SMA CLCON-10, CLCON-S-10 Installation Manual

Page 1
InstallationManual
SMA CLUSTER CONTROLLER
ClusterController-IA-en-15 | Version 1.5
ENGLISH
Page 2
Legal Provisions
SMA Solar Technology AG
Legal Provisions
The information contained in these documents is property of SMA Solar Technology AG. Any publication, whether in whole or in part, requires prior written approval by SMA Solar Technology AG. Internal reproduction used solely for the purpose of product evaluation or other proper use is allowed and does not require prior approval.
SMA Warranty
You can download the current warranty conditions from the Internet at www.SMA-Solar.com.
Software Licenses
The licenses for the software modules used with this product can be found on the supplied CD.
Trademarks
All trademarks are recognized, even if not explicitly identified as such. A lack of identification does not mean that a product or symbol is not trademarked.
The BLUETOOTH® word mark and logos are registered trademarks of BluetoothSIG,Inc. and any use of these marks by SMASolarTechnologyAG is under license.
Modbus® is a registered trademark of Schneider Electric and is licensed by the Modbus Organization, Inc.
QR Code is a registered trademark of DENSO WAVE INCORPORATED. Phillips® and Pozidriv® are registered trademarks of Phillips Screw Company. Torx® is a registered trademark of Acument Global Technologies, Inc.
SMASolarTechnologyAG
Sonnenallee 1 34266 Niestetal Germany Tel. +49 561 9522-0 Fax +49 561 9522-100 www.SMA.de E-mail: info@SMA.de © 2004 to 2015SMASolarTechnologyAG. All rights reserved.
Installation ManualClusterController-IA-en-152
Page 3
SMA Solar Technology AG
Table of Contents
Table of Contents
1 Information on this Document ................................................. 6
1.1 Validity................................................................................................ 6
1.2 Target group....................................................................................... 6
1.3 Additional Information....................................................................... 6
1.4 Symbols .............................................................................................. 6
1.5 Typographies...................................................................................... 7
1.6 Nomenclature..................................................................................... 7
2 Safety......................................................................................... 8
2.1 Intended Use ...................................................................................... 8
2.2 Safety Information.............................................................................. 8
2.3 Supported Products............................................................................ 9
2.4 System Requirements ......................................................................... 10
3 Scope of Delivery...................................................................... 11
4 Product Description................................................................... 12
4.1 Cluster Controller ............................................................................... 12
4.2 Type Label .......................................................................................... 17
4.3 LEDs..................................................................................................... 18
4.4 Display................................................................................................ 19
4.5 Keypad ............................................................................................... 20
5 Mounting ................................................................................... 22
5.1 Requirements for Mounting ............................................................... 22
5.2 Mounting the Cluster Controller........................................................ 23
6 Connection and Commissioning .............................................. 25
6.1 Overview of the Connection Area .................................................... 25
6.2 Functions of the Terminals and Pin Groups ...................................... 26
6.3 Cable Requirements........................................................................... 28
6.4 Performing Pin Coding....................................................................... 29
6.5 Preparing Connection Cables for Connection to Multipole Plugs .. 30
6.6 Connecting the Cluster Controller to the Voltage Supply................ 32
Installation Manual 3ClusterController-IA-en-15
Page 4
Table of Contents
SMA Solar Technology AG
6.7 Checking and Setting the Cluster Controller System Time............... 35
6.8 Connecting the Cluster Controller to a Speedwire Network .......... 36
6.9 Connecting the Cluster Controller to the LAN.................................. 38
6.10 Connecting USB Data Carriers to the Cluster Controller................. 39
6.11 Connecting Sensors to the Cluster Controller................................... 40
6.11.1 Connecting the Temperature Sensor............................................. 40
6.11.2 Connecting an Irradiation Sensor................................................. 43
6.11.3 Connecting Additional Sensors..................................................... 44
6.12 Connections for Grid Management Services................................... 47
6.12.1 Options for Implementing Grid Management Service Setpoints 47
6.12.2 Digital Setpoint Signal ................................................................... 48
6.12.2.1 Connection Options ................................................................ 48
6.12.2.2 Connecting a Signal Source to a Digital Input for Active
Power Limitation.......................................................................
6.12.2.3 Connecting a Signal Source to a Digital Input for Reactive
Power Setpoint.........................................................................
6.12.2.4 Digital Signal Setpoint when Using Multiple Cluster
Controllers................................................................................
6.12.3 Analog Setpoint Signal.................................................................. 54
6.12.3.1 Connecting a Signal Source to an Analog Input for Active
Power Limitation.......................................................................
6.12.3.2 Connecting a Signal Source to an Analog Input for
Reactive Power Setpoint..........................................................
6.12.3.3 Analog Setpoint Signal when Using Multiple Cluster
Controllers................................................................................
6.12.4 Setpoint via Modbus Client........................................................... 57
6.12.5 Feedback of the Cluster Controller ............................................... 57
6.12.5.1 Feedback Options................................................................... 57
6.12.5.2 Connecting a Remote Terminal for Feedback via Digital
Signal .......................................................................................
6.12.5.3 Connecting a Remote Terminal for Feedback via Analog
Signal .......................................................................................
6.12.5.4 Feedback When Using Multiple Cluster Controllers............. 63
6.13 Checking the Connections via the Display....................................... 64
6.14 Configuring a Static LAN................................................................... 65
6.15 Setting Up a Modbus Data Connection........................................... 65
49
51
53
54
55
56
58
59
7 Troubleshooting ........................................................................ 66
Installation ManualClusterController-IA-en-154
Page 5
SMA Solar Technology AG
Table of Contents
7.1 LED States........................................................................................... 66
7.1.1 Operation LEDs.............................................................................. 66
7.1.2 Network Port LEDs ......................................................................... 69
7.2 Errors in the Cluster Controller or the Connected Devices .............. 70
7.3 Resetting the Cluster Controller ......................................................... 74
8 Decommissioning...................................................................... 76
8.1 Disassembling the Cluster Controller ................................................ 76
8.2 Packing the Product for Shipment ..................................................... 76
8.3 Disposing of the Product.................................................................... 77
9 Technical Data........................................................................... 78
10 Accessories................................................................................ 82
11 Contact....................................................................................... 83
Installation Manual 5ClusterController-IA-en-15
Page 6

1 Information on this Document

SMA Solar Technology AG
1 Information on this Document

1.1 Validity

This document is valid for the SMAClusterController (models "CLCON-10" and "CLCON-S-10") from hardware versionA1 and from firmware version1.03.xx.R.

1.2 Target group

The tasks described in this document must only be performed by qualified persons. Qualified persons must have the following skills:
• Training in the installation and configuration of IT systems
• Knowledge of how an inverter works and is operated
• Training in how to deal with the dangers and risks associated with installing and using electrical devices and installations
• Training in the installation and commissioning of electrical devices and installations
• Knowledge of the applicable standards and directives
• Knowledge of and compliance with this document and all safety information

1.3 Additional Information

Links to additional information can be found at www.SMA-Solar.com:
Document title Document type
"SMASPEEDWIRE FIELDBUS" Technical Information

1.4 Symbols

Symbol Explanation
Indicates a hazardous situation which, if not avoided, will result in death or serious injury
Indicates a hazardous situation which, if not avoided, can result in death or serious injury
Indicates a hazardous situation which, if not avoided, can result in minor or moderate injury
Indicates a situation which, if not avoided, can result in property damage
Information that is important for a specific topic or goal, but is not safety-relevant
Indicates a requirement for meeting a specific goal
Desired result
A problem that might occur
Installation ManualClusterController-IA-en-156
Page 7
SMA Solar Technology AG
1 Information on this Document

1.5 Typographies

Typography Use Example
bold
>
[Button] [Key]
• Display texts
• Elements on a user interface
• Terminals
• Elements to be selected
• Elements to be entered
• Connects several elements to be selected
• Button or key to be selected or pressed
• The value can be found in the field Energy.
• Select Settings.
• Enter 10 in the field Minutes.
• Select Settings > Date.
• Select [Next].

1.6 Nomenclature

Complete designation Designation in this document
Large-scale PV power plant PV system PV inverter Inverter SMAClusterController ClusterController SMA Energy Meter Energy Meter
Installation Manual 7ClusterController-IA-en-15
Page 8

2 Safety

SMA Solar Technology AG
2 Safety

2.1 Intended Use

The ClusterController is a device for monitoring and controlling SMAinverters with Speedwire/ Webconnect interfaces in decentralized PV systems and large-scale PV power plants.
The ClusterController is an ITE classA device as per EN55022 and is designed for industrial use. The product is designed for indoor use only. Use this product only in accordance with the information provided in the enclosed documentation
and with the locally applicable standards and directives. Any other application may cause personal injury or property damage.
Alterations to the product, e.g. changes or modifications, are only permitted with the express written permission of SMA Solar Technology AG. Unauthorized alterations will void guarantee and warranty claims and in most cases terminate the operating license. SMA Solar Technology AG shall not be held liable for any damage caused by such changes.
Any use of the product other than that described in the Intended Use section does not qualify as appropriate.
The enclosed documentation is an integral part of this product. Keep the documentation in a convenient place for future reference and observe all instructions contained therein.
The type label must remain permanently attached to the product.

2.2 Safety Information

This section contains safety information that must be observed at all times when working on or with the product.
To prevent personal injury and property damage and to ensure long-term operation of the product, read this section carefully and observe all safety information at all times.
Danger to life due to electric shock from touching an ungrounded product
Touching an ungrounded product can cause a lethal electric shock.
• Ensure that the product is integrated in the existing overvoltage protection.
• Ground the enclosure of the product.
Damage to the product due to moisture
The product is not splash-proof (IP20). Moisture can penetrate the product and damage it.
• Only use the product in a dry, indoor environment.
Installation ManualClusterController-IA-en-158
Page 9
SMA Solar Technology AG

2.3 Supported Products

SMA Products
Availability of SMA products in your country
Not all SMA products are available in all countries. For information on whether an SMA product is available in your country, visit the website of your country's SMA subsidiary at www.SMA-Solar.com or contact your distributor.
The ClusterController can establish a connection to and display data on the following SMA products that are equipped with Speedwire communication:
Inverters:
• All inverters with integrated or retrofitted Speedwire/Webconnect interface Information on whether an inverter has an integrated Speedwire/Webconnect interface or can
be retrofitted with a Speedwire/Webconnect interface can be found on the inverter product page at www.SMA-Solar.com.
Other products:
• SunnyPortal
• SMA Energy Meter
• SMAFuelSaveController
• SMAGridGate of device type "GRIDGATE-20" from firmware version1.0
• SMAPowerPlantController
Products from Other Manufacturers
2 Safety
Sensors:
• Irradiation sensors that can output a current signal in the range from 0mAto20mA
• Temperature sensors with a Pt100 measuring shunt or a Pt1000 measuring shunt
• Other sensors that can output a current signal in the range from 0mAto20mA or a voltage signal in the range from −10V to+10V
Signal receivers and digital and analog signal sources:
• Signal sources with relay contacts
• Signal sources that provide digital output signals
• Signal sources that can output current signals in the range from 0mA to 20mA
• Signal sources that can output voltage signals in the range from −10V to+10 V
• Signal receivers that can process current signals in the range from 0mA to 20mA
Routers and network switches:
• Routers and network switches for Fast Ethernet with a data transfer rate of at least 100Mbit/s All network components used must support the IGMP version 1 protocol (IGMPv1).
Installation Manual 9ClusterController-IA-en-15
Page 10
2 Safety
Power supply units:
In addition to the top-hat rail power supply unit offered as an accessory (see Section10, page82 ), the ClusterController supports power supply units with the following properties:
• Maximum output current including short circuit: 8A
• Maximum output apparent power: 100VA
• DC output voltage: 24V
• Nominal current: minimum 1.8A
SMA Solar Technology AG

2.4 System Requirements

Supported web browsers:
☐ MicrosoftInternetExplorer from version8 ☐ MozillaFirefox from version3.6
Recommended display resolution:
☐ Minimum 1,024pixelsx768pixels
Installation ManualClusterController-IA-en-1510
Page 11
SMA Solar Technology AG

3 Scope of Delivery

3 Scope of Delivery
Check the scope of delivery for completeness and any externally visible damage. Contact your distributor if the scope of delivery is incomplete or damaged.
Figure 1: Components included in the scope of delivery
Position Quantity Designation
A 1 ClusterController B 1 Three-pole plug C 1 Two-pole plug* D 2 Five-pole plug E 8 Six-pole plug** F 2 Eight-pole plug G 2 Coding element H 20 Cable tie with caption field I 8 Shield clamp with ring terminal lug K 1 Ring terminal lug L 1 Fastening screw M 2 Washer N 1 Tooth lock washer O 1 Split lock washer P 1 CD with product documentation Q 1 Quick reference guide for commissioning and supplementary sheet
for noting down connected devices
* Reserved for future applications. Keep the plug in a safe place.
** Two of the eight plugs are reserved for future applications. Keep the twoplugs in a safe place.
Installation Manual 11ClusterController-IA-en-15
Page 12

4 Product Description

SMA Solar Technology AG
4 Product Description
4.1 ClusterController
The ClusterController is a device for monitoring and controlling SMAinverters with Speedwire/ Webconnect interfaces in decentralized PV systems and large-scale PV power plants.
The ClusterController primarily performs the following tasks:
• Set-up of the Speedwire network
• Reading out, provision and administration of PV system data
• Configuring device parameters
• Feedback on current total active power of the system
• Implementation and feedback of grid operator setpoints for active power limitation and reactive power operation under grid management services
• Implementation and feedback of setpoints for active power limitation when PV electricity is directly marketed
• Sending e-mail alarms in the event of critical system statuses
• Sending the system data to an FTP server and/or the SunnyPortal Internet portal
• Performing updates for the ClusterController and the inverters
Figure 2: Design of the ClusterController
Position Designation
A LEDs B Connection areas C Keypad D Display
Reading out, provision and administration of PV system data
The ClusterController is the central communication unit for the system and continuously reads out the data of the devices in the system (e.g. inverters, sensors). The ClusterController then makes this system data available via the display, user interface and Modbus data interface. In addition, the PV system data can be displayed, evaluated and managed using Sunny Portal.
Installation ManualClusterController-IA-en-1512
Page 13
SMA Solar Technology AG
4 Product Description
Configuring device parameters
You can configure specific parameters of individual devices or entire device classes via the user interface of the ClusterController. You must be logged into the user group Installer on the ClusterController. The device parameters that can be configured, if any, depend on the device and the rights of the user group. You may only change grid-sensitive device parameters (SMAGridGuard parameters) with the approval of the grid operator and using your personal SMAGridGuard code.
Sending e-mail alarms in the event of critical system statuses
You have the option of receiving prompt information on critical system statuses via e-mail. The ClusterController automatically sends a notification if alarm-related events occur in the system.
Feedback on current total active power of the system
You have the option of being informed of the total active power currently generated by the system via an analog current output signal.
Implementation and feedback of grid operator setpoints for active power limitation and reactive power operation under grid management services
With the ClusterController, as part of grid management services you can implement different grid operator setpoints for active power limitation and reactive power operation of your system. The ClusterController can implement the setpoints using open-loop control or closed-loop control.
For ClusterController systems without self-consumption and with direct limitation of active power feed-in, the operating mode Open-loop control is used. In this operating mode, the ClusterController can receive the setpoints either in the form of digital or analog signals, or via Modbus. The different types of signal source can be combined so that, for example, the setpoints for the active power limitation are received as digital signals and the reactive power setpoints are received as analog signals: For ClusterController systems with self-consumption, the operating mode Closed-loop control is used. In this operating mode, you can regulate the active power fed in by the system at the grid-connection point and limit it e.g. to a fixed percentage value. In agreement with your grid operator, you can use the user interface of the ClusterController to configure which setpoints of the ClusterController are to be transmitted to the connected inverters depending on the respective signal. In addition, you can use a digital response contact or an analog current output signal to inform the grid operator of the setpoints (if any) for active power limitation and reactive power operation that are currently being used in the system.
Implementation and feedback of setpoints for active power limitation when PV electricity is directly marketed
The PV current generated by your system can be directly marketed. The ClusterController can receive setpoints for active power limitation from the direct marketer as digital or analog signals or via Modbus. The "CLCON-S-10" model provides a Modbus register for sending setpoints via Modbus. The model "CLCON-10" provides two Modbus registers. The ClusterController can provide feedback about the current feed-in power of the system to the direct marketer via digital or analog signals. To avoid conflicts when different setpoints are used by the grid operator and the direct marketer, the ClusterController always implements the setpoint that more strongly limits the active power of the system.
Installation Manual 13ClusterController-IA-en-15
Page 14
4 Product Description
SMA Solar Technology AG
Sending the system data to an FTP server and/or the SunnyPortal Internet portal
The ClusterController can automatically send the system data that has been read out to an arbitrary FTP server and/or the SunnyPortal Internet portal via the Internet. The ClusterController establishes the connection to the FTP server and/or SunnyPortal e.g. via a router.
Performing updates for the ClusterController and the inverters
You have the option of performing updates for the Cluster Controller and the inverters in the system. You can perform the updates automatically or manually. The update source can be the SMAUpdate Portal or a USB data carrier with update files downloaded from the Internet. Alternatively, you can also upload the update files directly from the computer via the user interface of the ClusterController.
Figure 3: Decentralized large-scale PV power plant with ClusterController and implementation of grid operator setpoints via open-loop control (example)
Position Designation
A PV Modules B Module temperature sensor C Inverter D Outside temperature sensor
Installation ManualClusterController-IA-en-1514
Page 15
SMA Solar Technology AG
Position Designation
E Irradiation sensor F ClusterController G SunnyPortal H Router I Ripple control receiver or remote terminal unit K Grid station L Control room M Grid control room N Utility grid
4 Product Description
Installation Manual 15ClusterController-IA-en-15
Page 16
4 Product Description
SMA Solar Technology AG
Figure 4: Decentralized large-scale PV power plant with ClusterController and implementation of grid operator setpoints via closed-loop control (example)
Position Designation
A PV Modules B Module temperature sensor C Inverter D Outside temperature sensor E Irradiation sensor F ClusterController G Industrial load H SunnyPortal I Router K Ripple control receiver or remote terminal unit
Installation ManualClusterController-IA-en-1516
Page 17
SMA Solar Technology AG
Position Designation
L Energy meter M Control room N Grid control room O Grid station P Utility grid
4 Product Description

4.2 Type Label

The type label clearly identifies the product. The type label can be found on the back of the enclosure. You can read off the following data from the type label:
• Device type (Type)
• Serial Number
• Hardware version (Version)
• Model
• Device-specific characteristics
You will require the information on the type label to use the product safely and when seeking customer support from Service (see Section11 "Contact", page83).
Symbols on the Type Label
Symbol Designation Explanation
C-Tick The product complies with the require-
ments of the applicable Australian EMC standards.
CANICES-3(A)/ NMB-3(A)
IC marking The product complies with the require-
ments of the applicable Canadian EMC standards.
Indoors The product is only suitable for indoor
installation.
FCC designation The product complies with the require-
ments of the applicable FCC stan­dards.
CE marking The product complies with the require-
ments of the applicable EU directives.
Installation Manual 17ClusterController-IA-en-15
Page 18
4 Product Description
Symbol Designation Explanation
WEEE designation Do not dispose of the product together
with household waste but in accor­dance with the locally applicable dis­posal regulations for electronic waste.
Data matrix code 2Dcode for device-specific character-
istics

4.3 LEDs

Operation LEDs
LED Designation Explanation
Power LED Shows whether the ClusterController is starting or is in op-
eration (see Section7.1 "LED States", page66)
Status LED Shows the status of the ClusterController and the con-
nected devices as well as the communication status of the system and the status of the grid management services (see Section7.1 "LED States", page66)
Data carrier status LED
Shows the status of the connected USB data carrier (see Section7.1 "LED States", page66)
SMA Solar Technology AG
Network Port LEDs
Colors and functionality of the network port LEDs are not standardized
The colors and functionalities of the network port LEDs are not standardized. The colors used by SMA for the link/activity LED and the speed LED as well as the corresponding functionalities can deviate in products supplied by third-party manufacturers.
Installation ManualClusterController-IA-en-1518
Page 19
SMA Solar Technology AG
Figure 5: Network port LEDs
4 Product Description
Position Designation Color Explanation
A Link/activity LED Green Shows the status and the activity of the network
connection (see Section7.1.2 "Network Port LEDs", page69)
B Speed LED Yellow Shows the network connection speed (see Sec-
tion7.1.2 "Network Port LEDs", page69)

4.4 Display

The display shows information on the ClusterController and the connected devices as well as the system status and the system configuration. The display contrast can be configured. The display languages are "German" and "English". You can change the display language via the ClusterController user interface.
Figure 6: ClusterController display (example)
Position Designation Explanation
A Title line Displays the title of the display view
The system time is always displayed.
B Data lines Displays text and numeric values
The numeric values for measurement or yield data are dis­played with units.
Overview of the Display Views
Display view Explanation
Start view Displayed when the ClusterController starts up; includes the current
firmware version of the ClusterController
Installation Manual 19ClusterController-IA-en-15
Page 20
4 Product Description
Display view Explanation
System overview Displays the system status, the current daily yield, the nominal sys-
tem power and the current setpoints for active power and reactive power
If no button on the keypad is pressed within five minutes, the Clus-
terController switches to the display view System overview. Yield data Displays the yield data of the system System status Displays the current system status
The number of inverters detected by the ClusterController and the
status of the inverters is displayed here. ClusterController Displays the status and device information of the ClusterController
When a USB data carrier is inserted into USB port1, information on
the current memory usage of the USB data carrier will be displayed. SunnyPortal settings Displays the configured upload frequency and the date of the last
successful data upload to SunnyPortal Analog inputs Displays the analog inputs with the current level value and unit Digital inputs Displays the digital inputs in binary form
The digital inputs are summarized in two groups here. Meteorology Displays the measured values of the connected irradiation sensor
and the connected temperature sensors Active power limitation Displays the current setpoint for active power limitation with the set-
point size and the date of the last configuration change Reactive power setpoint Displays the current reactive power setpoint and the date of the last
configuration change Grid management services Displays the setpoint type and the signal sources selected via the
ClusterController user interface for the grid management services External communication Displays the settings for the LAN Speedwire Displays the settings for the Speedwire network Modbus settings Displays the Modbus settings with the activated network protocols
and the corresponding network ports Settings Enables the display contrast to be changed and the ClusterCon-
troller to be partially or fully reset (see Section7.3, page74)
SMA Solar Technology AG

4.5 Keypad

Designation Explanation
Any button Activates the display illumination Arrow buttons (◂▸▴▾) Changes display views and selects specific display lines
Installation ManualClusterController-IA-en-1520
Page 21
SMA Solar Technology AG
Designation Explanation
[OK] [ESC] ⓘ
Confirms the selected action Cancels the selected action Opens the display view System status
4 Product Description
Installation Manual 21ClusterController-IA-en-15
Page 22

5 Mounting

SMA Solar Technology AG
5 Mounting

5.1 Requirements for Mounting

Requirements for the mounting location:
Product can cause radio interference in living areas
The product is a device of ITE class A (EN55022) and can cause radio interference in living areas.
• Take suitable measures for shielding radio waves when the ClusterController is used in the vicinity of living areas.
☐ The mounting location must be indoors. ☐ The ambient conditions at the mounting location must be suitable for the operation of the
ClusterController (see Section9, page78).
☐ The mounting location must be protected against dust, moisture and corrosive substances.
Maximum permitted cable lengths:
☐ Observe the maximum cable length of 100 m each between any two nodes in the Speedwire
network and in the LAN.
☐ When connecting a digital or analog signal source (e.g. remote terminal unit, ripple control
receiver), observe the maximum cable length of 30 m from the ClusterController to the signal source.
☐ When connecting a temperature sensor using the four-conductor connection technology,
observe the maximum cable length of 20 m from the ClusterController to the temperature sensor.
☐ When connecting a temperature sensor using the two-conductor connection technology,
observe the maximum cable length of 2.5 m from the ClusterController to the temperature sensor.
Minimum clearances:
☐ The minimum clearances must be maintained to ensure adequate heat dissipation.
Installation ManualClusterController-IA-en-1522
Page 23
SMA Solar Technology AG
Figure 7: Minimum clearances
Permitted and prohibited mounting positions:
☐ The ClusterController must be mounted so that the ventilation slots face upward and
downward. This ensures optimum heat dissipation.
5 Mounting
Figure 8: Permitted and prohibited mounting positions
5.2 Mounting the ClusterController
Requirements:
☐ A top-hat rail must be available. ☐ The top-hat rail must 35 mm wide.
Installation Manual 23ClusterController-IA-en-15
Page 24
5 Mounting
SMA Solar Technology AG
☐ In order to mount the ClusterController, the top-hat rail must be at least 26 cm long. When a
top-hat rail power supply unit is used, the top-hat rail must be correspondingly longer.
☐ The top-hat rail must be securely mounted on the wall or in the switch cabinet.
Procedure:
• Use the rear-side upper retainers to hook the ClusterController into the upper edge of the top­hat rail and press down toward the top-hat rail. This will hook the spring-mounted top-hat rail locking mechanism on the ClusterController onto the lower edge of the top-hat rail.
☑ The top-hat rail locking mechanism snaps into place.
Installation ManualClusterController-IA-en-1524
Page 25
SMA Solar Technology AG
6 Connection and Commissioning

6.1 Overview of the Connection Area

Figure 9: Overview of the connection area

6 Connection and Commissioning

Position Quantity Designation Explanation
A 1 X1 Terminal for the voltage supply B 1 Terminal for grounding C 1 1 USB port for exporting system data D 1 2 USB port for updates E 1 X2 Digital outputs F 1 X3 Reserved for future applications G 1 X4 Digital inputs H 1 X5 Digital inputs I 1 X8 Analog inputs K 1 X7 Terminals for temperature sensors L 1 X6 Analog outputs M 2 X13, X14 Network ports for connecting the LAN
Installation Manual 25ClusterController-IA-en-15
Page 26
6 Connection and Commissioning
Position Quantity Designation Explanation
N 2 X11, X12 Reserved for future applications O 2 X9, X10 Network ports for connecting the inverters (Speed-
wire)
SMA Solar Technology AG

6.2 Functions of the Terminals and Pin Groups

The digital and analog terminals of the ClusterController are divided into pin groups. Each pin group forms one of the digital or analog inputs or outputs. On the enclosure, the upper row of contact pins is marked with A and the lower row is marked with B. The contact pins are counted from left to right.
The division of terminals into pin groups and the functions of the pin groups are described in the following table.
For the pin groups of terminals X2 and X6 there are several functions to choose from. You can find all selectable functions on the user interface of the Cluster Controller. In the following table you can find the factory-set function.
Terminal Pin group Pin Function
X1 1to 3 Voltage supply X2 Digital output1
Relay A Digital output2
Relay B Digital output3
Relay C
X3 Reserved for future applications X4 Digital input1 A1toA3 Signal 1 of 4 for the active power limita-
Digital input2 A4toA6 Signal 2 of 4 for the active power limita-
Digital input3 B1toB3 Signal 3 of 4 for the active power limita-
Digital input4 B4 to B6 Signal 4 of 4 for the active power limita-
A1toA3
A4toA6 Fault indicator contact for the status
B1toB3 Response contact for the current active
Fault indicator contact for the status Er-
ror
Warning or Error
power limitation in grid management ser­vices
tion in grid management services
tion in grid management services
tion in grid management services
tion in grid management services
Installation ManualClusterController-IA-en-1526
Page 27
SMA Solar Technology AG
6 Connection and Commissioning
Terminal Pin group Pin Function
X5 Digital input5 A1toA3 Signal 1 of 4 for the reactive power set-
point in grid management services
Digital input6 A4toA6 Signal 2 of 4 for the reactive power set-
point in grid management services
Digital input7 B1toB3 Signal 3 of 4 for the reactive power set-
point in grid management services
Digital input8 B4toB6 Signal 4 of 4 for the reactive power set-
point in grid management services
X6 Analog current output1 A1toA3 Analog current output for feedback on
current active power limitation in grid management services
Analog current output2 A4toA6 Analog current output for feedback on
current reactive power setpoint in grid management services
Analog current output3 B1toB3 Analog current output for feedback on
the current total active system power (as a percentage) based on the maximum nominal system power
X7 Temperature input1 A1toA5 Analog input for connecting an external
temperature sensor
Temperature input2 B1toB5 Analog input for connecting a module
temperature sensor
X8 Analog current input1 A1toA4 Analog current input for connecting an ir-
radiation sensor or for measuring the ac­tive power feed-in at the grid-connection point
Analog current input2 A5toA8 Analog current input for active power lim-
itation in grid management services or for measuring the active power feed-in at the grid-connection point
Analog current input3 B1toB4 Analog current input for reactive power
setpoint in grid management services or for measuring the active power feed-in at the grid-connection point
Analog voltage input 4 B5toB8 Analog voltage input for connecting a
sensor
X9, X10 1to 8 Network ports for connection to the in-
verters (Speedwire)
Installation Manual 27ClusterController-IA-en-15
Page 28
6 Connection and Commissioning
Terminal Pin group Pin Function
X11, X12 Reserved for future applications X13, X14 1to 8 Network ports for connection to LAN
SMA Solar Technology AG

6.3 Cable Requirements

UV resistance of connection cables
Connection cables to be laid outdoors must be UV-resistant or routed in a UV-resistant cable channel.
Terminal Cable requirements
Grounding ☐ Conductor cross-section: 2.5mm²
☐ Maximum cable length: 30 cm
Voltage supply ☐ Number of insulated conductors: at least two
☐ Conductor cross-section: 0.2 mm² to 1.5 mm² ☐ Maximum cable length: 3 m
Digital inputs ☐ Number of insulated conductors: at least two
☐ Conductor cross-section: 0.2 mm² to 1.5 mm² ☐ Maximum cable length: 30 m
Digital outputs ☐ Number of insulated conductors: at least two
☐ Conductor cross-section: 0.2 mm² to 1.5 mm² ☐ Maximum cable length: 30 m
Analog inputs, analog out­puts and temperature inputs (conductor)
Analog inputs (connection cable)
Analog outputs (connection cable)
☐ Conductor cross-section: 1.5mm² ☐ Cable length: 32 cm
☐ Number of insulated conductors: at least two ☐ Shielding: yes ☐ Conductor cross-section: 0.2 mm² to 1.5 mm² ☐ Maximum cable length: 30 m
☐ Number of insulated conductors: at least two ☐ Shielding: yes ☐ Conductor cross-section: 0.2 mm² to 1.5 mm² ☐ Maximum cable length: 3,000 m
Installation ManualClusterController-IA-en-1528
Page 29
SMA Solar Technology AG
Terminal Cable requirements
Temperature inputs (connec­tion cable)
Inverter (Speedwire) ☐ Number of insulated conductor pairs and insulated conductor
LAN ☐ Number of insulated conductor pairs and insulated conductor
☐ Number of insulated conductors for tolerance ±2°C: at least
two
☐ Number of insulated conductors for tolerance ±0.5°C: at least
four ☐ Conductor cross-section: at least 4 x 0.25 mm² ☐ External cable diameter: 4.5 mm to 7.0 mm ☐ Maximum cable length for four-conductor connection
technology: 20 m ☐ Maximum cable length for two-conductor connection
technology: 2.5 m
cross-section: at least 2 x 2 x 0.22 mm² ☐ External diameter: the maximum external diameter depends on
the size of the cable gland or the conduit (see the installation
manual of the Speedwire/Webconnect interface) ☐ Cable type: 100BaseTx, from Cat5 with shielding S-UTP, F-UTP
or higher ☐ Plug type: RJ45 of Cat5, Cat5e, Cat6, Cat6a
Cat7 plugs cannot be used. ☐ Cable length between two nodes: max. 50 m with patch cable,
max. 100 m with installation cable
cross-section: at least 2 x 2 x 0.22 mm² ☐ Cable type: 100BaseTx, from Cat5 with shielding S-UTP, F-UTP
or higher ☐ Plug type: RJ45 of Cat5, Cat5e, Cat6 or Cat6a. Cat7 plugs
cannot be used. ☐ Cable length between two nodes: max. 50 m with patch cable,
max. 100 m with installation cable
6 Connection and Commissioning

6.4 Performing Pin Coding

Pin coding prevents confusion when using multipole connectors, e.g. in the event of removal and later re-insertion of a multipole plug. Using the coded pins, you can be sure of inserting a multipole plug into the correct terminal. Tip: perform pin coding for all multipole connections now, even if you do not wish to use all multipole connections at this point. Then you will not need to perform pin coding later for the multipole connections that you are not currently using.
Code the pins correctly
When selecting the pins to be coded, be sure to code different pins for each terminal and for each pin row.
Installation Manual 29ClusterController-IA-en-15
Page 30
6 Connection and Commissioning
Procedure:
1. Insert one of the coding tabs on the coding element, parallel to the conductor axis, into the pin to be coded.
2. Remove the coding tab from the coding element by snapping it off.
3. On the multipole plug, remove the key from the conductor entry that will receive the coded pin when connected to the ClusterController.
SMA Solar Technology AG

6.5 Preparing Connection Cables for Connection to Multipole Plugs

Always proceed as follows to prepare connection cables for connection to multipole plugs.
1. Strip 40 mm of cable sheath from the end of the connection cable to which the multipole plug is to be attached.
2. Perform the following additional steps for the connection cables for the analog inputs, the analog outputs and the temperature inputs:
• Trim the cable shield of the connection cable to 15 mm.
• Fold the surplus cable shield back over the cable sheath.
Installation ManualClusterController-IA-en-1530
Page 31
SMA Solar Technology AG
6 Connection and Commissioning
• Press the shield clamp onto the cable shield. The cable shield must be clamped under the shield clamp as completely as possible.
• Depending on the number of connection cables, split the wire required for shielding into pieces with a length 40 mm.
• Remove 6 mm of the cable sheath and strip off the insulation by 6 mm at both ends of the insulated conductor.
• Insert the insulated conductor at one end of the wire into the ring terminal lug of the shield clamp and crimp with a crimping tool.
3. Trim unneeded insulated conductors flush with the cable sheath.
4. Strip off the conductor insulation by 6 mm.
☑ The connection cable is prepared for connection
to the multipole plug.
Installation Manual 31ClusterController-IA-en-15
Page 32
6 Connection and Commissioning
SMA Solar Technology AG
6.6 Connecting the ClusterController to the Voltage Supply
Danger to life due to electric shock from touching an ungrounded product
Touching an ungrounded product can cause a lethal electric shock.
• Ensure that the product is integrated in the existing overvoltage protection.
• Ground the enclosure of the product.
Damage to the product due to condensation
If the product is moved from a cold environment to a warm environment, condensation may form in the product.
• When there is a large temperature difference, wait for the product to reach room temperature before connecting to the voltage supply.
Procedure:
To connect the ClusterController to the voltage supply, perform the following actions in the specified order. The exact procedure is described in the following sections.
• Connecting the Grounding Conductor to the ClusterController
• Connecting the Power Supply Unit
Connecting the Grounding Conductor to the ClusterController
Additionally required material (not included in the scope of delivery):
☐ 1 grounding conductor (see Section6.3 "Cable Requirements", page28)
Procedure:
1. Remove 10 mm of the cable sheath from the grounding conductor.
2. Insert the insulated conductors into the ring terminal lug and crimp with a crimping tool.
Installation ManualClusterController-IA-en-1532
Page 33
SMA Solar Technology AG
6 Connection and Commissioning
3. Connect the grounding conductor to the grounding terminal. Observe the position of the terminal (see Section6.1, page25). Observe the order given below and hand-tighten the fastening screw (torque: 0.8Nm):
• Fastening screw
• Split lock washer
• Washer
• Ring terminal lug with grounding conductor
• Washer
• Tooth lock washer
Connecting the Power Supply Unit
Additionally required material (not included in the scope of delivery):
☐ 1 power supply unit (see Section10 "Accessories", page82) ☐ 1 AC connection cable ☐ 1 cable for connecting the power supply unit to the ClusterController (see Section6.3 "Cable
Requirements", page28)
If you are not using the top-hat rail power supply unit available as an accessory for the ClusterController, the power supply unit you are using must meet the requirements detailed below.
Requirements for the power supply unit:
☐ Maximum output current including short circuit: 8A ☐ Maximum output apparent power: 100VA ☐ DC output voltage: 24V ☐ Nominal current: minimum 1.8A
Requirement:
☐ The connection cable must be prepared for connection to the multipole plug (see Section6.5,
page30).
Installation Manual 33ClusterController-IA-en-15
Page 34
6 Connection and Commissioning
Figure 10: Pin assignment for terminal X1
SMA Solar Technology AG
Pin Signal Explanation
1 Not assigned Reserved for future applications 2 24 V Input voltage 24VDC 3 GND Ground
Procedure:
1. Mount the power supply unit (see manual from manufacturer).
2. Connect the connection cable to the power supply unit (see manual from manufacturer). Trim the unused insulated conductors up to the cable sheath and write down the conductor colors.
3. Connect the connection cable to the three-pole plug. Unlock conductor entries 2 and 3 with a screwdriver and insert the insulated conductors into the conductor entries. Observe the pin assignment.
4. Connect the three-pole plug to terminal X1 on the ClusterController.
5. Connect the AC connection cable to the power supply unit (see the manual from manufacturer).
6.
Danger to life due to electric shock
Lethal voltages are present at the connection point of the utility grid.
• Disconnect the connection point from voltage sources and ensure that the connection point is voltage-free.
7. Connect the other end of the AC connection cable to the voltage supply.
8. Connect the connection point to the utility grid.
☑ The power LED ( ) on the ClusterController is glowing red for twoseconds, then it is
permanently glowing green. The status LED ( ) is glowing corresponding to the current device status (see Section7.1,
page66). The ClusterController is ready for operation after a maximum of one minute.
✖ Is the power LED ( ) glowing permanently red, the status LED ( ) glowing yellow or
red and the ClusterController not starting? Possible fault cause: the voltage supply is too low.
• Ensure that the voltage supply is sufficient (see Section9, page78).
Installation ManualClusterController-IA-en-1534
Page 35
SMA Solar Technology AG
• If the problem persists, contact the Service (see Section11, page83).
6 Connection and Commissioning
6.7 Checking and Setting the ClusterController System Time
Before connecting the ClusterController to the Speedwire network and before commissioning the inverters, you must check the ClusterController display to verify that the correct system time is displayed on the ClusterController. If the correct system time is not displayed, you must set the correct system time via the ClusterController user interface. This way, you can avoid inconsistencies in the time settings of the inverters.
Available display languages
The display languages of the ClusterController are German and English. The default language is English. You can only change the display language to German via the ClusterController user interface by selecting German as the user interface language and then logging in.
Additionally required material (not included in the scope of delivery):
☐ 1 network cable (see Section6.3 "Cable Requirements", page28)
Requirements:
☐ The ClusterController must be connected to the voltage supply and be in operation (see
Section6.6, page32).
☐ A computer must be available for access to the user interface of the ClusterController (see
Section2.4, page10).
Procedure:
1. Connect the computer directly to the ClusterController using the network cable. Connect the network cable to the network port X13 or X14 on the ClusterController.
2. Select the display view External communication and read and write down the IP address of the ClusterController from the line IP address. Tip: if you wish to integrate the ClusterController in a static LAN, you will also need the IP address for the network configuration (see Section6.14, page65).
3. Call up the IP address of the ClusterController via the web browser.
☑ The login page opens: ✖ The login page does not open?
Possible error cause: you have not written down the IP address correctly or you have not entered it correctly.
• Enter the correct IP address and confirm the entry with the enter key.
• If the problem persists, read the troubleshooting information(see Section7.2 "Errors in the ClusterController or the Connected Devices", page70).
4. Select the desired language in the upper area of the login page.
Installation Manual 35ClusterController-IA-en-15
Page 36
6 Connection and Commissioning
5. Log in either as User or as Installer with the corresponding default system password for the user group. This makes the language change take effect on the user interface and on the display:
User group Default system password
User 0000 Installer 1111
☑ The user interface opens. ✖ The user interface does not open?
Cause: You have not entered the default system password for the selected user group correctly.
• On the login page, enter the correct default system password for the selected user group and confirm the entry with the enter key.
6. Select the ClusterController in the system tree and select the menu Settings in the device menu.
7. Select the parameter group Device > Time settings.
8. If required, use the drop-down list Standard/daylight saving time conversion on to set automatic conversion between standard and daylight saving time.
9. In the field Set system time, set the current date and time of the system.
10. In the drop-down list Time zone, select the time zone in which the system is located.
11. Select [Save]. ☑ The system time is updated.
12. Select [Logout] in the toolbar.
SMA Solar Technology AG
6.8 Connecting the ClusterController to a Speedwire Network
Interference in data transmission due to unshielded power cables
If unshielded power cables are used, they generate an electromagnetic field during operation which may induce interference in network cables during data transmission.
• When laying network cables, observe the following minimum clearances to unshielded energy cables:
– For installation without separating strip: at least 200 mm – For installation with aluminum separating strip: at least 100 mm – For installation with steel separating strip: at least 50 mm
Do not connect the Speedwire network and the LAN
The Speedwire network is a separate network managed by the ClusterController. If the Speedwire network and the LAN are connected, a disturbance of both networks is likely.
• In order to ensure proper communication, do not connect the Speedwire network and the LAN (the Speedwire bus and the Ethernet bus of the LAN must not be connected to the same network switch, for example).
Installation ManualClusterController-IA-en-1536
Page 37
SMA Solar Technology AG
6 Connection and Commissioning
Observe the configuration of the router and the network switch
For the Speedwire connection, the product uses IP addresses from the Unicast range and also IP addresses from the Multicast range 239/8 (239.0.0.0 to 239.255.255.255).
• When using a router or network switch, ensure that the router and the network switch forward the Multicast telegrams required for the Speedwire connection to all nodes in the Speedwire network (for further information on how to configure the router or network switch, see the manual from the manufacturer).
IGMP protocol version1 must be supported
The product works with multicasts. For correct function of the product, all network components used must support the IGMP protocol, version1 (IGMPv1).
Requirements:
☐ The nodes in the Speedwire network (e. g. inverters) must be cabled in accordance with one
of the possible network topologies (see the node installation manual and the Technical Information "SMASPEEDWIRE FIELDBUS").
☐ If your system uses an Energy Meter to measure the active power feed-in at the grid-
connection point, then the Energy Meter must be connected either to the router or network switch of the Speedwire network or directly to terminal X9 or X10 of the ClusterController, depending on the network topology of the system.
Additionally required material (not included in the scope of delivery):
☐ Depending on the network topology: network cable (see Section6.3 "Cable Requirements",
page28)
Figure 11: Pin assignment for network ports X9, X10, X13 and X14
Pin Designation Explanation
1 TX+ Data Out + 2 TX − Data Out − 3 RX+ Data In + 4 Not assigned Not assigned 5 Not assigned Not assigned 6 RX− Data In − 7 Not assigned Not assigned 8 Not assigned Not assigned
Installation Manual 37ClusterController-IA-en-15
Page 38
6 Connection and Commissioning
SMA Solar Technology AG
Procedure:
1. Connect the ClusterController to the Speedwire network. Take the desired network topology into account:
• When using a preassembled network cable, connect the network cable to network port X9 or X10.
• When using a network cable that is to be assembled by the user, connect the RJ45 connector to the network cable (see the manual from manufacturer) and connect the network cable to network port X9 or X10 on the ClusterController.
2. Write down the terminal assignment on the supplied supplementary sheet.
3. Deactivate the Webconnect function on the inverters after completion of ClusterController commissioning (see the ClusterController user manual).
6.9 Connecting the ClusterController to the LAN
Additionally required material (not included in the scope of delivery):
☐ 1 network cable (see Section6.3 "Cable Requirements", page28)
Figure 12: Pin assignment for network ports X9, X10, X13 and X14
Pin Designation Explanation
1 TX+ Data Out + 2 TX − Data Out − 3 RX+ Data In + 4 Not assigned Not assigned 5 Not assigned Not assigned 6 RX− Data In − 7 Not assigned Not assigned 8 Not assigned Not assigned
High costs possible due to inappropriate Internet tariff
Depending on use, the data volume transferred by the ClusterController via the Internet can be more than 1GB per month. The data volume depends, among other things, on the number of inverters, the frequency of device updates, the frequency of data transfer to SunnyPortal and the use of FTP push.
• SMA recommends using an Internet flat rate.
Installation ManualClusterController-IA-en-1538
Page 39
SMA Solar Technology AG
Different IP address ranges required for Speedwire network and LAN
In order for an unambiguous assignment of the IP addresses in the Speedwire network and in the LAN to be possible from the perspective of the ClusterController, the IP address ranges of both networks must be different. By default, the ClusterController uses address range
172.22/16 (172.22.0.1 to 172.22.255.255) for the Speedwire network.
• Ensure that different IP address ranges are used for the Speedwire network and the LAN.
Observe the configuration of the router and the network switch
For the Speedwire connection, the product uses IP addresses from the Unicast range and also IP addresses from the Multicast range 239/8 (239.0.0.0 to 239.255.255.255).
• When using a router or network switch, ensure that the router and the network switch forward the Multicast telegrams required for the Speedwire connection to all nodes in the Speedwire network (for further information on how to configure the router or network switch, see the manual from the manufacturer).
IGMP protocol version1 must be supported
The product works with multicasts. For correct function of the product, all network components used must support the IGMP protocol, version1 (IGMPv1).
Procedure:
1. Connect the network cable to the ClusterController:
• When using a preassembled network cable, connect the network cable to network port X13 or X14.
• When using a network cable that is to be assembled by the user, connect the two RJ45 connectors to both ends of the network cable (see the manual from manufacturer) and connect the network cable to network port X13 or X14.
2. Connect the other end of the network cable to the desired node in the LAN.
3. Write down the terminal assignment on the supplied supplementary sheet.
6 Connection and Commissioning
6.10 Connecting USB Data Carriers to the ClusterController
In order to save system data or perform an update, you can connect up to two USB data carriers to the ClusterController (for information on updates, see the the ClusterController user manual).
Use of USB hubs not possible
The product does not support USB hubs. You must connect the USB data carrier directly to the desired USB port on the product.
Additionally required material (not included in the scope of delivery):
☐ Up to two USB data carriers, e.g. two USB flash drives (see Section10 "Accessories", page82
)
If you use a USB data carrier other than that offered by SMA as an accessory, the USB data carrier must meet the requirements stated below.
Installation Manual 39ClusterController-IA-en-15
Page 40
6 Connection and Commissioning
Requirements for USB data carriers:
☐ Maximum storage capacity: 2TB ☐ Supported file systems: FAT16 or FAT32
Use of USB hard disks with external power supply is recommended
In the case of USB hard disks with power supply via the USB interface, malfunctions can occur if the connected USB hard disk temporarily has a greater electricity demand than that provided for by the USB2.0 standard.
• To avoid malfunctions as a result of excessive power demand when using USB hard disks, use only USB hard disks with external power supply.
Archival periods:
Depending on the available storage capacity of the USB data carrier and the configuration of your system, the following approximate archival periods for the system data are possible:
Number of connected invert­ers
5 10 years 20 years 10 5 years 10 years 25 2 years 4 years 50 1 year 2 years 75 9 months 18 months
4GB storage capacity 8GB storage capacity
Approximate archival period
SMA Solar Technology AG
Procedure:
1. To protect the USB data carrier against loss, attach the USB data carrier to the eyelets located on the underside of the USB port, for example with a loop attached to the USB data carrier.
2. Connect the USB data carrier to the desired USB port:
• To export system data, connect the USB data carrier to USB port 1.
• To transfer update files to the ClusterController, connect the USB data carrier to USB port
2.
3. If the USB data carrier is permanently inserted into the ClusterController, note the terminal assignment on the supplied supplementary sheet.
4. If the USB data carrier is to be removed from the ClusterController, wait until the data carrier status LED ( ) stops flashing.
6.11 Connecting Sensors to the ClusterController

6.11.1 Connecting the Temperature Sensor

You can connect one outside temperature sensor and one module temperature sensor to the ClusterController. The measured values from the temperature sensors are shown on the display and the user interface of the ClusterController and transmitted to SunnyPortal. In SunnyPortal, the measured values from the module temperature sensor are used to calculate the performanceratio.
Installation ManualClusterController-IA-en-1540
Page 41
SMA Solar Technology AG
6 Connection and Commissioning
Connecting the Outside Temperature Sensor
Additionally required material (not included in the scope of delivery):
☐ 1 outside temperature sensor ☐ 1 connection cable (see Section6.3 "Cable Requirements", page28)
Requirements:
☐ The sensor must be technically suitable for connection to the temperature inputs (see Section9,
page78).
☐ The connection cable must be prepared for connection to the multipole plug (see Section6.5,
page30).
Figure 13: Pin assignment for pin group Temperature input1
Pin Signal Explanation
A1 GND Shield ground A2 I+ Current input A3 V+ Voltage input A4 V− Voltage return A5 I− Current return
Procedure:
1. Connect the connection cable to the outside temperature sensor (see the manual from manufacturer). Trim the unneeded insulated conductors up to the cable shield and note down the conductor colors.
2. For connection to the ClusterController using two-conductor connection technology, perform the following steps:
• On the five-pole plug, unlock conductor entry 1 using a screwdriver and insert the insulated conductor of the wire into the conductor entry.
• On the five-pole plug, unlock conductor entries 3 and 4 using a screwdriver and insert the insulated conductors of the connection cable into the conductor entries. Observe the pin assignment.
• At terminal X7 in pin row A, place a bridge between pin2 and pin3 and between pin4 and pin5.
Installation Manual 41ClusterController-IA-en-15
Page 42
6 Connection and Commissioning
SMA Solar Technology AG
3. For connection to the ClusterController using four-conductor connection technology, perform the following steps:
• On the five-pole plug, unlock conductor entry 1 using a screwdriver and insert the insulated conductor of the wire into the conductor entry.
• On the five-pole plug, unlock conductor entries 2, 3, 4 and 5 using a screwdriver and insert the insulated conductors of the connection cable into the conductor entries. Observe the pin assignment.
4. Insert the five-pole plug into pin row A in terminal X7.
5. On the connection cable, mark the terminal and the pin row to which the connection cable is assigned. Use the supplied cable tie with caption field.
6. Write down the terminal assignment on the supplied supplementary sheet.
Connecting the Module Temperature Sensor
Additionally required accessories (not included in scope of delivery):
☐ 1 module temperature sensor ☐ 1 connection cable (see Section6.3, page28)
Requirements:
☐ The sensor must be technically suitable for connection to the temperature inputs (see Section9,
page78).
☐ The connection cable must be prepared for connection to the multipole plug (see Section6.5,
page30).
Figure 14: Pin assignment for pin group Temperature input2
Pin Signal Explanation
B1 GND Shield ground B2 I+ Current input B3 V+ Voltage input B4 V− Voltage return B5 I− Current return
Installation ManualClusterController-IA-en-1542
Page 43
SMA Solar Technology AG
6 Connection and Commissioning
Procedure:
1. Connect the connection cable to the module temperature sensor (see the manual from manufacturer). Trim the unneeded insulated conductors up to the cable shield and note down the conductor colors.
2. For connection to the ClusterController using two-conductor connection technology, perform the following steps:
• On the five-pole plug, unlock conductor entry 1 using a screwdriver and insert the insulated conductor of the wire into the conductor entry.
• On the five-pole plug, unlock conductor entries 3 and 4 using a screwdriver and insert the insulated conductors of the connection cable into the conductor entries. Observe the pin assignment.
• At terminal X7 in pin rowB, place a bridge between pin2 and pin3 and between pin4 and pin5.
3. For connection to the ClusterController using four-conductor connection technology, perform the following steps:
• On the five-pole plug, unlock conductor entry 1 using a screwdriver and insert the insulated conductor of the wire into the conductor entry.
• On the five-pole plug, unlock conductor entries 2, 3, 4 and 5 using a screwdriver and insert the insulated conductors of the connection cable into the conductor entries. Observe the pin assignment.
4. Insert the five-pole plug into pin row B in terminal X7.
5. On the connection cable, mark the terminal and the pin row to which the connection cable is assigned. Use the supplied cable tie with caption field.
6. Write down the terminal assignment on the supplied supplementary sheet.

6.11.2 Connecting an Irradiation Sensor

You can connect one irradiation sensor or pyranometer to the ClusterController. The measured value from the irradiation sensor or pyranometer is shown on the display and the user interface of the ClusterController and transmitted to SunnyPortal. In SunnyPortal, the measured values are used to calculate the performanceratio.
Additionally required material (not included in the scope of delivery):
☐ 1 irradiation sensor ☐ 1 connection cable (see Section6.3 "Cable Requirements", page28)
Requirements:
☐ The sensor must be technically suitable for connection to the analog inputs (see Section9,
page78).
☐ The connection cable must be prepared for connection to the multipole plug (see Section6.5,
page30).
Installation Manual 43ClusterController-IA-en-15
Page 44
6 Connection and Commissioning
Figure 15: Pin assignment for pin group Analog current input1
SMA Solar Technology AG
Pin Signal Explanation
A1 Not assigned Reserved for future applications A2 I+ Current input A3 I− Current return A4 GND Shield ground
Procedure:
1. Connect the connection cable to the irradiation sensor (see the manual from manufacturer). Trim the unneeded insulated conductors up to the cable shield and note down the conductor colors.
2. Connect the connection cable to the eight-pole plug:
• Unlock conductor entry4 with a screwdriver and insert the insulated conductor of the wire into the conductor entry.
• Unlock conductor entries 2 and 3 with a screwdriver and insert the insulated conductors of the connection cable into the conductor entries. Observe the pin assignment.
3. Insert the eight-pole plug into pin row A in terminal X8.
4. On the connection cable, mark the terminal and the pin row to which the connection cable is assigned. Use the supplied cable tie with caption field.
5. Write down the terminal assignment on the supplied supplementary sheet.
6. Adjust the characteristic curve of the irradiation sensor or pyranometer via the ClusterController user interface (see the ClusterController user manual). The measured irradiation values can then be shown on the display and the ClusterController user interface.

6.11.3 Connecting Additional Sensors

Depending on whether you are using an irradiation sensor (see Section6.11.2, page43), you can connect a maximum of three sensors to the analog current inputs and one sensor to the analog voltage input on terminal X8 on the ClusterController.
Installation ManualClusterController-IA-en-1544
Page 45
SMA Solar Technology AG
6 Connection and Commissioning
Display of measured values from pin group Analog voltage input4
If no sensor is connected to the pin group Analog voltage input4, a measured value for this pin group of up to 2.2V will nevertheless be shown on the display and the user interface of the ClusterController.
• In order for a measured value of 0V to be displayed for the pin group Analog voltage input4 when it is not connected, place a jumper wire between pins B5 and B7 in terminal X8.
Connecting a Sensor to an Analog Current Input
Additionally required material (not included in the scope of delivery):
☐ Up to three sensors ☐ Up to three connection cables (see Section6.3 "Cable Requirements", page28)
Requirements:
☐ The sensor must be technically suitable for connection to the analog inputs (see Section9,
page78).
☐ The connection cable must be prepared for connection to the multipole plug (see Section6.5,
page30).
Figure 16: Pin assignment for the pin groups Analog current input1, Analog current input2 and Analog
current input3
Pin group Pin Signal Explanation
Analog current input1 A1 Not assigned Reserved for future applications
A2 I+ Current input A3 I− Current return A4 GND Shield ground
Installation Manual 45ClusterController-IA-en-15
Page 46
6 Connection and Commissioning
SMA Solar Technology AG
Pin group Pin Signal Explanation
Analog current input2 A5 Not assigned Reserved for future applications
A6 I+ Current input A7 I− Current return A8 GND Shield ground
Analog current input3 B1 Not assigned Reserved for future applications
B2 I+ Current input B3 I− Current return B4 GND Shield ground
Procedure:
1. Connect the connection cable to the sensor (see the manual from manufacturer). Trim the unneeded insulated conductors up to the cable shield and note down the conductor colors.
2. For connection to the pin group Analog current input1, perform the following steps:
• Unlock conductor entry4 with a screwdriver and insert the insulated conductor of the wire into the conductor entry.
• Unlock conductor entries 2 and 3 with a screwdriver and insert the insulated conductors of the connection cable into the conductor entries. Observe the pin assignment.
• Insert the eight-pole plug into pin row A in terminal X8.
3. For connection to the pin group Analog current input2, perform the following steps:
• Unlock conductor entry8 with a screwdriver and insert the insulated conductor of the wire into the conductor entry.
• Unlock conductor entries 6 and 7 with a screwdriver and insert the insulated conductors of the connection cable into the conductor entries. Observe the pin assignment.
• Insert the eight-pole plug into pin row A in terminal X8.
4. For connection to the pin group Analog current input3, perform the following steps:
• Unlock conductor entry4 with a screwdriver and insert the insulated conductor of the wire into the conductor entry.
• Unlock conductor entries 2 and 3 with a screwdriver and insert the insulated conductors of the connection cable into the conductor entries. Observe the pin assignment.
• Insert the eight-pole plug into pin row B in terminal X8.
5. On the connection cable, mark the terminal and the pin row to which the connection cable is assigned. Use the supplied cable tie with caption field.
6. Write down the terminal assignment on the supplied supplementary sheet.
Connecting a Sensor to the Analog Voltage Input
Additionally required material (not included in the scope of delivery):
☐ 1 sensor ☐ 1 connection cable (see Section6.3 "Cable Requirements", page28)
Installation ManualClusterController-IA-en-1546
Page 47
SMA Solar Technology AG
Requirements:
☐ The sensor must be technically suitable for connection to the analog inputs (see Section9,
page78).
☐ The connection cable must be prepared for connection to the multipole plug (see Section6.5,
page30).
Figure 17: Pin assignment for pin group Analog voltage input4
Pin Signal Explanation
B5 V+ Voltage input B6 Not assigned Reserved for future applications B7 V− Voltage return B8 GND Shield ground
6 Connection and Commissioning
Procedure:
1. Connect the connection cable to the sensor (see the manual from manufacturer). Trim the unneeded insulated conductors up to the cable shield and note down the conductor colors.
2. Connect the connection cable to the eight-pole plug:
• Unlock conductor entry8 with a screwdriver and insert the insulated conductor of the wire into the conductor entry.
• Unlock conductor entries 5 and 7 with a screwdriver and insert the insulated conductors of the connection cable into the conductor entries. Observe the pin assignment.
3. Insert the eight-pole plug into pin row B in terminal X8.
4. On the connection cable, mark the terminal and the pin row to which the connection cable is assigned. Use the supplied cable tie with caption field.
5. Write down the terminal assignment on the supplied supplementary sheet.

6.12 Connections for Grid Management Services

6.12.1 Options for Implementing Grid Management Service Setpoints

You can have the ClusterController implement the grid management service setpoints by using open-loop or closed-loop control.
Installation Manual 47ClusterController-IA-en-15
Page 48
6 Connection and Commissioning
In the event that the ClusterController evaluates a setpoint as invalid or does not receive a setpoint within a configurable interval, you can make additional settings for the fallback.
Configure the grid management services via the ClusterController user interface (see the ClusterController user manual).
SMA Solar Technology AG
Open-loop control
For ClusterController systems without self-consumption and with direct limitation of active power feed-in, the operating mode Open-loop control is used. In this operating mode, the ClusterController can receive the grid management service setpoints from three different types of signal source. The different types of signal source can be combined so that, for example, the setpoints for the active power limitation can be received as digital signals and the reactive power setpoints can be received as analog signals:
Type of setpoint signal Explanation
Digital signals The setpoints are transmitted to the ClusterController as
digital signals in the form of binary values. Up to four re­lay contacts can be used for the active power limitation and the reactive power setpoint.
Analog signals The setpoints are transmitted to the ClusterController as
analog current signals. Current signals from 0mA to 20mA can be transmitted for the active power limitation and the reactive power setpoint.
Setpoint signal via Modbus client The setpoints are transmitted via a Modbus client to the
network port X13 or X14 on the ClusterController (for in­formation on Modbus configuration, see the ClusterCon­troller user manual).
Closed-loop control
For ClusterController systems with self-consumption, the operating mode Closed-loop control is used. In this operating mode, you can limit the active power fed in by the system at the grid­connection point to a fixed percentage value. In addition to the total system power, the ClusterController needs the measured actual value of the active power fed in at the grid-connection point.

6.12.2 Digital Setpoint Signal

6.12.2.1 Connection Options
You have two options for each pin group on terminal X4:
• Connection of a signal source with potential-free relay contact
or
• Connection of a 24V signal source with digital output signals
Installation ManualClusterController-IA-en-1548
Page 49
SMA Solar Technology AG
6 Connection and Commissioning
Connection of a signal source with potential-free relay contact
Figure 18: Connection of a signal source with potential-free relay contact (example)
Connection of a 24V Signal Source with Digital Output Signals
Figure 19: Connection of a 24 V signal source with digital output signals (example)
6.12.2.2 Connecting a Signal Source to a Digital Input for Active Power Limitation
Digital signals for active power limitation can be transmitted to up to four pin groups at terminal X4 on the ClusterController. A ripple control receiver or a remote terminal unit can be used as a digital signal source, for example.
Additionally required material (not included in the scope of delivery):
☐ Up to four digital signal sources ☐ Connection cable (see Section6.3 "Cable Requirements", page28)
Requirements:
☐ The signal source must be technically suitable for connection to the digital inputs (see
Section9, page78).
☐ The connection cable must be prepared for connection to the multipole plug (see Section6.5,
page30).
Installation Manual 49ClusterController-IA-en-15
Page 50
6 Connection and Commissioning
Figure 20: Pin assignment for pin groups on terminal X4
SMA Solar Technology AG
Pin group Pin Pin assignment Explanation
Digital input1 Signal 1 of 4 for active power
limitation
Digital input2 Signal 2 of 4 for active power
limitation
Digital input3 Signal 3 of 4 for active power
limitation
Digital input4 Signal 4 of 4 for active power
limitation
A1 24 V Voltage supply output A2 IN Input A3 GND Reference potential A4 24 V Voltage supply output A5 IN Input A6 GND Reference potential B1 24 V Voltage supply output B2 IN Input B3 GND Reference potential B4 24 V Voltage supply output B5 IN Input B6 GND Reference potential
Danger to life due to electric shock caused by incorrect connection of the ripple control receiver
Incorrect connection of the ripple control receiver can result in grid voltage on the ClusterController enclosure.
• Do not connect the insulated conductors of the connection cable to the line conductors of the ripple control receiver.
• When connecting, ensure that no bridge is being used in the ripple control receiver.
Installation ManualClusterController-IA-en-1550
Page 51
SMA Solar Technology AG
Procedure:
1. Connect the connection cable to the digital signal source (see the manual from manufacturer). Trim the unneeded insulated conductors up to the cable shield and note down the conductor colors.
2. Connect the connection cable to the six-pole plug:
• Depending on the digital signal source and the pin assignment in terminal X4, identify the conductor entries that are required for connecting the connection cable. The voltage supply (24V) and the reference potential (GND) only need to be connected once for each signal source.
• Release the required conductor entries using a screwdriver and insert the insulated conductors into the conductor entries. Observe the pin assignment.
3. Connect the six-pole plug to terminal X4. Observe the pin coding.
4. On the connection cable, mark the terminal and the pin row to which the connection cable is assigned. Use the supplied cable tie with caption field.
5. Write down the terminal assignment on the supplied supplementary sheet.
6 Connection and Commissioning
6.12.2.3 Connecting a Signal Source to a Digital Input for Reactive Power Setpoint
Digital signals for reactive power setpoints can be transmitted to up to four pin groups at terminal X5 on the ClusterController. A ripple control receiver or a remote terminal unit can be used as a digital signal source, for example.
Additionally required material (not included in the scope of delivery):
☐ Up to four digital signal sources ☐ Connection cable (see Section6.3 "Cable Requirements", page28)
Requirements:
☐ The signal source must be technically suitable for connection to the digital inputs (see
Section9, page78).
☐ The connection cable must be prepared for connection to the multipole plug (see Section6.5,
page30).
Installation Manual 51ClusterController-IA-en-15
Page 52
6 Connection and Commissioning
Figure 21: Pin assignment for pin groups on terminal X5
SMA Solar Technology AG
Pin group Pin Pin assignment Explanation
Digital input5 Signal 1 of 4 for reactive power
setpoint
Digital input6 Signal 2 of 4 for reactive power
setpoint
Digital input7 Signal 3 of 4 for reactive power
setpoint
Digital input8 Signal 4 of 4 for reactive power
setpoint
A1 24 V Voltage supply output A2 IN Input A3 GND Reference potential A4 24 V Voltage supply output A5 IN Input A6 GND Reference potential B1 24 V Voltage supply output B2 IN Input B3 GND Reference potential B4 24 V Voltage supply output B5 IN Input B6 GND Reference potential
Danger to life due to electric shock caused by incorrect connection of the ripple control receiver
Incorrect connection of the ripple control receiver can result in grid voltage on the ClusterController enclosure.
• Do not connect the insulated conductors of the connection cable to the line conductors of the ripple control receiver.
• When connecting, ensure that no bridge is being used in the ripple control receiver.
Installation ManualClusterController-IA-en-1552
Page 53
SMA Solar Technology AG
6 Connection and Commissioning
Procedure:
1. Connect the connection cable to the digital signal source (see the manual from manufacturer). Trim the unneeded insulated conductors up to the cable shield and note down the conductor colors.
2. Connect the connection cable to the six-pole plug:
• Depending on the digital signal source and the pin assignment in terminal X5, identify the conductor entries that are required for connecting the connection cable. The voltage supply (24V) and the reference potential (GND) only need to be connected once for each signal source.
• Release the required conductor entries using a screwdriver and insert the insulated conductors into the conductor entries. Observe the pin assignment.
3. Connect the six-pole plug to terminal X5. Observe the pin coding.
4. On the connection cable, mark the terminal and the pin row to which the connection cable is assigned. Use the supplied cable tie with caption field.
5. Write down the terminal assignment on the supplied supplementary sheet.
6.12.2.4 Digital Signal Setpoint when Using Multiple ClusterControllers
To implement digital setpoints from the grid operator, you can connect any number of ClusterControllers in parallel to one digital signal source.
Additionally required material (not included in the scope of delivery):
☐ Power supply unit (quantity depends on the number of ClusterControllers to be connected)
Requirements for the power supply unit:
☐ DC output voltage: 24V ☐ The power supply unit must supply at least 10mA per input signal for the ClusterControllers.
Installation Manual 53ClusterController-IA-en-15
Page 54
6 Connection and Commissioning
Figure 22: Transmission of digital signals for active power limitation to two ClusterControllers via relays K1 and K2 of a ripple control receiver (example)
SMA Solar Technology AG

6.12.3 Analog Setpoint Signal

6.12.3.1 Connecting a Signal Source to an Analog Input for Active Power Limitation
Analog signals for active power limitation are transmitted to the pin group Analog current input2 in terminal X8 on the ClusterController. A remote terminal unit can be used as an analog signal source, for example.
Additionally required material (not included in the scope of delivery):
☐ 1 analog signal source ☐ Connection cable (see Section6.3 "Cable Requirements", page28)
Requirements:
☐ The signal source must be technically suitable for connection to the analog inputs (see
Section9, page78).
☐ The connection cable must be prepared for connection to the multipole plug (see Section6.5,
page30).
Installation ManualClusterController-IA-en-1554
Page 55
SMA Solar Technology AG
Figure 23: Pin assignment for pin group Analog current input2
6 Connection and Commissioning
Pin Signal Explanation
A5 Not assigned Reserved for future applications A6 I+ Current input A7 I− Current return A8 GND Shield ground
Procedure:
1. Connect the connection cable to the analog signal source (see the manual from manufacturer). Trim the unneeded insulated conductors up to the cable shield and note down the conductor colors.
2. Connect the connection cable to the eight-pole plug:
• Unlock conductor entry8 with a screwdriver and insert the insulated conductor of the wire into the conductor entry.
• Unlock conductor entries 6 and 7 with a screwdriver and insert the insulated conductors of the connection cable into the conductor entries. Observe the pin assignment.
3. Insert the eight-pole plug into pin row A in terminal X8.
4. On the connection cable, mark the terminal and the pin row to which the connection cable is assigned. Use the supplied cable tie with caption field.
5. Write down the terminal assignment on the supplied supplementary sheet.
6.12.3.2 Connecting a Signal Source to an Analog Input for Reactive Power Setpoint
Analog signals for the reactive power setpoint are transmitted to the pin group Analog current input3 in terminal X8 on the ClusterController. A remote terminal unit can be used as an analog
signal source, for example.
Additionally required material (not included in the scope of delivery):
☐ 1 analog signal source ☐ Connection cable (see Section6.3 "Cable Requirements", page28)
Installation Manual 55ClusterController-IA-en-15
Page 56
6 Connection and Commissioning
SMA Solar Technology AG
Requirements:
☐ The signal source must be technically suitable for connection to the analog inputs (see
Section9, page78).
☐ The connection cable must be prepared for connection to the multipole plug (see Section6.5,
page30).
Figure 24: Pin assignment for pin group Analog current input3
Pin Signal Explanation
B1 Not assigned Reserved for future applications B2 I+ Current input B3 I− Current return B4 GND Shield ground
Procedure:
1. Connect the connection cable to the analog signal source (see the manual from manufacturer). Trim the unneeded insulated conductors up to the cable shield and note down the conductor colors.
2. Connect the connection cable to the eight-pole plug:
• Unlock conductor entry4 with a screwdriver and insert the insulated conductor of the wire into the conductor entry.
• Unlock conductor entries 2 and 3 with a screwdriver and insert the insulated conductors of the connection cable into the conductor entries. Observe the pin assignment.
3. Insert the eight-pole plug into pin row B in terminal X8.
4. On the connection cable, mark the terminal and the pin row to which the connection cable is assigned. Use the supplied cable tie with caption field.
5. Write down the terminal assignment on the supplied supplementary sheet.
6.12.3.3 Analog Setpoint Signal when Using Multiple ClusterControllers
To implement analog setpoints from the grid operator when using multiple ClusterControllers, you can use isolation amplifiers to duplicate the analog current signals. By switching the isolation amplifiers in series, the analog current signals can be transferred to any number of ClusterControllers.
Installation ManualClusterController-IA-en-1556
Page 57
SMA Solar Technology AG
Figure 25: Transmission of analog current signals for active power limitation to three ClusterControllers via isolation amplifiers (example)
6 Connection and Commissioning

6.12.4 Setpoint via Modbus Client

Requirements:
☐ The ClusterController and the Modbus client must be located in the same LAN. ☐ Commissioning of the ClusterController must be completed.
In order to receive the grid operator setpoints via a Modbus client, you must configure the Modbus via the ClusterController user interface after completing commissioning (see the ClusterController user manual).

6.12.5 Feedback of the Cluster Controller

6.12.5.1 Feedback Options
The Cluster Controller has three digital outputs (terminal X2) and three analog current outputs (terminal X6) that offer various feedback options. Using these outputs, you can give the grid operator feedback, for example, if and which specifications for the grid management services are currently implemented in the system. You can also use the outputs to be informed about the status of the system. Which feedback options were set at the factory for terminals X2 and X6 and their pin groups, is described in a previous section (see Section6.2, page26). The feedback options that you can choose from can be found in the menu Settings on the user interface of the ClusterController.
Installation Manual 57ClusterController-IA-en-15
Page 58
6 Connection and Commissioning
SMA Solar Technology AG
6.12.5.2 Connecting a Remote Terminal for Feedback via Digital Signal
Using suitable remote terminals (e.g. optical or acoustic signal generators), the status of the system can be fed back to you via the pin groups Digital output 1, Digital output 2, and Digital output 3 of the X2 terminal. Which feedback options were set at the factory for terminal X2 and its pin groups, is described in a previous section (see Section6.2, page26). The feedback options that you can choose from can be found in the menu Settings on the user interface of the ClusterController.
Observe the maximum load capacity of the relay contacts
The relay contacts may be loaded with a maximum switching power of 30W and a maximum voltage of 48VDC.
Requirements:
☐ The remote terminal must be technically suitable for connection to the digital output (see
Section9, page78).
☐ The connection cable must be prepared for connection to the multipole plug (see Section6.5,
page30).
Figure 26: Pin assignment for the pin groups Digital output 1, Digital output 2, and Digital output 3
Pin group Relay Pin Signal Explanation
Digital output1 A A1 NC Back contact
A2 CO Change-over con-
tact
A3 NO Front contact
Digital output2 B A4 NC Back contact
A5 CO Change-over con-
tact
A6 NO Front contact
Installation ManualClusterController-IA-en-1558
Page 59
SMA Solar Technology AG
6 Connection and Commissioning
Pin group Relay Pin Signal Explanation
Digital output3 C B1 NC Back contact
B2 CO Change-over con-
tact
B3 NO Front contact
Procedure:
1. Connect the connection cable to the remote terminal (see the manual from manufacturer). Trim the unneeded insulated conductors up to the cable shield and note down the conductor colors.
2. Connect the connection cable to the six-pole plug:
• Depending on the remote terminal and the pin assignment of the pin group, identify the conductor entries that are required for connecting the connection cable.
• Release the required conductor entries using a screwdriver and insert the insulated conductors into the conductor entries. Observe the pin assignment.
3. Insert the six-pole plug at terminal X2 into pin row A or B.
4. On the connection cable, mark the terminal and the pin row to which the connection cable is assigned. Use the supplied cable tie with caption field.
5. Write down the terminal assignment on the supplied supplementary sheet.
6.12.5.3 Connecting a Remote Terminal for Feedback via Analog Signal
Via the pin groups Analog current output 1, Analog current output 2, and Analog current output 3 of terminal X6 you can give the grid operator feedback, for example, if and which
specifications for the grid management services are currently implemented in the system. Which feedback options were set at the factory for terminal X6 and its pin groups, is described in a previous section (see Section6.2, page26). The feedback options that you can choose from can be found in the menu Settings on the user interface of the ClusterController.
Requirements:
☐ The remote terminal must be technically suitable for connection to the analog outputs (see
Section9, page78).
☐ The connection cable must be prepared for connection to the multipole plug (see Section6.5,
page30).
Installation Manual 59ClusterController-IA-en-15
Page 60
6 Connection and Commissioning
Figure 27: Pin assignment for the pin groups Analog current output1, Analog current output2 and
Analog current output3
SMA Solar Technology AG
Pin group Pin Signal Explanation
Analog current output1 A1 I+ Current output
A2 I− Current return A3 GND Shield ground
Analog current output2 A4 I+ Current output
A5 I− Current return A6 GND Shield ground
Analog current output3 B1 I+ Current output
B2 I− Current return B3 GND Shield ground
Example: Interpretation of the signal strength as a percentage value of the active power limitation
The strength of the feedback signal corresponds to the percentage value to which the active power of the inverters in the system is currently limited.
Installation ManualClusterController-IA-en-1560
Page 61
SMA Solar Technology AG
Figure 28: Interpretation of the signal strength as a percentage value of the active power limitation in relation to the inverter parameter Currently set active power limit or Pmax
6 Connection and Commissioning
Example: Interpretation of signal strength as a reactive power setpoint value
Depending on the value of the reactive power setpoint that was selected via the user interface (see the ClusterController user manual), the strength of the feedback signal corresponds either to the percentage value for the reactive power setpoint or to the latest displacement power factor cosφ sent to the inverters in the system.
Figure 29: Interpretation of the signal strength as a percentage value of the reactive power setpoint in relation to the inverter parameter Currently set active power limit or Pmax
Installation Manual 61ClusterController-IA-en-15
Page 62
6 Connection and Commissioning
Figure 30: Interpretation of the signal strength as displacement power factor cosφ
SMA Solar Technology AG
Procedure:
1. Connect the connection cable to the remote terminal (see the manual from manufacturer). Trim the unneeded insulated conductors up to the cable shield and note down the conductor colors.
2. When using the pin group Analog current output3, perform the following steps to connect the connection cable to the six-pole plug:
• Unlock conductor entry3 with a screwdriver and insert the insulated conductor of the wire into the conductor entry.
• Depending on the remote terminal and the pin assignment for the pin group Analog current output1, identify the conductor entries that are required for connecting the connection cable.
• Release the required conductor entries using a screwdriver and insert the insulated conductors into the conductor entries. Observe the pin assignment.
3. When using the pin group Analog current output2, perform the following steps to connect the connection cable to the six-pole plug:
• Unlock conductor entry6 with a screwdriver and insert the insulated conductor of the wire into the conductor entry.
• Depending on the remote terminal and the pin assignment for the pin group Analog current output2, identify the conductor entries that are required for connecting the connection cable.
• Release the required conductor entries using a screwdriver and insert the insulated conductors into the conductor entries. Observe the pin assignment.
4. When using the pin group Analog current output3, perform the following steps to connect the connection cable to the six-pole plug:
• Unlock conductor entry3 with a screwdriver and insert the insulated conductor of the wire into the conductor entry.
Installation ManualClusterController-IA-en-1562
Page 63
SMA Solar Technology AG
6 Connection and Commissioning
• Depending on the remote terminal and the pin assignment for the pin group Analog current output3, identify the conductor entries that are required for connecting the connection cable.
• Release the required conductor entries using a screwdriver and insert the insulated conductors into the conductor entries. Observe the pin assignment.
5. Insert the six-pole plug into the appropriate pin row in terminal X6:
• When using the pin group Analog current output1 or Analog current output2, insert the six-pole plug into pin row A.
• When using the pin group Analog current output3, insert the six-pole plug into pin row B.
6. On the connection cable, mark the terminal and the pin row to which the connection cable is assigned. Use the supplied cable tie with caption field.
7. Write down the terminal assignment on the supplied supplementary sheet.
6.12.5.4 Feedback When Using Multiple ClusterControllers
Feedback via Digital Signal
When using multiple ClusterControllers, you have two options for feedback on grid operator setpoints via digital signal:
• Connect one remote terminal to the digital output of each ClusterController (see Section6.12.5.2, page58)
or
• Switch the digital outputs of several ClusterControllers in series.
Switching digital outputs of several ClusterControllers in series:
If you switch the digital outputs of several ClusterControllers in series, feedback on an activated active power limitation only occurs if all ClusterControllers in the series acknowledge the active power limitation.
Figure 31: Series connection of the digital outputs of three ClusterControllers for feedback on grid operator setpoints for active power limitation (example)
Installation Manual 63ClusterController-IA-en-15
Page 64
6 Connection and Commissioning
SMA Solar Technology AG
Feedback via analog signal
When using multiple ClusterControllers, you must connect one remote terminal to the analog current outputs of each ClusterController (see Section6.12.5.3, page59).

6.13 Checking the Connections via the Display

You can use the ClusterController display to check whether the connections have been made correctly and whether all inverters, sensors and remote terminals have been detected by the ClusterController. The content of the display views takes one or two seconds to update. For technical reasons, presentation on the display depends on the ambient temperature and may be correspondingly delayed in the event of low ambient temperature.
Procedure:
1. Select the display view System status.
2. Check whether the correct number of connected inverters is displayed in the line Number of devices. If the correct number of connected inverters is not displayed, ensure that all inverters are connected correctly (see Section7.2, page70).
3. When using digital inputs, select the display view Digital inputs.
4. Check whether the expected binary values are displayed in the lines Digital input group1 and Digital input group2. If the expected binary values are not displayed, ensure that the digital signal source is correctly connected (see Section6.12.2, page48).
5. When using the analog inputs, select the display view Analog inputs.
6. If an analog signal source or a sensor is connected, check whether a current signal is displayed in the lines Analog current input1, Analog current input2 or Analog current input3. If no current signal is displayed, ensure that the analog signal source is correctly connected (see Section6.12.3, page54) or the sensor is correctly connected (see Section6.11.3, page44).
7. If a sensor is connected to the pin group Analog voltage input4, check whether a measured value is displayed in the line Analog voltage input4. If no measured value is displayed, ensure that the sensor is connected correctly (see Section6.11.3, page44).
8. If an irradiation sensor or a temperature sensor is connected, select the display view Meteorology.
9. Check whether measured values are displayed for each connected sensor. If no measured values are displayed for the connected temperature sensor, ensure that the temperature sensor is correctly connected (see Section6.11.1, page40). If no measured values are displayed for the connected irradiation sensor, either the characteristic curve of the irradiation sensor is not configured or the irradiation sensor is not correctly connected.
• Ensure that the characteristic curve of the irradiation sensor is configured (see the ClusterController user manual).
• Ensure that the irradiation sensor is correctly connected (see Section6.11.3, page44).
Installation ManualClusterController-IA-en-1564
Page 65
SMA Solar Technology AG
6 Connection and Commissioning

6.14 Configuring a Static LAN

You can configure the ClusterController and the inverters in the system for a static LAN (see the ClusterController user manual). The ClusterController and the inverters are configured for automatic address allocation via DHCP by default.

6.15 Setting Up a Modbus Data Connection

Additionally required material (not included in the scope of delivery):
☐ Up to twoModbus clients
Requirements:
☐ The ClusterController and the Modbus client must be located in the same LAN (see
Section6.9, page38).
☐ Commissioning of the ClusterController must be completed.
Set up the Modbus data connection via the ClusterController user interface (see the ClusterController user manual) and the Modbus client (see manual from manufacturer). For further information on possible Modbus settings on the ClusterController, see the Technical Description "SMACLUSTERCONTROLLER Modbus® Interface".
Installation Manual 65ClusterController-IA-en-15
Page 66

7 Troubleshooting

SMA Solar Technology AG
7 Troubleshooting

7.1 LED States

7.1.1 Operation LEDs

Configuration of the Status LED ( ):
The status LED can display the following statuses:
• Status of the ClusterController
• Status of the connected inverters
• Status of the system communication
• Status of the grid management services
In this document, the only states described below are those that the status LED can adopt during commissioning (for a complete description of the states, see the ClusterController user manual).
If the status LED is not glowing green after commissioning, refer also to the event log of the ClusterController to determine the precise cause of the error. The details of each error are logged in the event log (see the ClusterController user manual).
LED Status Cause and corrective measure
All off The ClusterController is not connected to the voltage
supply.
Corrective measures:
• Connect the ClusterController to the voltage supply (see Section6.13, page64).
The voltage supply is reverse-connected or the power supply unit is defective.
Corrective measures:
• Ensure that the voltage supply is correctly connected (see Section6.13, page64).
• If the voltage supply is connected correctly, replace the power supply unit.
Power ( ) and
Status ( )
Power ( )
Power glowing red, status glow­ing yellow or red
glowing green The start procedure is complete. The ClusterCon-
The voltage supply is too low.
Corrective measures:
• Ensure that the connected voltage supply is sufficient (see Section6.13, page64).
• If the problem persists, contact the Service (see Section11, page83).
troller is ready for operation.
Installation ManualClusterController-IA-en-1566
Page 67
SMA Solar Technology AG
LED Status Cause and corrective measure
Status ( )
glowing green Normal operation glowing yellow
At least one device has the status Warning.
Corrective measures:
• Check the ClusterController event log (see the ClusterController user manual).
• Refer to the device documentation.
glowing red
At least one device has the status Error.
Corrective measures:
• Check the ClusterController event log (see the ClusterController user manual).
• Refer to the device documentation.
The SD memory card in the ClusterController may be defective.
Corrective measures:
• Check the ClusterController event log (see the ClusterController user manual).
• If the SD memory card is defective, contact Service (see Section11, page83).
flashing red The ClusterController could not start correctly. A sys-
tem error has occurred.
Corrective measures:
• Contact the Service (see Section11, page83).
7 Troubleshooting
Installation Manual 67ClusterController-IA-en-15
Page 68
7 Troubleshooting
SMA Solar Technology AG
LED Status Cause and corrective measure
Data carrier status ( )
off The ClusterController is starting and no information is
yet available for data export or for the USB data car­rier.
Corrective measures:
• Wait until the ClusterController has completed the start process and is ready for operation. Once the start process is complete, the power
LED ( ) will glow green.
No USB data carrier was detected. It is possible that no USB data carrier is connected or the USB data carrier is not compatible.
Corrective measures:
• Ensure that a compatible USB data carrier is connected (see Section9, page78).
glowing green The USB data carrier is compatible. The free storage
capacity is above10%.
glowing yellow
The USB data carrier connected to USB port 1 is compatible but the free storage capacity is no more than 10%.
Corrective measures:
• Delete files that are no longer required from the USB data carrier.
or
• Replace the USB data carrier with a USB data carrier that has sufficient free storage capacity.
Data carrier status ( )
glowing red
The USB data carrier connected to USB port 1 is full or write-protected.
Corrective measures:
• If the USB data carrier is full, replace the USB data carrier.
• If the USB data carrier is write-protected, remove the write protection or use a USB data carrier without write protection.
flashing green or yellow or red
Write or read accesses are currently being per­formed on the USB data carrier.
Corrective measures:
• Only remove the USB data carrier once the data carrier status LED is no longer flashing.
Installation ManualClusterController-IA-en-1568
Page 69
SMA Solar Technology AG

7.1.2 Network Port LEDs

LED Status Cause and corrective measure
Link/Activity (green)
Speed (yellow) Off Network connection established.
Off No network connection established.
The ClusterController is not connected to the voltage sup­ply.
Corrective measures:
• Connect the ClusterController to the voltage supply (see Section6.6, page32).
No network connection established. The network cable is not correctly connected to the Clus-
terController, the router or the network switch.
Corrective measures:
• Ensure that the network cables are connected correctly (see Section6.9, page38).
No network connection established. One or more network components, network cables or con-
nectors are defective or damaged.
Corrective measures:
• Replace the defective or damaged network components, network cables or connectors.
flashing Network connection established.
Data is being sent or received.
The data transfer rate is up to 10Mbit/s.
on Network connection established.
The data transfer rate is up to 100Mbit/s.
7 Troubleshooting
Installation Manual 69ClusterController-IA-en-15
Page 70
7 Troubleshooting
SMA Solar Technology AG
7.2 Errors in the ClusterController or the Connected Devices
General information
Problem Cause and corrective measure
The ClusterController does not start. The LEDs and the display are off.
User Interface and Display
Problem Cause and corrective measure
The user interface is not displayed properly.
The ClusterController is not connected to the voltage sup­ply.
Corrective measures:
• Ensure that the three-pole plug for the voltage supply is connected to terminal X1 of the ClusterController.
The voltage supply is reverse-connected or the power sup­ply unit is defective.
Corrective measures:
• Ensure that the voltage supply is correctly connected (see Section6.13, page64).
• If the voltage supply is connected correctly, replace the power supply unit.
JavaScript is deactivated in the web browser.
Corrective measures:
• Activate JavaScript in the web browser.
Installation ManualClusterController-IA-en-1570
Page 71
SMA Solar Technology AG
Problem Cause and corrective measure
The correct number of connected in­verters is not shown on the display.
Communication with at least one inverter is disturbed. Either the ClusterController has not yet registered with one or more inverters or the connection to one or more in­verters has been interrupted.
Corrective measures:
• Wait six minutes and check again whether the correct number of all connected inverters is displayed.
If the correct number of connected inverters is still not displayed:
– Ensure that the inverters are in operation (see
inverter manual).
– Ensure that the network cables that connect the
inverters with one another are correctly connected (depending on the inverter equipment, see the inverter manual or the installation manual of the Speedwire/ Webconnect interface).
– Ensure that the network cable of the inverter
connected directly to the ClusterController is connected to network port X9 or X10 of the ClusterController.
– Ensure that no network components, network
cables or connectors are defective.
The expected binary values for the digital signal source are not shown on the display.
The digital signal source is not correctly connected.
Corrective measures:
• Ensure that the digital signal source is correctly connected (see Section6.12.2, page48).
No current signal for the analog sig­nal source or the sensor is shown on the display.
The analog signal source or the sensor are probably not correctly connected.
Corrective measures:
• Ensure that the analog signal source is correctly connected (see Section6.12.3, page54).
• Ensure that the sensor is correctly connected (see Section6.11.3, page44).
No measured values for the con­nected temperature sensor are shown on the display.
The temperature sensor is not correctly connected.
Corrective measures:
• Ensure that the temperature sensor is correctly connected (see Section6.11.1, page40).
7 Troubleshooting
Installation Manual 71ClusterController-IA-en-15
Page 72
7 Troubleshooting
Problem Cause and corrective measure
No measured values for the con­nected irradiation sensor are shown on the display.
If no measured values are displayed for the irradiation sensor, either the characteristic curve of the irradiation sen­sor is not configured or the irradiation sensor is not cor­rectly connected.
Corrective measures:
• Ensure that the characteristic curve of the irradiation sensor is configured (see the ClusterController user manual).
• Ensure that the irradiation sensor is correctly connected (see Section6.11.3, page44).
Though it is not connected, a mea­sured value of up to 2.2V for pin group Analog voltage input4 is shown on the display and the user in­terface.
If no sensor is connected to the pin group Analog volt- age input4, a measured value for this pin group of up to
2.2V will nevertheless be shown on the display and the user interface of the ClusterController.
Corrective measures:
• In order for a measured value of 0V to be displayed for the pin group Analog voltage input4 when it is not connected, place a jumper wire between pins B5 and B7 in terminal X8.
Login
SMA Solar Technology AG
Problem Cause and corrective measure
The login page does not open and the status LED ( ) is flashing red.
The ClusterController could not start correctly. A system error has occurred.
Corrective measures:
• Disconnect the ClusterController from the voltage supply and reconnect it to the voltage supply. Note that this can lead to loss of system data.
• If the problem persists, contact the Service (see Section11, page83).
Installation ManualClusterController-IA-en-1572
Page 73
SMA Solar Technology AG
7 Troubleshooting
Problem Cause and corrective measure
The login page does not open. The ClusterController is not connected to the voltage sup-
ply.
Corrective measures:
• Ensure that the three-pole plug for the voltage supply is connected to terminal X1 of the ClusterController.
The voltage supply is reverse-connected or the power sup­ply unit is defective.
Corrective measures:
• Ensure that the voltage supply is correctly connected (see Section6.13, page64).
• If the voltage supply is connected correctly, replace the power supply unit.
A firewall is blocking the connection.
Corrective measures:
• Adjust the firewall settings in order to allow the required connection.
If the ClusterController is connected to the LAN via DHCP and the voltage supply of the ClusterController was briefly interrupted, it is possible that the DHCP server has assigned the ClusterController a new IP address.
Corrective measures:
• Select the display view External communication and read out the current IP address of the ClusterController.
• Call up the IP address via the web browser.
Installation Manual 73ClusterController-IA-en-15
Page 74
7 Troubleshooting
Problem Cause and corrective measure
The login page does not open. There is a problem in the LAN.
Corrective measures:
• Ensure that the network cables are correctly connected to the ClusterController (see Section6.9, page38).
• Check whether the network components, network cables or connectors are defective or damaged. Replace defective or damaged network components, network cables or connectors.
• Check whether the network settings of the individual network components are correct. Adapt the network settings if required.
• Restart the ClusterController. Disconnect the ClusterController from the voltage supply and reconnect it to the voltage supply. Note that this can lead to loss of system data.
• If the problem persists, contact the network administrator.
Login to the user interface has failed. The system password has been entered incorrectly four
times. Access to the ClusterController is suspended for 15minutes.
Corrective measures:
• Wait 15minutes, then log in with the correct system password.
SMA Solar Technology AG
7.3 Resetting the ClusterController
You can reset the ClusterController via the keypad.
Procedure:
1. Call up the display view Settings. To do this, simultaneously press and hold the [OK] and [ ESC] buttons on the keypad for two seconds.
☑ The display view Settings opens.
2. Select the settings that are to be reset:
Settings to be reset Explanation
Reset password The user password and the installer password are re-
set. Reset network settings The network settings of the ClusterController are reset. Reset to default settings The ClusterController is reset to default settings. Stored
system data is deleted.
Installation ManualClusterController-IA-en-1574
Page 75
SMA Solar Technology AG
7 Troubleshooting
3. To exit the display view, press [ESC].
4. To confirm the settings that are to be reset, perform the following steps:
• Press [OK]. ☑ The display view Confirm the resetting appears.
• Select OK and confirm with [OK].
☑ The selected settings are reset. ☑ If the network settings were reset or the ClusterController was reset to default settings, the
ClusterController restarts.
5. If SunnyPortal is being used and the ClusterController was reset to default settings, adjust the system identifier for SunnyPortal in the ClusterController (see the ClusterController user manual).
Installation Manual 75ClusterController-IA-en-15
Page 76

8 Decommissioning

SMA Solar Technology AG
8 Decommissioning
8.1 Disassembling the ClusterController
1.
Danger to life due to electric shock
Lethal voltages are present at the connection point of the utility grid.
• Disconnect the connection point from the utility grid using the separator (e.g. circuit breaker).
• Remove the three-pole plug of the top-hat rail power supply unit from terminal X1 on the ClusterController.
2. Remove the network cable for the Speedwire network (e.g. for the inverter) from the ClusterController.
3. Remove the LAN network cable (e.g. for the router) from the ClusterController.
4. Remove the multipole plugs for the connected devices and sensors from the ClusterController.
5. Remove the ClusterController from the top-hat rail:
• Pull down the bracket for the top-hat rail locking mechanism located underneath the ClusterController, or press it down using a screwdriver.
• Tip the lower edge of the ClusterController forwards and lift upward to remove it from the top-hat rail.

8.2 Packing the Product for Shipment

• Pack the product for shipping. Use the original packaging or packaging that is suitable for the weight and size of the product.
Installation ManualClusterController-IA-en-1576
Page 77
SMA Solar Technology AG
8 Decommissioning

8.3 Disposing of the Product

• Dispose of the product in accordance with the locally applicable disposal regulations for electronic waste.
Installation Manual 77ClusterController-IA-en-15
Page 78

9 Technical Data

SMA Solar Technology AG
9 Technical Data
General Data
Status display LEDs, display Operation Keypad, integrated web server Mounting type Top-hat rail mounting Mounting location Indoors
Mechanical Data
Width x height x depth 275 mm x 133 mm x 71 mm Weight 1.2 kg
Display
Display LCD Resolution 240 pixels x 64 pixels Display languages German, English Operation Keypad
Memory
Internal ring buffer 1.7GB External storage* USB data carrier
* optional
Voltage supply
Voltage supply Power supply unit Input voltage 18 VDC to 30 V Typical power consumption 24 W Maximum power consumption 30 W
Ambient Conditions
Ambient temperature in operation* -25°C to +60 °C Ambient temperature during storage and trans-
port Relative humidity in operation** 4% to 95% Relative humidity during storage and transport
**
-40°C to +70°C
10% to 95%
DC
Installation ManualClusterController-IA-en-1578
Page 79
SMA Solar Technology AG
9 Technical Data
Degree of protection in accordance with
IP20
IEC60529 Electromagnetic compatibility as per EN55022 ClassA Maximum altitude above Mean Sea Level
3,000 m
(MSL)
* If the flow rate of the ambient air is constantly ≥0.5m/s, the ambient temperature range in operation
increases to -25°Cto+70°C.
** non-condensing
Communication
Inverter Speedwire Local area network (LAN) Ethernet Data interfaces HTTP, FTP, Modbus TCP / UDP, SMTP,
SunnyPortal
Maximum Cable Length for Communication
Speedwire* 100 m Ethernet* 100 m
* between two nodes when using installation cables
Maximum Number of Devices
SMA devices with Speedwire interface For model "CLCON-S-10": 25
For model "CLCON-10": 75
Network Ports
Quantity (Speedwire) 2 Quantity (LAN) 2 Auto-MDIX (auto-crossing) Yes Data transfer standard 10BaseT or 100BaseTx Data transfer rate* up to 10Mbit/s or up to 100Mbit/s
* Autonegotiation
Digital inputs
Quantity 8 Input voltage 24 V Maximum cable length 30 m
Installation Manual 79ClusterController-IA-en-15
DC
Page 80
9 Technical Data
SMA Solar Technology AG
Digital outputs
Quantity 3 Design Potential-free relay contacts Maximum switching power 30 W Maximum voltage load 48 V
DC
Maximum cable length 30 m
Analog inputs
Number of analog inputs for current signals 3 Number of analog inputs for voltage signals 1 Internal resistance 450Ω Measurement range for current signals 0mA to 20mA Measurement range for voltage signals 0V to +10V Typical tolerance ± 0.3% Maximum tolerance ± 2% Maximum cable length 30 m
Analog outputs
Number of analog outputs for current signals 3 Measurement range for current signals 4mA to 20mA Maximum tolerance ± 0.5% Maximum cable length 3,000 m
Temperature Inputs
Quantity 2 Measuring shunt Platinum sensor Pt100, platinum sensor Pt1000 Type of measurement Two-conductor connection technology, four-
conductor connection technology Measurement range -40°C to +85°C Maximum tolerance* ±0.5°C Maximum cable length* 20 m
* when measured with four-conductor connection technology
USB Ports
Quantity 2
Installation ManualClusterController-IA-en-1580
Page 81
SMA Solar Technology AG
Specification USB2.0 Hi‑Speed Maximum current 500 mA Maximum cable length 3 m
9 Technical Data
Installation Manual 81ClusterController-IA-en-15
Page 82

10 Accessories

SMA Solar Technology AG
10 Accessories
You will find the accessories for your product in the following overview. If required, these can be ordered from SMA Solar Technology AG or your distributor.
Designation Short description SMA order number
Top-hat rail power sup­ply unit*
USB flash drive 4GB USB flash drive with storage capacity of
USB flash drive 8GB USB flash drive with storage capacity of
* Not available in all countries. For information on whether an accessory is available in your country, visit
the website of your country's SMA subsidiary at www.SMA-Solar.com or contact your distributor.
Top-hat rail power supply unit for SMAClusterController
4GB
8GB
CLCON-PWRSUPPLY
USB-FLASHDRV4GB
USB-FLASHDRV8GB
Installation ManualClusterController-IA-en-1582
Page 83
SMA Solar Technology AG

11 Contact

11 Contact
If you have technical problems with our products, please contact the SMAServiceLine. We need the following information in order to provide you with the necessary assistance:
• ClusterController: – Serial number – Firmware version
• Inverters: – Type – Serial number – Firmware version
• When using a retrofitted Speedwire/Webconnect interface: – Serial number and firmware version of the Speedwire/Webconnect interface
You can read off the required information from the ClusterController user interface. Or you can find the serial number on the type label of the respective product (see the respective product manual). You can also find the serial number and the firmware version of the ClusterController in the display view ClusterController.
Danmark Deutschland Österreich Schweiz
France SMA France S.A.S.
SMA Solar Technology AG Niestetal SMA Online Service Center:
www.SMA.de/Service Sunny Boy, Sunny Mini Central,
SunnyTripower: +495619522‑1499
Monitoring Systems (Kommunika­tionsprodukte): +495619522‑2499
Fuel Save Controller (PV-Diesel­Hybridsysteme): +495619522-3199
Sunny Island, Sunny Backup, Hy­dro Boy: +495619522-399
Sunny Central: +495619522-299
Lyon +33 472 22 97 00
Belgien Belgique België Luxemburg Luxembourg Nederland
Česko Magyarország Polska România Slovensko
Ελλάδα Κύπρος
SMA Benelux BVBA/SPRL Mechelen +3215286 730
SMA Central & Eastern Europes.r.o.
Praha +420235010417
SMA Hellas AE Αθήνα +30 210 9856666
Installation Manual 83ClusterController-IA-en-15
Page 84
11 Contact
SMA Solar Technology AG
España Portugal
SMA Ibérica Tecnología Solar, S.L.U.
Barcelona +34935635099
Italia SMA Italia S.r.l.
Milano +39028934-7299
United Arab Emirates
SMA Middle East LLC Abu Dhabi +9712234-6177
SMA Solar (Thailand) Co., Ltd.
+6626706999
South Africa SMA Solar Technology South
Africa Pty Ltd. Cape Town 08600SUNNY (78669) International: +27 (0)21 826
0600
Australia SMA Australia Pty Ltd.
Sydney Toll free for Australia:
1800SMAAUS (1800762287)
International: +61294914200
United King­dom
SMA Solar UK Ltd. Milton Keynes +441908304899
France SMA France S.A.S.
Lyon +33 472 22 97 00
India SMA Solar India Pvt. Ltd.
Mumbai +912261713888
󷨺󹲖󸌶󷒧 SMA Technology Korea Co.,
Ltd. 󸡖󸷲 +82-2-520-2666
Argentina Brasil Chile
SMA South America SPA Santiago +562 2820 2101
Perú
Other countries International SMA Service Line
Niestetal Toll free worldwide:
00800SMASERVICE (+8007627378423)
Installation ManualClusterController-IA-en-1584
Page 85
Page 86
SMA Solar Technology
www.SMA-Solar.com
Loading...