer terminal (varistor connection without crimp)
You can check the functioning of the varistors in the following manner:
1. Open the Sunny Boy as described in section 7.1”Opening the Sunny Boy” (page29).
Installation Guide SB3300TLHC-IEN094121 33
Page 34
Troubleshooting SMA Solar Technology AG
2. Determine with the aid of a multimeter for both varistors in the installed state whether a conductive connection exists between connectors B and C
☑ If there is no conducting connection, then that
varistor is not working.
3. Replace both varistors, as illustrated in the adjacent drawing, with new ones.
Ensure the varistor is installed the right way round! If you do no t re ceive a s pec ial tool for operat ing the terminal clamps with your replacement varistors,
Insert the special tool to
open the terminal clamp contact SMA Solar Technology. As an alternative, the terminal contacts can be operated using a suitable screwdriver.
Since the failure of one varistor is generally due to
Remove the varistor
factors that affect all varistors in a similar way (temperature, age, inductive overvoltages), it is highly recommended that you replace both varistors. The varistors are specially manufactured for use in the Sunny Boy and are not commercially available. They must be ordered directly from SMA Solar Technology (see section 12”Accessories”
The pole with the crimp must be fitted to terminal A when reassembling.
(page39)).
NOTICE!
The Sunny Boy could be irreparably damaged by overvoltage!
If varistors are missing, the Sunny Boy is no longer protected against overvoltages.
• Replacement varistors should be obtained as soon as possible.
• The Sunny Boy must not be operated without varistors in systems with a high risk of overvoltages.
4. Close the Sunny Boy as described in section 7.2”Closing the Sunny Boy” (page30).
If no ground fault and no defective varistor were found, there is probably a fault in the Sunny Boy. In this case, contact the SMA Serviceline to discuss what to do next.
34 SB3300TLHC-IEN094121 Installation Guide
Page 35
SMA Solar Technology AG Decommissioning

10 Decommissioning

10.1 Disassembly

1. Open the Sunny Boy as described in section 7.1”Opening the Sunny Boy” (page29).
2. Remove all cables from the Sunny Boy.
3. Close the Sunny Boy: fasten the housing cover to the Sunny Boy with the 4 screws.
4. Loosen the cylinder head screw between the Sunny Boy and wall mounting bracket.
5. Dismantle the Sunny Boy by lifting it out of the wall mounting bracket.

10.2 Packaging

If possible, always package the Sunny Boy in the original packaging. If this is no longer available, you can also use an equivalent box that fulfills the following requirements:
• Suitable for loads up to 28 kg
• With handle system
• Completely closable

10.3 Storage

Store the Sunny Boy in a dry place where ambient temperatures are always between -25 °C and +60 °C.

10.4 Disposal

Dispose of the Sunny Boy at the end of its service life in accordance with the disposal regulations for electronic waste which apply at the installation site at that time. Alternatively, send it back to SMA Solar Technology with shipping paid by sender, and labeled "ZUR ENTSORGUNG" ("for disposal").
Installation Guide SB3300TLHC-IEN094121 35
Page 36
Technical Data SMA Solar Technology AG

11 Technical Data

PV generator connection data Setting
Max. input voltage U
DC max
Input voltage, MPP range Upv 125 V ... 600 V
Max. input current I
Max. input power P
Voltage ripple U
PV max
DC
pp
< 10 % of the input voltage
Internal consumption during operation < 10 W (standby)
a) The maximum open circuit voltage, which can occur at a cell temperature of -10 °C, must not exceed the maximum input voltage.
Grid Connection Data Setting
Nominal output power P
Max. output power P
Nominal output current I
Max. output current I
ACnom
ACmax
ACnom
AC max
Max. fuse protection 32 A
Harmonic distortion of output current (at T
< 2 %, PAC > 0.5 P
HD
ACNom
Nominal AC voltage U
Voltage range
K
IAC
)
ACnom
U
AC
220 V / 230 V / 240 V
180 ... 260 V AC
(extended operating range)
AC- Grid frequency f
Frequency range
ACnom
f
AC
45.5 ... 52.5 Hz
(extended operating range)
Power factor (at nominal output power) cos Phi 1
Overvoltage category III
Test voltage (50 Hz) 1.65 kV
Test surge voltage 4 kV (serial interface: 6 kV)
Internal consumption in night mode 0.25 W
750 V
11 A
3440 W
3000 W
3300 W
13 A
16 A
< 4 %
50 Hz
a)
36 SB3300TLHC-IEN094121 Installation Guide
Page 37
SMA Solar Technology AG Technical Data
General Data
EC Declaration of Conformity You will find the EC Declaration of Conformity in
the accompanying document set or in the
download area of www.SMA.de/en under
Certificate.
Protection category per DIN EN 60529 IP65
Dimensions (W x H x D) approx. 470 mm x 490 mm x 225 mm
Weight approx. 28 kg
Protection class I
Topology Transformerless
Climatic conditions according to DIN EN 50178:1998-04
Location of type C: Class 4K4H
Extended temperature range: -25 °C ... +60 °C
Extended humidity range: 0 ... 100 %
Extended air pressure range: 70 kPa ... 106 kPa
Transport of type E: Class 2K3
Temperature range: -25 °C ... +70 °C
Operating temperature range -25 °C ... +60 °C
Max. operating altitude 2000 m above sea level NN
Noise emission (typical) ≤ 29 dB (A)
Protective function DC side
All-pole isolator on the DC input side Electronic Solar Switch, DC plug connectors
Overvoltage protection Thermally monitored varistors
Personal protection Ground fault monitoring (Riso > 1 MOhm)
Pole Confusion Protection via short-circuit diode
Protective function AC side
Short Circuit Proof Grid-side via current regulation
All-pole disconnection unit on grid side Automatic disconnection device (grid guard 2.1),
double design
Installation Guide SB3300TLHC-IEN094121 37
Page 38
Technical Data SMA Solar Technology AG
Communication Interfaces
RS485 (galvanically isolated) optional
Radio optional
Electronic Solar Switch
Electrical lifetime (in the event of a short circuit,
min. 50 switching processes
with a nominal current of 30 A) Maximum switching current 30 A Maximum switching voltage 800 V Maximum PV power Approx. 10 kW Protection rating when plugged IP65 Protection rating in unplugged state IP21
Efficiency
Max. efficiency η European standard efficiency η
max
euro
96 %
94.6 %
Efficiency curve
38 SB3300TLHC-IEN094121 Installation Guide
Page 39
SMA Solar Technology AG Accessories

12 Accessories

You will find the corresponding accessories and replacement parts for your product In the following overview. If needed, you can order these from SMA Solar Technology or your dealer.
designation Brief description SMA order number
Replacement varistors Set of thermally monitored varistors (2 pcs.)
including insertion tool Electronic Solar Switch ESS handle replacement part ESS-HANDLE:03 RS485 upgrade kit RS485 interface 485PB-MS-NR Radio upgrade kit Radio Piggy-Back for upgrading a Sunny Boy
for communication with Sunny Beam,
including antenna, coaxial cable, and PG
cable gland (metal)
Bluetooth
Wireless
Bluetooth Interface on request
®
Technology upgrade kit DC- Connection set
Multi-Contact 3 mm: DC- Connection set
Multi-Contact 4 mm:
Multi-Contact adapter set 3,
max. flow current: 21 A
Multi-Contact adapter set 4,
max. flow current: 30 A Tyco DC connection set TYCO adapter set,
max. flow current: 30 A
MSWR-TV7
BEAMPB-NR
SWR-MC
MC-SET
TYCO-SET
Installation Guide SB3300TLHC-IEN094121 39
Page 40
Contact SMA Solar Technology AG

13 Contact

If you have technical problems concerning our products, please contact our Serviceline. We require the following information in order to provide you with the necessary assistance:
• Inverter type
• Type and number of modules connected
•Communication
• Series number of the Sunny Boy
• Blink code or display of the Sunny Boy
SMA Solar Technology AG
Sonnenallee 1 34266 Niestetal, Germany www.SMA.de
Serviceline
Inverters: +49 561 9522 1499 Communication: +49 561 9522 2499 Fax +49 561 9522 4699 E-mail: Serviceline@SMA.de
40 SB3300TLHC-IEN094121 Installation Guide
Page 41
SMA Solar Technology AG Contact
Installation Guide SB3300TLHC-IEN094121 41
Page 42
Contact SMA Solar Technology AG
42 SB3300TLHC-IEN094121 Installation Guide
Page 43
SMA Solar Technology AG Legal Restrictions
The information contained in this document is the property of SMA Solar Technology AG. Publishing its content, either partially or in full, requires the written permission of SMA Solar Technology AG. Any internal company copying of the document for the purposes of evaluating the product or its correct implementation is allowed and does not require permission.
Exclusion of liability
The general terms and conditions of delivery of SMA Solar Technology AG shall apply. The content of these documents is continually checked and amended, where necessary. However, discrepancies cannot be
excluded. No guarantee is made for the completeness of these documents. The latest version is available online at www.SMA.de or from the usual sales channels.
Guarantee or liability claims for damages of any kind are excluded if they are caused by one or more of the following:
• Damages during transportation
• Improper or inappropriate use of the product
• Operating the product in an unintended environment
• Operating the product whilst ignoring relevant, statutory safety regulations in the deployment location
• Ignoring safety warnings and instructions contained in all documents relevant to the product
• Operating the product under incorrect safety or protection conditions
• Altering the product or supplied software without authority
• The product malfunctions due to operating attached or neighboring devices beyond statutory limit values
• In case of unforeseen calamity or force majeure The use of supplied software produced by SMA Solar Technology AG is subject to the following conditions:
• SMA Solar Technology AG rejects any liability for direct or indirect damages arising from the use of software developed by SMA Solar Technology AG. This also applies to the provision or non-provision of support activities.
• Supplied software not developed by SMA Solar Technology AG is subject to the respective licensing and liability agreements of the manufacturer.
SMA Factory Warranty
The current guarantee conditions come enclosed with your device. These are also available online at www.SMA.de and can be downloaded or are available on paper from the usual sales channels if required.
Trademarks
All trademarks are recognized even if these are not marked separately. Missing designations do not mean that a product or brand is not a registered trademark.
The Bluetooth Solar Technology is under license.
SMA Solar Technology AG
Sonnenallee 1 34266 Niestetal Germany Tel. +49 561 9522-0 Fax +49 561 9522-100 www.SMA.de E-Mail: info@SMA.de © 2004 to 2009 SMA Solar Technology AG. All rights reserved
®
wor d mark an d logos are registere d trademarks owned by Bl uetoot h SIG, Inc. and an y use of s uch marks by S MA
Installation Guide SB3300TLHC-IEN094121 43
Page 44
SMA Solar Technology AG
www.SMA.de
Loading...